Rooftops Goodman
Rooftops Goodman
Rooftops Goodman
PRODUCT SPECIFICATIONS
PC SERIES
50 Hertz Self-Contained
Packaged Air Conditioners
4 and 5 Ton
[14.1 kW to 17.6 kW] The PC 50 Hz self-contained packaged air
Nominal Cooling Capacity: conditioners are designed for side-by-side and
48,000 to 60,000 BTUH ground-level or rooftop applications.
Standard Features Cabinet Construction
• Two-speed evaporator blower motor; low-speed for • Heavy-gauge, G-90 galvanized steel with removable
low-static applications, high-speed for high-static access panels
applications • Completely weatherized, properly reinforced and
• Quiet operating top condenser discharge braced
• Copper tubes/aluminum fin coils • Steel sheet metal is zinc-coated and galvanized by
• Hermetically sealed reciprocating compressor the hot-dip process
with internal relief valve and internal overload • Fully insulated air handling compartment
protection • Convenient access panels
• Fully charged R-22 system
• Liquid line filter drier Accessories
• High-efficiency performance • Heat Kit with plug-in connection (nominal capacity
• Bottom pan rails elevate unit above slab from 12-15 kW)
• High-pressure manual reset control • Room Thermostat (CHT18-60)
• Totally enclosed, permanently lubricated condenser • Outdoor Thermostat (OT18-60)
fan motor • Thermostat (CHT18-60HD)
• Both condenser fan and evaporative blower motors
are provided with internal thermal overload Accessories (Field Supplied)
protection • Roof Curb
• Downflow Plenum (includes filter rack)
Third-Party Tested • Manual Freash Air Damper (to be used with
• Independent third party performance tested by ETL Downflow Plenum)
Testing Laboratories, Inc. Per ARI Standard 210- • Economizer (to be used with Downflow Plenum)
240 Accessory Heat Kit Features
•Primary limit protection
•Rust-resistant nickel Chromium heating elements
(see Electrical Data Chart)
PRODUCT SPECIFICATIONS
Specifications
PC048-5A PC060-5A
Total Cooling Capacity BTUH [KW] 42,200 [12.4] 50,300 [14.7]
Sensible Cooling Capacity BTUH [KW] 29,800 [8.7] 32,200 [9.4]
EER 9.63 8.15
Sound Rating (bels) 8.4 8.4
Indoor Blower
Type DD DD
Size -D x W in [cm] 9 x 8 [22.9 x 20.3] 10 x 8 [25.4 x 20.3]
Motor H.P. [KW] 1/2 3/4
Evaporator Coil
Face Area ft2 [m²] 6.44 [0.60] 6.22 [0.58]
Fins/In FPI [Fins per cm] 15 [5.9] 12 [4.7]
No. of Rows 2 3
Outdoor Fan
Fan Dia. In [cm] 22 [56] 22 [56]
Motor H.P. 1/4 1/4
Condenser Coil
Face Area ft2 [m²] 16.2 [1.5] 16.2 [1.5]
Fins/In FPI [Fins per cm] 22 [8.7] 22 [8.7]
No. of Rows 1 1
Model Identification
P C 0 6 0 – 5A
Electrical Designator
5 - 380 -415 V, 3 Ph, 50 Hz
Nominal Capacity
048 - 42200 BTUH
060 - 50300 BTUH
Unit Type
PC - Package Cooling Unit
* All units are direct drive (DD)
Electrical Ratings
*Minimum Maximum
Power Supply Max Min Compressor Blower Motor Cond. Fan Motor
Model Circuit Overcurrent
Volts Volts
Volts Ph Hz Ampacity Protection RLA LRA Watts FLA Watts FLA Watts
PCO48-5A 380/415 3 50 12.9 20 456 342 8.4 45 3680 1.3 355 0.6 225
PC060-5A 380/415 3 50 16.4 20 456 342 10.5 62 4955 2.2 715 0.6 215
*Wire s ize should be determined in accordance with Local Electrical Codes. Extensive wire runs will require larger wire sizes.
