- The document is a technical offer from Paradigm Engineers & Consultants Pvt. Ltd. for MLDB & EMLDB systems for Jindal Steel & Power Ltd.
- It includes bill of materials, technical specifications, and dimensions for the MLDB and EMLDB panels with details of components like MCCBs, contactors, instruments, busbars, cables, etc.
- The panels will have 800A and 630A main incomers respectively along with 125A outgoing feeders and control wiring as per specifications provided in the document.
- The document is a technical offer from Paradigm Engineers & Consultants Pvt. Ltd. for MLDB & EMLDB systems for Jindal Steel & Power Ltd.
- It includes bill of materials, technical specifications, and dimensions for the MLDB and EMLDB panels with details of components like MCCBs, contactors, instruments, busbars, cables, etc.
- The panels will have 800A and 630A main incomers respectively along with 125A outgoing feeders and control wiring as per specifications provided in the document.
- The document is a technical offer from Paradigm Engineers & Consultants Pvt. Ltd. for MLDB & EMLDB systems for Jindal Steel & Power Ltd.
- It includes bill of materials, technical specifications, and dimensions for the MLDB and EMLDB panels with details of components like MCCBs, contactors, instruments, busbars, cables, etc.
- The panels will have 800A and 630A main incomers respectively along with 125A outgoing feeders and control wiring as per specifications provided in the document.
- The document is a technical offer from Paradigm Engineers & Consultants Pvt. Ltd. for MLDB & EMLDB systems for Jindal Steel & Power Ltd.
- It includes bill of materials, technical specifications, and dimensions for the MLDB and EMLDB panels with details of components like MCCBs, contactors, instruments, busbars, cables, etc.
- The panels will have 800A and 630A main incomers respectively along with 125A outgoing feeders and control wiring as per specifications provided in the document.
Kindly accept our sincere regards for your valuable inquiry. In inviting reference to above kindly find our offer attached for your Plant.
Kindly find the detailed offer attached herewith. Hope you shall find the offer in line with your requirement and we are sincerely looking forward to your valuable order. In case you require any further clarification, kindly feel absolutely free to contact us.
Thanking you and assuring you for our best services,
Yours faithfully
For PARADIGM ENGINEERS & CONSULTANTS PVT.LTD.
Diptendu Patra
( 09614328514 )
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 2 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
uaLe : 13.03.2012 age no. 3 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
aradlgm lnLegraLlng luLure Technical Details
System Description
1. SYSTEM PARAMETER:- AMBIENT TEMPERATURE 35DEG. C MAXIMUM AMBIENT AIR TEMPERATURE 50DEG. C.
REFERENCE AMBIENT TEMPERATURE FOR DESIGN 50DEG. C 2. MAIN SYSTEM 3PH.,4W,AC,50HZ.6% RATED OPERATIONAL VOLTAGE 415V10% AC NEUTRAL SYTEM SOLIDLY EARTHED ALTITUDE <100 MTRS HUMIDITY 90% SYSTEM FAULT LEVEL 50KA FOR 1 SEC AC CONTROL VOLTAGE 240V AC 3. CONSTRUCTION TYPE OF SWITCHBOARD SINGLE FRONT INSTALLATION IN DOOR LOCATION FLOOR MOUNTED MOUNTING LIFTING HOOK
ADDITIONAL BASE CHANNEL FOR EMBEDMENT IN FOUNDATION PROVIDED 75MM HEIGHT OF ISMC FRONT & REAR ACCESS HINGED DOOR FUTURE EXTENSION BOTH SIDE DEGREE OF PROTECTION IP- 42 SHEET STEEL THICKNESS SHEET THICKNESS FOR , 2 MM THICK WITH BASE CHANNEL ISMC 75MM. 3.10 PAINTING PROCEDURE PRE-TREATMENT & POWDER COATING AS PER 10 TANK PROCESS MATERIAL POWDER COATED SHADE INSIDE & OUTSIDE RAL 7035 3.11 NAME PLATE NAME PLATE MATERIAL AL. ANODIZED COLOUR OF LETTERING WHITE LETTERS OF BLACK BACKGROUND SIZE OF LETTERING/NAME PLATE 25MM FOR MCC NAME & 5MM FOR FEEDER NAME
IDENTIFICATION OF EQUIPMENT MOUNTED INSIDE PANEL SELF- ADHESIVE STICKERS 4 BUSBARS/CONNECTIONS 4.1 MAIN BUSBARS SYSTEM 3PH. 4W, R,Y,B,N
