Electrical Works BoQ RA4ATC2 PDF
Electrical Works BoQ RA4ATC2 PDF
Electrical Works BoQ RA4ATC2 PDF
BSR Ref
DESCRIPTION
WIRING
Providing Wiring for the light point with 2x1.5sq. mmPVC insulated multistrand copper conductor cable in recessed
25mm dia HDPE pipe I/c all accessories as required for light point . Including providing accessories, Platinum brand
switches 6A 1-gang / 2gang White colour Code CQ000501/02 for front cover. 6A 1 gang switch Code CQAT0006,
Outer Plate for 1 module Code CQAT0501 for 2 module Code CQAT0502. Inner Plate for 1 module Code CQAT1501
for 2 module Code CQAT1502. Platinum brand switches 6A 4-gang White colour Code CQ000504 for front cover.
6A 1 gang switch Code CQAT0006, Outer Plate for 4 module Code CQAT0504. Inner Plate for 4 module Code
CQAT1504 Havells make. Use maximum 3 CFL fixture by 1 switch. Maximum 2single tube light fitting by 1 switch
and double tube light fitting by 1 switch.
1a
1b
1c
QTY.
UNIT
25
13
15
Point
Point
Point
WC0391
Providing Wiring for the light point with 2x2.5sq. mm PVC insulated multistrand copper conductor cable in recessed
25mm dia HDPE pipe I/c all accessories as required for light circuit wiring .
320
WC0400
Providing Wiring for the power point with 2x4sq. mm PVC insulated multistrand copper conductor cable in recessed
25mm dia HDPE pipe I/c all accessories as required for power wiring .
425
Each
IL0170
IL0201
Supplying of Tubelight fitting recess mounted 1x36w/40w fluorscent. Code No.LHCF 1136811 White Havells/Equivalent.
16
Each
AR01
Supplying of Surface mounted ceiling fitting square decorative downlighter with HF electronic ballast and translucent
diffuser, pre-fitted with flat profile, for 1x25W CFL lamp LONON SQUARE White Code No.LHDC70125670 Havells/Equivalent.
Each
Page 1 of 10
RATE (Nu.)
S.NO.
BSR Ref
DESCRIPTION
QTY.
UNIT
AR02
Supplying of Surface mounted ceiling fitting round decorative downlighter with HF electronic ballast and translucent
diffuser, pre-fitted with flat profile, for 1x25W CFL lamp Surface Round White Code No.LHDC71125670 Havells/Equivalent.
Each
AR03
Supplying of Recessed modular downlighter with drop glass for 1x150W MH DE-White Code No.LHOM74115399
with 150W MH lamp. Havells/Equivalent.
15
Each
AR04
Supplying of Bulkhead fitting for 1x 15W CFL White Code No.LHKL01160099 Havells / Equivalent
Each
SS0220
Supplying and fixing 16 Amp 6pin Switch Socket Combined shuttered having rectangle edge (Crabtree/ equivalent).
15
Each
LS0127
17
Each
AR05
Each
10
AR06
17
Each
17
Each
21
Each
45
C
1
EI0041
EI0002
1a
PC0153
3-1/2Cx70mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB (Sub
distribution board). Actual length will be as per site condition.
Page 2 of 10
RATE (Nu.)
S.NO.
BSR Ref
1b
PC0150
DESCRIPTION
3-1/2Cx25mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB (Sub
distribution board). Actual length will be as per site condition.
QTY.
UNIT
Supplying of the following items including all accessories whether specifically mentioned or not but required to make
the Installation complete in all respect.
2a
GB0541
8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB (Level 1) (SQCA Appd)
Each
2b
2c
2d
GB0355
Each
GB0270
6Amp SPMCB
Each
GB0272
16Amp SPMCB
15
Each
GB0225
Supplying of 160A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 36kA, 4pole
415volt, A.C complete with all accessories etc. as required at the MCPB.
Each
GB0006
Copper busbar chamber of size 200Amp 4x450mm including all accessories etc. at the MCPB.
Set
AR07
Providing and fixing 63A 3-Phase 4 wire system Energy Meter at the apprppriate location in consultation with BPCL.
Set
each
ROUTE MARKER
Providing and making route marker of size 600mmx600mm at bottom and 500mmx500mm at top with a thickness of
100mm including inscription as required.
1a
CL0070
Installation, testing and commissioning of end termination with single/double compresion gland for PVC insulated and
sheathed aluminium conductor cable of 1.1kV grade including connections etc. as required.
1a
1b
CL0110
6/10/16/25mm dia
each
CL0115
82/85mm dia
each
Page 3 of 10
RATE (Nu.)
S.NO.
BSR Ref
DESCRIPTION
QTY.
UNIT
EI0340
EI0440
1
1
each
each
each
each
280
240
G
1
1a
1b
Installation, testing and commissioning of TPN DB (DIN type) single/double door complete with all accessories to
accommodate incoming MCB/MCCB/RCCB 4pole 32/40/63A sensitivity 30/100/300mA and outgoing SPMCB
6A/16A in prefabricated MS surface /MS cubical panel board including drilling holes, connections etc. as required.
1a
EI0545
8way TPN DB
SUB-TOTAL FOR INSTALN. of DISTRIBUTION BOARD
1
1a
EI0610
Providing and fixing medium volt danger notice plate made of mild steel and painted with viterous enamelled white
paint on both sides, and with inscription in signal red colour written as 440V/1100V in Dzongkha/English on front side
as required on prefabricated MS surface/MS cubical control panel board on surface including drilling holes etc. as
required.
200mmx150mmx2mm
SUB-TOTAL FOR METAL PANEL BOARD
ET0075
ET0121
Supplying & drawing 14SWG copper wire for loop earthing / earthing for electrical equipments.
LG0002
P/F of lightning arrestor final made of 25mm dia 900mm long GI tube having five prong at top with 85mm dia 6mm
thick copper plate I/c holes and spring washer etc. as required.
Page 4 of 10
RATE (Nu.)
S.NO.
BSR Ref
DESCRIPTION
QTY.
UNIT
ET0001
Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure with cover
plate having locking arrangement & watering pipe. (For Lightning Arrestor) NOTE: This earthing shall be
independently looped to each other and not to be interconnected with the electrical earthing.
Each
ET0001
Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure with cover
plate having locking arrangement & watering pipe. (For General electrical earthing)
Each
10
K
1
1a
PO0021
HDPE PIPE
Providing and Laying HDPE Pipe including trenching and refilling.
(Pl. refer page 47 civil BSR 2009)
Providing & laying 90mm dia HDPE pipe for Main Incoming BPC Cable.
SUBTOTAL FOR HDPE PIPE
In Words:
Page 5 of 10
RATE (Nu.)
AMOUNT (Nu.)
Page 6 of 10
AMOUNT (Nu.)
Page 7 of 10
AMOUNT (Nu.)
Page 8 of 10
AMOUNT (Nu.)
Page 9 of 10
AMOUNT (Nu.)
Page 10 of 10