Manual Liebert GXT2-6000RT230

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

POWER AVAILABILITY

GXT2-6000RT230™ & GXT2-4500RT230™


USER MANUAL

230VAC

More user manuals on ManualsBase.com


More user manuals on ManualsBase.com
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 4
2.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5 DC-to-DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.1 Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Internal Battery Packs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.0 WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.0 INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1.1 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1.2 Rack-Mount UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3 Connect the Internal Batteries Using the External Connector . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4 Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.1 Distribution Box Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.0 INITIAL START-UP AND ELECTRICAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.0 CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.1 GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features . . . . . . . . . . . . 17
7.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.0 CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.1 ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.2 Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.3 Load Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.4 Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.5 Fault Indicator LED (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

More user manuals on ManualsBase.com


8.6 Bypass Indicator LED (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.7 UPS ON Indicator LED (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.8 Battery Indicator LED (Amber). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.9 AC Input Indicator LED (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.1 Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.2 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3 Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.1 Communications Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.2 Pin 4 - Remote Shutdown on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.3 UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.4 Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11.1 Internal Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11.1.1 Internal Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11.2 AC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.2.1 PD-CEHDWR—Manual Bypass Switch Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
12.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
12.0.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
13.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FIGURES
Figure 1 GXT2, front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 2 GXT2, rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 3 Internal battery pack with connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4 Power distribution boxes, basic, optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5 Tower-use support bases, spacers for external battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 6 Distribution box electrical connections diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

TABLES
Table 1 Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 2 DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 3 Indicator meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 4 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 5 Alarm conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 6 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 7 UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 8 Power distribution specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 9 External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

ii

More user manuals on ManualsBase.com


IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS


This Manual Contains Important Safety Instructions. Read all safety and operating instructions
before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in
this manual. Follow all operating and user instructions. This equipment can be operated by individu-
als without previous training.
This product is designed for Commercial/Industrial use only. It is not intended for use with life sup-
port and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer.
See Limited Warranty.
This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply,
for installation by qualified personnel. A qualified electrician must review and approve customer sup-
plied wiring, circuit breakers, intended loads, and verify correct input, output and earth connections
to ensure compliance with technical standards and local electrical codes of practice. Installation
instructions and warning notices only for use by qualified personnel are located after the UPS opera-
tor instructions in this manual.

! WARNING
This UPS should not be supplied from electrical power systems of the “IT” (Impédance à
Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)

ELECTROMAGNETIC COMPATIBILITY—This UPS complies with the requirements of the EMC


Directive 89/336/EEC and the published technical standards. Continued compliance requires installa-
tion in accordance with these instructions and the use of manufacturer approved accessories only.

! WARNING
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent radio interference.

Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C
(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corro-
sive substances.
This UPS contains no user serviceable parts. The UPS ON/OFF push buttons do not electrically iso-
late internal parts. Under no circumstances attempt to gain access internally, due to the risk of elec-
tric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operat-
ing instructions, or the UPS performance alters in use. Refer all faults to your dealer.
Only trained engineers authorized by Liebert should perform troubleshooting. To replace batteries,
refer all servicing to qualified service personnel. Proper disposal of batteries is required. Refer to your
local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,
for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half
wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the off UPS and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol
cleaners.

More user manuals on ManualsBase.com


GLOSSARY OF SYMBOLS

Risk of electrical shock

! Indicates caution followed by important instructions

AC input

AC output

i Requests the user to consult the manual

- +
Indicates the unit contains a valve-regulated lead acid battery
PbH2SO4

R Recycle

DC voltage

Equipment grounding conductor

Bonded to ground

AC voltage

ON/Alarm Silence/Battery Test

OFF/Bypass

Indicates the position of a fuse

More user manuals on ManualsBase.com


Introduction

1.0 INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT2-6000RT230 and GXT2-4500RT230
Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it
may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera-
tions, cause data loss, or even damage equipment. The UPStation GXT2 protects equipment from
these disturbances.
The UPStation GXT2 comes in nominal power ratings of 4500 VA and 6000 VA. Complete model spec-
ifications appear at the end of this manual.
The UPStation GXT2 is a compact, on-line UPS. An on-line UPS continuously conditions and regu-
lates its output voltage, whether mains power is present or not. It supplies connected equipment with
clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT2 features a light-emitting diode (LED) display to indicate both
load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm
Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of
alarms when the unit is operating on battery.
The UPStation GXT2 has an interface port for communication between the UPS and a network server
or other computer systems. This port provides detailed operating information including voltages, cur-
rents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ soft-
ware. MultiLink software can also remotely control UPS operation.

More user manuals on ManualsBase.com


System Description

2.0 SYSTEM DESCRIPTION


Input Output
Dynamic
Bypass

L1 Rectifier L1
TVSS &
EMI/RFI /PFC Inverter
Filters DC-to-DC
N Converter
N

Battery Battery
Charger

G G

2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters


These UPS components provide surge protection and filter both electromagnetic interference (EMI)
and radio frequency interference (RFI). They minimize any surges or interference present in the
mains line and keep the sensitive equipment protected.

2.2 Rectifier/Power Factor Correction (PFC) Circuit


In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to
regulated DC power for use by the inverter while ensuring that the waveshape of the input current
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The mains power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the mains is reduced.
This results in cleaner power being available to other devices in the building not being protected by
the UPStation GXT2.

2.3 Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and
inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter
receives its required energy from the battery through the DC to DC converter. In both modes of oper-
ation, the UPS inverter is on-line and continuously generating clean, precise, Regulated Ac Output
Power.

2.4 Battery Charger


The battery charger utilizes energy from the mains power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the UPStation GXT2 is con-
nected to mains power.

More user manuals on ManualsBase.com


System Description

2.5 DC-to-DC Converter


The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-
mum efficiency and voltage, thus increasing reliability.

