Air System Sizing Summary For AHU-01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

Air System Sizing Summary for AHU-01

Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-01 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 2498.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 20.6 Tons Load occurs at ....................................................... Jun 1600
Total coil load ....................................................... 247.5 MBH OA DB / WB ......................................................... 90.4 / 80.7 °F
Sensible coil load ................................................. 137.6 MBH Entering DB / WB ................................................ 77.8 / 68.0 °F
Coil CFM at Jun 1600 ........................................... 4705 CFM Leaving DB / WB ................................................. 50.6 / 50.0 °F
Max block CFM ..................................................... 4705 CFM Coil ADP .......................................................................... 47.5 °F
Sum of peak zone CFM ....................................... 4705 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.556 Resulting RH ...................................................................... 49 %
ft²/Ton ..................................................................... 121.1 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) .............................................................. 99.1 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 49.53 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 4705 CFM Fan motor BHP ............................................................... 2.53 BHP
Standard CFM ....................................................... 4683 CFM Fan motor kW ................................................................. 2.01 kW
Actual max CFM/ft² ................................................ 1.88 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1624 CFM CFM/person .................................................................. 54.12 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 1 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-02 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 3454.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 26.1 Tons Load occurs at ...................................................... Aug 1500
Total coil load ....................................................... 313.4 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................. 172.3 MBH Entering DB / WB ................................................ 79.8 / 69.3 °F
Coil CFM at Aug 1500 .......................................... 5429 CFM Leaving DB / WB ................................................. 50.3 / 49.7 °F
Max block CFM ..................................................... 5429 CFM Coil ADP .......................................................................... 47.0 °F
Sum of peak zone CFM ....................................... 5429 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.550 Resulting RH ...................................................................... 45 %
ft²/Ton ..................................................................... 132.2 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) .............................................................. 90.7 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 62.72 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 5429 CFM Fan motor BHP ............................................................... 2.92 BHP
Standard CFM ....................................................... 5404 CFM Fan motor kW ................................................................. 2.32 kW
Actual max CFM/ft² ................................................ 1.57 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2245 CFM CFM/person ................................................................ 224.51 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 2 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-03 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 1117.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 9.9 Tons Load occurs at ........................................................ Jul 1500
Total coil load ....................................................... 118.4 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................... 68.8 MBH Entering DB / WB ................................................ 79.4 / 68.8 °F
Coil CFM at Jul 1500 ............................................ 2575 CFM Leaving DB / WB ................................................. 54.5 / 53.8 °F
Max block CFM ..................................................... 2575 CFM Coil ADP .......................................................................... 51.8 °F
Sum of peak zone CFM ....................................... 2575 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.581 Resulting RH ...................................................................... 52 %
ft²/Ton ..................................................................... 113.2 Design supply temp. ...................................................... 54.0 °F
BTU/(hr·ft²) ............................................................ 106.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 23.70 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 2575 CFM Fan motor BHP ............................................................... 1.38 BHP
Standard CFM ....................................................... 2563 CFM Fan motor kW ................................................................. 1.10 kW
Actual max CFM/ft² ................................................ 2.31 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 726 CFM CFM/person .................................................................. 29.04 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 3 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-04 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 2567.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 19.0 Tons Load occurs at ....................................................... Jun 1500
Total coil load ....................................................... 228.6 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ................................................. 124.6 MBH Entering DB / WB ................................................ 80.8 / 70.3 °F
Coil CFM at Jun 1500 ........................................... 4218 CFM Leaving DB / WB ................................................. 53.3 / 52.6 °F
Max block CFM ..................................................... 4218 CFM Coil ADP .......................................................................... 50.2 °F
Sum of peak zone CFM ....................................... 4218 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.545 Resulting RH ...................................................................... 48 %
ft²/Ton ..................................................................... 134.8 Design supply temp. ...................................................... 54.0 °F
BTU/(hr·ft²) .............................................................. 89.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 45.74 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 4218 CFM Fan motor BHP ............................................................... 2.27 BHP
Standard CFM ....................................................... 4198 CFM Fan motor kW ................................................................. 1.80 kW
Actual max CFM/ft² ................................................ 1.64 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1669 CFM CFM/person .................................................................. 83.43 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 4 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-05 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 3508.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 27.2 Tons Load occurs at ...................................................... Aug 1500
