596 B 4
596 B 4
596 B 4
The new GALAXY Switchmode Rectifier 596B4 provides the highest-quality dc power for telecommunications and data processing systems and their batteries.
The GALAXY Switchmode Rectifier 596B4 integrates the latest switchmode technology with superior power, protection, and control features in a compact, cost-efficient power-conversion system. Designed as a key element in the Tyco Electronics GALAXY Power System (GPS) 2424 Battery Plants, the 596B4 rectifier converts ac input voltage into the dc-voltage level required to power end-user equipment, as well as to float-charge batteries at precise voltage levels. Operation over a wide temperature range (40C to +85C) makes the 596B4 suitable for controlled and uncontrolled environments.
Benefits Compact, Power-Packed For high power density, Tyco Electronics revolutionary technology packs ever-greater power into ever-shrinking packages. The result is a rectifier that packs more power per cubic inch, weighs just 20 lb. (9 kg), requires minimal maintenance, and frees up valuable floor space. Quick Setup Installation is swift and straight-forward. Interconnections to ac-input, dc-output, and control signals are automatic during insertion. No adjustments or settings are required.
Economical Operation The 596B4 exhibits an excellent 0.98 power factor and high efficiency, thereby minimizing ac usage and contributing to highly reliable, low-cost operation. Extended Service Life For greater reliability and robust operation, the 596B4 features parallel operation with digital load sharing, which evenly balances the load current among multiple rectifiers in the event one fails or is removed from the system. Fail-Safe Performance Hot-insertion capabilities allow for rectifier replacement without system shutdown; softstart circuits and inrush control prevent upstream breakers from tripping. To avoid load or rectifier damage, the 596B4 is
equipped with overvoltage/ overcurrent protection. A variable-speed fan maintains safe operation in 40C to 85C ambient temperatures. The 596B4 operates with or without batteries. Simplified Control/Monitoring A digital meter indicates current, temperature, or rectifier alarm messages for convenient system status. A microprocessor manages all internal alarm and state decisions, and, for more extensive monitoring and control capabilities, provides serial digital communication with the GALAXY family of controllers. Overall, the unit is easy to install with minimal labor, lowers typical operating and installation expense, and
delivers the reliable high performance required by the most stringent telecommunication and data processing applications. The 596B4 is UL* recognized and CE marked. Features Microprocessor controlled Digital load-sharing 2-wire interface Three-digit meter: current, failure codes, rectifier ID Hot pluggable Compact, modular construction 3000W output (110A at 27.24V) UL Recognized CE marked
* UL is a registered trademark of Underwriters Laboratories, Inc. This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed.
Outline Drawing
Specifications
Electrical Input Nominal Voltage, Single-Phase Voltage Limit, Steady State Frequency Nominal AC Input Current Power Factor Total Harmonic Distortion Output Float/Boost Voltage Limits Regulation (with GALAXY controller) Ripple Noise Output Current Current-Limit Set Point Physical Width Height Depth Weight Environmental Efficiency Operating Temperature Operating Relative Humidity Storage Temperature Storage Relative Humidity Audible Noise EMC Safety/Standards Compliance NEBS Safety Standard CE Marks Control and Monitoring Visual Indicators Meter Control Switch (One) Serial Interface Signaling: Controller-to-Rectifier Serial Interface Signaling: Rectifier-to-Controller
208 Vac / 240 Vac, 2-wire plus ground 176 Vac to 264 Vac 47 Hz to 63 Hz 16.8A at 208 Vac 14.6A at 240 Vac >0.98 from 50% to 110% load <10% from 50% to 110% load 22 Vdc to 30 Vdc 0.5% 100 mVrms <2 mV psophometric -40C to +65C: 110 Adc max +65C to +85C: derate at 2A per C 30 Adc to 110 Adc 5.25 in. (133 mm) 8 in. (203 mm, 5U) 15.5 in. (394 mm) 20 lb (9 kg) >86% from 50 Adc to 110 Adc output current -40C to +85C (-40F to 185F) 0% to 90% (noncondensing) -40C to +85C (-40F to 185F) 5% to 90% 0C to 30C: <52 dBA 31C to 50C: <60 dBA EN55022, CISPR22, Level B, conducted and radiated Evaluated by independent test lab with NRTL status to Telcordia GR63 and GR1089 (including level 3 testing) UL1950, EN60950/IEC950, and CSA* 234/950 UL Recognized (Canada and U.S.), VDE Licensed, CE Marked (meets 73/23/EEC and 93/68/EEC directives) ON (green), STBY (yellow), LIM (yellow), ALM (red), FAN ALM (red) Three digit: current, failure codes, rectifier ID ID/ON/STBY Remote sense, load share, voltage set points, current set points, selective HVSD set points, float/boost mode, HVSD, ON/STBY, lamp test Rectifier current, rectifier temperature, ID, serial number, manufacturing information, RFA, CB, ON/STBY, ACF, phase fail, TA, fan fail
* CSA is a registered trademark of Canadian Standards Assiciation. VDE is a trademark of Verband Deutscher Elektrotechniker e.V. Note: STBY = Standby, EQL = Equalize, LIM = Limit, ALM = Alarm, HVSD = High-Voltage Shutdown, RFA = Rectifier Fail Alarm, CB = Circuit Breaker, ACF = AC Failure, TA = Temperature
Ordering Information
Description 596B4 Switchmode Rectifier +24 Vdc, 100 Adc, 208/240 Vac Comcode 108687765
Europe, Middle-East and Africa Headquarters Tyco Electronics (UK) Ltd Tel: +44 1344 469 300, Fax: +44 1344 469 301 Caribbean-Latin America-Brazil Headquarters Tyco Electronics Power Systems Tel: +56 2 209 8211, Fax: +56 2 223 1477 Asia-Pacific Headquarters Tyco Electronics Singapore Pte Ltd Tel: +65 6416 4283, Fax: 65 6416 4299 India Tyco Electronics Systems India Pte Ltd Tel: +91 80 841 1633 x3001
World Wide Headquarters Tyco Electronics Power Systems, Inc. 3000 Skyline Drive, Mesquite, TX 75149, USA +1-800-843-1797 (Outside U.S.A.: +1-972-284-2626) power.tycoelectronics.com e-mail: [email protected]
Tyco Electronics Corporation reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s) or information. 2007 Tyco Electronics Power Systems, Inc., (Mesquite, Texas) All International Rights Reserved. Printed in U.S.A.
4 DS03-041 Rev 3
March 2007