Safety information
Operation
1. Read this manual carefully and thoroughly before operating the UPS and save this manual
properly for future reference.
2. All the warnings and operating instructions on the UPS and in this manual must be strictly
complied with.
3. Avoid installation of the UPS in a location under direct sunlight, near running water, or
excessive humidity.
4. Do not install the UPS in the environment where it is close to heating facilities such as space
heaters or furnaces.
5. Position the UPS in a room with good ventilation, enough space for installation and adequate
airflow for heat sinking. Refer to the manual to carry out the installation.
6. Cleaning with dry stuff, do not use liquid or spray detergent.
7. In the event of a fire occurring in the vicinity, please use dry powder fire extinguishers.The use
of liquid fire extinguishing agents may causes electric shock.
Electricity
1. Verify the cabling and the polarities of the battery cable (for S models) are correct with
protective earth ground provided before powering on the UPS.
2. Before moving or re-wiring the UPS, please disconnect it from the mains source outlet and
make sure the UPS is completely powered off. Otherwise, the output outlets of the UPS may
have live voltage, thus presenting electric shock risk.
3. Choose optional accessories from SANTAK or consult the authorized distributors or service
center for further information.
4. The length of the output cables should be less than 10m in order to comply with EMC
requirements.
Battery
1. High ambient temperature shortens the battery s lifespan, the battery should be replaced
periodically to ensure normal operation of the UPS and for adequate autonomy.
2. Servicing of battery should be performed or supervised by personnel who is knowledgeable of
battery.
3. In replacement of battery, please use the same number and same type of the battery.
-2-
4. A battery can present a risk of electrical shock and high short circuit current. Pay attention to
the following precautions prior to battery replacement.
A. Metal objects, such as rings and watches shall be removed;
B. Use tools with insulated handles;
C. Wear rubber gloves and boots;
D. Do not lay tools or metal parts on the batteries;
E. Disconnect the load before removing the wirings from the battery.
5. Do not dispose of batteries in a fire, they may explode.
6. Do not open or mutilate the battery. It may cause an electrolyte leakage that is toxic and
harmful to the skin and eyes. If electrolyte comes into contact with the skin, wash the affected
area with plenty of clean water immediately and go to the hospital for further checkup.
7. Do not make the positive and negative terminals of the battery short circuit; otherwise it may
cause electric shock or fire.
Maintenance
1. The operating environment and storage method are two main factors affecting the service
lifetime and reliability of the UPS. It is advisable not to use the UPS in the following
environments:
Where the temperature and relative humidity are out of the specifications (temperature:0
40, relative humidity: 20%90%.)
Where vibrations or shocks are existing.
Dust, corrosive agents or inflammable gas are present.
2. If the UPS does not use for a long period, it shall be kept in a dry environment. The storage
temperature should be between 25 55 (without battery). If the UPS has been kept
in the area where its temperature is lower than 0 , please keep the UPS in a location
with the ambient temperature over 0 for a certain period of time before powering on the
UPS.
-3-
Contents
1
2
2.1
2.2
2.3
3
3.1
3.2
3.3
3.3.1
3.3.2
3.3.3
4
4.1
4.2
4.2.1
4.2.2
4.2.3
4.3
4.3.1
4.3.2
4.3.3
5
5.1
5.2
6
7
7.1
7.2
7.3
7.4
7.5
7.6
8
Introduction
Descriptions of Commonly Used Symbols
Product Description
Models and Configuration
The Appearance of the UPS
Operating Principle
Installation
Unpacking and Inspections
Installation Notes
Cable Connections
Connections of Input and Output
Operation Procedures of External Battery for Long Backup Time models
Connection of Communication Cable
Operation
Display and Control Panel
Operating Mode
AC mode (Utility Power mode)
Battery mode
Bypass mode
Operating Instructions
Turn On and Turn off the UPS
Battery self-diagnosis
Audible alarm and LED indication of UPS operating status and faults
Maintenance
Battery Maintenance
UPS functional check
Troubleshooting
Specifications
Electrical
Mechanical
Environmental
EMC standards
Safety
Industry Standards
Warranty
-4-
5
5
5
5
6
7
8
8
8
9
9
10
11
13
13
14
14
15
16
16
16
17
17
19
19
19
20
22
22
23
23
23
23
23
24
1 INTRODUCTION
Descriptions of Commonly Used Symbols
Some of the following symbols may be used in this manual and may appear in your application
process. Therefore, all users should be familiar with them and understand their meanings.