Total coil load ....................................................... 326.2 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................. 180.2 MBH Entering DB / WB ................................................ 79.9 / 69.3 °F
Coil CFM at Aug 1500 .......................................... 5922 CFM Leaving DB / WB ................................................. 51.5 / 50.9 °F
Max block CFM ..................................................... 5922 CFM Coil ADP .......................................................................... 48.4 °F
Sum of peak zone CFM ....................................... 5922 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.552 Resulting RH ...................................................................... 48 %
ft²/Ton ..................................................................... 129.0 Design supply temp. ...................................................... 52.0 °F
BTU/(hr·ft²) .............................................................. 93.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 65.28 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 5922 CFM Fan motor BHP ............................................................... 3.18 BHP
Standard CFM ....................................................... 5895 CFM Fan motor kW ................................................................. 2.53 kW
Actual max CFM/ft² ................................................ 1.69 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2280 CFM CFM/person .................................................................. 76.01 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 5 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-06 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 5217.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 40.1 Tons Load occurs at ........................................................ Jul 1400
Total coil load ....................................................... 481.7 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ................................................. 264.2 MBH Entering DB / WB ................................................ 79.8 / 69.4 °F
Coil CFM at Jul 1400 ............................................ 8647 CFM Leaving DB / WB ................................................. 51.3 / 50.7 °F
Max block CFM ..................................................... 8647 CFM Coil ADP .......................................................................... 48.2 °F
Sum of peak zone CFM ....................................... 8647 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.548 Resulting RH ...................................................................... 48 %
ft²/Ton ..................................................................... 130.0 Design supply temp. ...................................................... 52.0 °F
BTU/(hr·ft²) .............................................................. 92.3 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 96.39 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 8647 CFM Fan motor BHP ............................................................... 4.65 BHP
Standard CFM ....................................................... 8607 CFM Fan motor kW ................................................................. 3.69 kW
Actual max CFM/ft² ................................................ 1.66 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 3391 CFM CFM/person .................................................................. 67.82 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 6 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-07 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................. 10933.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 94.3 Tons Load occurs at ....................................................... Jun 1500
Total coil load ..................................................... 1132.0 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ................................................. 608.0 MBH Entering DB / WB ................................................ 78.2 / 68.8 °F
Coil CFM at Jun 1500 ........................................ 20374 CFM Leaving DB / WB ................................................. 50.5 / 50.0 °F
Max block CFM ................................................... 20374 CFM Coil ADP .......................................................................... 47.4 °F
Sum of peak zone CFM ..................................... 20374 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.537 Resulting RH ...................................................................... 52 %
ft²/Ton ..................................................................... 115.9 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 103.5 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ................................ 226.53 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ................................................. 20374 CFM Fan motor BHP ............................................................. 10.96 BHP
Standard CFM ..................................................... 20280 CFM Fan motor kW ................................................................. 8.69 kW
Actual max CFM/ft² ................................................ 1.86 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 7106 CFM CFM/person .................................................................. 28.43 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 7 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-08 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 2181.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 18.8 Tons Load occurs at ...................................................... Aug 1500
Total coil load ....................................................... 225.3 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................. 128.9 MBH Entering DB / WB ................................................ 77.9 / 67.6 °F
Coil CFM at Aug 1500 .......................................... 4467 CFM Leaving DB / WB ................................................. 51.0 / 50.4 °F
Max block CFM ..................................................... 4467 CFM Coil ADP .......................................................................... 48.0 °F
Sum of peak zone CFM ....................................... 4467 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.572 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 116.2 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 103.3 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 45.08 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 4467 CFM Fan motor BHP ............................................................... 2.40 BHP
Standard CFM ....................................................... 4446 CFM Fan motor kW ................................................................. 1.91 kW
Actual max CFM/ft² ................................................ 2.05 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1418 CFM CFM/person .................................................................. 47.26 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 8 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-09 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 4291.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 34.6 Tons Load occurs at ....................................................... Jun 1500
Total coil load ....................................................... 415.1 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ................................................. 224.8 MBH Entering DB / WB ................................................ 78.6 / 69.0 °F
Coil CFM at Jun 1500 ........................................... 7612 CFM Leaving DB / WB ................................................. 51.2 / 50.6 °F
Max block CFM ..................................................... 7612 CFM Coil ADP .......................................................................... 48.1 °F
