Siemens s7-300 Programming

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 94
At a glance
Powered by AI
The document provides an overview of Siemens SIMATIC PLCs and the STEP 7 software used for configuring and programming them. It discusses the components of S7-300 PLCs and basic instructions for programming in statement list.

The main components of a SIMATIC S7-300 PLC include the rail, power supply, CPU, signal modules, function modules, communication processor, interface module and SINEC L2 cable.

The basic tasks when creating an automation solution with STEP 7 include installation and authorization, hardware configuration, block programming, compiling and loading, commissioning and going into operation.

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

INDUSTRIAL AUTOMATION TRAINING

SIEMENS S7-300 PROGRAMMING IN STATEMENT LIST

COURSE CONDUCTED BY: PROLIFIC SYSTEMS AND TECHNOLOGIES PVT. LTD. 202,SUCHITA INDUSTRIAL ESTATE, OPP. OSWAL PARK, POKHARAN RD. NO.2 THANE(W)-400601,INDIA TEL: (022) 5443307,5422887 FAX:(022) 5422887,5338399 E-MAIL :[email protected]

PAGE 1

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

CONTENTS:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22.

PAGE NO 3 7 9 12 13 14 16 23 27 29 38 45 48 49 51 54 56 58 71 73 75 86

STEP7 OVERVIEW COMPARISON OF CPU's AND MODULES AVAILABLE ADDRESSING OF MODULES LOAD MEMORY AND WORK MEMORY BLOCKS IN THE USER PROGRAM DATA TYPES STATEMENT LIST PROGRAMMING BIT LOGIC INSTRUCTIONS COMPARISON INSTRUCTIONS CONVERSION INSTRUCTIONS COUNTER INSTRUCTIONS DATA BLOCK AND LOGIC CONTROL INSTRUCTIONS LOAD AND TRANSFER INSTRUCTIONS FLOATING POINT MATH INSTRUCTIONS INTEGER MATH INSTRUCTIONS PROGRAM CONTROL INSTRUCTIONS SHIFT INSTRUCTIONS TIMER INSTRUCTIONS WORD LOGIC INSTRUCTIONS ACCUMULATOR INSTRUCTIONS PROGRAMMING EXAMPLES GLOSSARY

PAGE 2

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SIMATIC S7
PLC
S7-400 S7-300 S7-200 SIMATIC S7-300 COMPONENTS

RANGE
HIGH END RANGE/MEDIUM RANGE MID AND LOW END PERFORMANCE RANGE MICRO PLC'S

S.No. 1. 2. Rail

COMPONENT

FUNCTION Accomodates the S7-300 modules Converts the power system voltage (120/230VAC) into 24VDC for the S7-300 and load power supply for 24 VDC load circuits. Executes the user program, provides the 5V supply For the S7-300 backplane bus, communicates with other CPU's or with a programming device via the MPI(Multi Point Interface). Match different process signal levels to the internal signal level of S7-300 For time critical and memory intensive process signal processing tasks eg. Closed loop control Relieves the CPU of communication tasks eg-CP 342-5 DP for connection to SINEC L2-DP. Interconnects the individual tiers of an S7-300 Interconnects CPUs and PCs Connects a CPU to a programming device Interfaces the S7-300 over large distances to other S7300s or programming devices

Power Supply (PS)

3.

CPU

4. 5. 6. 7. 8. 9. 10.

Signal Modules(SM)DI,DO,AI,AO Function Modules (FMs) Communication Processor (CP) Interface Module(IM) Sinec L2 cable with LAN connector Programmer Cable RS 485 Repeater

PAGE 3

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Overview of STEP 7
What is STEP 7? STEP 7 is the standard software package used for configuring and programming SIMATIC programmable logic controllers. It is part of the SIMATIC industry software. Basic Tasks When you create an automation solution with STEP 7, there are a series of basic tasks. The following figure shows the tasks that need to be performed for most projects and assigns them to a basic procedure.

Alternative Procedures As shown in the figure above, you have two alternative procedures: You can configure the hardware first and then program the blocks. You can, however, program the blocks first without configuring the hardware. This is recommended for service and maintenance work, for example, to integrate programmed blocks into in an existing project. PAGE 4

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Brief Description of the Individual Steps Installation and authorization The first time you use STEP 7, install it and transfer the authorization from diskette to the hard disk Plan your controller Before you work with STEP 7, plan your automation solution from dividing the process into individual tasks to creating a configuration diagram Design the program structure Turn the tasks described in the draft of your controller design into a program structure using the blocks available in STEP 7 Start STEP 7 You start STEP 7 from the Windows 95/98/NT user interface Create a project structure A project is like a folder in which all data are stored in a hierarchical structure and are available to you at any time. After you have created a project, all other tasks are executed in this project Configure a station When you configure the station you specify the programmable controller you want to use; for example, SIMATIC 300, SIMATIC 400 Configure hardware When you configure the hardware you specify in a configuration table which modules you want to use for your automation solution and which addresses are to be used to access the modules from the user program. The properties of the modules can also be assigned using Configure networks and communication connections The basis for communication is a pre-configured network. For this, you will need to create the subnets required for your automation networks, set the subnet properties, and set the network connection properties and any communication connections required for the networked stations Define symbols You can define local or shared symbols, which have more descriptive names, in a symbol table to use instead of absolute addresses in your user program Create the program Using one of the available programming languages create a program linked to a module or independent of a module and store it as blocks, source files, or charts S7 only: generate and evaluate reference data You can make use of these reference data to make debugging and modifying your user program easier Configure messages You create block-related messages, for example, with their texts and attributes. Using the transfer program you transfer the message configuration data created to the operator interface system database (for example, SIMATIC WinCC, SIMATIC ProTool) Configure operator control and monitoring variables You create operator control and monitoring variables once in STEP 7 and assign them the required attributes. Using the transfer program you transfer the operator control and monitoring variables created to the database of the operator interface system WinCC Download programs to the programmable controller S7 only: after all configuration, parameter assignment, and programming tasks are completed, you can download your entire user program or individual blocks from it to the programmable controller (programmable module for your hardware solution). Test programs S7 only: for testing you can either display the values of variables from your user program or a CPU, assign values to the variables, and create a variable table for the variables that you want to display or modify Monitor operation, diagnose hardware You determine the cause of a module fault by displaying online information about a module. You determine the causes for errors in user program processing with the help of the diagnostic buffer and the stack contents. You can also check whether a user program can run on a particular CPU Document the plant After you have created a project/plant, it makes sense to produce clear documentation of the project data to make further editing of the project and any service activities easier PAGE 5

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

COMPARISON OF CPU'S
CPU's Mem Statement/Bytes Memory Cards Processing Time 1024 Statements DI & DO Max AI & AO Max Rack Configuration Expansion Modules Max Bit Memories Counters Timers MPI Interface 187.5 Kbit/s Max 32 Nodes Integrated functions+Interfaces CPU312IFM 2K/6KB 0.6 ms 256 64 1-Tier 8 1024 32 64 Yes 10DI/6DQ onboard. int. functions:Count ers/Freq. Measuremensts CPU313 4K/12KB 512KB FEPROM 0.6 ms 256 64 1-Tier 8 2048 32 64 Yes CPU314IFM 8K/24KB 0.3 ms 1024 256 4-Tier 31 2048 64 72 Yes 20DI/16DQ , 4AI,1AO onboard. int. functions:Co unters/Freq. Measuremen sts/Positionin g PID Control CPU314 16K/48KB 512KB FEPROM 0.3 ms 1024 256 4-Tier 31 2048 64 128 Yes -

CPU's Mem Statement/Bytes Memory Cards Processing Time 1024 Statements DI & DO Max AI & AO Max Rack Configuration Expansion Modules Max Bit Memories Counters Timers MPI Interface 187.5 Kbit/s Max 32 Nodes Integrated functions+Interfaces

CPU315 16K/48KB 512KB FEPROM 0.3 ms 1024 256 4-Tier 32 2048 64 128 Yes -

CPU315-2DP 16K/48KB 512KB FEPROM 0.3 ms 2048 256 4-Tier 32 2048 64 128 Yes PROFIBUSDP Master/Slave (64 DP stations,12M baud)

