Deltapilot S
FMB70
These Instructions are Brief Operating Instructions; they are not a substitute for the
Operating Instructions pertaining to the device.
Detailed information about the device can be found in the Operating Instructions
and the other documentation:
Available for all device versions via:
– Internet: www.endress.com/deviceviewer
– Smart phone/tablet: Endress+Hauser Operations App
KA01023P/00/EN/16.14
71270391
Deltapilot S PROFIBUS PA
Serial number
A0023555
2 Endress+Hauser
Deltapilot S PROFIBUS PA Table of contents
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Operational safety and process safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Safety icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Product identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Measuring arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Assembling and mounting the "separate housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Connecting the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 On-site display (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 On-site operation via on-site display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.4 Configuring the device address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.5 Locking/unlocking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.1 Position adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.2 Level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3 Pressure measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Endress+Hauser 3
Safety instructions Deltapilot S PROFIBUS PA
1 Safety instructions
1.1 Designated use
The Deltapilot S is a hydrostatic pressure transmitter for measuring level and pressure.
The manufacturer accepts no liability for damages resulting from incorrect use or use other than
that designated.
4 Endress+Hauser
Deltapilot S PROFIBUS PA Product identification
1.4 Return
Follow the instructions on returning the device as outlined in the Operating Instructions.
Symbol Meaning
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury,
a safety hazard or destruction of the instrument.
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or
incorrect functioning of the instrument.
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation
or may lead to an instrument response which is not planned.
2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is displayed.
For an overview of the technical documentation provided, enter the serial number from the
nameplates in the W@M Device Viewer (www.endress.com/deviceviewer).
3 Installation
3.1 General installation instructions
# Warning!
The seal is not allowed to press on the process isolating diaphragm as this could affect the
measurement result.
Endress+Hauser 5
Installation Deltapilot S PROFIBUS PA
! Note!
• If a heated Deltapilot S is cooled during the cleaning (e.g. by cold water), a vacuum develops
for a short time, whereby water can penetrate the sensor through the pressure compensation
(1). If this is the case, mount the sensor with the pressure compensation (1) pointing
downwards.
1
FIELD TERMINALS
SLANIMRET DLEIF
1
• Keep the pressure compensation and GORE-TEX® filter (1) free from contaminations.
• Do not use sharp or hard objects to handle or clean the process isolating diaphragm.
• Due to the orientation of the Deltapilot S, there may be a shift in the measured value, i.e.
when the container is empty, the measured value does not display zero. You can correct this
zero point shift either via the "zero" key on the electronic insert, or on the outside of the
device or via the on-site display.See Page 14, Section 4.2.1 "Position of operating
elements", Page 15, Section 4.2.2 "Function of the operating elements" and Page 24, Section
5.1 "Position adjustment".
• To ensure optimal readability of the on-site display, it is possible to rotate the housing up to
380°.
• The on-site display can be rotated in 90° stages.
• Endress+Hauser offers a mounting bracket for installing on pipes or walls.
6 Endress+Hauser
Deltapilot S PROFIBUS PA Installation
P01-PMP75xxx-11-xx-xx-xx-000
Fig. 1: Measuring arrangement for level
Endress+Hauser 7
Installation Deltapilot S PROFIBUS PA
6
8
5
3
2
1 r ³ 120 mm
P01-FMB70xxx-11-xx-xx-xx-003
Fig. 2: "Separate housing" version
1 In the "separate housing" version, the sensor is supplied with process connection and cable fitted.
2 Cable with connection jack
3 Pressure compensation
5 Plug
6 Locking screw
7 Housing fitted with housing adapter, included
8 Mounting bracket suitable for wall and pipe mounting, included
8 Endress+Hauser
Deltapilot S PROFIBUS PA Wiring
4 Wiring
4.1 Connecting the device
# Warning!
Risk of electric shock!
If the operating voltage is > 35 VDC: Dangerous contact voltage at terminals.
In a wet environment, do not open the cover if voltage is present.
# Warning!
Limitation of electrical safety due to incorrect connection!