Sum of peak zone CFM ....................................... 7612 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.542 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 124.0 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) .............................................................. 96.7 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 83.07 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 7612 CFM Fan motor BHP ............................................................... 4.09 BHP
Standard CFM ....................................................... 7577 CFM Fan motor kW ................................................................. 3.25 kW
Actual max CFM/ft² ................................................ 1.77 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2789 CFM CFM/person .................................................................. 46.49 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 9 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-10 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 1063.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 18.8 Tons Load occurs at ...................................................... Aug 1500
Total coil load ....................................................... 225.9 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................... 97.7 MBH Entering DB / WB ................................................ 91.0 / 80.2 °F
Coil CFM at Aug 1500 .......................................... 2232 CFM Leaving DB / WB ................................................. 50.3 / 50.3 °F
Max block CFM ..................................................... 2232 CFM Coil ADP .......................................................................... 45.7 °F
Sum of peak zone CFM ....................................... 2232 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.432 Resulting RH ...................................................................... 52 %
ft²/Ton ....................................................................... 56.5 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 212.5 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 45.21 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 2232 CFM Fan motor BHP ............................................................... 1.20 BHP
Standard CFM ....................................................... 2222 CFM Fan motor kW ................................................................. 0.95 kW
Actual max CFM/ft² ................................................ 2.10 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2121 CFM CFM/person ................................................................ 106.03 CFM/person
CFM/ft² ..................................................................... 1.99 CFM/ft²

Hourly Analysis Program v5.01 Page 10 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-11 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 2272.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 19.9 Tons Load occurs at ........................................................ Jul 1500
Total coil load ....................................................... 239.0 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................. 134.9 MBH Entering DB / WB ................................................ 78.0 / 67.8 °F
Coil CFM at Jul 1500 ............................................ 4587 CFM Leaving DB / WB ................................................. 50.6 / 50.0 °F
Max block CFM ..................................................... 4587 CFM Coil ADP .......................................................................... 47.6 °F
Sum of peak zone CFM ....................................... 4587 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.565 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 114.1 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 105.2 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 47.82 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 4587 CFM Fan motor BHP ............................................................... 2.47 BHP
Standard CFM ....................................................... 4566 CFM Fan motor kW ................................................................. 1.96 kW
Actual max CFM/ft² ................................................ 2.02 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1477 CFM CFM/person .................................................................. 36.92 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 11 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-12 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 7635.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 68.1 Tons Load occurs at ........................................................ Jul 1500
Total coil load ....................................................... 816.6 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................. 449.3 MBH Entering DB / WB ................................................ 78.1 / 68.4 °F
Coil CFM at Jul 1500 .......................................... 15560 CFM Leaving DB / WB ................................................. 51.2 / 50.7 °F
Max block CFM ................................................... 15560 CFM Coil ADP .......................................................................... 48.3 °F
Sum of peak zone CFM ..................................... 15560 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.550 Resulting RH ...................................................................... 54 %
ft²/Ton ..................................................................... 112.2 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 107.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ................................ 163.42 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ................................................. 15560 CFM Fan motor BHP ............................................................... 8.37 BHP
Standard CFM ..................................................... 15488 CFM Fan motor kW ................................................................. 6.64 kW
Actual max CFM/ft² ................................................ 2.04 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 4963 CFM CFM/person .................................................................. 24.81 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 12 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. AHU-13 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 2008.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 17.4 Tons Load occurs at ...................................................... Aug 1700
Total coil load ....................................................... 208.6 MBH OA DB / WB ......................................................... 90.0 / 80.1 °F
Sensible coil load ................................................. 126.3 MBH Entering DB / WB ................................................ 76.6 / 66.1 °F
Coil CFM at Aug 1700 .......................................... 4634 CFM Leaving DB / WB ................................................. 51.2 / 50.5 °F
Max block CFM ..................................................... 4634 CFM Coil ADP .......................................................................... 48.4 °F
Sum of peak zone CFM ....................................... 4634 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.605 Resulting RH ...................................................................... 47 %
ft²/Ton ..................................................................... 115.5 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 103.9 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 41.73 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 4634 CFM Fan motor BHP ............................................................... 2.49 BHP
Standard CFM ....................................................... 4613 CFM Fan motor kW ................................................................. 1.98 kW