Descriptions
Alert you to pay special attention
Danger of electrical hazard
Alternating current source (AC)
Direct current source (DC)
Protective ground
Recyclable
Do not dispose of with ordinary trash
2 PRODUCT DESCRIPTION
Castle E Series is of true online UPS (Uninterruptible Power Systems) designed with an advanced
double-conversion technology. It provides perfect protection especially for critical loads, such as
computers, communications systems as well as computerized instruments.
The double-conversion design eliminates all mains power disturbances. A rectifier converts the
alternating current from the utility power to direct current. This direct current charges the batteries
and powers the inverter. On the basis of this DC voltage, the inverter generates a pure sine wave
AC power which is constantly powering the loads.
-5-
Model
Remark
1kVA UPS
C1K_E
2kVA UPS
C2K_E
3kVA UPS
C3K_E
1kVA UPS
C1KS_E
2kVA UPS
C2KS_E
3kVA UPS
C3KS_E
Input
External Battery Connector
Intelligent Slot
EPO
RS232
Network/Fax/Modem
Surge Protection
Output
Intelligent Slot
EPO
RS232
Network/Fax/Modem
Surge Protection
Output
Output Terminal Block
External Battery Connector
Input
Input
AC/DC
Converter
Input Filter
DC/AC Inverter
Output Filter
DC/DC
Converter
Charger
Battery
3 INSTALLATION
3.1 Unpacking and Inspections
1. Unpack the UPS and examine the unit to see if there is any damage during transportation.
2. Check the accessories of the UPS as below.(Refer to Table 3-1)
3. If the appearance of the UPS is damaged, or there is any missing accessory, please contact the
distributor immediately.
Table 3-1 List of Accessories
Model
Standard model
Accessory
Quantity
User manual
Communication cable
User manual
Communication cable
-8-
Rating
Model
Quantity of output
socket
1kVA
C1K_E/C1KS_E
Nil
2kVA
C2K_E/C2KS_E
Nil
3kVA
C3K_E,/C3KS_E
Available
1)
2)
3)
4)
Apart from using the sockets for output connections, C3K_E/C3KS_E has the terminal block
available for output as well. It is recommended to use this terminal block for output connection
when its drawing current of the equipment is over 10A. The wring configuration is shown in
the following diagram. Refer to the procedures as below,
Remove the small cover of the terminal block;
Use AWG14 (2.1mm2 ) wires for wiring configuration;
Upon completion of the wiring configuration, please check whether the wires are securely
affixed;
Put back the small cover to the rear panel.
3.3.2 Operation Procedures of External Battery for Long Backup Time models
The battery connection procedures are very important. Any incompliance may result in the risk of
electric shock. Therefore, the following steps must be strictly complied with.
1. Firstly connect the batteries in series of a battery pack to ensure proper battery voltage that is
36Vdc for C1KS_E, 72Vdc for C2KS_E and 96Vdc for C3KS_E.
2. A battery cable for connection of the external battery pack comes with the UPS, one end of the
external battery cable is a plug for connection to the UPS, the other end has 3 open wires for
connection to the output of the battery pack.
3. Connect the external battery cable to the output terminals of the battery pack (DO NOT
connect the plug of the cable to the external battery socket of the UPS first. Otherwise, it may
cause electric shock). Connect the red wire to the: + terminal of the output of the battery
pack. The black wire is connected to the - terminal of the output of the battery pack. The
green/yellow wire is grounded for protection purpose.
4. Connect the plug of the external battery cable to the external battery socket on the rear panel of
the UPS to complete the connection procedure.
-10-
RS232
RS232
RS232 interface It is used to communicate the UPS through a computer which has WinPower
software installed on it for power monitoring and management.