RATED SHORT TIME WITHSTAND CURRENT 50KA DURATION OF SHORT TIME RATING 1 SEC RATED CURRENT AS REQUIRED MATERIAL ALUMINIUM INSULATION (EXCEPT AT JOINTS & TOP- HEAT SHRINKABLE SLEEVE
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 4 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
aradlgm lnLegraLlng luLure OFFS)
LOCATION/ARRANGEMENT OF MAIN BUSBARS IN BUSBAR CHAMBER AT TOP/HORIZONTAL COLOUR COADING R / Y / B / BL 4.2 NEUTRAL BUSBAR NEUTRAL BUSBARS SIZE AS REQUIRED (HALF OF THE PHASE BUSBARS) MATERIAL ALUMINIUM
RATED SHORT TIME WITHSTAND CURRENT 50KA DURATION OF SHORT TIME RATING 1 SEC
LOCATION/ARRANGEMENT OF MAIN BUSBARS ALONG BUSBAR COLOUR COADING BLACK 4.3 EARTH BUSBAR EARTH BUSBARS SIZE AS REQUIRED MATERIAL GI 4.4 VERTICAL BUSBAR, IF APPLICABLE SYSTEM 3PH. 4W, R,Y,B,N RATED CURRENT AS PER CONNECTED LOAD
RATED SHORT TIME WITHSTAND CURRENT 50KA FOR 1 SEC MATERIAL ALUMINIUM 5.0 WIRING 5.1 POWER CIRCUIT INSULATION GRADE 660V/1100V AC SIZE AS PER FEEDER RATING COLOUR COADING FOR IDENTIFICATION COLOUR SLEEVES AT TERMINATION FOR HIGHER RATING FDRS & COLOUR CABLE FOR SMALL RATING FDRS. TERMINATION WITH CRIMPING TYPE COPPER LUGS 5.2 AUXILIARY CIRCUIT (PVC INSULATED CU. STRANDED) INSULATION GRADE 1100V AC 5.3 SIZE OF WIRE (CONTROL & AUXILIARY CIRCUITS) CT CIRCUIT 2.5SQ.MM (RED-R PH, YELLOW-Y PH, BLUE-B PH.) CONTROL 1.5SQ.MM (RED-R PH, YELLOW-Y PH, BLUE-B PH.) AUXILIARY BUSWIRE 1.5SQ.MM (PHASE-RED, NEUTRAL-BLACK) CIRCUIT IDENTIFICATION PRINTED FERRULES PVC SLEEVE AT TERMINATIONS END (AS PER CONTROL CIRCUIT.)
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 3 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
aradlgm lnLegraLlng luLure Bill of Materials
EMLDB SL.NO DESCRIPTION QTY MAKE A 630A Main Incomer 2 Nos 1 630 A 4P, 50KA, Microprocessor Base MCCB with O/L, S/C, E/F Protection & RHOM with 1 C/O Aux. Contact 2 Schneider 2 630A, TPN Contactor with 2NO+2NC Aux. Contact Coil voltage - 240V AC 2 Schneider 3 SIF-96, 0- 600A, Digital Ammeter with CTR-600/5 A 2 Conzerv 4 SIF-96, 0-500V Digital Voltmeter 2 Conzerv 5 Ammeter Selector Switch 2 Recom 6 Voltmeter Selector Switch 2 Recom 7 600/5A, 15VA, Class -1 Current Transformer 6 Kappa 8 LED Type R / Y / B Phase Indication Lamp , 240V AC 6 Schneider 9 LED Type ON / OFF Indication Lamp , 240V AC 4 Schneider 10 6 A,10KA, SP MCB 14 Schneider 11 Neutral Link 4 Reputed 12 Caselt Key for Mechanical Interlock 1 Reputed B Control Feeder 1 No 1 415V/240V AC,1KVA Resin Cast Control Transformer with +2.5%, +5% Primary Taps 1 Gupta 2 6A,10KA,DP MCB 1 Schneider 3 10A,10KA,DP MCB 1 Schneider 4 LED Type Indication Lamp 1 Schneider 5 6A,10KA,SPN,MCB 1 Schneider C Bus bar and Earth Bus Bus bar with heat shrinkable PVC sleeves supported on Glass Epoxy Bus bar support Phase : 1 No x 75 x 10 mm per phase, Al Neutral: 1 No. X 75 x 6 mm, Al Control Bus : 2 Nos x 15 x 3 mm, Copper Earth Bus : 1 No. x 50 x 6 mm, GI D OUTGOING FEEDERS 8 Nos D1 125A Power Supply Feeder 8 Nos 1 125A 4P 50 KA Microprocessor Base MCCB O/L, S/C, E/F Protection & RHOM, 1C/O Aux. Contact 8 Schneider 2 SIF-96, 0- 125A, Digital Ammeter with CTR-125/5 A 8 Conzerv 3 Ammeter Selector Switch 8 Recom 4 125/5A, 5VA, Class - 1 Current Transformer 24 Kappa 5 LED Type ON Indication Lamp. 8 Schneider 6 6 A,10KA,SP MCB 8 Schneider 7 Neutral Link 8 Reputed Tentative Panel Dimension : (H) 2375 mm x ( L/W ) 3000 mm x (D) 600 mm
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 6 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
aradlgm lnLegraLlng luLure