Actual max CFM/ft² ................................................ 2.31 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1305 CFM CFM/person .................................................................. 87.01 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 13 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-01 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ........................................................................ 93.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0.9 Tons Load occurs at ........................................................ Jul 1600
Total coil load .......................................................... 10.5 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ..................................................... 6.1 MBH Entering DB / WB ................................................ 76.4 / 66.6 °F
Coil CFM at Jul 1600 .............................................. 233 CFM Leaving DB / WB ................................................. 51.9 / 51.2 °F
Max block CFM ........................................................ 233 CFM Coil ADP .......................................................................... 49.2 °F
Sum of peak zone CFM ......................................... 233 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.587 Resulting RH ...................................................................... 52 %
ft²/Ton ..................................................................... 106.7 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 112.4 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 2.09 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 233 CFM Fan motor BHP ............................................................... 0.13 BHP
Standard CFM ......................................................... 232 CFM Fan motor kW ................................................................. 0.10 kW
Actual max CFM/ft² ................................................ 2.51 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 60 CFM CFM/person .................................................................. 30.23 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 14 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-02 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 312.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2.5 Tons Load occurs at ........................................................ Jul 1400
Total coil load .......................................................... 30.3 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ................................................... 16.4 MBH Entering DB / WB ................................................ 79.0 / 69.1 °F
Coil CFM at Jul 1400 .............................................. 532 CFM Leaving DB / WB ................................................. 50.4 / 49.8 °F
Max block CFM ........................................................ 532 CFM Coil ADP .......................................................................... 47.2 °F
Sum of peak zone CFM ......................................... 532 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.541 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 123.7 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) .............................................................. 97.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 6.06 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 532 CFM Fan motor BHP ............................................................... 0.29 BHP
Standard CFM ......................................................... 530 CFM Fan motor kW ................................................................. 0.23 kW
Actual max CFM/ft² ................................................ 1.71 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 203 CFM CFM/person .................................................................. 40.56 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 15 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-03 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 111.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.2 Tons Load occurs at ........................................................ Jul 1400
Total coil load .......................................................... 14.6 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ..................................................... 8.7 MBH Entering DB / WB ................................................ 75.7 / 65.9 °F
Coil CFM at Jul 1400 .............................................. 323 CFM Leaving DB / WB ................................................. 50.7 / 50.0 °F
Max block CFM ........................................................ 323 CFM Coil ADP .......................................................................... 47.9 °F
Sum of peak zone CFM ......................................... 323 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.594 Resulting RH ...................................................................... 53 %
ft²/Ton ....................................................................... 90.9 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 132.0 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 2.93 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 323 CFM Fan motor BHP ............................................................... 0.17 BHP
Standard CFM ......................................................... 321 CFM Fan motor kW ................................................................. 0.14 kW
Actual max CFM/ft² ................................................ 2.91 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 72 CFM CFM/person .................................................................. 18.04 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 16 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-04 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ........................................................................ 47.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0.6 Tons Load occurs at ........................................................ Jul 1500
Total coil load ............................................................ 7.1 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ..................................................... 4.4 MBH Entering DB / WB ................................................ 74.9 / 64.7 °F
Coil CFM at Jul 1500 .............................................. 166 CFM Leaving DB / WB ................................................. 50.2 / 49.4 °F
Max block CFM ........................................................ 166 CFM Coil ADP .......................................................................... 47.4 °F
Sum of peak zone CFM ......................................... 166 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.619 Resulting RH ...................................................................... 52 %
ft²/Ton ....................................................................... 79.2 Design supply temp. ...................................................... 51.0 °F
BTU/(hr·ft²) ............................................................ 151.5 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 1.42 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 166 CFM Fan motor BHP ............................................................... 0.09 BHP
Standard CFM ......................................................... 165 CFM Fan motor kW ................................................................. 0.07 kW
Actual max CFM/ft² ................................................ 3.53 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 31 CFM CFM/person .................................................................. 15.28 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 17 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-05 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 211.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.7 Tons Load occurs at ...................................................... Aug 1500
