04 Air Distribution System
04 Air Distribution System
04 Air Distribution System
CHAPTER 4:
PRELIMINARIES
The economic operation of Air Distribution system requires careful design of
the duct network distributing the air to the zones and the pumping system
conveying the chilled water to the AHU. The important design aspects of air
distribution systems are the following criteria (i) computation of pressure losses
across ducts and fittings, (ii) arrangement of the duct network, (iii) characteristics
of fans, (iv) interaction of fan and duct network, and (v) distribution of air within
the conditioned space.
Moreover, the design of duct–fan systems involve a number of interrelated cost
considerations, including energy cost, duct system cost, and building space cost. In
view of the somewhat tedious and iterative computations involved, duct system
design is often carried out using computer programs. In the following sections we
shall present the fundamental physical principles needed for designing duct
systems.
In this chapter, we shall concern ourselves with the distribution aspects of the
system, design of ducts and the pressure required to be developed by the fan.
Where
v = air velocity in the ducting
Q = Volume flow rate of air (Analyzed in both main and branch)
A = Cross Sectional area of the ducting based from duct geometry
Similarly, the equation presented can also be used to determine the area of
the supply air outlets (plotted values are for noise control)
Where:
∆P = Pressure loss (Pa)
f = dimensionless friction factor (using Colebrook’s, Moody Chart)
L = Length of the straight duct (m)
v = velocity of supply/return air (m/s)
ρ = density (kg/m3)
Deq. = Equivalent diameter of the duct (m)
For Equivalent Diameter of the Ducting, (A= cross sectional area)
The obtained value is the exact value of friction coefficient and next
procedure can be followed immediately.
4. Apply the equation to find the pressure loss in ducting inserting the
coefficient of friction f in the equation.
Estimation from the graph (values from fig. 21.15 and 21.16)
Estimation can be made if the type of material used for ducting is a
galvanized steel which is made to conform to the widely manufactured
absolute surface roughness of 0.15mm. The table also applies to a round
ducting as specified in the graph. For a rectangular ducting, use the
correction formula to determine the equivalent diameter as:
b. Sudden Enlargement:
Revising the Bernoulli’s equation to include pressure losses, we may
calculate the loss of pressure due to sudden enlargement.
Sudden Enlargement
c. Sudden Contraction:
A sudden contraction occurs in the duct section where the duct size is
abruptly reduced in the direction of flow. The flow pattern is predicted as
shown in the figure. A correction factor must be selected and applied
accordingly to adjust the pressure losses.
Sudden Contraction
Due to turbulence a vena contracta appears in section 1’ is observed. That is,
the factor can be obtained from Table 6-3 to apply the below formula:
3. Determine the factor multiplier for V2ρ/2 in figure 6-8 to calculate the
pressure loss.
For circular turns:
1. Calculate the geometry factor (RCURVATURE/Diameter)
2. See table 6-4 to locate the geometry factor multiplier for V2ρ/2 to yield
the pressure loss
Branch Take-off
For Branch Take-off pressure loss considering flow from u to b
1. Calculate the ratio Vb/Vu
2. From the design geometry, measure the take-off angle of the branch
3. In figure 6-11, locate the factor multiplier for V2ρ/2 to yield the
pressure loss
If the branch entry angle is 900, the equation above reduces as follow:
Branch Entry
C. FAN SIZING
After calculating the pressure losses in both the ducting and fittings in
the longest duct run, total frictional and geometry losses will now be used
to estimate the fan power.
As per application, fans and blowers are used simultaneously where
great amount of fluid (gases) volume is to be displaced requiring a low
pressure flow. Thus, basic flow and energy equation for fans and blowers
can be also used simultaneously.
Basically the total air power needed to drive the flow can be
computed using the below equation:
where:
TAP = total air power
γa = specific weight of air existing in the given air temperature
Q = Volume flow rate of air
ha = total head of air measure in both side of fans/blowers
streamline
Applying the bernoulli’s equation to calculate the total head of the
air:
Equation above can calculate the value of the total head of air
required after determining the static pressures in suction and in discharge
as well as air velocities and including the head losses where the fluid travels.
There are some instances where suction and discharge pressure are not
measured using a pressure gauge and the only means is the use of water
filled manometer. In this case, head of the fluid inside the manometer must
be converted to the equivalent static head of air given as:
Static Efficiency:
Fan Laws for Variable Motor Speed, Constant fan size and air density:
SUPPLEMENTARY PROBLEMS:
1. Design to size up the fan power of a certain Air handling unit having the
following data:
Material used: Commercial GI Sheet, Circular ducting design
Supply pressure in the diffuser: 2mm H2O
Velocity at diffuser: 5m/s
Supply temperature and humidity ratio: 180C, 0.00324kgv/kg da
Turn radius are equal to the corresponding duct diameter
The diameter reduction in each of the section follows a converging geometry
Fan Vacuum requirement: 100Pa
No difference in suction and discharge velocity in the fan side
Motor and Total Fan efficiency: 87%/80%