2.6 Battery
The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
design life, operate the UPS
in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are
available to extend battery run times.

2.7 Dynamic Bypass


The UPStation GXT2 provides an alternate path for mains power to the connected load in the
unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is
indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to
indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass,
press the Standby button once.

NOTE
The bypass power path does NOT protect the connected equipment from disturbances
in the mains supply.

More user manuals on ManualsBase.com


Major Components

3.0 MAJOR COMPONENTS


The GXT2 is composed of three major assemblies to provide easier handling, installation, and versa-
tility.

3.1 Main Frame and Electronics


This 5U cabinet is shipped with internal batteries installed and a basic, hardwire distribution box
attached and ready to install.

Figure 1 GXT2, front view


Top Trim
(2 pieces;
tower use
only)
Lower Bezel &
Battery Access
Door

Status
!

Indicators
UPStation GXT

& Controls

Upper
Bezel

More user manuals on ManualsBase.com


Major Components

Figure 2 GXT2, rear view

Battery
Disconnect

External Battery Fans


Connector

UPS Output
Circuit Breaker

DB-9
Communication REPO Connector
Port

Relay Card Slot

Removable Power
Distribution Box
Serial Card Slot
(SNMP, OCWEB, USB)

3.2 Internal Battery Packs


The UPS has two internal battery packs behind a battery access door on the front of the unit. Each
pack is fitted with a connector to link to the UPS.

Figure 3 Internal battery pack with connector

More user manuals on ManualsBase.com


Major Components

3.3 Removable Power Distribution Box


The UPS arrives with a basic hardwire power distribution pack installed. This box always contains
the UPS input circuit breaker.
Optional versions may be available to replace the standard box for custom installations.

Figure 4 Power distribution boxes, basic, optional

Basic Hardwire Power Distribution Box Optional Hardwire Power Distribution


PD-CEHDWR Box with Maintenance Bypass Switch
PD-CEHDWRBYP

NOTE
Hardwire and hardwire/receptacle boxes that include a manual bypass switch allow
AC power to continue to flow from the mains input to the load while the box is removed
from the UPS. For details, refer to 11.2 - AC Power Connections.

More user manuals on ManualsBase.com


What’s Included

4.0 WHAT’S INCLUDED


The GXT2 are shipped with the following items:
• GXT2-6000RT230 and GXT2-4500RT230 user manual
• Vertical display overlay
• Top bezels - 2
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• Rack mount handles
• Support base - 2
• Mounting hardware
• Configuration program disk
• DB9 port cover

Top bezels
(tower use)

MultiLink
software CD MultiLink
serial cable
10 ft (3m)
Vertical
Rack mount
display
handles
overlay
www.liebert.com
GXT2™ Configuration
Program
For use with LiebertGXT2U model UPS
systems
Version 1.6
For Windows 95/98/NT
To Install:
Choose the Start button on the Taskbar
and select Run

Mounting hardware

Configuration
disk
RS232
Support base
with spacers

DB9 port cover

More user manuals on ManualsBase.com


Installation and Configuration

5.0 INSTALLATION AND CONFIGURATION


Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until
instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer
or Liebert representative.

! CAUTION
The UPS is heavy (see 13.0 - Specifications). Take proper precautions
when lifting or moving it.

Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off.
Place it where air flows unrestricted around the unit. The installation location must be free of water,
flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of
100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to
40°C (32 -104°F).

NOTE
UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.
This device is intended for use in an Installation Category II environment.

5.1 Install the Main Cabinet


The GXT2 may be installed in either a tower configuration or in a rack, depending on available space
and use considerations. Determine the type of installation and follow the appropriate instructions in
either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1 Tower UPS Installation


When using the GXT2 in a tower configuration, use the included support base (shown below, left) to
stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommo-
date the additional cabinets (shown below, right).

Figure 5 Tower-use support bases, spacers for external battery cabinets

3U
3U
2U
2U

5U support base for GXT2 Spacers added to support base


End bases and 3U spacer to accommodate additional battery cabinets

5.1.2 Rack-Mount UPS Installation


When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed
rails or a shelf.
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig-
ures accompanying 5.1.3 - Installing the Adjustable Rack-Mount Kit—Sold Separately shows
the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out
of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.

! CAUTION
Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box
is located. The fourth mounting hole is above the Power Distribution Box and is not used.

10

More user manuals on ManualsBase.com


Installation and Configuration

5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately


This kit contains parts needed to mount several different models of UPS and external battery cabi-
nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per
pair of adjustable rack-mounting brackets is 91 kg (200lbs.).
Parts included are:
Item Quantity
Rear bracket members 2
Front bracket members 2
Inner bracket members 2
M4 x 8mm machine screws 16
M4 locking hex nuts 8
M5 x 16 mm machine screws 12
Grease packet. 1

Tools needed for installation are:


• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent
users from inadvertently sliding the UPS or battery cabinet out of the rack.
To install the rack mount brackets: Return
1. Unpack two (2) rack-mounting bracket assemblies and flanges
mounting hardware from this kit. Bracket assemblies are Retaining
interchangeable between left-hand or right-hand. Latches
Remove inner member of each bracket assembly as shown
at right by extending it to its outermost position, depress-
ing the retaining latch and then pulling the inner member
out of the bracket assembly.
2. Determine the height position inside the rack enclosure
Front
where you want to mount the UPS or battery cabinet. Inner members
members
! CAUTION
Reduce the risk of tipping the rack enclosure by
placing the UPS or battery cabinet in the lowest
possible rack position.