• Risk of electric shock and/or explosion in hazardous areas! In a wet environment, do not open
the cover if voltage is present.
• When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
• Devices with integrated overvoltage protection must be earthed.
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
• The supply voltage must match the supply voltage on the nameplate.
• Switch off the supply voltage before connecting the device.
• Remove housing cover of the terminal compartment.
• Guide cable through the gland. Preferably use twisted, screened two-wire cable.
• Connect device in accordance with the following diagram.
• Screw down housing cover.
• Switch on supply voltage.
Endress+Hauser 9
Wiring Deltapilot S PROFIBUS PA
➀
➃
PA PA
➁ ➄
PA PA
➂
P01-xMx7xxxx-04-xx-xx-xx-008
Fig. 3: Electrical connection PROFIBUS PA Observe also the following section.
For devices with plug see Operating Instructions.
1 Housing
2 Internal earth terminal
3 External earth terminal
4 Supply voltage, for version in non-hazardous area = 9...32 V DC
5 Devices with integrated overvoltage protection are labelled OVP (overvoltage protection) here.
As of HW Version 02.00:
13 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21.
As of Hardware Version 1.10, you will find a label in the device on the electronic insert.
10 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
! Note!
For further information on the cable specifications, see Operating Instructions BA00034S
"Guidelines for planning and commissioning PROFIBUS DP/PA", PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
5 Operation
5.1 On-site display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The on-site display shows
measured values, dialog texts, fault messages and notice messages.
The display of the device can be turned in 90° steps.
Depending on the installation position of the device, this makes it easy to operate the device and
read the measured values.
Endress+Hauser 11
Operation Deltapilot S PROFIBUS PA
Header line
Main line
Unit
Information
line
– + E Symbol
Bargraph
Editing modes
Operating keys
Selection
options
Value that
can be edited
12 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
The following table illustrates the symbols that can appear on the on-site display. Four symbols
can occur at one time.
Symbol Meaning
Alarm symbol
– Symbol flashing: warning, device continues measuring.
– Symbol permanently lit: error, device does not continue measuring.
Note: The alarm symbol may overlie the tendency symbol.
Lock symbol
The operation of the device is locked. Unlock device, see Page 22, Section 4.5.
Communication symbol
Data transfer via communication
Endress+Hauser 13
Operation Deltapilot S PROFIBUS PA
➅➆
t
➀ ➁ ➂
on
➀ ➃
off 0%
Sensor
Zero
Display ➄
0%
Zero on on ON CK S D A 0 8
1 2 off off 1 2 3 4 5 6 7 8
PC
1 2 3 4 5 6 7 8
Address
Histo ROM
SW
HW
P01-PMx7xxxx-19-xx-xx-xx-075 P01-xxxxxxxx-19-xx-xx-xx-105
Fig. 4: Operating key, external under the protective flap Fig. 5: Operating key and operating elements, internal
1 Operating key or position adjustment 1 Green LED to indicate value is accepted
(zero point-correction) or total reset 2 Operating key for position adjustment
(zero point-correction) or total reset
3 DIP switch for hardware address
4 Slot for optional display
5 Slot for optional HistoROM®/M-DAT
6 DIP-switch for locking/unlocking
measured-value-relevant parameters
7 DIP-switch for damping on/off
14 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
– Position adjustment (zero point correction): Press key for at least 3 seconds. If the
LED on the electronic insert lights up briefly, the pressure applied has been
0% accepted for position adjustment.
See also Page 27 (Level measuring mode) or Page 29 (Pressure measuring
Zero mode).
– Total reset: Press key for at least 12 seconds. If the LED on the electronic insert
P02-xxxxxxxx-19-xx-xx-xx-107
lights up briefly, the reset is being carried out.
Set address in the bus. See also Page 21, Section 4.4 "Configuring the device
on ON CK S D A 0 8
address".
off 01 1 2 3 4 5 6 7 8
1 2 3 4 5 67 8
Address
SW
HW
P01-xxxxxxxx-19-xx-xx-xx-109
Endress+Hauser 15
Operation Deltapilot S PROFIBUS PA
F – Confirm entry
– Jump to the next item
O F
Contrast setting of on-site display: darker
and
S F
Contrast setting of on-site display: brighter
and
ESC functions:
– Exit edit mode without saving the changed value.