Total coil load .......................................................... 19.9 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................... 11.6 MBH Entering DB / WB ................................................ 81.1 / 70.1 °F
Coil CFM at Aug 1500 ............................................ 441 CFM Leaving DB / WB ................................................. 56.6 / 55.8 °F
Max block CFM ........................................................ 441 CFM Coil ADP .......................................................................... 53.9 °F
Sum of peak zone CFM ......................................... 441 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.584 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 127.4 Design supply temp. ...................................................... 56.0 °F
BTU/(hr·ft²) .............................................................. 94.2 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 3.98 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 441 CFM Fan motor BHP ............................................................... 0.24 BHP
Standard CFM ......................................................... 439 CFM Fan motor kW ................................................................. 0.19 kW
Actual max CFM/ft² ................................................ 2.09 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 137 CFM CFM/person .................................................................. 45.72 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 18 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-06 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ........................................................................ 66.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0.7 Tons Load occurs at ........................................................ Jul 1700
Total coil load ............................................................ 7.9 MBH OA DB / WB ......................................................... 90.0 / 80.1 °F
Sensible coil load ..................................................... 4.4 MBH Entering DB / WB ................................................ 78.1 / 68.6 °F
Coil CFM at Jul 1700 .............................................. 176 CFM Leaving DB / WB ................................................. 54.6 / 54.0 °F
Max block CFM ........................................................ 176 CFM Coil ADP .......................................................................... 52.0 °F
Sum of peak zone CFM ......................................... 176 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.564 Resulting RH ...................................................................... 57 %
ft²/Ton ..................................................................... 100.5 Design supply temp. ...................................................... 54.0 °F
BTU/(hr·ft²) ............................................................ 119.4 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 1.58 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 176 CFM Fan motor BHP ............................................................... 0.09 BHP
Standard CFM ......................................................... 175 CFM Fan motor kW ................................................................. 0.08 kW
Actual max CFM/ft² ................................................ 2.67 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 43 CFM CFM/person .................................................................. 14.30 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 19 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-07 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 304.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2.8 Tons Load occurs at ....................................................... Jun 1500
Total coil load .......................................................... 33.9 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ................................................... 20.2 MBH Entering DB / WB ................................................ 78.7 / 68.0 °F
Coil CFM at Jun 1500 ............................................. 757 CFM Leaving DB / WB ................................................. 53.9 / 53.1 °F
Max block CFM ........................................................ 757 CFM Coil ADP .......................................................................... 51.1 °F
Sum of peak zone CFM ......................................... 757 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.596 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 107.6 Design supply temp. ...................................................... 54.0 °F
BTU/(hr·ft²) ............................................................ 111.5 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 6.79 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 757 CFM Fan motor BHP ............................................................... 0.41 BHP
Standard CFM ......................................................... 753 CFM Fan motor kW ................................................................. 0.32 kW
Actual max CFM/ft² ................................................ 2.49 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 198 CFM CFM/person .................................................................. 32.93 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 20 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-08 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 421.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 3.6 Tons Load occurs at ....................................................... Jun 1500
Total coil load .......................................................... 43.1 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ................................................... 24.8 MBH Entering DB / WB ................................................ 79.4 / 68.8 °F
Coil CFM at Jun 1500 ............................................. 901 CFM Leaving DB / WB ................................................. 53.8 / 53.1 °F
Max block CFM ........................................................ 901 CFM Coil ADP .......................................................................... 51.0 °F
Sum of peak zone CFM ......................................... 901 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.575 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 117.1 Design supply temp. ...................................................... 54.0 °F
BTU/(hr·ft²) ............................................................ 102.5 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 8.63 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 901 CFM Fan motor BHP ............................................................... 0.48 BHP
Standard CFM ......................................................... 897 CFM Fan motor kW ................................................................. 0.38 kW
Actual max CFM/ft² ................................................ 2.14 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 274 CFM CFM/person .................................................................. 39.09 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 21 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-09 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 421.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 3.1 Tons Load occurs at ........................................................ Jul 1400
Total coil load .......................................................... 37.3 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ................................................... 20.2 MBH Entering DB / WB ................................................ 80.4 / 70.0 °F
Coil CFM at Jul 1400 .............................................. 647 CFM Leaving DB / WB ................................................. 51.4 / 50.8 °F