CPU316-2DP 42K/128KB 4MB FEPROM 0.3 ms 4096 256 4-Tier 32 2048 64 128 Yes PROFIBUSDP Master/Slave (64 DP stations,12M baud)

CPU318-2 256KB 4MB FEPROM 0.1 ms 16384 1024 4-Tier 32 8192 512 512 Upto 12Mbaud PROFIBUS-DP Master/Slave (125 DP stations,12Mb aud)

* 1 K statements correspond to approx. 3Kbytes of user memory. PAGE 6

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

THE DIFFERENT TYPES OF MODULES AVAILABLE ARE


1. SIGNAL MODULES - FOR DIGITAL AND ANALOG SIGNALS DIGITAL INPUTS 16 X 24 VDC 8 X 120 / 230 VAC 16 X 120 V AC 32 X 24 V DC DIGITAL OUTPUTS 16 x 24 VDC ,0.5A 8 X 24 VDC ,2A 8 X 120 / 230 VAC, 2A 16 X 120 VAC, 1A 32 X 24 V DC, 0.5A DI/DO MODULES 8DI/8DO X 24VDC 0.5A

RELAY OUTPUTS 8 X Relay 30 VDC ,0.5A 8 X Relay 250 VAC ,3A 16 X Relay 30VDC,0.5A 16 X Relay 120VAC, 2.5A

ANALOG INPUTS PARAMETERIZABLE 8 Analog Inputs/ 2 Analog Inputs +/- 10V , +/- 50 mV, +/-1 V, +/-20 Ma, 4 to 20mA, Pt100, Thermocouple

ANALOG OUTPUTS PARAMETERIZABLE 4 Analog Outputs/ 2 Analog Outputs +/-10V, +/-50mV, +/-1 V, +/-20 mV, 4 to 20 mA

2. FUNCTION MODULES High Speed Counter Modules - Upto 100 KHz range Positioning Modules - For position control, Stepper Motor Control, Cam Controllers All function modules are enclosed and can be installed in any slot. 3. COMMUNICATION PROCESSORS - FOR DATA EXCHANGE WITH PRINTERS,COMPUTERS, SIMATIC SYSTEMS CP340 - Point to Point Communication for the serial link with RS232, 3964R and any ASCII protocol 4. INTERFACE MODULES - FOR MULTI TIER CONFIGURATION For Central Controller Expansion For Expansion Unit Connection 5. POWER SUPPLY MODULES - FOR 24 VDC LOAD CIRCUITS WITH DIFFERENT RATINGS.

MPI - MULTI POINT INTERFACE FOR COMMUNICATION


MPI INTEGRATED IN CPU DATA EXCHANGE RATE : 187.5 Kbits / s SIMULTANEOUS COMMUNICATION WITH PG/PC/OP(OPERATOR PANEL) AND FURTHER PLCS REQUIRING NO ADDITIONAL HARDWARE PAGE 7

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

UPTO 32 NODES CAN BE CONNECTED

ADDRESSING OF MODULES

Slot Addressing for Rack 0

RACK 0

CPU

Slot Number Digital Address Analog Address

4 0 256

5 4 272

6 8 288

7 12 304

8 16 320

9 20 336

10 24 352

11 28 368

Module Starting Addresses of the Signal Modules on Rack 0

Slot Addressing for Rack 1


CPU IM AI / AO / DI / DO Modules

RACK 1

Slot Number Digital Address Analog Address

4 64 32 512 384

5 36 400

6 40 416

7 44 432

8 48 448

9 52 464

10 56 480

11 60 496

Module Starting Addresses of the Signal Modules on Rack 1


PAGE 8

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Slot Addressing for Rack 2

RACK 2

Slot Number Digital Address Analog Address

4 64 512

5 68 528

6 72 544

7 76 560

8 80 576

9 84 592

10 88 608

11 92 624

Module Starting Addresses of the Signal Modules on Rack 2

Slot Addressing for Rack 3


CPU IM AI / AO / DI / DO Modules

RACK 3

Slot Number Digital Address Analog Address

4 64 96 512 640

5 100 656

6 104 672

7 108 688

8 112 704

9 116 720

10 120 736

11 124 752

Module Starting Addresses of the Signal Modules on Rack 3

PAGE 9

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Rack 3

Slot Number

IM

4 64 512

10

11

Rack 2

Slot Number

IM

10

11

Connecting cable 368 64


512

Rack 1

Slot Number

IM

10

11

Connecting cable 368 64


512

Rack 0

PS

CPU

Slot Number

(IM) 3

10

11

PAGE 10

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Load Memory and Work Memory in the CPU


After completing the configuration, parameter assignment, and program creation and establishing the online connection, you can download complete user programs or individual blocks to a programmable controller. To test individual blocks, you must download at least one organization block (OB) and the function blocks (FB) and functions (FC) called in the OB and the data blocks (DB) used. To download the system data created when the hardware was configured, the networks configured, and the connection table created to the programmable controller, you download the object System Data". You download user programs to a programmable controller using the SIMATIC Manager, for example, during the end phase of the program testing or to run the finished user program. Relationship - Load Memory and Work Memory The complete user program is downloaded to the load memory; the parts relevant to program execution are also loaded into the work memory. CPU Load Memory The load memory is used to store the user program without the symbol table and the comments (these remain in the memory of the programming device). Blocks that are not marked as required for startup will be stored only in the load memory. The load memory can either be RAM, ROM, or EPROM memory, depending on the programmable controller. CPU Work Memory The work memory (integrated RAM) is used to store the parts of the user program required for program processing. Possible Downloading/Uploading Procedures You use the download function to download the user program or loadable objects (for example, blocks) to the programmable controller. If a block already exists in the RAM of the CPU, you will be prompted to confirm whether or not the block should be overwritten. You can select the loadable objects in the project window and download them from the SIMATIC Manager (menu command: PLC > Download). When programming blocks and when configuring hardware and networks you can directly download the object you were currently editing using the menu in the main window of the application you are working with (menu command: PLC > Download). Another possibility is to open an online window with a view of the programmable controller (for example, using View > Online or PLC > Display Accessible Nodes) and copy the object you want to download to the online window. Alternatively you can upload the current contents of blocks from the RAM load memory of the CPU to your programming device via the load function.

PAGE 11

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Blocks in the User Program


The STEP 7 programming software allows you to structure your user program, in other words to break down the program into individual, self-contained program sections. This has the following advantages: Extensive programs are easier to understand. Individual program sections can be standardized. Program organization is simplified. It is easier to make modifications to the program. Debugging is simplified since you can test separate sections. Commissioning your system is made much easier. The example of an industrial blending process illustrated the advantages of breaking down an automation process into individual tasks. The program sections of a structured user program correspond to these individual tasks and are known as the blocks of a program. Block Types There are several different types of blocks you can use within an S7 user program:

Block
Organization blocks (OB) System function blocks (SFB) and system functions (SFC) Function blocks (FB) Functions (FC) Instance data blocks (instance DB) Data blocks (DB)

Brief Description Of Function


OBs determine the structure of the user program. SFBs and SFCs are integrated in the S7 CPU and allow you access to some important system functions. FBs are blocks with a "memory" which you can program yourself. FCs contain program routines for frequently used functions. Instance DBs are associated with the block when an FB/SFB is called. They are created automatically during compilation. DBs are data areas for storing user data. In addition to the data that are assigned to a function block, shared data can also be defined and used by any blocks.

OBs, FBs, SFBs, FCs, and SFCs contain sections of the program and are therefore also known as logic blocks. The permitted number of blocks per block type and the permitted length of the blocks is CPU-specific.