-11-
2. Optional accessories
Intelligent Slot
Intelligent Slot: It is compatible with optional communication cards, please consult the distributor
or service center for further details.
a. AS400: Dry-contact closure interface.
b. WebPower Card(SNMP) : Remote monitoring and management of your UPS system over the
network.
c. CMC: It is a Central monitor card and gives an easy and simple way to achieve remote
monitoring and controlling of all the UPSs at the same time.
d. USB+RS232 card
* Note
1. Remove the cover of the intelligent slot before installation of an optional card.
2. Refer to some other relative documents for the use of the WinPower software and the
AS400 card, WebPower(SNMP)card or WinPower CMC card. please consult the
distributor or service center for further details if you have any questions.
a
b
-12-
4 OPERATION
4.1 Display and Control Panel
3# Load/battery capacity indicator
1# Fault indicator
7# Bypass indicator
8# Utility power indicator
9# Inverter indicator
ON/OFF
TEST/
1. ON/OFF button:
The ON/OFF button is used to power ON or OFF the UPS:
1) Turn on the UPS system:
By pressing the ON/OFF button for more than 1 second to turn on the UPS system.
2) Turn off the UPS system:
By pressing the ON/OFF button again for more than 1 second, the UPS system will be
powered off.
2. TEST/
button
The TEST/
button provides the following functions:
1) Battery self-diagnosis
When the UPS is operating in AC mode (Utility Power mode), by pressing the TEST/
button for more than 2 seconds, the UPS will perform battery self-diagnosis for 10 seconds.
2) Silence function in battery mode
When the UPS is working in battery mode, the UPS gives an audible alarm every four seconds,
by pressing this TEST/
button for more than 2 seconds to silence the audible alarm; By
pressing it again for more than 2 seconds to resume the audible alarm.
* Note: The alarm silence function of the TEST/
button is valid only in battery mode.
It cannot silence other fault warning alarms of the UPS system
3. LED indicators
The LEDs display contains Fault indicator, Load/battery capacity indicators, Bypass indicator,
utility power indicator, Inverter indicator and Battery indicator.
-13-
Indicator
Color
Description
1#
Fault indicator
Red
2#
Orange
3#
Green
4#
Green
5#
Green
6#
Green
7#
Bypass indicator
Orange
8#
Green
9#
Inverter indicator
Green
10#
Battery indicator
Orange
ON/OFF
TEST/
-14-
2. If output overloaded, the load level indicators will be turned on and alarm will beep twice
every second. You should get rid of some unnecessary loads one by one to decrease the loads
connected to the UPS less than 100% capacity of the UPS.
3. If the battery indicator blinks, it indicates that no battery is connected to the UPS or battery
voltage is too low. You should check if the battery pack is properly connected to the UPS. If
the connection between the battery pack and the UPS is confirmed without any problem, it
may be due to the defect or aging of the battery, please refer to the troubleshooting in
chapter 6 to solve the problem accordingly.
* Note Connection to the power generator should be made according to the following
steps:
Activate the power generator and wait until the operation is stable before connecting
the output of the power generator to the UPS (be sure that the UPS is in idle mode).
Then, turn on the UPS according to the start-up procedure. After the UPS is turned
on, the loads are connected one by one.
It is recommended that the capacity of the AC generator chosen should double that of
the UPS.
ON/OFF
TEST/
2. When the battery capacity decreases, the number of battery capacity indicators turned on will
decrease. If the battery voltage drops to the pre-alarm level (capable of maintaining the backup
time for more than 2 minutes for standard models), the alarm will beep every second to remind
the user of insufficient battery capacity. Then, the load operations should be carried out
promptly and the load should be eliminated one by one.
3. It is possible to check the backup function of the UPS even though utility power is not
connected. The UPS can be powered up in battery mode.
-15-
ON/OFF
TEST/
Without supply of the utility power to the UPS, press the ON/OFF button for more than 1
second until the buzzer beeps. In the power-on process, the UPS has the same operation as if it
is connected to utility power except that the utility power indicator is not turned on and the
battery indicator is turned on instead.