– You are in a menu within a function group. The first time you press the keys
simultaneously, you go back a parameter within the function group. Each time you
O S and press the keys simultaneously after that, you go up a level in the menu.
– You are in a menu at a selection level. Each time you press the keys simultaneously,
you go up a level in the menu.
Note: The terms function group, level and selection level are explained in Section
4.3.1, Page 17.
Set address in the bus. See also Page 21, Section 4.4 "Configuring the device
on ON CK S D A 0 8
address".
off 01 1 2 3 4 5 6 7 8
1 2 3 4 5 67 8
Address
SW
HW
P01-xxxxxxxx-19-xx-xx-xx-109
16 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
Measured value
GROUP SELECTION
➀
➁
SETTINGS DISPLAY
➂
➃ POS. INPUT VALUE
CALIB. OFFSET
P01-xxxxxxxx-19-xx-xx-xx-145
Fig. 6: Structure of the operating menu
1 1. Selection level
2 2. Selection level
3 Function groups
4 Parameter
Endress+Hauser 17
Operation Deltapilot S PROFIBUS PA
P01-xxxxxxxx-19-xx-xx-xx-017
P01-xxxxxxxx-19-xx-xx-xx-033
P01-xxxxxxxx-19-xx-xx-xx-034
18 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
P01-xxxxxxxx-19-xx-xx-xx-023
P01-xxxxxxxx-19-xx-xx-xx-027
P01-xxxxxxxx-19-xx-xx-xx-028
P01-xxxxxxxx-19-xx-xx-xx-029
P01-xxxxxxxx-19-xx-xx-xx-030
Use "E" to save the new value and exit the editing mode.
See next graphic.
P01-xxxxxxxx-19-xx-xx-xx-031
Endress+Hauser 19
Operation Deltapilot S PROFIBUS PA
P01-xxxxxxxx-19-xx-xx-xx-032
P01-xxxxxxxx-19-xx-xx-xx-158
P01-xxxxxxxx-19-xx-xx-xx-159
Use "E" to assign the value (3.9 mbar) to the POS. ZERO
ADJUST parameter. The device confirms the calibration
and jumps back to the parameter, here POS. ZERO
ADJUST (see next graphic).
P01-xxxxxxxx-19-xx-xx-xx-037
P01-xxxxxxxx-19-xx-xx-xx-160
20 Endress+Hauser
Deltapilot S PROFIBUS PA Operation
➀ 0%
➁
Zero
Sensor Display
on on ON CK S D A 0 8
2 + 8 = 10
1 2 off off 1 2 3 4 5 6 7 8
PC
1 2 3 4 5 6 7 8
Address
Histo ROM
SW
HW ON CK S D A 08
on
250002272-–
HW-Version: 1
SW-Version: 2
– + E
off 01 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Address
SW
HW
P01-xxxxxxxx-19-xx-xx-xx-112
Fig. 7: Configuring the device address using the DIP switches
1 If necessary, remove on-site display (optional)
2 Set the hardware address via the DIP switches
DIP switch 1 2 3 4 5 6 7
Endress+Hauser 21
Operation Deltapilot S PROFIBUS PA
! Note!
• If operation is locked by means of the DIP-switch, you can only unlock operation again by
means of the DIP-switch. If operation is locked by means of remote operation e.g. FieldCare,
you can only unlock operation again by means of remote operation.
The table provides an overview of the locking functions:
1) Parameters which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST can still be
altered.
22 Endress+Hauser
Deltapilot S PROFIBUS PA Commissioning
6 Commissioning
# Warning!
• If a pressure smaller than the minimum permitted pressure is present at the device, the
messages "E120 Sensor low pressure" and "E727 Sensor pressure error - overrange" are output
in succession.
• If a pressure greater than the maximum permitted pressure is present at the device, the
messages "E115 Sensor overpressure" and "E727 Sensor pressure error - overrange" are
output in succession.