Max block CFM ........................................................ 647 CFM Coil ADP .......................................................................... 48.2 °F
Sum of peak zone CFM ......................................... 647 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.540 Resulting RH ...................................................................... 47 %
ft²/Ton ..................................................................... 135.4 Design supply temp. ...................................................... 52.0 °F
BTU/(hr·ft²) .............................................................. 88.6 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 7.47 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 647 CFM Fan motor BHP ............................................................... 0.35 BHP
Standard CFM ......................................................... 644 CFM Fan motor kW ................................................................. 0.28 kW
Actual max CFM/ft² ................................................ 1.54 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 274 CFM CFM/person .................................................................. 91.22 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 22 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-10 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 344.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2.6 Tons Load occurs at ........................................................ Jul 1500
Total coil load .......................................................... 31.6 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................... 17.5 MBH Entering DB / WB ................................................ 80.5 / 69.7 °F
Coil CFM at Jul 1500 .............................................. 585 CFM Leaving DB / WB ................................................. 52.6 / 51.9 °F
Max block CFM ........................................................ 585 CFM Coil ADP .......................................................................... 49.5 °F
Sum of peak zone CFM ......................................... 585 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.555 Resulting RH ...................................................................... 48 %
ft²/Ton ..................................................................... 130.7 Design supply temp. ...................................................... 53.0 °F
BTU/(hr·ft²) .............................................................. 91.8 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 6.32 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 585 CFM Fan motor BHP ............................................................... 0.31 BHP
Standard CFM ......................................................... 582 CFM Fan motor kW ................................................................. 0.25 kW
Actual max CFM/ft² ................................................ 1.70 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 224 CFM CFM/person .................................................................. 74.53 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 23 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-11 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 113.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0.9 Tons Load occurs at ........................................................ Jul 1500
Total coil load .......................................................... 11.3 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ..................................................... 6.1 MBH Entering DB / WB ................................................ 80.2 / 70.1 °F
Coil CFM at Jul 1500 .............................................. 206 CFM Leaving DB / WB ................................................. 52.7 / 52.2 °F
Max block CFM ........................................................ 206 CFM Coil ADP .......................................................................... 49.7 °F
Sum of peak zone CFM ......................................... 206 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.536 Resulting RH ...................................................................... 54 %
ft²/Ton ..................................................................... 120.1 Design supply temp. ...................................................... 53.0 °F
BTU/(hr·ft²) .............................................................. 99.9 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 2.26 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 206 CFM Fan motor BHP ............................................................... 0.11 BHP
Standard CFM ......................................................... 205 CFM Fan motor kW ................................................................. 0.09 kW
Actual max CFM/ft² ................................................ 1.82 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 73 CFM CFM/person .................................................................. 24.48 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 24 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-12 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ..................................................................... 101.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0.8 Tons Load occurs at ....................................................... Jun 1500
Total coil load ............................................................ 9.7 MBH OA DB / WB ......................................................... 91.0 / 81.0 °F
Sensible coil load ..................................................... 5.1 MBH Entering DB / WB ................................................ 80.1 / 70.2 °F
Coil CFM at Jun 1500 ............................................. 173 CFM Leaving DB / WB ................................................. 52.5 / 51.9 °F
Max block CFM ........................................................ 173 CFM Coil ADP .......................................................................... 49.4 °F
Sum of peak zone CFM ......................................... 173 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.531 Resulting RH ...................................................................... 52 %
ft²/Ton ..................................................................... 125.4 Design supply temp. ...................................................... 53.0 °F
BTU/(hr·ft²) .............................................................. 95.7 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 1.93 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 173 CFM Fan motor BHP ............................................................... 0.09 BHP
Standard CFM ......................................................... 172 CFM Fan motor kW ................................................................. 0.07 kW
Actual max CFM/ft² ................................................ 1.71 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 66 CFM CFM/person .................................................................. 32.83 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 25 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-13 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 1191.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 9.8 Tons Load occurs at ...................................................... Aug 1600
Total coil load ....................................................... 118.0 MBH OA DB / WB ......................................................... 91.4 / 80.7 °F
Sensible coil load ................................................... 66.5 MBH Entering DB / WB ................................................ 79.4 / 68.9 °F
Coil CFM at Aug 1600 .......................................... 2311 CFM Leaving DB / WB ................................................. 52.7 / 52.0 °F
Max block CFM ..................................................... 2311 CFM Coil ADP .......................................................................... 49.7 °F
