Mechanical Calculation 6
Mechanical Calculation 6
Mechanical Calculation 6
AHU-CH-01-04 03/13/2012
FANAR 04:39PM
1. General Details:
Floor Area ............................................................. 31.0 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 27.0 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 23.0 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................. 100 % of supply air
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 2.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C
1. General Details:
Floor Area ............................................................. 31.5 m²
Avg. Ceiling Height .................................................. 3.0 m
Building Weight ................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................ 20.0 L/s/person
OA Requirement 2 ................................................ 0.00 L/(s-m²)
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................... 3.0 People
Wattage ............................................................... 14.00 W/m² Activity Level ........................................ Seated at Rest
Ballast Multiplier .................................................... 1.25 Sensible ................................................................. 67.4 W/person
Schedule ....................................... Lighting Schedule Latent ..................................................................... 35.2 W/person
Schedule .......................................... people Schedule
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 17.6 11 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 14.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 26.7 °C
Ambient at Space Max Temp ................................ 39.0 °C
Uncondit. Space Min Temp ................................... 20.0 °C
Ambient at Space Min Temp ................................... 7.2 °C