67 47.5 31.3 4.80 45.1 30.3 5.07 42.3 29.2 5.33 39.5 29.2 5.59 38.1 29.2 5.72
1118
62 43.7 37.2 4.54 42.5 36.2 4.80 41.4 35.1 5.07 39.0 33.8 5.27 37.8 33.1 5.38
57 42.3 39.7 4.44 40.4 37.9 4.70 38.1 35.8 5.01 36.2 33.8 5.22 35.3 32.7 5.33
72 54.1 27.8 5.27 51.2 26.8 5.54 48.4 26.1 5.80 45.1 24.7 6.06 43.5 24.0 6.19
67 49.8 35.8 4.96 47.0 34.8 5.22 44.2 33.8 5.48 41.4 32.7 5.74 40.0 32.2 5.88
1315
62 46.1 42.8 4.70 43.7 41.1 4.96 41.8 39.0 5.22 39.5 36.9 5.54 38.3 35.8 5.69
57 45.6 43.2 4.70 43.7 41.1 4.96 41.8 39.0 5.22 39.5 36.9 5.54 38.3 35.8 5.69
72 55.5 30.3 5.38 52.6 29.2 5.64 49.4 28.2 5.90 46.5 27.5 6.16 45.1 27.1 6.29
67 51.2 40.0 5.07 48.4 39.0 5.33 45.6 37.6 5.59 42.8 36.5 5.85 41.4 36.0 5.98
1512
62 48.9 45.6 4.91 46.1 43.5 5.17 44.2 41.4 5.43 41.4 39.0 5.74 40.0 37.8 5.90
57 48.9 45.6 4.91 46.1 43.5 5.17 44.2 41.4 5.43 41.4 39.0 5.74 40.0 37.8 5.90
Sensible heat capacities shown are based on 80F DB entering air at the evaporator coil. For sensible heat capacities at other than 80F DB, deduct 84 BTUH per 100 CFM
of evaporator coil air for each degree below 80F, or add 84 BTUH per 100 CFM of evaporator coil air per degree above 80F.
PC060-5A
Indoor Condenser Air Temperature (Degree F)
Air 85 95 105 115 120
Total Sens Watts Total Sens Watts Total Sens Watts Total Sens Watts Total Sens Watts
SCFM WB Mbtuh
Mbtuh Kw Mbtuh Mbtuh Kw Mbtuh Mbtuh Kw Mbtuh Mbtuh Kw Mbtuh Mbtuh Kw
72 64.4 31.3 6.38 60.9 30.0 6.64 57.4 28.7 6.96 53.9 27.4 7.28 52.2 26.8 7.44
67 58.6 39.2 5.93 55.7 37.8 6.25 52.2 36.5 6.57 48.7 36.5 6.90 47.0 36.5 7.06
1615
62 53.9 46.5 5.61 52.5 45.2 5.93 51.0 43.9 6.25 48.1 42.2 6.51 46.7 41.3 6.64
57 52.2 49.6 5.48 49.9 47.4 5.80 47.0 44.8 6.19 44.7 42.2 6.44 43.5 40.9 6.57
72 66.7 34.8 6.51 63.2 33.5 6.83 59.7 32.6 7.15 55.7 30.9 7.48 53.7 30.0 7.64
67 61.5 44.8 6.12 58.0 43.5 6.44 54.5 42.2 6.77 51.0 40.9 7.09 49.3 40.2 7.25
1900
62 56.8 53.5 5.80 53.9 51.3 6.12 51.6 48.7 6.44 48.7 46.1 6.83 47.3 44.8 7.02
57 56.3 53.9 5.80 53.9 51.3 6.12 51.6 48.7 6.44 48.7 46.1 6.83 47.3 44.8 7.02
72 68.4 37.8 6.64 65.0 36.5 6.96 60.9 35.2 7.28 57.4 34.4 7.60 55.7 33.9 7.77
67 63.2 50.0 6.25 59.7 48.7 6.57 56.3 47.0 6.90 52.8 45.7 7.22 51.0 45.0 7.38
2010
62 60.3 57.0 6.06 56.8 54.4 6.38 54.5 51.8 6.70 51.0 48.7 7.09 49.3 47.2 7.28
57 60.3 57.0 6.06 56.8 54.4 6.38 54.5 51.8 6.70 51.0 48.7 7.09 49.3 47.2 7.28
Sensible heat capacities shown are based on 80F DB entering air at the evaporator coil. For sensible heat capacities at other than 80F DB, deduct 84 BTUH per 100 CFM
of evaporator coil air for each degree below 80F, or add 84 BTUH per 100 CFM of evaporator coil air per degree above 80F.