3. Install the rear member of each bracket assembly into the M5 screws
rack enclosure with two (2) M5 screws provided in this kit Front rack
(see figure at right). The return flanges on the bracket mounting rails
assembly fit to the inside of rack mounting rails. Insert
screws loosely (finger-tight) into the top and bottom holes of
the return flange on the rear member. Extend the bracket
assembly by sliding the front member forward until it
touches the front rack mounting rail. Insert two (2) M5
screws loosely (finger-tight) into the top and bottom holes of
the return flange on each front member. Make sure that the Rear rack
bracket assemblies are at the same mounting height on all mounting
four (4) rack mounting rails. rails
M5 screws

11

More user manuals on ManualsBase.com


Installation and Configuration

4. Get eight (8) M4 screws and eight (8) M4 nuts from the M4 nuts M4
hardware pack in this kit. Each nut has a locking, nylon screws
insert that begins gripping the screw when it is halfway
tight. Make sure to tighten the nut and screw completely to
ensure locking action. Fasten the rear member and the front
member together using (4) screws and (4) nuts per bracket
assembly as shown in at right. For maximum support, insert
fasteners for each bracket assembly as far apart as possible, 457mm
depending on rack depth, while still joining both members (18")
rack
(see figures at right). Check alignment of bracket assemblies depth M4 nuts
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for M4 nuts M4
rack mounting by following instructions in the equipment’s screws
user manual. The equipment may require additional parts to
be added or parts to be removed for rack mounting. After it is
prepared, lay the equipment in rack-mounting position.
Fasten the inner members from Step 1 to the equipment on 813mm
both sides as shown at right with eight (8) M4 screws (32") rack
provided in the kit. Make sure retaining latch is near the rear depth M4 nuts
of the equipment as shown (see figure at right).
6. Open the grease packet provided in the kit. Apply a bead of M4 screws Retaining latch
grease 25mm (1") long at four (4) places inside the bottom,
curved tracks of the front members as shown below right. The
grease will allow the equipment to slide into the bracket
assemblies more easily. UPS or battery
cabinet
! CAUTION
Lifting equipment into the rack may be a two-person
job, depending on the weight of the equipment.
6.

Liebert recommends taking the internal batteries Front


out of the UPS during rack installation. This will
make the UPS cabinet lighter and easier to handle. M4 screws
The GXT2 weighs 67kg (151lb). For the battery
cabinet’s weight, see the unit’s user manual.
Apply
7. Insert the equipment, with inner members attached in grease
Step 5, into the bracket assemblies by inserting the top and
UPS or
bottom edges of the inner members into the top and bottom battery
curved tracks of the front members and sliding the cabinet
equipment into the rack (see figure at right). Ends of inner
members are tapered to allow the rear of the equipment to be
angled upward before insertion, if space allows.
Apply
Then the rear, bottom edges of the inner members can be grease
placed into the front edge of the bottom tracks and the front (inside)
of the equipment can be tipped up so they are level to insert
the top edges of the inner members before sliding the equip-
ment into the rack (see figure below right). The equipment
should move smoothly into the bracket assemblies. If it does ... and push it
not, recheck the alignment of the front and rear members into the rack.
from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting rails
to prevent the equipment from sliding out of position. If
securing holes are provided on the front of the equipment
that align with the center holes on the return flange of the
front members, you can use the four (4) extra M5 screws Insert the UPS into the front
provided in the kit to secure the equipment. Otherwise, the members, lift the front ...
equipment should be secured to the front of the rack with
four (4) customer-supplied fasteners.

12

More user manuals on ManualsBase.com


Installation and Configuration

5.2 External Battery Cabinet Installation


Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked
beneath the UPS.

! CAUTION
The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.

1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier
and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift
up to remove. Optional rack-mount handles are shipped with the external battery cabinet and
may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert
representative for these additional options and any assistance needed. Fasten the slides into
position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of
support base extensions ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,
then to the rear of the UPS.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run
times, refer to Table 6.

NOTE
You must use the included configuration program to program the UPS for the number
of external battery cabinets connected. Instructions for the configuration program are in
7.0 - Configuration Program.

3U

2U
2U

Spacers added to support


base to accommodate
additional battery cabinets

13

More user manuals on ManualsBase.com


Installation and Configuration

5.3 Connect the Internal Batteries Using the External Connector


The internal connectors of the internal battery packs will be connected when shipped. However, the
internal batteries will be disconnected from the UPS using a rear panel connector. The connector
attaches to the UPS in both the open and closed position using two screws. The picture on the left
shows the connector in the open position, as shipped.
When the UPS is installed, remove the two screws to release the connector. Plug the connector into
the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to
secure the connector in the closed position.

Remove these screws


to release connector

5.3.1 Storage
If the UPS is to be shipped or stored for an extended time, the connector should be removed and
attached in the open position, as shown above. This will minimize any standby current drain on the
batteries.

5.4 Connect Input/Output Power


The UPS should arrive with the basic hardwire
box attached. If the box needs to be exchanged for
an optional model, remove and install the desired
box using the three captive screws marked in the
illustration at right. Unscrew
To remove: these
captive
Loosen the screws about 20 turns until the box screws
can be pulled away from the UPS.
To install:
Align the connectors on the box and UPS. Push
the box into place. While holding the box firmly
against the UPS, tighten the three captive screws
until the box is secure. Do not over tighten.

5.4.1 Distribution Box Electrical Connections


Electrical connections are made through a remov-
able power distribution box that attaches to the rear of the UPS.
The installer must provide a 32A branch circuit breaker. The Input circuit breaker on the distribution
box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between
the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass switch.