PAGE 12

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

DATA TYPES
Introduction to Data Types and Parameter Types All the data in a user program must be identified by a data type. The following data types are available: Elementary data types provided by STEP 7 Complex data types that you yourself can create by combining elementary data types Parameter types with which you define parameters to be transferred to FBs or FCs General Information Statement List, Ladder Logic, and Function Block Diagram instructions work with data objects of specific sizes. Bit logic instructions work with bits, for example. Load and transfer instructions (STL) and move instructions (LAD and FBD) work with bytes, words, and double words. A bit is a binary digit "0" or "1." A byte is made up of eight bits, a word of 16 bits, and a double word of 32 bits. Math instructions also work with bytes, words, or double words. In these byte, word, or double word addresses you can code numbers of various formats such as integers and floating-point numbers. When you use symbolic addressing, you define symbols and specify a data type for these symbols (see table below). Different data types have different format options and number notations. This chapter describes only some of the ways of writing numbers and constants. The following table lists the formats of numbers and constants that will not be explained in detail. Format Size in Bits Number Notation Hexadecimal Binary date time Time of day Character 8, 16, and 32 8, 16, and 32 16 32 32 8 B#16#, W#16#, and DW#16# 2# D# T# TOD# 'A'

Elementary Data Types Each elementary data type has a defined length. The following table lists the elementary data types. Size Range and Number Type and in Format Options Notation (lowest Example Description Bits to highest value)_ BOOL(Bit) BYTE (Byte) Boolean text 8 Hexadecimal number TRUE/FALSE B16#0 to B16#FF TRUE L B#16#10 L byte#16#10

WORD (Word)

16

L 2#0001_0000_0000_0000 2. 0 to 2#1111_1111_1111_1111 Hexadecimal number W#16#0 to W#16#FFFF L W#16#1000 L word16#1000 BCD C#0 to C#999 L C#998 Decimal number unsigned B#(0.0) to B#(255.255) L B#(10,20) L byte#(10,20) Binary number Binary number Hexadecimal number 2#0 to 2#1000_0001_0001_1000_ 2#1111_1111_1111_1111 1011_1011_0111_1111 1111_1111_1111_1111 DW#16#0000_0000 to L DW#16#00A2_1234 PAGE 13

DWORD (Double word)

32

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

DW#16#FFFF_FFFF B#(0,0,0,0) to Decimal number unsigned B#(255,255,255,255) INT (Integer) 16 Decimal number signed Decimal number signed IEEE Floating-point number S7 time in steps of 10 ms (default) -32768 to 32767 L#-2147483648 to L#2147483647

L dword#16#00A2_1234 L B#(1, 14, 100, 120) L byte#(1,14,100,120) L1 L L#1

DINT 32 (Integer, 32 bits) REAL (Floating-point number) S5TIME (SIMATIC time) 32

Upper limit: 3.402823e+38 L 1.234567e+13 Lower limit: 1.175 495e-38 S5T#0H_0M_0S_10MS to S5T#2H_46M_30S_0MS and S5T#0H_0M_0S_0MS L S5T#0H_1M_0S_0MS L S5TIME#0H_1H_1M_0S_0 MS

16

TIME (IEC time)

32

IEC time in steps of 1 ms, integer signed

L T#0D_1H_1M_0S_0MS T#24D_20H_31M_23S_64 L 8MS to TIME#0D_1H_1M_0S_0MS T#24D_20H_31M_23S_64 7MS D#1990-1-1 to D#2168-12-31 TOD#0:0:0.0 to TOD#23:59:59.999 'A','B' etc. L D#1996-3-15 L DATE#1996-3-15 L TOD#1:10:3.3 L TIME_OF_DAY#1:10:3.3 L 'E'

DATE (IEC date) TIME_OF_DAY (Time) CHAR (Character)

16 32 8

IEC date in steps of 1 day Time in steps of 1 ms ASCII characters

Parameter Types In addition to elementary and complex data types, you can also define parameter types for formal parameters that are transferred between blocks. STEP 7 recognizes the following parameter types: TIMER or COUNTER: this specifies a particular timer or particular counter that will be used when the block is executed. If you supply a value to a formal parameter of the TIMER or COUNTER parameter type, the corresponding actual parameter must be a timer or a counter, in other words, you enter "T" or "C" followed by a positive integer. BLOCK: specifies a particular block to be used as an input or output. The declaration of the parameter determines the block type to be used (FB, FC, DB etc.). If you supply values to a formal parameter of the BLOCK parameter type, specify a block address as the actual parameter. Example: FC101" (when using absolute addressing) or Valve" (with symbolic addressing). Parameter TIMER COUNTER Capacity Description

Indicates a timer to be used by the program in the called logic block. 2. Byte Format: T1 s 2 bytes Indicates a counter to be used by the program in the called logic block. Format: C10 Indicates a block to be used by the program in the called logic block. Format: FC101 DB42 PAGE 14

BLOCK_FB BLOCK_FC 2 bytes BLOCK_DB BLOCK_SDB

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PROGRAMMING IN STATEMENT LIST


What is Statement List? Statement List (STL) is a textual programming language that can be used to create the code section of logic blocks. Its syntax for statements is similar to assembler language and consists of instructions followed by addresses on which the instructions act. The Programming Language STL Of all the programming languages with which you can program S7 controllers, STL is the closest to the machine code MC7 of the S7 CPU. This means that by using it to program S7 controllers, you can optimize the run time and the use of memory. The programming language STL has all the necessary elements for creating a complete user program. It contains a comprehensive range of instructions. A total of over 130 different basic instructions and a wide range of addresses are available. Functions and function blocks allow you to structure your STL program clearly. The Programming Package The STL programming package is an integral part of the STEP 7 Standard Software. This means that following the installation of your STEP 7 software, all the editor functions, compiler functions and test/debug functions for STL are available to you. Using STL, you can create your own user program as follows: _ With the Incremental Editor. The input of the local data structure is made easier with the help of table editors. _ With a source file in the Text Editor. Text input is made easier with the help of block templates. There are three programming languages in the standard software, STL, FBD, and LAD. You can switch from one language to the other almost without restriction and choose the most suitable language for the particular block you are programming. If you write programs in LAD or FBD, you can always switch over to the STL representation. If you convert LAD programs into FBD programs and vice versa, program elements that cannot be represented in the destination language are displayed in STL. A STATEMENT CONSISTS OF AN INSTRUCTION AND AN ADDRESS Address of an Instruction The address of an instruction indicates a constant or the location where the instruction finds a value (data object) on which to perform an operation. The address can have a symbolic name or an absolute designation. The address can point to any of the following items : _ A constant, the value of a timer or counter, or an ASCII character string to be loaded into accumulator 1 (for example, L +27 See Table 2.1) _ A bit in the status word of the programmable logic controller _ A symbolic name (for example, A Motor.On, see Table 2-3) _ A data block and a location within the data block area (for example, L DB4.DBD10, see Table 2-4) _ A function (FC), function block (FB), integrated system function (SFC), or integrated system function block (SFB) and the number of the function or block (see Table 2-5) _ An address identifier and a location within the memory area that is indicated by the address identifier (for example, A I 1.0)

PAGE 15

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 16

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 17

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 18

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 19

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 20

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 21

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

COMMANDS USED IN STATEMENT LIST Bit Logic Instructions


) = A A( AN AN( FN FP O O O( ON ON( R S Nesting Closed Assign And And with Nesting Open And Not And Not with Nesting Open Edge Negative Edge Positive Or And before Or Or with Nesting Open Or Not Or Not with Nesting Open Reset Set

PAGE 22

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 23

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 24

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Comparison Instructions

PAGE 25

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 26

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Conversion Instructions

PAGE 27

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

BTD BCD to Double Integer (32-Bit) Example: L MD10 Load the BCD number into ACCU 1. BTD Convert from BCD to integer; store result in ACCU 1. T MD20 Transfer result (double integer number) to MD20.

BTI BCD to Integer (16-Bit) Example: L MW10 Load the BCD number into ACCU 1-L. BTI Convert from BCD to integer; store result in ACCU 1-L. T MW20 Transfer result (integer number) to MW20.

