SPECIFICATION
FOR
22.9kV ACSR/AW-TR/OC
Prepared by
M. H. PARK
Checked by
K. S. JEONG
Approved by
C. J. HONG
1. Applicable standard
The construction of cables shall be based on KEPCO ES-6145-0021 & Customer requirement.
2.1 Conductor
The conductor shall be consist of aluminum coated steel wire and aluminum wires.
The conductor shall be circular compacted stranded.
The inside of the conductor is filled with watertight semi-conductive tape.
2.3 Insulation
The insulation shall be extruded of 90℃ grade natural XLPE (Cross-linked Polyethylene).
The average thickness of the insulation shall be 90% of the table and the minimum thickness shall be not less than
80% of the table.
3. Cable identification
One lines of a distinctive marking shall be performed continuously on a suitable place of the outer sheath by
indenting.
4. Test
The following test shall be carried out on complete cable and sample in accordance with manufacturer standard.
1. Construction test
2. Conductor resistance test
3. Insulation resistance test
4. AC voltage test
5. Tracking test
5. Packing
The completed cable shall be wound on a strong reel and lagged securely in order to protect from any possibilities
damage during transportation.
The following information shall be provided on the outside of the flange:
The cable end shall be sealed with end cap in order to avoid water penetration.
FA01-01(0) DAESHIN CABLE CO., LTD. A4(210mm X 297mm)
SPEC. NO. DSA-E906-068
Specification DATE 15-DEC-16
REV. NO. A
for 22.9KV ACSR/AW-TR/OC
DAESHIN CABLE PAGE 3
Conductor screen
Insulation
-Material XLPE(Natural)
Outer sheath
-Color Black
Test Voltage KV 25
Cross-sectional drawing
(22.9KV ACSR/AW-TR/OC)
with rib
5 Outer sheath Extruded of Black track resistance XLPE
(two line)