Ups Traing
Ups Traing
Ups Traing
•Line-interactive UPSs- regulate input utility voltage up or down as necessary before allowing it to pass
through to protected equipment. However, like standby UPSs, they use their battery to guard
against
Line Interactive UPS internal design
Double-conversion systems - As the name suggests, these devices convert power
twice. First, an input rectifier converts AC power into DC and feeds it to an output
inverter. The output inverter then processes the power back to AC before sending it on
to IT equipment. This double-conversion process isolates critical loads from raw utility
power completely, ensuring that IT equipment receives only clean, reliable electricity. In
normal operation, a double-conversion UPS continually processes power twice. If the
AC input supply falls out of predefined limits, however, the input rectifier shuts off
and the output inverter begins drawing power from the battery instead.
The UPS continues to utilize battery power until the AC input returns to normal
tolerances or the battery runs in case of a severe overload of the inverter, or a failure of
the rectifier or inverter, the static switch bypass path is turned on quickly, to support the
output loads.
.
Double Conversion UPS internal design
M ulti-mode systems - These combine features of both single- and
double-conversion technologies while providing substantial
improvements in both efficiency and reliability.
•Batteries are connected both in series parallel to get desired voltage and capacity
•Batteries can be connected in series to achieve whatever voltage is required (add the number of 2 volt
cells), and in parallel to achieve the capacity required (add the capacities of each parallel battery or string of
batteries).
•For larger systems, a number of series connected strings may be connected in parallel with each other.
This achieves both a higher voltage and capacity.
•Batteries are electrically live at all times, take great care never to short circuit the battery terminals.
3. Operation of UPS
.
3.1. LED FUNCTION
3.2. LCD DISPLAY FUNCTION
4.3. Turn ON/OFF operations
Operation
The 10KVA – 160KVA UPS are made up of input switch, filter, rectifier, inverter,
static switch, bypass switch, output transformer and batteries, etc. when the AC
input is normal, the AC power will be converted into DC power by rectifier to
supply power for inverter, and charge the batteries with enough power to supply
pour power for load without transfer time when mains disconnect.
Operating principle of single-unit
5.1 Work Mode
Mains mode
When mains normal, the rectifier will convert the AC power into DC power to
charge
battery and supply power for inverter to provide pure AC for load.
Battery mode
When mains abnormal or rectifier stops working, the batteries connected with
DC.BUS
will supply power for inverter and the AC output will not interrupt.
Bypass mode
When the inverter abnormal (such as over-temperature, short circuit, output
voltage
abnormal or overload and exceed the range that the inverter can withstand), the
inverter
will shut down automatically to avoid damage. If the mains still normal at this
moment, bypass power will instead of mains power to supply power for load by static
switch.
Maintenance bypass mode
When the UPS needs to be maintained or the battery needs to be replaced and at the
same
time, the power supply for load cannot be interrupted, shut down the UPS
firstly, then
switch on the maintenance bypass switch and then switch off the switches of
mains, bypass, output and external battery cabinet. During switching to
maintenance bypass manually, AC power supplies power for load through
maintenance bypass switch. Meanwhile, there is no electricity inside UPS (except
N), and maintainer can carry out the maintenance safely.
Operation panel of Three-Phase (10kVA -30kVA) series UPS
operation panel of Three-Phase (40kVA -160kVA) series
UPS
Menu Hierarchy
In the monitoring page, it shows the topological structure of UPS. The
icon meaning is as follows:
In the monitoring page, click icon and it will enter battery information on page. When
battery is discharging, it shows discharge current. When battery is equalizing charging or
float charging, it will show charge current. Besides, the page also shows battery
temperature, battery remaining me and battery status. If it exists battery under-voltage
alarm and the battery remaining me is less than 10 minutes, the battery remaining me
shows battery is going to run out and turn off.
Battery status shows current battery e status. It includes discharging,
equalizing charge, flow charge, standard test, depth test and battery loop
abnormal.
Output information
In the monitoring page, click, icon and it will enter output information page. It shows
phase voltage and load capacity
Warning Information
When UPS is working, if UPS failure, it will pop up the abnormal information on
window. After closing
the window, if you want to view the abnormal information again, click icon on the
top right corner of monitoring page.
There is buzzer icon on the top right corner
Buzzer status
Working Status
In the information management page, click Working Status icon and it will
enter the working status page. It shows mains status, bypass status, battery
status, load status, fan status, AC/DC status, DC/A status, etc.
Working status page
Event Log
In the information management page, click Event Log icon and it will
enter the event log page. It shows history alarm, fault, bypass open,
startup, etc.
