Pressure drop calculation theory

Go to pressure drop calculator In this calculator well known equations have been used. Here you can find all of them for your review. First of all, pressure drop through the pipe due to friction and local losses can be calculated as follows:

where is: Dp - pressure drop rho - fluid density view table Q - volumetric flow rate D - pipe diameter lambda - friction coefficient L - pipe length sum ksi - the sum of minor losses coefficient

To calculate mass flow rate following equation has been used:

where is: G - mass flow rate For pressure drop calculation because of friction, viscosity of fluid has to be known. Relation between dynamic and kinematics viscosity is as follows:

where is: mi - dynamic viscosity view table ni - kinematic viscosity view table Velocity of flowing fluid is calculated based on the continuity equation:

where the cross section of round pipe is:

To find out if the flow is laminar or turbulent, Reynolds number must be calculated:

Friction coefficient for laminar flow is:

for flow in hydraulically smooth pipe (Blasius equation):

for turbulent flow with Re<100 000 (Prandtl equation):

for turbulent flow with Re>100 000 (Karman equation):

The boundary layer thickness (delta) can be calculated based on the Prandtl equation as:

and when the boundary layer thickness is bigger than pipe roughness and if the flow is turbulent, than it can be considered as flow in hydraulically smooth pipe and Blasius equation is used.

Pipe Flow 3D - Pressure Drop Theory


This page describes in detail which factors need to be considered when calculating pressure drops through pipe systems, their effects on fluid flow and conditions at the pump inlet, and how Pipe Flow 3D can help with the calculations. Resistance to fluid flow Fluids in motion are subjected to various resistances, which are due to friction. Friction may occur between the fluid & the pipe work, but friction also occurs within the fluid as sliding between adjacent layers of fluid takes place. The friction within the fluid is due to the fluids viscosity. When fluids have a high viscosity, the speed of flow tends to be low, and resistance to flow becomes almost totally dependant on the viscosity of the fluid, this condition is known as Laminar flow. How do you establish the pipework resistance losses? Before the pipework losses can be established, the friction factor must be calculated. The friction factor will be dependant on the pipe size, inner roughness of the pipe, flow velocity and fluid viscosity. The flow condition, whether Turbulent or not, will determine the method used to calculate the friction factor. The starting point must be to find the fluids viscosity. This will be the factor that has most effect on the pipework losses.

Understanding viscosity units (dynamic viscosity)

Many terms can be used to describe a fluid's viscosity (its resistance to flow): Centipoise, Poise, Saybolt Universal (SSU), Saybolt Furol, Ford Cup No. 3, Ford Cup No.4, Redwood No.1, Degrees Engler, Zahn No.1, Zahn No.2 and Zahn No. 3 are some of the scales that have been used in the immediate past. All of these scales have differing upper and lower values and are usually not directly related to each other. Some references may be found in text books which attempt to list equivalent values for these different methods of measuring viscosity. Pipe Flow 3D provides a means of calculating the equivalent centistokes viscosity from some other known viscosity scales. Kinematic viscosity and Reynolds numbers Dynamic viscosity must be converted to its Kinematic viscosity equivalent before the viscosity value can be used to calculate Reynolds numbers and hence friction factors. It is very common today to express dynamic viscosity in centipoise. one Centipoise = 1 mPa.s or 0.001 (kg/m) x s The units of centipoise are: Force per unit area x Time

It is very common today to express kinematic viscosity in centistokes. one Centistoke = 1 mm/s or 0.000001 m/s The units of centistokes are: Length Time Kinematic viscosity is simply: Reynolds numbers Reynolds numbers (Re) describe the relationship between a fluids velocity, the pipe size and the fluids kinematic viscosity. Reynolds number = Fluid velocity x Internal pipe diameter Kinematic viscosity Dynamic viscosity Mass density

Effect of the inner roughness of the pipe The inner roughness of the pipe can create eddy currents. This increases the friction

between the pipe wall and the fluid. The relative roughness of the inside of the pipe is used in determining the friction factor to be used. Relative roughness = Inside pipe roughness Inside pipe diameter

The average inner roughness of commercial pipes: Steel tube Copper tubing Glass tubing Polythene Flexible P.V.C. Rigid P.V.C. Cast iron tube Concrete tube Friction factor chart 0.0460 mm 0.0015 mm 0.0001 mm 0.0010 mm 0.2000 mm 0.0050 mm 0.2600 mm 2.0000 mm

The chart above shows the relationship between Reynolds number and pipe friction. Calculation of friction factors is dependant on the type of flow that will be encountered.