CAD Change Byte Sequence in ACCU 1 (32-Bit) Example: L MD10 Load the value of MD10 into ACCU 1. CAD Reverse the sequence of bytes in ACCU 1. T MD20 Transfer the results to MD20. Contents of ACCU 1 before execution of CAD: ACCU 1-H-H: ACCU 1-H-L: ACCU 1-L-H: value "A" value "B" value "C" Contents of ACCU 1 after execution of CAD: ACCU 1-H-H: ACCU 1-H-L: ACCU 1-L-H: value "D" value "C" value "B" ACCU 1-L-L: value "D" ACCU 1-L-L: value "A"

PAGE 28

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

CAW Change Byte Sequence in ACCU 1-L (16-Bit) Example: L MW10 Load the value of MW10 into ACCU 1. CAW Reverse the sequence of bytes in ACCU 1-L. T MW20 Transfer the result to MW20. Contents of ACCU 1 before execution of CAW: ACCU 1-H-H: value "A" ACCU 1-H-L: value "B" ACCU 1-L-H: value "C" ACCU 1-L-L: value "D" ACCU 1-L-L: value "C"

Contents of ACCU 1 after execution of CAW: ACCU 1-H-H: ACCU 1-H-L: ACCU 1-L-H: value "A" value "B" value "D"

DTB Double Integer (32-Bit) to BCD Example: L MD10 Load the 32-bit integer into ACCU 1. DTB Convert from integer (32-bit) to BCD, store result in ACCU 1. T MD20 Transfer result (BCD number) to MD20.

DTR Example:

Double Integer (32-Bit) to Floating-Point Number (32-Bit, IEEE-FP) PAGE 29

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

L DTR T

MD10 MD20

Load the 32-bit integer into ACCU 1. Convert from double integer to floating point (32-bit IEEE FP); store result in ACCU 1. Transfer result (BCD number) to MD20.

INVD Example: Bit

Ones Complement Double Integer (32-Bit) 31


0110 1001 1111 0000 1000 0111

16
1100 0011

15
0110 1001 0011 1100 1010 0101

0
1110 0001

Contents of ACCU 1 before execution of INVD Contents of ACCU 1 after execution of INVD

L INVD T

ID8 MD10

Load value into ACCU 1. Form ones complement (32-bit). Transfer result to MD10.

INVI Ones Complement Integer (16-Bit) Example: Bit 15 Contents of ACCU 1-L before execution of INVI 0110 Contents of ACCU 1-L after execution of INVI 1001 L INVI T IW8 MW10 Load value into ACCU 1-L. Form ones complement 16-bit. Transfer result to MW10.

0011 1100

1010 0101

0 1110 0001

PAGE 30

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

ITB Integer (16-Bit) to BCD Example: L MW10 Load the integer number into ACCU 1-L. ITB Convert from integer to BCD (16-bit); store result in ACCU 1-L. T MW20 Transfer result (BCD number) to MW20.

ITD Integer (16-Bit) to Double Integer (32-Bit) Example: L MW12 Load the integer number into ACCU 1. ITD Convert from integer (16-bit) to double integer (32-bit); store result in ACCU 1. T MD20 Transfer result (double integer) to MD20.
MW12 = "-10" (Integer, 16-bit): Bit:
Contents of ACCU 1 before execution of ITD: Contents of ACCU 1 after execution of ITD:

ACCU 1-H 31
XXXX 1111 XXXX 1111 XXXX 1111 XXXX 1111

ACCU 1-L 16 : 15
1111 1111 1111 1111 1111 1111

0
0110 0110

(X = 0 or 1, bits are not used for conversion)

NEGD Example:

Twos Complement Double Integer (32-Bit) PAGE 31

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD. ACCU 1-H Bit:


Contents of ACCU 1 before execution of NEGD: Contents of ACCU 1 after execution of NEGD:

ACCU 1-L .0
0100 1011 0101 1010 1101 0010 0011 1100 1000 1000

31
0101 1010 1111 0000 0110 1001

L ID8 NEGD T MD10

Load value into ACCU 1. Generate twos complement (32-bit). Transfer result to MD10.

NEGI Twos Complement Integer (16-Bit) Example: Bit 15 Contents of ACCU 1-L before execution of NEGI 0101 Contents of ACCU 1-L after execution of NEGI 1010 L NEGI T IW8 MW10 Load value into ACCU 1-L. Form twos complement 16-bit. Transfer result to MW10.

1101 0010

0011 1100

0 1000 1000

NEGR Negate Floating-Point Number (32-Bit, IEEE-FP) Example: L ID8 Load value into ACCU 1 (example: ID 8 = 1.5E+02). NEGR Negate floating-point number (32-bit, IEEE-FP); stores the result in ACCU 1. T MD10 Transfer result to MD10 (example: result = -1.5E+02).

PAGE 32

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

RND Round Example: L MD10 Load the floating-point number into ACCU 1-L. RND Convert the floating-point number (32-bit, IEEE-FP) into an integer (32-bit) and round off the result. T MD20 Transfer result (double integer number) to MD20. Value before conversion: Value after conversion: MD10 = "100.5" => RND => MD20 = "+100" MD10 = "-100.5" => RND => MD20 = "-100"

PAGE 33

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

RND+ Round to Upper Double Integer Example: L MD10 Load the floating-point number (32-bit, IEEE-FP) into ACCU 1-L. RND+ Convert the floating-point number (32-bit, IEEE-FP) to an integer (32-bit) and round result.Store output in ACCU 1. T MD20 Transfer result (double integer number) to MD20. Value before conversion: Value after conversion: MD10 = "100.5" => RND+ => MD20 = "+101" MD10 = "-100.5" => RND+ => MD20 = "-100"

RNDRound to Lower Double Integer Example: L MD10 Load the floating-point number into ACCU 1-L. RNDConvert the floating-point number (32-bit, IEEE-FP) to an integer (32-bit) and round result.Store result in ACCU 1. T MD20 Transfer result (double integer number) to MD20. Value before conversion: Value after conversion: MD10 = "100.5" => RND- => MD20 = "+100" MD10 = "-100.5" => RND- => MD20 = "-101" PAGE 34

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

TRUNC Truncate Example: L MD10 Load the floating-point number into ACCU 1-L. TRUNC Convert the floating-point number (32-bit, IEEE-FP) to an integer (32-bit) and round result.Store the result in ACCU 1. T MD20 Transfer result (double integer number) to MD20. Value before conversion: Value after conversion: MD10 = "100.5" => TRUNC => MD20 = "+100" MD10 = "-100.5" => TRUNC => MD20 = "-100"

PAGE 35

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Counter Instructions

PAGE 36

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 37

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 38

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 39

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 40

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 41

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

CD Example: L C#14 A I 0.1 S C1 A I 0.0 CD C1 input AN = C1 Q 0.0

Counter Down Counter preset value. Preset counter after detection of rising edge of I 0.1. Load counter 1 preset if enabled. One count down per rising edge of I 0.0. Decrement counter C1 by 1 when RL0 transitions from 0 to 1 depending on I 0.0. Zero detection using the C1 bit. Q 0.0 = 1 if counter 1 value is zero.

CU Example: A I 2.1 CU C3 L Example: L C3 LC Example: LC C3 format.

Counter Up If there is a positive edge change at input I 2.1. Counter C3 is incremented by 1 when RL0 transitions from 0 to 1. Load Current Counter Value into ACCU 1 Load ACCU 1-L with the count value of counter C3 in binary format. Load Current Counter Value into ACCU 1 as BCD Load ACCU 1-L with the count value of counter C3 in binary coded decimal

R Example: A I 2.3 R C3

Reset Counter Check signal state at input I 2.3. Reset counter C3 to a value of 0 if RLO transitions from 0 to 1.

S Example: A I 2.3 L C#3 S C1

Set Counter Preset Value Check signal state at input I 2.3. Load count value 3 into ACCU 1-L. Set counter C1 to count value if RLO transitions from 0 to 1

PAGE 42

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Data Block Instructions


Format: Example: OPN L T OPN L T OPN <data block> Open data block DB10 as a shared data block. Load data word 35 of the opened data block into ACCU 1-L. Transfer the content of ACCU 1-L into MW22. Open data block DB20 as an instance data block. Load data byte 12 of the opened instance data block into ACCU 1-L. Transfer the content of ACCU 1-L to data byte 37 of the opened shared data block.

