Manual Liebert GXT2-6000RT230
Manual Liebert GXT2-6000RT230
Manual Liebert GXT2-6000RT230
230VAC
TABLES
Table 1 Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 2 DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 3 Indicator meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 4 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 5 Alarm conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 6 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 7 UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 8 Power distribution specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 9 External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ii
! WARNING
This UPS should not be supplied from electrical power systems of the “IT” (Impédance à
Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)
! WARNING
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C
(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corro-
sive substances.
This UPS contains no user serviceable parts. The UPS ON/OFF push buttons do not electrically iso-
late internal parts. Under no circumstances attempt to gain access internally, due to the risk of elec-
tric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operat-
ing instructions, or the UPS performance alters in use. Refer all faults to your dealer.
Only trained engineers authorized by Liebert should perform troubleshooting. To replace batteries,
refer all servicing to qualified service personnel. Proper disposal of batteries is required. Refer to your
local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,
for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half
wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the off UPS and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol
cleaners.
AC input
AC output
- +
Indicates the unit contains a valve-regulated lead acid battery
PbH2SO4
R Recycle
DC voltage
Bonded to ground
AC voltage
OFF/Bypass
1.0 INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT2-6000RT230 and GXT2-4500RT230
Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it
may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera-
tions, cause data loss, or even damage equipment. The UPStation GXT2 protects equipment from
these disturbances.
The UPStation GXT2 comes in nominal power ratings of 4500 VA and 6000 VA. Complete model spec-
ifications appear at the end of this manual.
The UPStation GXT2 is a compact, on-line UPS. An on-line UPS continuously conditions and regu-
lates its output voltage, whether mains power is present or not. It supplies connected equipment with
clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT2 features a light-emitting diode (LED) display to indicate both
load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm
Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of
alarms when the unit is operating on battery.
The UPStation GXT2 has an interface port for communication between the UPS and a network server
or other computer systems. This port provides detailed operating information including voltages, cur-
rents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ soft-
ware. MultiLink software can also remotely control UPS operation.
L1 Rectifier L1
TVSS &
EMI/RFI /PFC Inverter
Filters DC-to-DC
N Converter
N
Battery Battery
Charger
G G
2.3 Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and
inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter
receives its required energy from the battery through the DC to DC converter. In both modes of oper-
ation, the UPS inverter is on-line and continuously generating clean, precise, Regulated Ac Output
Power.
2.6 Battery
The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
design life, operate the UPS
in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are
available to extend battery run times.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances
in the mains supply.
Status
!
Indicators
UPStation GXT
& Controls
Upper
Bezel
Battery
Disconnect
UPS Output
Circuit Breaker
DB-9
Communication REPO Connector
Port
Removable Power
Distribution Box
Serial Card Slot
(SNMP, OCWEB, USB)
NOTE
Hardwire and hardwire/receptacle boxes that include a manual bypass switch allow
AC power to continue to flow from the mains input to the load while the box is removed
from the UPS. For details, refer to 11.2 - AC Power Connections.
Top bezels
(tower use)
MultiLink
software CD MultiLink
serial cable
10 ft (3m)
Vertical
Rack mount
display
handles
overlay
www.liebert.com
GXT2™ Configuration
Program
For use with LiebertGXT2U model UPS
systems
Version 1.6
For Windows 95/98/NT
To Install:
Choose the Start button on the Taskbar
and select Run
Mounting hardware
Configuration
disk
RS232
Support base
with spacers
! CAUTION
The UPS is heavy (see 13.0 - Specifications). Take proper precautions
when lifting or moving it.
Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off.
Place it where air flows unrestricted around the unit. The installation location must be free of water,
flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of
100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to
40°C (32 -104°F).
NOTE
UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.
This device is intended for use in an Installation Category II environment.
3U
3U
2U
2U
! CAUTION
Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box
is located. The fourth mounting hole is above the Power Distribution Box and is not used.