14

More user manuals on ManualsBase.com


Installation and Configuration

Figure 6 Distribution box electrical connections diagram


PD-CEHDWR PD-CEHDWRBYP

Mains Input Mains Input


Byp.
Input Input Output
32A CB Output 32A CB
External External Inv.
30 30
Branch Branch
CB CB

UPS UPS
Output Output
30 CB 30 CB

UPS - PFC, Battery, Inverter UPS - PFC, Battery, Inverter

PD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections


Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not
share the same conduit.
Table 1 Electrical specifications
Input Recommended Recommended Wire Maximum Wire Terminal
Current (Maximum) External (Including ground wire) Accepted by Tightening
Rating Overcurrent Protection (758C copper wire) Terminal Block Torque
24A 32A 6-10mm2 (8-10AWG) 10mm2 (8AWG) 2.26 Nm (20 in-lb)

N L N L
OUTPUT INPUT Overcurrent
32Amp Max Branch
Protection

6-10mm2 - Use Copper Wire Only

N L N L

OUTPUT TO LOAD INPUT TO UPS

NOTE
1. Note1 The installer must provide circuit breaker protection according to local codes. The
mains disconnect should be within sight of the UPS or have appropriate an appropriate
lock-out. Maintain service space around the UPS or use flexible conduit.
2. Note 2 The installer must provide output distribution panels, circuit breaker protection, or
emergency disconnects according to local codes. Output circuits must not share a common
conduit with any other wiring.

15

More user manuals on ManualsBase.com


Initial Start-Up and Electrical Checks

6.0 INITIAL START-UP AND ELECTRICAL CHECKS


1. Verify that the Input Output circuit breakers are off.
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables, and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted
in the sockets.
5. If you are using a distribution box that includes a Manual Bypass Switch, place the switch in
BYPASS position.
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.
7. Using a voltmeter, verify the expected L1-N voltage.
If no Manual Bypass Switch is used, there will be no output voltage at this time. If a Manual
Bypass Switch is used, verify that the same voltages appear at the Output terminals. If a Manual
Bypass Switch is used, the Bypass lamp will light by the switch. If no manual bypass switch is
used, there will be no output voltage at this time.
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,
close all access panels to the distribution box, and reapply input power.
9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should
illuminate on the front panel.
10. Press the ON button for 1 second. The BYPASS lamp will light for several seconds before the UPS
ON lamp turn on continuously. If the batteries are determined to charged above 80%, an
automatic battery test will run for about 15 seconds.
11. Close the Output circuit breaker on the rear of the UPS. If a Manual Bypass Switch is used, the
Inverter lamp by the switch will light. If a Manual Bypass Switch is used, transfer the switch to
the Inverter position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will
light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.
13. Review all setting option provided by the configuration program. Some changes require that the
UPS be OFF. If this is the case, these should be programmed before powering the loads. The
configuration program is described in the next section.
14. Connect all loads for normal operation.

16

More user manuals on ManualsBase.com


Configuration Program

7.0 CONFIGURATION PROGRAM


The final step of installation may require custom configuration of your UPS using the enclosed config-
uration program. Some configuration settings may be changed only while the UPS is off. These should
be set before the UPS is put into full-time service powering the critical load.
For most users operating with 230VAC and with no external batteries, the factory default settings
will be adequate.

7.1 GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features


• Select one of three L-N output voltages to match local voltages.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculations reported by Liebert software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 2).

7.1.1 What You Will Need


In addition to the GXT2 UPS, you will need the configuration program diskette and serial cable (beige
or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Win-
dows 95® or later computer, desktop or laptop, is also required to set up and run the configuration
program.

17

More user manuals on ManualsBase.com


Controls and Indicators

8.0 CONTROLS AND INDICATORS

All indicators illuminated


for illustration only.

UPStation GXT

AC INPUT BATTERY UPS ON BYPASS

8.1 ON/Alarm Silence/Manual Battery Test Button


This button controls output power to connected load(s) and has three functions:
• ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and
protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the
alarm is silenced, the UPStation GXT2 will reactivate the alarm system to alert of
additional problems.

NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second
while operating from mains power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24
hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact
your local dealer, Liebert representative or Liebert Worldwide Support Group.

8.2 Standby/Manual Bypass Button


This button controls output power to connected load(s) and has dual functions:
Standby and Manual Bypass.

! CAUTION
Pressing the Standby/Manual Bypass button once will transfer the
load to bypass power. Pressing the Standby/Manual Bypass button a
second time within 4 seconds will cut off power to the output sockets
and connected loads. Perform all necessary shutdown procedures on
connected loads before pressing this button twice.

18

More user manuals on ManualsBase.com


Controls and Indicators

8.3 Load Level Indicators (4 Green, 1 Amber)


The load level indicators display the approximate electrical load placed upon the UPS at all times.

8.4 Battery Level Indicators (5 Green)


The battery level indicators display approximate battery capacity at all times.
The UPStation GXT2 is equipped with automatic and remote battery test features. The automatic
test occurs every 14 days (this option is user configurable) if mains has not been interrupted. Should
the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will
illuminate and an alarm will sound (refer to 12.0 - Troubleshooting). The remote test feature func-
tions with MultiLink 3.x software and can remotely initiate the battery test.

8.5 Fault Indicator LED (Red)


The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the
battery level indicators may be illuminated (refer to 12.0 - Troubleshooting).

8.6 Bypass Indicator LED (Amber)


The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm
will sound indicating the UPS detected a problem, or the manual bypass function has been activated.

8.7 UPS ON Indicator LED (Green)


The UPS ON indicator LED is illuminated when the UPS inverter is operating and supplying power
to the connected loads.

8.8 Battery Indicator LED (Amber)


The Battery indicator LED is illuminated when the UPS is operating on battery.

8.9 AC Input Indicator LED (Green)


The AC Input indicator LED is illuminated when mains power is available and within the input spec-
ifications.