DB10 DBW35 MW22 DI20 DIB12 DBB37

Logic Control Instructions


JC Example: A A JC L T JOVR: A Jump if RLO = 1 I 1.0 I 1.2 JOVR Jump if RLO=1 to jump label JOVR. IW8 Program scan continues here if jump is not executed. MW22 I 2.1 Program scan resumes here after jump to jump label JOVR.

JCB Example: A A JCB L T JOVR: A

Jump if RLO = 1 with BR I 1.0 I 1.2 JOVR Jump if RLO = 1 to jump label JOVR. Copy the contents of the RLO bit into the BR bit. IW8 Program scan continues here if jump is not executed. MW22 I 2.1 Program scan resumes here after jump to jump label JOVR.

JCN Example: A A JCN L T JOVR: A

Jump if RLO = 0 I 1.0 I 1.2 JOVR Jump if RLO = 0 to jump label JOVR. IW8 Program scan continues here if jump is not executed. MW22 I 2.1 Program scan resumes here after jump to jump label JOVR.

JM Example: L L -I JM AN S JU

Jump if Minus IW8 MW12 //Subtract contents of MW12 from contents of IW8. NEG //Jump if result < 0 (that is, contents of ACCU 1 < 0). M 4.0 //Program scan continues here if jump is not executed. M 4.0 NEXT PAGE 43

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

NEG:

AN M 4.1 S M 4.1 NEXT: NOP 0

//Program scan resumes here after jump to jump label NEG. //Program scan resumes here after jump to jump label NEXT.

JMZ Jump if Minus or Zero Example: L IW8 L MW12 -I Subtract contents of MW12 from contents of IW8. JMZ RGE0 Jump if result <=0 (that is, contents of ACCU 1 <= 0). AN M 4.0 Program scan continues here if jump is not executed. S M 4.0 JU NEXT RGE0: AN M 4.1 Program scan resumes here after jump to jump label RGE0. S M 4.1 NEXT: NOP 0 Program scan resumes here after jump to jump label NEXT.

JN Example: L L XOW JN AN S JU NOZE: AN S NEXT: NOP 0

Jump if Not Zero IW8 MW12 NOZE Jump if the contents of ACCU 1-L are not equal to zero. M 4.0 Program scan continues here if jump is not executed. M 4.0 NEXT M 4.1 Program scan resumes here after jump to jump label NOZE. M 4.1 Program scan resumes here after jump to jump label NEXT.

JP Example: L L -I JP AN S JU POS: AN S NEXT: NOP 0

Jump if Plus IW8 MW12 Subtract contents of MW12 from contents of IW8. POS Jump if result >0 (that is, ACCU 1 > 0). M 4.0 Program scan continues here if jump is not executed. M 4.0 NEXT M 4.1 Program scan resumes here after jump to jump label POS. M 4.1 Program scan resumes here after jump to jump label NEXT.

JPZ Example: L L -I JPZ AN S JU REG0: AN

Jump if Plus or Zero IW8 MW12 Subtract contents of MW12 from contents of IW8. REG0 Jump if result >=0 (that is, contents of ACCU 1 >= 0). M 4.0 Program scan continues here if jump is not executed. M 4.0 NEXT M 4.1 Program scan resumes here after jump to jump label REG0. PAGE 44

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

S M 4.1 NEXT: NOP 0

Program scan resumes here after jump to jump label NEXT.

JU Example: A A JC L INC T JU DELE: L T FORW: A

Jump Unconditional I 1.0 I 1.2 DELE Jump if RLO=1 to jump label DELE. MB10 1 MB10 FORW Jump unconditionally to jump label FORW. 0 MB10 I 2.1 Program scan resumes here after jump to jump label FORW.

JUO Example: L L /D JUO T A R JU ERRO: AN S NEXT: NOP 0 JZ Example: L SRW JZ L INC T JU ZERO: L INC T NEXT: NOP 0

Jump if Unordered MD10 ID2 Divide contents of MD10 by contents of ID2. ERRO Jump if division by zero (that is, ID2 = 0). MD14 Program scan continues here if jump is not executed. M 4.0 M 4.0 NEXT M 4.0 Program scan resumes here after jump to jump label ERRO. M 4.0 Program scan resumes here after jump to jump label NEXT. Jump if Zero MW10 1 ZERO Jump to jump label ZERO if bit that has been shifted out = 0. MW2 Program scan continues here if jump is not executed. 1 MW2 NEXT MW4 Program scan resumes here after jump to jump label ZERO. 1 MW4 Program scan resumes here after jump to jump label NEXT.

LOOP Loop Example for calculating the factor of 5: L L#1 Load the integer constant (32 bit) into ACCU 1. T MD20 Transfer the contents from ACCU 1 into MD20 (initialization). L 5 Load number of loop cycles into ACCU 1-L. NEXT: T MW10 Jump label = loop start / transfer ACCU 1-L to loop counter. L MD20 * D Multiply current contents of MD20 by the current contents of MB10. T MD20 Transfer the multiplication result to MD20. L MW10 Load contents of loop counter into ACCU 1.
LOOP NEXT Decr. the contents of ACCU 1 and jump to the NEXT jump label if ACCU 1-L > 0.

PAGE 45

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

L L >I

MW24 Program scan resumes here after loop is finished. 200

Load and Transfer Instructions


L Load L <address> loads the addressed byte, word, or double word into ACCU 1 after the old contents of ACCU 1 have been saved into ACCU 2, and ACCU 1 is reset to "0". Example: L IB10 L MB120 L DBB12 L DIW15 L LD252 Load input byte IB10 into ACCU 1-L-L. Load memory byte MB120 into ACCU 1-L-L. Load data byte DBB12 into ACCU 1-L-L. Load instance data word DIW15 into ACCU 1-L. Load local data double word LD252 ACCU 1.

T Transfer T <address> transfers (copies) the contents of ACCU 1 to the destination address if the Master Control Relay is switched on (MCR = 1). If MCR = 0, then the destination address is written with 0. The number of bytes copied from ACCU 1 depends on the size expressed in the destination address. ACCU 1 also saves the data after the transfer procedure. A transfer to the direct I/O area (memory type PQ) also transfers the contents of ACCU 1 or "0" (if MCR=0) to the corresponding address of the process image output table (memory type Q). The instruction is executed without regard to, and without affecting, the status bits. Example: T QB10 T MW14 T DBD2 Transfers contents of ACCU 1-L-L to output byte QB10. Transfers contents of ACCU 1-L to memory word MW14. Transfers contents of ACCU 1 to data double word DBD2.

PAGE 46

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Floating-Point Math Instructions; Basic


*R Multiply ACCU 1 and ACCU 2 as Floating Point Numbers (32-Bit IEEE-FP) Example: OPN DB10 L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the value of ACCU 1 into ACCU 2.Load the value of MD14 into ACCU 1. *R Multiply ACCU 2 and ACCU 1; store the result in ACCU 1. T DBD25 The content of ACCU 1 (result) is transferred to DBD25 in DB10.

+R Add ACCU 1 and ACCU 2 as a Floating Point Number (32-Bit IEEE-FP) Example: OPN DB10 L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the value of ACCU 1 into ACCU 2.Load the value of MD14 into ACCU 1. +R Add ACCU 2 and ACCU 1; store the result in ACCU 1. T DBD25 The content of ACCU 1 (result) is transferred to DBD25 in DB10.

-R Example: OPN DB10 L ID10 L MD14 ACCU 1. -R T DBD25

Subtract ACCU 1 from ACCU 2 as a Floating Point Number (32-Bit IEEE-FP)

Load the value of ID10 into ACCU 1. Load the value of ACCU 1 into ACCU 2.Load the value of MD14 into Subtract ACCU 1 from ACCU 2; store the result in ACCU 1. The content of ACCU 1 (result) is transferred to DBD25 in DB10.