10
3. Install the rear member of each bracket assembly into the M5 screws
rack enclosure with two (2) M5 screws provided in this kit Front rack
(see figure at right). The return flanges on the bracket mounting rails
assembly fit to the inside of rack mounting rails. Insert
screws loosely (finger-tight) into the top and bottom holes of
the return flange on the rear member. Extend the bracket
assembly by sliding the front member forward until it
touches the front rack mounting rail. Insert two (2) M5
screws loosely (finger-tight) into the top and bottom holes of
the return flange on each front member. Make sure that the Rear rack
bracket assemblies are at the same mounting height on all mounting
four (4) rack mounting rails. rails
M5 screws
11
4. Get eight (8) M4 screws and eight (8) M4 nuts from the M4 nuts M4
hardware pack in this kit. Each nut has a locking, nylon screws
insert that begins gripping the screw when it is halfway
tight. Make sure to tighten the nut and screw completely to
ensure locking action. Fasten the rear member and the front
member together using (4) screws and (4) nuts per bracket
assembly as shown in at right. For maximum support, insert
fasteners for each bracket assembly as far apart as possible, 457mm
depending on rack depth, while still joining both members (18")
rack
(see figures at right). Check alignment of bracket assemblies depth M4 nuts
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for M4 nuts M4
rack mounting by following instructions in the equipment’s screws
user manual. The equipment may require additional parts to
be added or parts to be removed for rack mounting. After it is
prepared, lay the equipment in rack-mounting position.
Fasten the inner members from Step 1 to the equipment on 813mm
both sides as shown at right with eight (8) M4 screws (32") rack
provided in the kit. Make sure retaining latch is near the rear depth M4 nuts
of the equipment as shown (see figure at right).
6. Open the grease packet provided in the kit. Apply a bead of M4 screws Retaining latch
grease 25mm (1") long at four (4) places inside the bottom,
curved tracks of the front members as shown below right. The
grease will allow the equipment to slide into the bracket
assemblies more easily. UPS or battery
cabinet
! CAUTION
Lifting equipment into the rack may be a two-person
job, depending on the weight of the equipment.
6.
12
! CAUTION
The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier
and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift
up to remove. Optional rack-mount handles are shipped with the external battery cabinet and
may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert
representative for these additional options and any assistance needed. Fasten the slides into
position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of
support base extensions ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,
then to the rear of the UPS.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run
times, refer to Table 6.
NOTE
You must use the included configuration program to program the UPS for the number
of external battery cabinets connected. Instructions for the configuration program are in
7.0 - Configuration Program.
3U
2U
2U
13
5.3.1 Storage
If the UPS is to be shipped or stored for an extended time, the connector should be removed and
attached in the open position, as shown above. This will minimize any standby current drain on the
batteries.
14
UPS UPS
Output Output
30 CB 30 CB
N L N L
OUTPUT INPUT Overcurrent
32Amp Max Branch
Protection
N L N L
NOTE
1. Note1 The installer must provide circuit breaker protection according to local codes. The
mains disconnect should be within sight of the UPS or have appropriate an appropriate
lock-out. Maintain service space around the UPS or use flexible conduit.
2. Note 2 The installer must provide output distribution panels, circuit breaker protection, or
emergency disconnects according to local codes. Output circuits must not share a common
conduit with any other wiring.
15
16
17
UPStation GXT
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second
while operating from mains power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24
hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact
your local dealer, Liebert representative or Liebert Worldwide Support Group.
! CAUTION
Pressing the Standby/Manual Bypass button once will transfer the
load to bypass power. Pressing the Standby/Manual Bypass button a
second time within 4 seconds will cut off power to the output sockets
and connected loads. Perform all necessary shutdown procedures on
connected loads before pressing this button twice.
18
19
! CAUTION
Turning OFF the UPS while in it is battery mode will cut off output power.
20
10.0 COMMUNICATIONS
6 7 8 9 Open
(+) Collector
330 Ohms
(-) Open
Emitter
1 2 3 4 5
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA
21
NOTE
The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove
the cable after setup is complete.
When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector
needs to be covered. The DB9 cover is included with the UPS.
Liebert's MultiLink software continually monitors the UPS and can shut down your computer or
server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the
network with other computers running MultiLink when you purchase a MultiLink License Kit. For
more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site
(www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT2. The Intellislot
SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the net-
work.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-
dinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv-
ers support for built-in shutdown for AS/400 systems.
! CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables, where applicable.
