Air System Sizing Summary For Cat First Floor
Air System Sizing Summary For Cat First Floor
Air System Sizing Summary For Cat First Floor
Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated
Total coil load ............................................................ 7.1 kW Load occurs at ..................................................... Jul 1500
Sensible coil load ..................................................... 6.4 kW OA DB / WB ...................................................... 46.0 / 30.0 C
Coil L/s at Jul 1500 .................................................. 716 L/s Entering DB / WB ............................................. 23.0 / 18.0 C
Max block L/s .......................................................... 716 L/s Leaving DB / WB .............................................. 15.6 / 15.1 C
Sum of peak zone L/s ............................................. 716 L/s Coil ADP ..................................................................... 14.7 C
Sensible heat ratio ............................................... 0.912 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 7.9 Resulting RH ................................................................. 63 %
W/m ..................................................................... 125.9 Design supply temp. ................................................... 15.0 C
Water flow @ 6.0 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K
Actual max L/s ......................................................... 716 L/s Fan motor BHP ........................................................... 0.09 BHP
Standard L/s ............................................................ 714 L/s Fan motor kW ............................................................. 0.07 kW
Actual max L/(s-m) .............................................. 12.78 L/(s-m) Fan static ....................................................................... 50 Pa