For Re numbers <2300 the fluid flow is Laminar, when Re number is >2300 the fluid flow is Turbulent. Laminar flow (Re < 2300) f = 64/Re Turbulent flow (Re > 2300) 1/sqrt(f) = -1.8 log [ (6.9/Re) + ((k/3.7)^1.11 ] (where k = inner pipe roughness / inner pipe diameter) Most commercial applications involve Turbulent flow. In these cases the inner roughness of the pipework can have a significant effect on the Friction factor. The Relative roughness is the inner roughness divided by the internal diameter of the pipe work. The Friction factor is found by plotting the intersection of Re and Relative roughness, and reading the friction factor on the left hand axis of the chart. The Fluid head loss can be calculated once the friction factor is known. The Pressure drop in pipe work can be calculated from fluid head loss, the density of fluid and the acceleration due to gravity. Calculating the fluid head resistance Fluid head resistance can be calculated from h = f (L/d) x (v /2g) where h = head loss (m) f = friction factor L = length of pipe work (m) d = inner dia of pipe work (m) v = velocity of fluid (m/s) g = acceleration due to gravity (m/s ) Calculating the losses through pipe work fittings The fluid head resistance through various pipe work fittings can be calculated when the 'K' factor of the fitting is known. Manufacturers of pipe work fittings & valves publish 'K' factors for their products. Usually a particular type of fitting from various manufacturers have similar 'K' factors, therefore this computer program tends to use average 'K' factor values. Fluid head loss of these fitting can be calculated from h = total 'K' x v / 2g where

h = head loss (m) total 'K' = total of 'K' factors for each fitting v = velocity of fluid (m/s) g = acceleration due to gravity (m/s ) Note: If the pipework involves different pipe sizes, this calculation must be carried out separately for each pipe size, using the appropriate velocity within that pipe section. The 'K' value of entry & exit points can be taken as 0.8 and 1.0 respectively to calculate the head loss attributable to these features. Calculating the total pressure drop The total fluid head resistance may be used to calculate the pressure required to overcome the resistance to fluid flow. Pd = h x p x g / 100000 where Pd = pressure drop (bar) h = head loss (m) p = fluid density (kg/m3) g = acceleration due to gravity (m/s ) Finally, the fluid is most likely to exit into atmospheric pressure. The difference between the pressure on the fluid surface during storage & the atmospheric pressure must be taken into account in determining the pressure drop to be overcome by the pump. This difference in pressure may be positive (assisting fluid flow) or negative (resisting fluid flow). Summarising the steps to be considered Factors that affect fluid flow Fluid flow in pipes is affected by many different factors:

The viscosity, density, and velocity of the fluid. Changes in the fluid temperature will change the viscosity & density of the fluid. The length, inner diameter, and in the case of turbulent flow, the internal roughness of the pipe. The position of the supply and discharge containers relative to the pump position. The addition of rises & falls within the pipe layout.

The number & types of bends in the pipe layout. The number & types of valves, & other fittings, in the pipe layout. Entrance & exit conditions of the pipe work.

Calculating the fluid head When all of the above information is known, the following steps must be carried out to determine the fluid head necessary to overcome the flow of the fluid through the pipe work layout:

Calculate the Reynolds number Determine if the flow is Laminar or Turbulent Calculate the friction factor for either Laminar flow or Turbulent flow Calculate the fluid head resistance to overcome the flow through the pipe work Determine the K factors for the fittings within the pipe work layout Calculate the fluid head resistance to overcome the flow through the fittings Determine which lengths & components within the pipe work layout are significant in establishing the maximum fluid head to be considered (branch lines may be important).

The effect of fluid density & gravity must be applied to the maximum fluid head to calculate the pressure required to overcome the resistance to fluid flow.