2. Turn off the UPS
The operation of turning off the UPS is shown as follows:
1) Completely power off the UPS in AC mode
Press the ON/OFF button persistently for more than 1 second to power off the UPS. If it is set
up to supply output in bypass mode by WinPower software, the bypass indicator will be turned
on to indicate that the UPS is working in bypass mode. In order to cut off the output from the
UPS, simply cut off the utility power supply. Finally, not any display is shown on the front
panel and no output is available from the UPS outlets.
2) Completely power off the UPS in Battery mode
Press the ON/OFF button persistently for more than 1 second to power off the UPS. When
being powered off, the UPS will start self-diagnosis and all the load/battery capacity indicators
will be turned on and off one after another. Finally, not any display is shown on the front panel
and no voltage output is available from the UPS outlets.
4.3.3 Audible alarm and LED indication of UPS operating status and faults
Solid On
Flash
Depending on other conditions
-17-
S/
N
Operating status
LED indicators
1#
AC
0%--35% load
mode
36%--55% load
2#
56%--75% load
76%--95% load
96%--105% load
Battery
0%--25% of battery
mode
capacity
3#
4#
5#
6#
7#
Audible alarm
8#
9#
10#
None
None
None
None
None
second
26%--50% of
battery
capacity
8
battery
capacity
of
battery capacity
100%
Once every 4
seconds
76%--100%
10
Once every 4
seconds
51%--75% of
Once every 1
of
Once every 4
seconds
Once every 2
Continuously beep
battery
capacity
Once every 4
seconds
11
Bypass mode
12
minutes
14
15
Twice every 1
second
Continuously beep
output
16
Over temperature
17
Inverter fault
18
19
20
Over charging
21
Battery fault
22
or
disconnected
Continuously beep
Continuously beep
Continuously beep
Continuously beep
Continuously beep
Once every 2
with
minutes
protective ground
23
24
Once every 1
second
-18-
Continuously beep
5 MAINTENANCE
5.1 Battery Maintenance
The battery is the key component of the UPS. The battery life depends on the ambient
temperature, charge and discharge times. High ambient temperature and deep discharge will
shorten the battery life.
1. Sealed lead acid maintenance-free battery is used in the standard models. When being
connected to the utility power whether the UPS is turned on or not, the UPS keeps charging the
battery and also offers the protective function of over-charging and discharging.
2. Keep the ambient temperature between 15 and 25
3. If the UPS has not been used for a long period, charging is recommended at the intervals of 3
months.
4. Normally, the battery should be charged and discharged every 4 to 6 months. Charging should
begin after the UPS shuts down automatically in the course of discharging. In the regions of
hot climates, the battery should be charged and discharged every 2 months. Moreover, the
standard charging time should be not less than 10 hours.
5. Batteries should not be replaced individually. All batteries should be replaced at the same time
following the instructions of the battery supplier.
6. Under normal conditions, the battery life lasts 3 to 5 years. In case the battery is found not in
good condition, earlier replacement should be made. The battery should only be replaced by
qualified service personnel.
* Note
1. Prior to battery replacement, the UPS must be turned off and disconnected from utility
power.
2. Metal objects such as rings and watches should be removed.
3. Use the screwdriver with insulated handle. Tools and other metal objects should not
be placed on the battery.
4. Short circuit or reverse connection between the positive and negative terminals of the
battery is strictly forbidden.
Disconnect the mains input to simulate mains failure, the UPS should transfer to battery mode
and operate normally; then recover the mains input, the UPS should transfer to normal AC
mode and operate normally
3. Check the LED indicators of the UPS
During the checkup processes stated above, check that the LED indication of the UPS
complies with the UPS operating mode.
6 TROUBLESHOOTING
The troubleshooting chart, Table 6-1, covers most of the difficulties that you may encounter under
normal operating conditions. Such information can be used to determine whether the fault is
caused by external factors or how to tackle the problem. If the fault still persists, please contact
the distributor or service center as soon as possible.