19

More user manuals on ManualsBase.com


Operating Instructions

9.0 OPERATING INSTRUCTIONS

9.1 Normal Mode Operation


During normal operation, mains power provides energy to the
UPS. The filters, power factor correction circuit and the inverter
process this power to provide computer grade power to connected
loads. The UPS maintains the batteries in a fully charged state.
The four green load level LEDs indicate an approximate level of
AC INPUT BATTER Y UPS ON BYPAS S
load in 25% increments. If the UPS becomes loaded beyond full
rating, the fifth (amber) LED indicator will illuminate and the
UPS will sound an audible alarm. The display template indicates Normal Mode Operation
the percentage of load (10% of load shown in example) on the UPS Batteries at 100% Charge
output. Load at 10%

9.2 Battery Mode Operation


Battery mode occurs in event of an extreme input voltage condition
or complete mains failure. The battery system supplies power
through the DC to DC converter to the inverter to generate power
for the connected load. During battery mode an alarm sounds
every 10 seconds. This will change to two beeps every 5 seconds
when the battery runs low (approximately 2 minutes remaining,
but this is user configurable). The AC Input LED will extinguish,
and the Battery LED will illuminate to warn that a mains problem Battery Mode Operation
has occurred. Each battery level indicator represents a 20% capac- Batteries at 30% Charge
ity level. As capacity decreases, fewer indicators remain illumi- Load at 50%
nated. Refer to 12.0 - Troubleshooting. For approximate battery
run times, refer to Table 6. These times are approximate, based on resistive load and an ambient
temperature of 25°C (77°F). To increase this time, turn off non-essential pieces of equipment (such as
idle computers and monitors) or add the optional external battery cabinet.

! CAUTION
Turning OFF the UPS while in it is battery mode will cut off output power.

9.3 Bypass Mode Operation


Bypass mode occurs when the OFF button is pressed once while
the UPS is in Normal Mode. During bypass operation, mains
power provides energy to the UPS. The mains power bypasses the
inverter and provides power for the connected load.
The four green load level LEDs indicate an approximate level of AC INPUT BAT UPS ON BYPAS S

load in 25% increments. If the UPS becomes loaded beyond full


rating, the fifth (amber) LED indicator will illuminate and the
UPS will sound an audible alarm. The display template indicates
the percentage of load (26-50% of load shown in the example above) on the UPS output.

9.4 Battery Recharge Mode


Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger
begins recharging.

20

More user manuals on ManualsBase.com


Communications

10.0 COMMUNICATIONS

10.1 Communications Interface Port


The UPStation GXT2 UPS has a standard DB-9 serial port female connector located on the rear of the
UPS unit. Several signals are provided on this port and are assigned as follows:
Table 2 DB-9 pin assignment
DB-9 Assignment Description
Pin

1 Low Battery (open collector)


2 UPS TxD (typically RS-232 levels)
3 UPS RxD (typically RS-232 levels)
4 Remote Shutdown (5-12VDC, 10-24mA max; battery operation)
5 Common
6 Remote Shutdown (short to pin 5); all modes of operation
7 Low Battery (open emitter)
8 Mains Fail (open emitter)
9 Mains Fail (open collector)

Pin Assignment Collector to Emitter*

6 7 8 9 Open
(+) Collector
330 Ohms

(-) Open
Emitter
1 2 3 4 5

* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA

10.2 Pin 4 - Remote Shutdown on Battery


1. 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the
mains, Pin 4 will ignore any signal on this pin.
2. 2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using
Liebert's contact closure cable. It cannot be used with just a contact closure unless the relay is
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown
signal for 1.5 seconds, the command cannot be canceled.
3. 3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown
signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the
UPS will shut down.
4. 4. If the mains returns during the 2-minute timer countdown, the shutdown timer will continue
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least
10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and
restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled
or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown
delay.

21

More user manuals on ManualsBase.com


Communications

10.3 UPS Intelligent Communications


The UPStation GXT2 is equipped with two Intellislot® ports to provide advanced communication and
monitoring options.
The Intellislot port closer to the corner of the UPS chassis is the serial card slot. This Intellislot port is
used for the OCWEBCARD and the USBCARD. The other Intellislot port is used for
RELAYCARD-INT or the MULTIPORT Card.
Liebert’s OCWEBCARD

DB9 (RS232) port


covered

NOTE
The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove
the cable after setup is complete.
When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector
needs to be covered. The DB9 cover is included with the UPS.

Liebert's MultiLink software continually monitors the UPS and can shut down your computer or
server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the
network with other computers running MultiLink when you purchase a MultiLink License Kit. For
more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site
(www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT2. The Intellislot
SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the net-
work.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-
dinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv-
ers support for built-in shutdown for AS/400 systems.

! CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables, where applicable.

22

More user manuals on ManualsBase.com


Communications

10.4 Remote Emergency Power Off


The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply
with national and local wiring codes and regulations.

REPO switch connection diagram


UPS ships with REPO jumper Opening the REPO connection will disable the UPS.
installed allowing the UPS Manual restart using the front panel is required after
to operate the REPO connection is closed again.

1 2 1 2

Normally closed switch system


(fail-safe)

! CAUTION
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.

23

More user manuals on ManualsBase.com


Maintenance

11.0 MAINTENANCE

11.1 Internal Battery


The UPStation GXT2 requires very little maintenance. The batteries are valve-regulated, non-spill-
able, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS
continuously charges the batteries when connected to the mains supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-
odically will result in permanent degradation of battery capacity.

UPStation GXT !
-+

AC INPUT BATTERY UPS ON BYPASS

The UPStation GXT2 is designed to allow the user to safely replace the internal batteries. Read the
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.

24

More user manuals on ManualsBase.com


Maintenance

11.1.1 Internal Battery Replacement

! CAUTION
A battery can present a risk of electrical shock and high short circuit current. Observe the
following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.