/R Divide ACCU 2 by ACCU 1 as a Floating Point Number (32-Bit IEEE-FP) Example: OPN DB10 L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the contents of ACCU 1 into ACCU 2.Load the value of MD14 into ACCU 1. /R Divide ACCU 2 by ACCU 1; store the result in ACCU 1. T DBD20 The content of ACCU 1 (result) is transferred to DBD20 in DB10.

ABS Absolute Value of a Floating Point Number (32-Bit IEEE-FP) Example: L ID8 Load value into ACCU 1 (example: ID8 = -1.5E+02). ABS Form the absolute value; store the result in ACCU 1. T MD10 Transfer result to MD10 (example: result = 1.5E+02).

PAGE 47

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Floating-Point Math Instructions: Extended

PAGE 48

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Integer Math Instructions


+ Add Integer Constant (16, 32 Bit) + <integer constant> adds the integer constant to the contents of ACCU 1 and stores the result in ACCU 1. The instruction is executed without regard to, and without affecting, the status word bits. The contents of accumulator 2 remain unchanged for CPUs with two ACCUs. The contents of accumulator 3 are copied into accumulator 2, and the contents of accumulator 4 are copied into accumulator 3 for CPUs with four ACCUs. The contents of accumulator 4 remain unchanged. + <16-bit integer constant>: Adds a 16-bit integer constant (in the range of -32768 to +32767) to the contents of ACCU 1-L and stores the result in ACCU 1-L. The contents of accumulator 2 remain unchanged for CPUs with two ACCUs. The contents of accumulator 3 are copied into accumulator 2, and the contents of accumulator 4 are copied into accumulator 3 for CPUs with four ACCUs. The contents of accumulator 4 remain unchanged. + <32-bit integer constant>: Adds a 32-bit integer constant (in the range of -2,147,483,648 to 2,147,483,647) to the contents of ACCU 1 and stores the result in ACCU 1. The contents of accumulator 2 remain unchanged for CPUs with two ACCUs. The contents of accumulator 3 are copied into accumulator 2, and the contents of accumulator 4 are copied into accumulator 3 for CPUs with four ACCUs. The contents of accumulator 4 remain unchanged. Example 1: L IW10 L MW14 +I + T 25 DB1.DBW25 Load the value of IW10 into ACCU 1-L. Load the contents of ACCU 1-L to ACCU 2-L. Load the value of MW14 into ACCU 1-L. Add ACCU 2-L and ACCU 1-L; store the result in ACCU 1-L. Add ACCU 1-L and 25; store the result in ACCU 1-L. Transfer the contents of ACCU 1-L (result) to DBW25 of DB1.

Example 2: L IW12 L IW14 + 100 >I JC NEXT Example 3: L MD20 L MD24 +D + L#-200 T MD28

Add ACCU 1-L and 100; store the result in ACCU 1-L. If ACCU 2 > ACCU 1, or IW12 > (IW14 + 100) then conditional jump to jump label NEXT.

Add ACCU 1and ACCU 2; store the result in ACCU 1. Add ACCU 1 and -200; store the result in ACCU 1.

+D Add ACCU 1 and ACCU 2 as Double Integer (32-Bit) Example: L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the contents of ACCU 1 to ACCU 2.Load the value of MD14 into ACCU 1. +D Add ACCU 2 and ACCU 1; store the result in ACCU 1. T DB1.DBD25 The contents of ACCU 1 (result) are transferred to DBD25 of DB1.

-D Example: L ID10

Subtract ACCU 1 from ACCU 2 as Double Integer (32-Bit) Load the value of ID10 into ACCU 1. PAGE 49

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

L MD14 ACCU 1. -D T DB1.DBD25

Load the contents of ACCU 1 into ACCU 2.Load the value of MD14 into Subtract ACCU 1 from ACCU 2; store the result in ACCU 1. The contents of ACCU 1 (result) are transferred to DBD25 of DB1.

*D Example: L ID10 L MD14 *D T DB1.DBD25

Multiply ACCU 1 and ACCU 2 as Double Integer (32-Bit) Load the value of ID10 into ACCU 1. Load contents of ACCU 1 into ACCU 2.Load contents of MD14 into ACCU 1. Multiply ACCU 2 and ACCU 1; store the result in ACCU 1. The contents of ACCU 1 (result) are transferred to DBD25 in DB1.

/D Divide ACCU 2 by ACCU 1 as Double Integer (32-Bit) Example: L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the contents of ACCU 1 into ACCU 2.Load the value of MD14 into ACCU 1. /D Divide ACCU 2 by ACCU 1; store the result (quotient) in ACCU 1. T MD20 The contents of ACCU 1 (result) are transferred to MD20. Example above: 13 divided by 4 Contents of ACCU 2 before instruction (ID10): Contents of ACCU 1 before instruction (MD14): Instruction /D (ACCU 2 / ACCU 1) Contents of ACCU 1 after instruction (quotient): "13" "4" : "3"

"13/4"

+I Add ACCU 1 and ACCU 2 as Integer (16-Bit) Example: L IW10 Load the value of IW10 into ACCU 1-L. L MW14 Load the contents of ACCU 1-L into ACCU 2-L.Load the value of MW14 into ACCU 1-L. +I Add ACCU 2-L and ACCU 1-L; store the result in ACCU 1-L. T DB1.DBW25 The contents of ACCU 1-L (result) are transferred to DBW25 of DB1.

-I Subtract ACCU 1 from ACCU 2 as Integer (16-Bit) Example: L IW10 Load the value of IW10 into ACCU 1-L. L MW14 Load the contents of ACCU 1-L into ACCU 2-L.Load the value of MW14 into ACCU 1-L. -I Subtract ACCU 1-L from ACCU 2-L; store the result in ACCU 1-L. T DB1.DBW25 The contents of ACCU 1-L (result) are transferred to DBW25 of DB1.

*I Multiply ACCU 1 and ACCU 2 as Integer (16-Bit) Example: L IW10 Load the value of IW10 into ACCU 1-L. L MW14 Load contents of ACCU 1-L into ACCU 2-L.Load contents of MW14 into ACCU 1L. *I Multiply ACCU 2-L and ACCU 1-L, store result in ACCU 1. T DB1.DBD25 The contents of ACCU 1 (result) are transferred to DBW25 in DB1. PAGE 50

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

/I Example: L L IW10 MW14

Divide ACCU 2 by ACCU 1 as Integer (16-Bit) Load the value of IW10 into ACCU 1-L. Load the contents of ACCU 1-L into ACCU 2-L.Load the value of MW14 into ACCU 1-L. Divide ACCU 2-L by ACCU 1-L; store the result in ACCU 1:ACCU 1-L:

/I quotient,

ACCU 1-H: remainder T MD20 The contents of ACCU 1 (result) are transferred to MD20. Example above: 13 divided by 4 Contents of ACCU 2-L before instruction (IW10): "13" Contents of ACCU 1-L before instruction (MW14): "4" Instruction /I (ACCU 2-L / ACCU 1-L): "13/4" Contents of ACCU 1-L after instruction (quotient): "3" Contents of ACCU 1-H after instruction (remainder): "1"

MOD Division Remainder Double Integer (32-Bit) Example: L ID10 Load the value of ID10 into ACCU 1. L MD14 Load the contents of ACCU 1 into ACCU 2.Load the value of MD14 into ACCU 1. MOD Divide ACCU 2 by ACCU 1, store the result (remainder) in ACCU 1. T MD20 The contents of ACCU 1 (result) are transferred to MD20. Example above : 13 divided by 4 Contents of ACCU 2 before instruction (ID10): "13" Contents of ACCU 1 before instruction (MD14): "4" Instruction MOD (ACCU 2 / ACCU 1): "13/4" Contents of ACCU 1 after instruction (remainder): "3"

PAGE 51

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Program Control Instructions


BE Block End BE (block end) terminates the program scan in the current block and causes a jump to the block that called the current block. The program scan resumes with the first instruction that follows the block call statement in the calling program.

BEC Block End Conditional If RLO = 1, then BEC (block end conditional) interrupts the program scan in the current block and causes a jump to the block that called the current block. Example: A I 1.0 BEC L IW4 T MW10 Update RLO. End block if RLO = 1. Continue here if BEC is not executed, RLO = 0.