Table 6-1 troubleshooting table
Problem
Possible cause
solution
The voltage or
frequency of the
utility power is out of
the input range of the
UPS
Maybe reversed
polarities (L, N) of
the site wiring. The
alarm beeps once
every 2 minutes
-20-
The #1 Fault LED and #2 The UPS overloaded Check the load and remove the non-Critical
LED are on, the buzzer
or the load device is equipment. Recalculate the load power and
beeps continuously
faulty in battery mode reduce the number of loads connected to the
UPS. Check whether the load device is faulty
The #1 Fault LED and #2 Fan of the UPS is not Please contact the distributor or Service
LED and #6 are on, the
connected or faulty
center
buzzer beeps once every
second
The #1 Fault LED and #2 The UPS output is
LED and #5 LED are on, short circuited
the buzzer beeps
continuously
Battery is not
connected or its
voltage is too low.
The UPS is
overloaded
Battery aged
When you contact the distributor or service center reporting UPS fault, please provide the
following information:
The UPS model and its serial No.
The date when the problem arose.
Complete descriptions of the problem, including LED indications, power condition, load
capacity, audible alarm and configuration of battery pack (if Long Backup time models).
7 SPECIFICATIONS
7.1 Electrical
Model
C1K_E
Rating
Input
Output
C1KS_E
C2K_E
1kVA/800W
C2KS_E
C3K_E
2kVA/1600W
C3KS_E
3kVA/2400W
Input
Nominal voltage
220VAC
Voltage range
115VAC300VAC
Frequency
50/60 Hz (auto-sensing)
Power factor
0.98
Output
Rated voltage
220VAC
Power factor
0.8
Voltage precision
2%
Output
AC mode
frequency
Battery mode
50/60 0.2 Hz
108%5%<Load150%5% : 47s25s
overload capacity
150%5%< Load <200%5% : 25s300ms
Utility power25
Load 200%5%
: 300ms
Transfer time
Battery
Crest factor
3:1 (max)
nominal voltage
36VDC
72VDC
96VDC
Quantity
Backup Time25
(Standard models)
7.2 Mechanical
Model
W*H*D(mm)
Weight(kg)
C1K_E
145220355
15 kg
C1KS_E
145220355
9 kg
C2K_E
190318383
28 kg
C2KS_E
190318383
14 kg
C3K_E
190318433
33 kg
C3KS_E
190318433
15 kg
7.3 Environmental
Item
Ambient temperature
Normal range
040
Humidity
Altitude
Storage temperature
-1545
Standard
Level
ESD
IEC61000-4-2
LEVEL4
RS
IEC61000-4-3
LEVEL3
EFT
IEC61000-4-4
LEVEL4
Surge
IEC61000-4-5
LEVEL4
7.5 Safety
Comply with IEC62040-1 and CE requirements.
-23-
8 WARRANTY
Santak Corp. offers the buyer and the client (hereinafter referred to as 'the buyer') the following
limited warranty for repair:
Starting from the initial date when the buyer purchases the product from Santak or the
distributor/the reseller of Santak, the Uninterruptible Power System and its components related in
this 'user manual' will not be short of materials and services under normal use, service and
maintenance within three years. The foregoing warranty card is only acceptable warranty card
unless other reasonable commercial agreements with specified purposes have been reached. In
certain places where local laws have special provisions for the term of warranty, the foregoing
term shall not be applicable. This warranty offers special legal rights. You are able to obtain other
different pursuant to local laws. The buyer is responsible for certain service and maintenance
expensive. The following situation is not covered by warranty: finished goods lost or serial
number manipulated, loss or damage due to force majeure or external reasons, misuse, accident,
negligence, unauthorized alternation or repair, overuse, violation of operation stipulations.
Warning: The warranty does not cover any loss caused by the over discharge of the battery. In
order to prevent over discharge, when utility power supply is cut off, do not keep the UPS
working in battery mode for more than two days without recharging of the battery. Moreover, the
battery should be charged again at the interval of 4 to 6 months.
With the warranty period of three years, in case if any damage of the machine is covered by the
warranty, Santak shall offer repair or replacement according to its own means. In case of need for
the warranty services, please contact your local Santak service center. The transportation charges
shall be borne by the buyer.