1. Remove the 3U battery access panel on the front of Battery Door Captive Screws
the UPS by loosening the two captive screws
located between the bezels (see illustration at
right). UPStation GXT
!

2. Once the captive screws are loosened, tip the panel AC OUTPUT BATTERY UPS ON BYPASS

forward and lift to remove it from the main


cabinet.
3. Use a Phillips (cross-head) screwdriver to remove
the screw in the battery retaining bracket on each
battery pack (see illustration at right). Remove the
retaining brackets.
4. Disconnect the battery connectors in the front of !
each battery pack. 3U Battery Access Door and
UPStation GXT

Battery Bezel
-+

5. Lift the internal connector out of the way and slide


the battery out of the UPS. Support the weight of
AC INPUT BATTERY UPS ON BYPASS

Retaining screw Retaining bracket


the battery to prevent it from falling.
6. Unpack the new battery assembly, taking care not
to destroy the packing. Compare new and old
battery assemblies to make sure they are the
same. If so, proceed with Step 7; otherwise STOP
and contact your local dealer, Liebert
representative or the Liebert Worldwide Support
Group.
7. Line up and slide in the new replacement battery
pack while holding the internal connector out of
the way.
8. Reconnect the electrical connections for each
battery pack.
9. Install the battery retaining brackets using the
Phillips removed earlier. UPStation GXT

-+
!

10. Install the battery access panel and tighten the


AC INPUT BATTERY UPS ON BYPASS

captive screws.

NOTE
These are hot-swappable replacement
batteries. However, caution should be
exercised because during this procedure the
load is unprotected from disturbances and Battery Connectors
power outages.

25

More user manuals on ManualsBase.com


Maintenance

11.2 AC Power Connections


Power connections may be disconnected from the UPS cabinet via a removable distribution box. This
may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows
power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to
the UPS to describe these procedures.
Hardwire and Hardwire/Receptacle boxes that include a Manual Bypass Switch allow AC power to
continue to flow from the mains input to the load while the box is removed from the UPS.

11.2.1 PD-CEHDWR—Manual Bypass Switch Available


Disconnect
1. DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect
all power to the load.
2. Ensure that the Maintenance Bypass Lamp is ON.
3. Switch to the maintenance bypass position.
The Load is now unprotected from line disturbances or interruptions.
4. Turn off the UPS using the front panel controls.
a. If needed, push the OFF button for one second once to transfer the load to bypass.
b. Press the OFF button twice within four seconds to turn the UPS off.
5. Turn off the UPS input circuit breaker on the box at the rear of the UPS.
This input circuit breaker only cuts power to the connector between the box and UPS. The input
circuit breaker does not cut power to the manual bypass switch.
6. Turn off the output circuit breaker on the rear of the UPS.
7. Remove the distribution box from the UPS
a. Loosen all three captive screws until box releases.
b. Pull box away from the UPS and set the box aside on a padded surface.

! CAUTION
Power is still passing through the box from mains to the load.

Reconnect
1. Align connectors and press the box onto the rear of the UPS.
2. 2. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.
3. If the Mains branch circuit breaker and load is off, turn the branch breaker on now.
4. Turn on the output circuit breaker on the rear of the UPS.
5. Turn on the input circuit breaker on the box.
6. Start the UPS according to the startup instructions.
Press the ON button for one second.
7. Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.
8. Turn the manual bypass switch to the UPS position.
9. The UPS now protects the load.

26

More user manuals on ManualsBase.com


Troubleshooting

12.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the UPStation
GXT2 develops a problem. Use this information to determine whether external factors caused the
problem and how to remedy the situation.
1. 1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. 2. An alarm will sound, alerting that the UPS requires attention.
Fault
Example shows UPS
on bypass because
of output overload,
signified by amber
load indicator.

AC INPUT BAT ON BYPAS S

3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic
aid to the operator, as described below:
Table 3 Indicator meanings
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep every half-second
A LED On bypass due to overtemperature condition; beep every 4 sec.
B LED On bypass due to DC bus overvoltage; beep every 4 sec.
C LED DC-DC failure during battery mode; beep every 4 sec.
D LED On bypass due to PFC failure; beep every 4 sec.
E LED On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
C&E LEDs UPS shutdown due to command from communication port (SNMP); no beep
Internal Battery source not available (continuous horn). Check Battery connection,
Battery LED Flashing
completely power down and reboot UPS.
A&E LEDs Fan locked
B&C REPO active. UPS cannot run with REPO loop open.
B&D UPS is OFF due to previous REPO shutdown. Autorestart disabled.
D&E Charger Malfunction

Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-
wide Support Group. Please have the UPS model number and serial number available at the time of
your inquiry.