BEU Block End Unconditional BEU (block end unconditional) terminates the program scan in the current block and causes a jump to the block that called the current block. The program scan resumes with the first instruction that follows the block call. Example: A I 1.0 JC NEXT Jump to NEXT jump label if RLO = 1 (I 1.0 = 1). L IW4 Continue here if no jump is executed. T IW10 A I 6.0 A I 6.1 S M 12.0 BEU Block end unconditional. NEXT: NOP 0 Continue here if jump is executed.

CALL Block Call CALL <logic block identifier> is used to call functions (FCs) or function blocks (FBs), system functions (SFCs) or system function blocks (SFBs) you created yourself or to call the standard pre-programmed blocks shipped by Siemens. The CALL instruction calls the FC and SFC or the FB and SFB that you input as an address, independent of the RLO or any other condition. Example: CALL FB1, DB1 or CALL FILLVAT1, RECIPE1 Logic Block FC SFC FB SFB Block Type Function System function Function block System function block Absolute Address Call Syntax CALL FCn CALL SFCn CALL FBn1,DBn2 CALL SFBn1,DBn2

Example 1: Assigning parameters to the FC6 call CALL FC6 Formal parameter Actual parameter NO OF TOOL := MW100 TIME OUT := MW110 FOUND:= Q 0.1 ERROR := Q 100.0 Example 2: Calling an SFC without parameters PAGE 52

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

CALL

SFC43 Call SFC43 to re-trigger watchdog timer (no parameters).

Example 3: Calling FB99 with instance data block DB1 CALL FB99,DB1 Formal parameter Actual parameter MAX_RPM := #RPM1_MAX MIN_RPM := #RPM2 MAX_POWER := #POWER MAX_TEMP := #TEMP Example 4: Calling FB99 with instance data block DB2 CALL FB99,DB2 Formal parameter Actual parameter MAX_RPM := #RPM3_MAX MIN_RPM := #RPM2 MAX_POWER := #POWER1 MAX_TEMP := #TEMP

CC Conditional Call CC <logic block identifier> (conditional block call) calls a logic block if RLO=1. CC is used to call logic blocks of the FC or SFC type without parameters. Example: A I 2.0 Check signal state at input I 2.0. CC FC6 Call function FC6 if I 2.0 is "1". A M 3.0 Executed upon return from called function (I 2.0 = 1) or directly after A I 2.0 statement if I 2.0 = 0.

UC Unconditional Call UC <logic block identifier> (unconditional block call) calls a logic block of the FC or SFC type. UC is like the CALL instruction, except that you cannot transfer parameters with the called block. Example 1: UC FC6 Call function FC6 (without parameters).

Example 2: UC SFC43 Call system function SFC43 (without parameters).

PAGE 53

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Shift Instructions
SLD Shift Left Double Word (32-Bit) SLD <number>: The number of shifts is specified by the address <number>. The permissible value range is from 0 to 32. The status word bits CC 0 and OV are reset to zero if <number> is greater than zero. If <number> is equal to zero, then the shift instruction is regarded as a NOP operation. Examples: ACCU 1-H
Bit: 31 ACCU 1 before execution of SLD 5: 0101 ACCU 1 after execution of SLD 5: 1110 1111 1100 0110 1000 16 0100 1011 15 0101 1010 1101 0111

ACCU 1-L
0011 0110 0 1011 0000

Example 1: L MD4 SLD 5 T MD8

Load value into ACCU 1. Shift bits in ACCU 1 five places to the left. Transfer result to MD8.

SLW Shift Left Word (16-Bit) SLW <number>: The number of shifts is specified by the address <number>. The permissible value range is from 0 to 15. The status word bits CC 0 and OV are reset to zero if <number> is greater than zero. If <number> is equal to zero, then the shift instruction is regarded as a NOP operation. Examples: ACCU 1-H Bit:
ACCU 1 before execution of SLW 5: ACCU 1 after execution of SLW 5:

ACCU 1-L 16 15
0101 1010 1101 0111 0011 0110

31
0101 0101 1111 1111 0110 0110

0
1011 0000

0100 0100

Example 1: L MW4 SLW 5 T MW8

Load value into ACCU 1. Shift the bits in ACCU 1 five places to the left. Transfer result to MW8.

SRD Shift Right Double Word (32-Bit) SRD <number>: The number of shifts is specified by the address <number>. The permissible value range is from 0 to 32. The status word bits CC 0 and OV are reset to 0 if <number> is greater thnan zero. Examples: ACCU 1-H ACCU 1-L
Bit: 31 ACCU 1 before execution of SRD 7:0101 ACCU 1 after execution of SRD 7: 0000 1111 0000 0110 1011 16 0100 1110 15 0101 1100 1101 1000 0011 1011 0 1011 1010

Example 1: L MD4 SRD 7 T MD8

Load value into ACCU 1. Shift bits in ACCU 1 seven places to the right. Transfer result to MD8.

SRW Shift Right Word (16-Bit) SRW <number>: The number of shifts is specified by the address <number>. The permissible value range is from 0 to 15. The status word bits CC 0 and OV are reset to 0 if <number> is greater than zero. Examples: ACCU 1-H ACCU 1-L
Bit: 31 16 15 0

PAGE 54

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD. ACCU 1 before execution of SRW 6: 0011 1011 ACCU 1 after execution of SRW 6: 0101 0100 0101 1111 1111 0110 0110 0100 0100 0000 0101 0001 1101 0111

Example 1: L MW4 SRW 6 T MW8

Load value into ACCU 1. Shift bits in ACCU 1-L six places to the right. Transfer result to MW8.

PAGE 55

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Timer Instructions

PAGE 56

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SD On-Delay Timer SD <timer> starts the addressed timer when the RLO transitions from "0" to "1". The programmed time interval elapses as long as RLO = 1. The time is stopped if RLO transitions to "0" before the programmed time interval has expired. This timer start instruction expects the time value and the time base to be stored as a BCD number in ACCU 1-L. Example: A I 2.1 L S5T#10s SD T1

Preset 10 seconds into ACCU 1. Start timer T1 as an on-delay timer.

PAGE 57

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 58

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SE Extended Pulse Timer SE <timer> starts the addressed timer when the RLO transitions from "0" to "1". The programmed time interval elapses, even if the RLO transitions to "0" in the meantime. The programmed time interval is started again if RLO transitions from "0" to "1" before the programmed time has expired. This timer start command expects the time value and the time base to be stored as a BCD number in ACCU 1-L. Example: A I 2.1 L S5T#10s Preset 10 seconds into ACCU 1. SE T1 Start timer T1 as an extended pulse timer. A I 2.2 R T1 Reset timer T1. A T1 Check signal state of timer T1. = Q 4.0

PAGE 59

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 60

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SF Off-Delay Timer SF <timer> starts the addressed timer when the RLO transitions from "1" to "0". The programmed time elapses as long as RLO = 0. The time is stopped if RLO transitions to "1" before the programmed time interval has expired. This timer start command expects the time value and the time base to be stored as a BCD number in ACCU 1-L. Example: A I 2.1 L S5T#10s Preset 10 seconds into ACCU 1. SF T1 Start timer T1 as an off-delay timer. A I 2.2 R T1 Reset timer T1. A T1 Check signal state of timer T1. = Q 4.0

PAGE 61

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 62

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SP Pulse Timer SP <timer> starts the addressed timer when the RLO transitions from "0" to "1". The programmed time elapses as long as RLO = 1. The timer is stopped if RLO transitions to "0" before the programmed time interval has expired. This timer start command expects the time value and the time base to be stored as a BCD number in ACCU 1-L. Example: A I 2.1 L S5T#10s Preset 10 seconds into ACCU 1. SP T1 Start timer T1 as a pulse timer. A I 2.2 R T1 Reset timer T1. A T1 Check signal state of timer T1. = Q 4.0

PAGE 63

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 64

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

SS Retentive On-Delay Timer SS <timer> (start timer as a retentive ON timer) starts the addressed timer when the RLO transitions from "0" to "1". The full programmed time interval elapses, even if the RLO transitions to "0" in the meantime. The programmed time interval is re-triggered (started again) if RLO transitions from "0" to "1" before the programmed time has expired. This timer start command expects the time value and the time base to be stored as a BCD number in ACCU 1-L. Example: A I 2.1 L S5T#10s Preset 10 seconds into ACCU 1. SS T1 Start timer T1 as a retentive on-delay timer. A I 2.2 R T1 Reset timer T1. A T1 Check signal state of timer T1. = Q 4.0

PAGE 65

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 66

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 67

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

R Reset Timer R <timer> stops the current timing function and clears the timer value and the time base of the addressed timer word if the RLO transitions from 0 to 1. Example: A I 2.1 R T1 Check the signal state of input I 2.1 If RLO transitioned from 0 = 1, then reset timer T1.

