NetSure 701 A61 20091105

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Platform Power System, NetSure 701 Series

-48 VDC, up to 19.2 kW NetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )

DC Power Solution TM for Business-Critical Continuity

Introduction
Platform Power System NetSure 701 A61 is Emerson next generation system for medium exchanges, rural telecom networks and access networks, 2G and 3G base station, transmission relay station, microwave/satellite communication stations as well as other applications requiring the power up to 19.2 kW. The system can be optimized cost-effectively to meet initial requirements, whilst allowing for easy expansion in the future. Configurable distribution and number of rectifier modules are available to meet various demands

NetSure 701 A61


Configuration Item Rectifier Monitoring module AC input DC distribution Battery routes PS48300-4/2900-Y6 or PS48300-4/2900-W6 Model: R48-3200 or R482900U Optional configuratio 2piece 6pieces Standard configuration: 5 pieces Model: M520S Standard configuration: 1 piece AC input mode:3P+N+PE/380V+SPD 6 BLVD routes:2 9LLVD routes: 3 63A/1P, 2 32A/1P, 2 10A/1P MCB 32A/1P, 6 63A/1P MCB 4 (12V/165Ah) or 3 4 (12V/100Ah)

Battery MCB:3 100A/1P(SFA) Maximum configuration: 3 Temperature sensors, modem

Features
< High flexible configuration to meet various customer requirements, easy for fast construction of communication sites < Hot swap rectifier and controller, high power density < Safety EN60950 < Compliant with global standards delivers quality, performance and dependability < Two over-voltage protection methods for options: hardware protection and software protection. < Perfect battery management includes the LLVD, temperature compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and on-line battery test, etc < The monitoring module can save up to 200 pieces of historical alarm records, and 10 sets of battery test data records < Perfect lightning protection at perfect lightning protection at both AC side and DC side < The high power density rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99

Optional parts

Mechanical Parameter
600 600 2000 (Y6) Cabinet 600 600 1800 (SFA) 600 600 500 (W6) Rectifier 85.3 272 87.9 540 545 350 Battery compartment (accommodating 4 165Ah battery) 540 545 280 (Accommodating 4 100Ah battery) 2000mm cabinet 140 1800mm cabinet 130 500mm cabinet 2.0 50

Size (W D H) (mm)

Cabinet(excludingrectifiers,

Weight (kg)

Monitoring module and Batteries) Rectifier

Technical specifications -Environmental Parameter


Operating Temperature Storage Temperature Relative Humidity Elevation -5 C -40oC 5%RH
o

45 C 70oC 95%RH

2000m (derating is necessary above 2000m)

Platform Power System, NetSure 701 Series


-48 VDC, up to 19.2 kW NetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )
DC Power Solution for Business-Critical Continuity TM

Rectifier Module R48-2900 ,R48-3200 Features


Input voltage Input voltage Power factor THD Output voltage Output power Max output current Efficiency Temperature range RH (non-condensing) EMC Safety Dimensions Weight nominal 200 to 240 Vac permitted variation 85 to 290 Vac 0.99 <5% from 50 to 100% of rated load -42 to -58 Vdc 3200 W 67A 92% or 96% for HE R48-3200 -40 to +75 C for R48-3200 and -40 to +65 C for R48-2900U 0 to 95% EN 300 386:2001, class B & FCC part 15, class B IEC / EN / UL 60950 (H W D) 132 85.3 287 mm, 5.20 3.36 11.3 inches 3.5 kg, 7.7 lbs
o o

Controller: M520S
Intelligent battery management Latest 200 alarm history log Display LCD with 4 16 characters Language: English, Chinese External Communication: RS232(modem) or TCP/IP Protocol: YDN23 Inputs: 8 Digital Inputs Alarms/Events Outputs: 8 Relay Outputs 1A, max 60V Examples of Alarms: DC Power Plant Alarms AC mains failure, Rectifier failure, DC/DC converter failure, High voltage shut-down, Fan failure, Thermal derating

Battery Cabinet (rack)


See separate datasheet for the detailed cabinet (rack) information