27

More user manuals on ManualsBase.com


Troubleshooting

Table 4 Troubleshooting guide


Problem Cause Solution
Ensure UPS is OFF. Disconnect all loads and ensure nothing is
UPS fails to start when the UPS is short-circuited or
lodged in output receptacles.
ON button is pressed. overloaded.
Ensure loads are not defective or shorted internally.
UPS is operating from battery mode, make certain UPS is
UPS not plugged in.
securely plugged into the wall receptacle.
UPS input protection fuse UPS is operating from battery mode. Save data and close
Battery indicator LED is
has blown/opened. applications. Replace UPS input fuse, then restart UPS.
illuminated.
UPS is operating from battery mode. Save data and close
Mains voltage out of UPS
applications. Ensure mains supply voltage is within acceptable
input range.
limits for UPS.
Batteries are not fully Keep UPS plugged in continuously at least 24 hours to
charged. recharge batteries.
UPS has reduced battery UPS is overloaded. Check load level display and reduce the load on the UPS.
time. Replace batteries. Contact your local dealer, Liebert
Batteries may not be able to
representative or the Liebert Worldwide Support Group for
hold a full charge due to age.
replacement battery kit.
Fault and Bypass indicator Check load level display and remove non-essential loads.
UPS overloaded or load
LEDs and all load level LEDs Recalculate the load and reduce number of loads connected to
equipment is faulty.
are illuminated. UPS. Check load equipment for faults.
Ensure UPS is not overloaded, ventilation openings not
UPS internal fan has a
Fault and Bypass indicator blocked, or room ambient temperature is not excessive. Wait
problem or UPS shutdown
LEDs and diagnostic LED A 30 minutes to allow UPS to cool, then restart UPS. If UPS does
due to temperature condition.
are illuminated. not restart, contact your local dealer, Liebert representative or
Load is on bypass power.
the Liebert Worldwide Support Group.
Fault and Bypass indicator
UPS internal DC bus UPS requires service. Contact your local dealer, Liebert
LEDs and diagnostic LED B
overvoltage. representative or the Liebert Worldwide Support Group.
are illuminated.
Bus voltage under 315VDC(O/P 220VAC) / 330VDC(O/P
Fault indicator LED and
DC-DC failure during battery 230VAC) / 345VDC(O/P 240VAC). UPS requires service.
diagnostic LED C are
mode. Contact your local dealer, Liebert representative or the Liebert
illuminated.
Worldwide Support Group.
Fault and Bypass indicator
UPS PFC (Power Factor UPS requires service. Contact your local dealer, Liebert
LEDs and diagnostic LED D
Correction Circuit) fault. representative or the Liebert Worldwide Support Group.
are illuminated.
Fault and Bypass indicator
UPS requires service. Contact your local dealer, Liebert
LEDs and diagnostic LED E UPS inverter fault.
Representative or the Liebert Worldwide Support Group.
are illuminated.
Fault indicator LED and
Replace batteries. Contact your local dealer, Liebert
diagnostic LEDs A and C are UPS failed the battery test.
representative or the Liebert Worldwide Support Group.
illuminated.
Your UPS has received a signal or command from the attached
Fault and Bypass indicator UPS shutdown due to a computer. If this was inadvertent, ensure the communication
LEDs and diagnostic LED C command from the cable used is correct for your system. For assistance, contact
and E are illuminated. communications port(s). your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
Check for external obstruction entering fan guard. UPS
Fault and LEDs A&E are
Fan locked requires service. Contact your local dealer, Liebert
Illuminated
representative or Liebert Worldwide Support Group.
Fault and LEDs B&C are circuit is closed. If not used, a wire jumper must connect the
REPO active
Illuminated REPO terminals.
UPS is OFF due to previous
REPO shutdown, but the
Fault and LEDs B&D are
REPO has been connected Start the UPS using the front panel.
Illuminated
or reset. Autorestart
disabled.

28

More user manuals on ManualsBase.com


Troubleshooting

Table 4 Troubleshooting guide (cont’d)


Problem Cause Solution
If the charger is overvoltage, the UPS will shutdown. If the
charger is undervoltage and the batteries are nearly depleted,
Fault and LEDs D&E are
Charger malfunction this alarm will give a temporary warning before the UPS shuts
Illuminated
down. UPS requires service. Contact your local dealer, Liebert
representative or Liebert Worldwide Support Group.
Check battery connections, completely power down and restart
UPS.
Battery source is not NOTE: If the battery circuit
Battery LED is flashing.
available; continuous horn. opens while the UPS is running,
it will be detected when the next
battery test is performed.

Table 5 Alarm conditions


Condition Alarm
Battery Mode (mains failure) One short beep every 10 seconds: more than 2 minutes of run time remaining
Low Battery Two short beeps every 5 seconds: less than 2 minutes of run time remaining
Output Overload (Bypass) One short beep every half second
Overtemperature (Bypass) A one-second beep every 4 seconds
DC Bus Overvoltage (Bypass) A one-second beep every 4 seconds
DC-DC failure during battery A one-second beep every 4 seconds
mode
PFC Failure (Bypass) A one-second beep every 4 seconds
Inverter Failure A one-second beep every 4 seconds
Battery Test Failure A two-second beep every 1 minute
Fan Locked A one-second beep every 4 seconds
REPO Active A 0.25-second beep every 0.25 seconds
UPS OFF; Autorestart disabled
A one-second beep every 4 seconds
from previous REPO shutdown
Charger Malfunction A one-second beep every 4 seconds

29

More user manuals on ManualsBase.com


Troubleshooting

Table 6 Battery run times


Load% 4500VA 6000VA
10% 125 94
20% 66 46
30% 41 29
40% 30 21
Internal Battery 50% 24 17
(minutes) 60% 19 13
70% 16 11
80% 14 9
90% 12 8
100% 10 7
10% 296 222
20% 166 124
30% 114 81
40% 86 60
Internal Battery 50% 70 49
+ 1 External Battery
Cabinet (minutes) 60% 56 39
70% 48 33
80% 41 28
90% 35 24
100% 31 21
10% 467 350
20% 262 197
30% 180 135
40% 142 105
Internal Battery 50% 120 85
+ 2 External Battery
Cabinets (minutes) 60% 98 70
70% 83 58
80% 72 50
90% 62 43
100% 54 38
10% 638 478
20% 358 269
30% 247 185
40% 193 145
Internal Battery 50% 164 123
+ 3 External Battery
Cabinets (minutes) 60% 138 101
70% 120 85
80% 104 73
90% 90 63
100% 80 55
10% 809 606
20% 454 341
30% 313 235
40% 245 184
Internal Battery 50% 208 156
+ 4 External Battery
Cabinets (minutes) 60% 175 131
70% 153 113
80% 135 97
90% 120 85
100% 106 75
Using the configuration program, the user may specify the number of GXT2-240VBATT external bat-
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 6 above shows the estimated run times at different loads.