PAGE 68

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Word Logic Instructions


AD AND Double Word (32-Bit) AD (AND double word) combines the contents of ACCU 1 with ACCU 2 or a 32-bit constant bit by bit according to the Boolean logic operation AND. A bit in the result double word is "1" only when the corresponding bits of both double words combined in the logic operation are "1". Examples:
Bit: 31 ACCU 1 before execution of AD: 0101 0000 ACCU 2 or 32-bit constant: 1111 0011 Result (ACCU 1) after execution of AD:0101 0000 1111 1000 1000 1100 0101 0100 1000 0111 0000 1001 0110 0000 0011 1011 0011 Bit:0 1011 0101

0001

L L AD T

ID20 ID24 MD8

Load contents of ID20 into ACCU 1. Load contents of ACCU 1 into ACCU 2.Load contents of ID24 into ACCU 1. Combine bits from ACCU 1 with ACCU 2 by AND, store result in ACCU 1. Transfer result to MD8.

AW AND Word (16-Bit) AW (AND word) combines the contents of ACCU 1-L with ACCU 2-L or a 16 bit-constant bit by bit according to the Boolean logic operation AND. A bit in the result word is "1" only when the corresponding bits of both words combined in the logic operation are "1". Examples: Bit: 15 Bit:0 ACCU 1-L before execution of AW: 0101 1001 0011 1011 ACCU 2-L or 16-bit constant: 1111 0110 1011 0101 Result (ACCU 1-L) after execution of AW: 0101 0000 0011 0001 L L AW T IW20 IW22 Load contents of IW20 into ACCU 1-L. Load contents of ACCU 1 into ACCU 2.Load contents of IW22 into ACCU 1-L. Combine bits from ACCU 1-L with ACCU 2-L bits by AND; store result in ACCU 1-L. MW 8 Transfer result to MW8.

OD OR Double Word (32-Bit) OD (OR double word) combines the contents of ACCU 1 with ACCU 2 or a 32-bit constant bit by bit according to the Boolean logic operation OR. A bit in the result double word is "1" when at least one of the corresponding bits of both double words combined in the logic operation is "1". Examples: Bit: 31
1111 1000 1111 1100 0101 1101 1000 0111 1111 0101 0110 0111 0011 1011 1011

Bit:0
1011 0101

ACCU 1 before execution of OD: 0101 0000 ACCU 2 or 32-bit constant: 1111 0011 Result (ACCU 1) after execution of OD:1111 0011

1111

L L OD T

ID20 ID24 MD8

Load contents of ID20 into ACCU 1. Load contents of ACCU 1 into ACCU 2.Load contents of ID24 into ACCU 1. Combine bits from ACCU 1 with ACCU 2 bits by OR; store result in ACCU 1. Transfer result to MD8.

OW OR Word (16-Bit) OW (OR word) combines the contents of ACCU 1-L with ACCU 2-L or a 16 bit-constant bit by bit according to the Boolean logic operation OR. A bit in the result word is "1" when at least one of the corresponding bits of both words combined in the logic operation is "1". Examples: Bit: 15 Bit:0 PAGE 69

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

ACCU 1-L before execution of OW: 0101 ACCU 2-L or 16 bit constant: 1111 Result (ACCU 1-L) after execution of OW: L L OW T IW20 IW22 MW8

0101 0110 1111

0011 1011 0111

1011 0101 1011

1111

Load contents of IW20 into ACCU 1-L. Load contents of ACCU 1 into ACCU 2.Load contents of IW22 into ACCU 1-L. Combine bits from ACCU 1-L with ACCU 2-L by OR, store result in ACCU 1-L. Transfer result to MW8.

XOD Exclusive OR Double Word (32-Bit) XOD (XOR double word) combines the contents of ACCU 1 with ACCU 2 or a 32-bit constant bit by bit according to the Boolean logic operation XOR (Exclusive Or). A bit in the result double word is "1" when only one of the corresponding bits of both double words combined in the logic operation is "1". Examples: Bit: 31
1111 1000 0111 1100 0101 1001 1000 0111 1111 0101 0110 0011 0011 1011 1000

Bit:0
1011 0101 1110

ACCU 1 before execution of XOD: 0101 0000 ACCU 2 or 32-bit constant: 1111 0011 Result (ACCU 1) after execution of OD:1010 0011

L L XOD T

ID20 ID24 MD8

Load contents of ID20 into ACCU 1. Load contents of ACCU 1 into ACCU 2.Load contents of ID24 into ACCU 1. Combine bits from ACCU 1 with ACCU 2 by XOR; store result in ACCU 1. Transfer result to MD8.

XOW Exclusive OR Word (16-Bit) XOW (XOR word) combines the contents of ACCU 1-L with ACCU 2-L or a 16 bit-constant bit by bit according to the Boolean logic operation XOR. A bit in the result word is "1" only when one of the corresponding bits of both words combined in the logic operation is "1". Examples: Bit: 15 Bit:0 ACCU 1 before execution of XOW: 0101 0101 0011 1011 ACCU 2-L or 16-bit constant: 1111 0110 1011 0101 Result (ACCU 1) after execution of XOW: 1010 0011 1000 1110 L L XOW T IW20 IW22 MW8 Load contents of IW20 into ACCU 1-L. Load contents of ACCU 1 into ACCU 2.Load contents of ID24 into ACCU 1-L. Combine bits of ACCU 1-L with ACCU 2-L bits by XOR, store result in ACCU 1-L. Transfer result to MW8.

PAGE 70

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

Accumulator Instructions
DEC Decrement ACCU 1-L-L Example: L MB250 Load the value of MB250 DEC 1 Instruction "Decrement ACCU 1-L-L by 1"; store result in ACCU 1-L-L. T MB250 Transfer the contents of ACCU 1-L-L (result) back to MB250.

INC Increment ACCU 1-L-L Example: L MB22 Load the value of MB22 INC 1 Instruction "Increment ACCU 1 (MB22) by 1"; store result in ACCU 1-L-L T MB22 Transfer the contents of ACCU 1-L-L (result) back to MB22

TAK Toggle ACCU 1 with ACCU 2 Example: Subtract smaller value from greater value: Example: L MW10 Load contents of MW10 into ACCU 1-L. L MW12 Load contents of ACCU 1-L into ACCU 2-L.Load contents of MW12 into ACCU 1>I Check if ACCU 2-L (MW10) greater than ACCU 1-L (MW12). JC NEXT Jump to NEXT jump label if ACCU 2 (MW10) is greater than ACCU 1 (MW12). TAK Swap contents ACCU 1 and ACCU 2 NEXT: -I Subtract contents of ACCU 2-L from contents of ACCU 1-L. T MW14 Transfer result (= greater value minus smaller value) to MW14.

PAGE 71

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PROGRAMMING EXAMPLES

PAGE 72

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 73

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 74

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 75

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 76

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 77

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 78

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 79

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 80

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 81

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 82

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 83

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 84

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 85

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 86

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 87

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 88

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 89

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 90

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 91

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 92

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

PAGE 93

PROLIFIC SYSTEMS & TECHNOLOGIES PVT. LTD.

----------------------------------------------------------------------------------------------------------------

THANK YOU FOR ATTENDING OUR INDUSTRIAL AUTOMATION TRAINING COURSE !

PAGE 94

You might also like