MLDB - 1 SL.NO DESCRIPTION QTY MAKE A 800A Main Incomer 2 Nos 1 800 A 4P, 50KA, Microprocessor Base MCCB with O/L, S/C, E/F Protection & RHOM with 1 C/O Aux. Contact 2 Schneider 2 800A, TPN Contactor with 2NO+2NC Aux.Contact Coil voltage - 240V AC 2 Schneider 3 SIF-96, 0- 800A, Digital Ammeter with CTR-800/5 A 2 Conzerv 4 SIF-96, 0-500V Digital Voltmeter 2 Conzerv 5 Ammeter Selector Switch 2 Recom 6 Voltmeter Selector Switch 2 Recom 7 800/5A, 15VA, Class -1 Current Transformer 6 Kappa 8 LED Type R / Y / B Phase Indication Lamp , 240V AC 6 Schneider 9 LED Type ON / OFF Indication Lamp , 240V AC 4 Schneider 10 6 A,10KA, SP MCB 14 Schneider 11 Neutral Link 4 Reputed 12 Caselt Key for Mechanical Interlock 1 Reputed B Control Feeder 1 No 1 415V/240V AC,1KVA Resin Cast Control Transformer with +2.5%, +5% Primary Taps 1 Gupta 2 6A,10KA,DP MCB 1 Schneider 3 10A,10KA,DP MCB 1 Schneider 4 LED Type Indication Lamp 1 Schneider 5 6A,10KA,SPN,MCB 1 Schneider C Bus bar and Earth Bus Bus bar with heat shrinkable PVC sleeves supported on Glass Epoxy Bus bar support Phase : 2 Nos x 75 x 10 mm per phase, Al Neutral: 1 No. X 75 x 10 mm, Al Control Bus : 2 Nos x 15 x 3 mm, Copper Earth Bus : 1 No. x 50 x 6 mm, GI D OUTGOING FEEDERS 15 Nos D1 125A Power Supply Feeder 15 Nos 1 125A 4P 50 KA Microprocessor Base MCCB O/L, S/C, E/F Protection & RHOM, 1C/O Aux. Contact 15 Schneider 2 SIF-96, 0- 125A, Digital Ammeter with CTR-125/5 A 15 Conzerv 3 Ammeter Selector Switch 15 Recom 4 125/5A, 5VA, Class - 1 Current Transformer 45 Kappa 5 LED Type ON Indication Lamp. 15 Schneider 6 6 A,10KA,SP MCB 15 Schneider 7 Neutral Link 15 Reputed Tentative Panel Dimension : (H) 2375 mm x ( L/W ) 4100 mm x (D) 600 mm
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 7 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
Sl. No. Description UNIT PRICE ( INR ) Qty (Sets) AMOUNT (INR) Price Schedule and Break-up 1. Supply of EMLDB 6,65,000.00 5 Nos 33,25,000.00 2. Supply of MLDB 10,55,000.00 5 Nos 52,75,000.00 Total Package Price 86,00,000.00
Commercial Terms & Conditions
1 Prices Prices quoted are Ex-Works Basis.
2 Taxes & Duties Sales Tax (Central or State), Excise, Octroi and / or any other levy as applicable at the time of delivery shall be charged extra. Excise Duty 10.30 % CST 2 % Against Form `C` Service Tax 10.30 % (If Applicable). 3 P & F 2.5% Extra on Basic Prices.
4 Freight Charges Freight charges to be borne by Customer.
5 Transit Insurance Transit Insurance shall be in Customers Scope. In case the Insurance to be arranged by us, an additional amount @ 0.1% shall be charged on total invoice value.
6 Payment Terms 20% Advance along with P.O. and balance 80% along-with all taxes and duties against Proforma Invoice after inspection at our works but before dispatch.
7 Validity The quotation is valid for acceptance 30 days.
8 Delivery 14 - 15 Weeks Ex-works from the date of approved drawings.
uocumenL 8eference no. : LCL/Cll/11-12/3116
uaLe : 13.03.2012 age no. 11 of 11 www.parad|gmeng|neers.com An ISC 9001-2008 Cert|f|ed Crgan|sat|on
aradlgm lnLegraLlng luLure
9 Force Majeure Every effort will be made to deliver the goods within the scheduled deliver period, but we take no responsibility for any delay occasioned by causes beyond our control known as Force Majeure. Delayed delivery will not be the reasons for the cancellation of the contract. NO claim for refund of deposits / advance or damages will be entertained. 10 Inspection Inspection of goods will be arranged at our Jamshedpur Works at Purchasers Cost failing that our guarantee before dispatch of goods shall have to be accepted.
11 Warranty All items supplied by us carry manufacturing warranty for their satisfactory working for 18 months from the date of dispatch / 12 months from the date of commissioning whichever is earlier. 12 Insurance / Indemnity / Guarantee Unless instructed otherwise, the goods will be dispatched at buyers risk. We however, offer our indemnity guarantee service by which we ensure satisfactory working of the instruments at the destination after delivery. For this service an additional amount of 3 % (6% for the glass parts) is charged. Any breakage or loss must be intimated to us within 7 days from the date of receipt of goods, otherwise we shall not entertain claim.
13 Jurisdiction All disputes relating to the above contract are subject to East Singbhum Jurisdiction. 14 Order to be placed on M/s. Paradigm Engineers & Consultants Pvt. Ltd. A-3 ,Phase-1, Adityapur Industrial Estate, Adityapur, Jamshedpur 832 109.