Total capacity shown is gross capacity. Senssible heat capacities shown are based on 80F (26.7C) DB entering air at the evaporator coil. For sensible heat capacities at
other than 80 F (26.7) DB, deduct 84 BTUH (0.25 KW) per 100 CFM (50L/s) of evaporator coil air per 1 F (0.6C) below 80 F (26.7C), or add 84 BTUH (0.025 KW) per
100 CFM (50 L/s) of evaporator coil air per 1 F (0.6C) above 80 F (26.7C).
PC060-5A (Metric)
Indoor Condenser Air Temperature (Degree C)
Air 29 35 41 46 49
Total Sens Watts Total Sens Watts Total Sens Watts Total Sens Watts Total Sens Watts
L/S WB
Kw Kw Kw Kw Kw Kw Kw Kw Kwh Kw Kw Kwh Kw Kw Kwh
22.2 18.9 9.2 6.38 17.8 8.8 6.64 16.8 8.4 6.96 15.8 8.0 7.28 15.3 7.8 7.44
19.4 17.2 11.5 5.93 16.3 11.1 6.25 15.3 10.7 6.57 14.3 10.7 6.90 13.8 10.7 7.06
762
16.7 15.8 13.6 5.61 15.4 13.3 5.93 15.0 12.9 6.25 14.1 12.4 6.51 13.7 12.1 6.64
13.9 15.3 14.5 5.48 14.6 13.9 5.80 13.8 13.1 6.19 13.1 12.4 6.44 12.7 12.0 6.57
22.2 19.5 10.2 6.51 18.5 9.8 6.83 17.5 9.6 7.15 16.3 9.1 7.48 15.7 8.8 7.64
19.4 18.0 13.1 6.12 17.0 12.7 6.44 16.0 12.4 6.77 15.0 12.0 7.09 14.4 11.8 7.25
897
16.7 16.7 15.7 5.80 15.8 15.0 6.12 15.1 14.3 6.44 14.3 13.5 6.83 13.9 13.1 7.02
13.9 16.5 15.8 5.80 15.8 15.0 6.12 15.1 14.3 6.44 14.3 13.5 6.83 13.9 13.1 7.02
22.2 20.1 11.1 6.64 19.0 10.7 6.96 17.8 10.3 7.28 16.8 10.1 7.60 16.3 9.9 7.77
19.4 18.5 14.7 6.25 17.5 14.3 6.57 16.5 13.8 6.90 15.5 13.4 7.22 15.0 13.2 7.38
949
16.7 17.7 16.7 6.06 16.7 15.9 6.38 16.0 15.2 6.70 15.0 14.3 7.09 14.4 13.8 7.28
13.9 17.7 16.7 6.06 16.7 15.9 6.38 16.0 15.2 6.70 15.0 14.3 7.09 14.4 13.8 7.28
Total capacity shown is gross capacity. Senssible heat capacities shown are based on 80F (26.7C) DB entering air at the evaporator coil. For sensible heat capacities at
other than 80 F (26.7) DB, deduct 84 BTUH (0.25 KW) per 100 CFM (50L/s) of evaporator coil air per 1 F (0.6C) below 80 F (26.7C), or add 84 BTUH (0.025 KW)
per 100 CFM (50 L/s) of evaporator coil air per 1 F (0.6C) above 80 F (26.7C).
PRODUCT SPECIFICATIONS
Dimensions
A B C D E F G
63.15 32.15 34.62 32.50 19.56 27.06 2.12
[160.4] [81.7] [87.9] [82.6] [49.7] [68.7] [5.4]
A B C D E F G H* A B C D E F G H I J
10.75 20.25 3.75 2.00 9.00 14.00 14.00 18.00 3.75 14 6.25 14 14 24 18.68 11.62 2.25 2.75
[27.3] [51.4] [9.5] [5.1] [22.9] [35.6] [35.6] [45.7] [9.5] [35.6] [15.9] [35.6] [35.6] [61.0] [47.4] [29.5] [5.7] [7.0]
* H return opening is equivalent to round duct stated
PRODUCT SPECIFICATIONS
Schematic Wiring Diagrams