Event log
Maintenance
Check Electrical Connection
Don't regard ON/OFF button on the UPS panel as the power switch of load.
Don't start UPS frequently.
When UPS works steadily, it can turn on load. Some devices generate large
current when startup, and may lead to overload protection . It is better to
start them first. Start the high-power devices first and then the small-power
devices. If you want to close UPS, turn off the load first.
Before starting UPS for the first me, perform checking before power on. If it
is ok, power on UPS. If UPS hasn’t been used for a long me, it need to
perform checking before power on.
UPS Announcements
Before starting UPS, check whether load is proper. The load
capacity shouldn't exceed rated output capacity of UPS to avoid
overload protection .
Don't regard ON/OFF button n the UPS panel as the power switch of load. Don't
start UPS frequently.
When UPS works steadily, it can turn on load. Some devices generate large
current when startup, and may lead to overload protection . It is better to start
them first. Start the high-power devices first and then the small-power devices.
If you want to close UPS, turn off the load first.
Before starting UPS for the first me, perform checking before power on. If it is
ok, power on UPS. If UPS hasn’t been used for a long me, it need to perform
checking before power on.
Start UPS
Step 1 Switch on bypass switch.
Power board starts working and touch screen begins initializing. About
10s later, the initialization on is finished, the panel and LED works normally.
When power on, press and hold ON combination button , the green indicator is
on. 30s later, finish starting inverter. Check whether the output voltage is the
required voltage value.
Before switching on external battery cabinet switch, the bus voltage should be higher
than the rated DC input voltage.
After finishing starting rectifier, ensure the float charging/ equalized charging
voltage setting match with practical battery parameters.
When power on, press and hold ON combination button , the green indicator
is on. 30s later, finish starting inverter. Check whether the output voltage is the
required voltage value.
Some devices (e.g. motor type load) generate large current when startup, and may lead
to overload protection (or on bypass). It is better to start them first.
Close UPS
Before closing UPS, close load first and keep UPS working without load for 10
minutes to exhaust heat.
Press "OFF" combination button to turn off inverter and the green indicator is off. The
bypass power instead of the inverter supplies power for load by static switch
automatically.
After switching off mains switch, the rectifier will not supply DC power
for DC BUS from AC mains.
Step 5
When the touch screen and LED are off, switch off output switch
(output), UPS will power down
completely.
The RECTIFIER charges the battery at the same me. On the control panel the
green LEDS MAINS and OUTPUT is lit for normal opera on.
Transfer From UPS Status to Maintenance Bypass Status
Don't switch on output switch when UPS is on the maintenance bypass status
Step 2
Press the "OFF" combination button, the green indicator is
green
off and the indicator is on. The UPS works on the bypass
status.
Switch off mains switch, bypass switch, output switch and external battery
cabinet switch.
When the
panel powers down about 10 minutes, it can do the
maintenance.
Transfer From Maintenance Bypass Status to UPS Status
Switch on mains switch, the works normally green indicator will be on. About 10s
later, the rectifier
Keep watching the fans operation for proper Daily (every 24Hr)
function of ups
Check on display if in and out light (led) are Always
glowing. Both led should
Check on display if batt and out light (led) Daily (every 24Hr)
are glowing. Both led
should glow when UPS is on battery mode
If buzzer sounds in ups check the display of ups. Always
Ensure that the air intake slots (located on the front Weekly
door and at the
back of the cabinet) and the output grilles located
on the top of the cabinet are clean;
Charge and discharge battery once every four to six months, and Six months
the
charging time should be no less than four hours.
check whether battery cables are properly connected Six months
Trouble shooting
10KVA – 160KVA UPS
N Abnormal phenomena Fault diagnosis and checking Solu on
o. items
Check if mains switch is switched
on and —
fuse is OK.
Check if the range of mains check input voltag using
voltage is e
1 red indicator is on. normal.
Change the phase
sequence of
Check if the phase of AC input is mains input wire of rec fier.
wrong.
The rectifier doesn't start
completely. The
buzzer beeps continuously and ba
2
The inverter can't giveery low-voltage indicator is on. Ba Wait the rectifier starting
output normally and the ttery input switch is not switched and buzzer beeping will be
buzzer beeps on. removed.
continuously
Output is overload. The red
Frequency
Comment
s
Sub-
Divisio Categor Ac vi es
6 months
n
Monthly
Weekly
y
Yearly
daily
Visually check for liquid contamina X
1 on from
ba eries and capacitors
Inspec on of electronic circuits and X
2 control
cards
3 Check of output frequency X
Electrical
Clean battery X
14
Charge and discharge ba ery once every X
four to six months, and the charging me
15 should be no less than four hours.