22
1 2 1 2
! CAUTION
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.
23
11.0 MAINTENANCE
UPStation GXT !
-+
The UPStation GXT2 is designed to allow the user to safely replace the internal batteries. Read the
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.
24
! CAUTION
A battery can present a risk of electrical shock and high short circuit current. Observe the
following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
1. Remove the 3U battery access panel on the front of Battery Door Captive Screws
the UPS by loosening the two captive screws
located between the bezels (see illustration at
right). UPStation GXT
!
2. Once the captive screws are loosened, tip the panel AC OUTPUT BATTERY UPS ON BYPASS
Battery Bezel
-+
-+
!
captive screws.
NOTE
These are hot-swappable replacement
batteries. However, caution should be
exercised because during this procedure the
load is unprotected from disturbances and Battery Connectors
power outages.
25
! CAUTION
Power is still passing through the box from mains to the load.
Reconnect
1. Align connectors and press the box onto the rear of the UPS.
2. 2. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.
3. If the Mains branch circuit breaker and load is off, turn the branch breaker on now.
4. Turn on the output circuit breaker on the rear of the UPS.
5. Turn on the input circuit breaker on the box.
6. Start the UPS according to the startup instructions.
Press the ON button for one second.
7. Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.
8. Turn the manual bypass switch to the UPS position.
9. The UPS now protects the load.
26
12.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the UPStation
GXT2 develops a problem. Use this information to determine whether external factors caused the
problem and how to remedy the situation.
1. 1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. 2. An alarm will sound, alerting that the UPS requires attention.
Fault
Example shows UPS
on bypass because
of output overload,
signified by amber
load indicator.
3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic
aid to the operator, as described below:
Table 3 Indicator meanings
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep every half-second
A LED On bypass due to overtemperature condition; beep every 4 sec.
B LED On bypass due to DC bus overvoltage; beep every 4 sec.
C LED DC-DC failure during battery mode; beep every 4 sec.
D LED On bypass due to PFC failure; beep every 4 sec.
E LED On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
C&E LEDs UPS shutdown due to command from communication port (SNMP); no beep
Internal Battery source not available (continuous horn). Check Battery connection,
Battery LED Flashing
completely power down and reboot UPS.
A&E LEDs Fan locked
B&C REPO active. UPS cannot run with REPO loop open.
B&D UPS is OFF due to previous REPO shutdown. Autorestart disabled.
D&E Charger Malfunction
Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-
wide Support Group. Please have the UPS model number and serial number available at the time of
your inquiry.
27
28
29
30
31
13.0 SPECIFICATIONS
Table 7 UPS specifications
Model Number GXT2-6000RT230 GXT2-4500RT230
Model Rating 6KVA / 4,200W 4.5KVA / 3,150W
Dimensions mm (in.)
Unit, W x D x H 221 x 547 x 430 (8.7 x 21.5 x 16.9)
Shipping, W x D x H 560 x 690 x 500 (22.05 x 27.17 x 19.7)
Weight kg (lbs)
Unit 67 (151) 67 (151)
Shipping 79.5 (175.3) 79.5 (175.3)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 50)
Factory Default VAC 230VAC
220/230/240VAC
User Configurable VAC
(May be modified using configuration program)
Operating Voltage Range Without
176 – 276VAC
Battery Operation
Maximum Allowable VAC 276VAC
Input Frequency Without Battery
40 - 70Hz
Operation
Input Power Connection PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Output AC Parameters
Factory Default VAC 230VAC
Output Connections PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode >200% for 96 milliseconds; 131 - 199% for 2 seconds;
Overload 112- 129% for 10 seconds with transfer to bypass
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # Yuasa / REW 28-12
Back-up Time See Table 6 - Battery run times
Recharge Time (Internal Batteries) 3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature 0°C to +40°C (+32°F to +104° F)
Storage Temperature -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 2000m (6600 ft) at 40°C (104° F) without derating
Storage Elevation 15,000m (50,000 ft.) maximum
<55 dBA, at 1 meter from the rear
Audible Noise
<50 dBA, at 1 meter from the front or sides
Agency
Safety EN62040-1-1; TUV/GS
EMI/EMC/C-Tick EMC EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1B
32
33
34