Sum of peak zone CFM ....................................... 2311 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.563 Resulting RH ...................................................................... 50 %
ft²/Ton ..................................................................... 121.1 Design supply temp. ...................................................... 53.0 °F
BTU/(hr·ft²) .............................................................. 99.1 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 23.61 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 2311 CFM Fan motor BHP ............................................................... 1.24 BHP
Standard CFM ....................................................... 2301 CFM Fan motor kW ................................................................. 0.99 kW
Actual max CFM/ft² ................................................ 1.94 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 774 CFM CFM/person .................................................................. 38.71 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 26 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-14 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ........................................................................ 85.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.6 Tons Load occurs at ........................................................ Jul 1700
Total coil load .......................................................... 19.3 MBH OA DB / WB ......................................................... 90.0 / 80.1 °F
Sensible coil load ................................................... 14.8 MBH Entering DB / WB ................................................ 74.8 / 62.9 °F
Coil CFM at Jul 1700 .............................................. 641 CFM Leaving DB / WB ................................................. 53.3 / 52.3 °F
Max block CFM ........................................................ 641 CFM Coil ADP .......................................................................... 50.9 °F
Sum of peak zone CFM ......................................... 641 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.767 Resulting RH ...................................................................... 48 %
ft²/Ton ....................................................................... 52.8 Design supply temp. ...................................................... 53.0 °F
BTU/(hr·ft²) ............................................................ 227.1 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 3.86 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM ...................................................... 641 CFM Fan motor BHP ............................................................... 0.34 BHP
Standard CFM ......................................................... 638 CFM Fan motor kW ................................................................. 0.27 kW
Actual max CFM/ft² ................................................ 7.54 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 55 CFM CFM/person .................................................................. 18.42 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 27 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-15 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 1048.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 9.5 Tons Load occurs at ........................................................ Jul 1500
Total coil load ....................................................... 113.9 MBH OA DB / WB ......................................................... 92.0 / 81.0 °F
Sensible coil load ................................................... 60.6 MBH Entering DB / WB ................................................ 81.8 / 71.7 °F
Coil CFM at Jul 1500 ............................................ 2226 CFM Leaving DB / WB ................................................. 56.5 / 55.8 °F
Max block CFM ..................................................... 2226 CFM Coil ADP .......................................................................... 53.7 °F
Sum of peak zone CFM ....................................... 2226 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.533 Resulting RH ...................................................................... 57 %
ft²/Ton ..................................................................... 110.4 Design supply temp. ...................................................... 57.0 °F
BTU/(hr·ft²) ............................................................ 108.6 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 22.78 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 2226 CFM Fan motor BHP ............................................................... 1.20 BHP
Standard CFM ....................................................... 2216 CFM Fan motor kW ................................................................. 0.95 kW
Actual max CFM/ft² ................................................ 2.12 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 681 CFM CFM/person .................................................................. 13.62 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 28 of 29


Air System Sizing Summary for AHU-01
Project Name: Pusat Transfusi Darah

Air System Information


Air System Name ............................................. FCU-16 Number of zones ................................................................. 1
Equipment Class ........................................... CW AHU Floor Area ................................................................... 1122.0 ft²
Air System Type ............................................... SZCAV Location ........................................................ Ipoh, Malaysia

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 13.5 Tons Load occurs at ....................................................... Jun 1600
Total coil load ....................................................... 162.4 MBH OA DB / WB ......................................................... 90.4 / 80.7 °F
Sensible coil load ................................................... 83.5 MBH Entering DB / WB ................................................ 80.4 / 71.5 °F
Coil CFM at Jun 1600 ........................................... 3304 CFM Leaving DB / WB ................................................. 56.9 / 56.3 °F
Max block CFM ..................................................... 3304 CFM Coil ADP .......................................................................... 54.3 °F
Sum of peak zone CFM ....................................... 3304 CFM Bypass Factor ............................................................... 0.100
Sensible heat ratio ............................................... 0.514 Resulting RH ...................................................................... 62 %
ft²/Ton ....................................................................... 82.9 Design supply temp. ...................................................... 57.0 °F
BTU/(hr·ft²) ............................................................ 144.7 Zone T-stat Check ....................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 32.49 gpm Max zone temperature deviation ................................... 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................... 3304 CFM Fan motor BHP ............................................................... 1.78 BHP
Standard CFM ....................................................... 3288 CFM Fan motor kW ................................................................. 1.41 kW
Actual max CFM/ft² ................................................ 2.94 CFM/ft² Fan static ......................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 729 CFM CFM/person .................................................................... 6.95 CFM/person
CFM/ft² ..................................................................... 0.65 CFM/ft²

Hourly Analysis Program v5.01 Page 29 of 29