TECHNICAL SPECIFICATION

FOR
ABC (Aerial Bundled Conductor) Al 2×16mm2 4×16mm2

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
1. GENERAL
This listed specification covers the structure, test and packing information of power cables as
manufactured by HANGZHOU EASY ELECTRIC WIRE AND CABLE CO.,LTD Matters not mentioned in
this technical specification shall be negotiated by purchaser & supplier. This document confirms the two
parties agreement as technical agreement of contract unless otherwise in official written annexes.

2. STANDARDS
The cable which EES offered shall be designed, manufactured and tested according to international
standards as follows:
ISO 9001:2015 Quality Management Systems
ISO 14001:2015 Environmental Management Systems
OHSAS 18001:2007 Occupational health and safety management system

Insulated or coated conductors for power systems Bundle insulated conductors for 0.6/1kv
NF C 33-209
rated voltage power systems

BS EN 50182 Conductors for overhead lines- Round wire concentric lay stranded conductors

BS EN 50183 Conductors for overhead lines -Aluminium-magnesium-silicon alloy wires

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
3.1CONSTRUCTION AND SPECIFICATIONS FOR
ABC (Aerial Bundled Conductor) 2×16mm2 4×16mm2

Aluminum Conductor

Weatherability XLPE

Aluminum Conductor

Weatherability XLPE

No. Description Unit Standard Equivalent


1 Type of Cable - Aerial Bundled Conductors
2 Size of Cable mm2 2×16 4×16
3 Rated Voltage V 600/1000 600/1000
4 Reference Standard NF C 33-209 NF C 33-209
Construction Data -
5 Conductor
Section mm2 16 16
Core 2 4
Material Hard-Drawn Aluminum
Shape Stranded Circular Compact Round
Aluminum wire No. 7 7
Normal Conductor Dia. mm 4.8 4.8
Breaking Load kN 1.9 1.9
6 Insulation
Material Weatherability-XLPE
Color Black Black

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
Normal thickness of insulation mm 1.2 1.2
Min. thickness of insulation mm 0.98 0.98
Maximum Operating Temperature ℃ 90 90
Nominal Dia. Over insulation mm 7.2 7.2
Marking on the insulation It depends on the requirement
7 Assembly (Twisting)
7.1 Direction of lay - Right Hand Lay
7.2 Approx Core Dia. mm 14.4 17.4
7.3 Approx weight of completed cable kg/km 125 260
8 Electrical Data
Max D.C. resistance of conductor at 20℃ Ω/km 1.91 1.91
9 The type of package - Wooden drum

3.2Cable Characteristics

Value
Parameter Unit
2×16 4×16
Max. D.C. conductor resistance at 20’C Ω/km ≤1.91 ≤1.91

Diameter of cable mm 14.4 17.4

Weight of the finished cable (Approx.) kg/km 125 260

Normal operating temperature °C 90 90

Emergency operating temperature °C 130 130


Current Ratings (in air 30°C) A 93 83

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China
4 ROUTINE TEST AND SAMPLE TEST FOR ABC (Aerial Bundled Conductor) 2×16mm2 4×16mm2

ABC shall be accordance with applicable standard of A B C and requirements of customer. The following test
items shall be carried out according to corresponding reference.

No Item Reference
Tests for ABC (Aerial Bundled Conductor) 2×16mm2 4×16mm2

1 Dimensions NF C 33-209

2 Tensile strength of conductors NF C 33-209

3 Properties of dielectric NF C 33-209

4 Conductor resistance NF C 33-209

5 Voltage withstand NF C 33-209

6 Dielectric resistance NF C 33-209

Hangzhou Easy Electric Wire and Cable Co.,LTD


Add: Room 305, Building 2, No. 380 Fengxin Road, Hangzhou, China