30

More user manuals on ManualsBase.com


Troubleshooting

12.0.1 Auto-Learning Battery Run Times


As batteries age, the estimated runtimes may become less accurate. The GXT2 is programmed to
“learn” from a full battery discharge and modify the estimated runtime for the measured battery
capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at
different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis-
charge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is Auto-Learned.

31

More user manuals on ManualsBase.com


Specifications

13.0 SPECIFICATIONS
Table 7 UPS specifications
Model Number GXT2-6000RT230 GXT2-4500RT230
Model Rating 6KVA / 4,200W 4.5KVA / 3,150W
Dimensions mm (in.)
Unit, W x D x H 221 x 547 x 430 (8.7 x 21.5 x 16.9)
Shipping, W x D x H 560 x 690 x 500 (22.05 x 27.17 x 19.7)
Weight kg (lbs)
Unit 67 (151) 67 (151)
Shipping 79.5 (175.3) 79.5 (175.3)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 50)
Factory Default VAC 230VAC
220/230/240VAC
User Configurable VAC
(May be modified using configuration program)
Operating Voltage Range Without
176 – 276VAC
Battery Operation
Maximum Allowable VAC 276VAC
Input Frequency Without Battery
40 - 70Hz
Operation
Input Power Connection PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Output AC Parameters
Factory Default VAC 230VAC
Output Connections PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode >200% for 96 milliseconds; 131 - 199% for 2 seconds;
Overload 112- 129% for 10 seconds with transfer to bypass
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # Yuasa / REW 28-12
Back-up Time See Table 6 - Battery run times
Recharge Time (Internal Batteries) 3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature 0°C to +40°C (+32°F to +104° F)
Storage Temperature -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 2000m (6600 ft) at 40°C (104° F) without derating
Storage Elevation 15,000m (50,000 ft.) maximum
<55 dBA, at 1 meter from the rear
Audible Noise
<50 dBA, at 1 meter from the front or sides
Agency
Safety EN62040-1-1; TUV/GS
EMI/EMC/C-Tick EMC EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1B

32

More user manuals on ManualsBase.com


Specifications

Table 8 Power distribution specifications


Model Number PD-CEHDWR PD-CEHDWRBYP
Amps Rating 32 Amps
Input Power Connection 3-Wire Hardwired, 6-10mm2 (8-10AWG)
Output Power Connection 3-Wire Hardwired, 6-10mm2 (8-10AWG)
Two IEC320 C19 16A/250V sockets
Includes: Two IEC320 C19 16A/250V sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 32A, Supplied by User

Table 9 External battery cabinet specifications


Model Number GXT2-240VBATT
Used w/ UPS model GXT2-6000RT230, GXT2-4500RT230
Dimensions, W x D x H, mm (in.)
Unit (with bezel) 176 x 522 x 430 (6.9 x 20.55 x 16.9)
Shipping 560 x 690 x 455 (22 x 27.2 x 17.9)
Weight, kg (lbs)
Unit 65 (145)
Shipping 78.5 (173.1)
Battery Parameters
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V 20 x 12V
Battery Manufacturer, Part # Yuasa / REW 45-12
Backup Time See Battery Run Times charts
Environmental
Operating Temp 0°C to +40°C (+32°F to +104° F)
Storage Temp -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 2000m (6600 ft.) at 40°C (104° F) without derating
Storage Elevation 15,000m (50,000 ft.) maximum
Agency
Safety EN62040-1-1; TUV/GS
Transportation ISTA Procedure 1B

33

More user manuals on ManualsBase.com


Specifications

34

More user manuals on ManualsBase.com


More user manuals on ManualsBase.com
POWER AVAILABILITY

GXT2-6000RT230™ & GXT2-4500RT230™


USER MANUAL

The Company Behind the Products Technical Support/Service


Web Site
With over a million installations around the globe,
www.liebert.com
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has Monitoring
developed a complete range of support and 800-222-5877
protection systems for sensitive electronics: [email protected]
Outside the US: 614-841-6755
• Environmental systems—close-control air Single-Phase UPS
conditioning from 1 to 60 tons 800-222-5877
• Power conditioning and UPS with power [email protected]
ranges from 300 VA to more than 1000 kVA Outside the US: 614-841-6755
• Integrated systems that provide both
Three-Phase UPS
environmental and power protection in a
800-543-2378
single, flexible package
[email protected]
• Monitoring and control—from systems of any
size or location, on-site or remote Environmental Systems
• Service and support through more than 100 800-543-2778
service centers around the world and a 24/7 Outside the United States
Customer Response Center 614-888-0246
While every precaution has been taken to ensure Locations
the accuracy and completeness of this literature, United States
Liebert Corporation assumes no responsibility and 1050 Dearborn Drive
disclaims all liability for damages resulting from P.O. Box 29186
use of this information or for any errors or Columbus, OH 43229
omissions.
Italy
© 2004 Liebert Corporation Via Leonardo Da Vinci 8
All rights reserved throughout the world. Zona Industriale Tognana
Specifications subject to change without notice. 35028 Piove Di Sacco (PD)
+39 049 9719 111
® Liebert and the Liebert logo are registered Fax: +39 049 5841 257
trademarks of Liebert Corporation. All names
Asia
referred to are trademarks or registered
23F, Allied Kajima Bldg.
trademarks of their respective owners. 138 Gloucester Road
Wanchai
Hong Kong
SLI-23170 (7/04) Rev. 3 +852 2 572 2201
Fax: +852 2 831 0114

You might also like