• Messages E727, E115 and E120 are "Error"-type messages and can be configured as a
"Warning" or an "Alarm". These messages are configured as "Warning" messages at the
factory. These messages are configured as "Warning" messages at the factory. In applications
where the user is consciously aware of the fact that the sensor range can be exceeded (e.g.
cascade measurement), this setting prevents the transference of status BAD.
• We recommend setting messages E727, E115 and E120 to "Alarm" in the following instances
( see Operating Instructions BA00356P):
– The sensor range does not have to be exceeded for the measuring application.
– Position adjustment has to be carried out that has to correct a large measured error as a
result of the orientation of the device.
! Note!
By default, the device is set up for the Level measuring mode, "Level Easy Pressure" level
selection and "%" as the unit.
Endress+Hauser 23
Commissioning Deltapilot S PROFIBUS PA
POS. ZERO ADJUST (685) Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure need not be known. (A reference pressure is present at the device.)
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Factory setting:
0
POS. INPUT VALUE Position adjustment – the pressure difference between zero (set point) and the measured
(563) pressure need not be known. (A reference pressure is present at the device.)
Entry
Example:
– MEASURED VALUE = 0.5 mbar
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2 mbar.
(MEASURED VALUEnew = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUEold – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
Factory setting:
0
CALIB. OFFSET (319) Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure is known.
Example:
– MEASURED VALUE = 2.2 mbar
– Via the CALIB. OFFSET parameter, enter the value by which the MEASURED VALUE
should be corrected. To correct the MEASURED VALUE to 0.0 mbar, you must enter
the value 2.2 here.
(MEASURED VALUE new = MEASURED VALUEold – CALIB. OFFSET)
– MEASURED VALUE (after entry for calib. offset) = 0.0 mbar
Factory setting:
0
24 Endress+Hauser
Deltapilot S PROFIBUS PA Commissioning
! Note!
• Some parameters are only displayed if other parameters are appropriately configured (see the
following table).
• The following parameters are set to the following values in the factory:
– LEVEL SELETION: Level Easy Pressure
– CALIBRATION MODE: Wet
– OUTPUT UNIT or LIN. MEASURAND: %
– EMPTY CALIB.: 0.0
– FULL CALIB.: 100.0
• For parameter description see CD-ROM, Operating Instructions BA00296P.
• The quick setup is suitable for simple and quick commissioning. If you wish to make more
complex settings, e.g. change the unit from "%" to "m", you will have to calibrate using the
BASIC SETTINGS group.
• See also Page 16, Section 4.2.3 "Function of the operating elements" and Page 17,
4.3 "On-site operation via on-site display".
MEASURED VALUE
GROUP SELECTION
LEVEL SELECTION
Pressure Level
1)
1) – LEVEL SELECTION "Level Easy Pressure"
and CALIBRATION MODE "Wet" FULL CALIB.
– LEVEL SELECTION = "Level Standard",
LEVEL MODE = "Linear" and
DAMPING VALUE
CALIBRATION MODE = "Wet"
P01-xMx7xxxx-19-xx-xx-xx-049
Fig. 8: Quick Setup menu for the Level measuring mode
Endress+Hauser 25
Commissioning Deltapilot S PROFIBUS PA
On-site operation
GROUP SELECTION
Select MEASURING MODE.
MEASURING MODE
Select "Level" option.
LEVEL SELECTION
Select level mode.
GROUP SELECTION
Select QUICK SETUP menu.
EMPTY CALIB. 1)
Enter level for the lower calibration point.
For this parameter, enter a level value which is assigned to the pressure present at the device.
FULL CALIB. 1)
Enter level for the upper calibration point.
For this parameter, enter a level value which is assigned to the pressure present at the device.
DAMPING TIME
Enter damping time (time constant ). The damping affects the speed at which all subsequent elements, such as the
on-site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.
26 Endress+Hauser
Deltapilot S PROFIBUS PA Commissioning
! Note!
• The operation must be unlocked. See page 22, Section 4.5 "Locking/unlocking operation".
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
Carry out position adjustment:
1. Pressure is present at device.
2. Press key for at least 3 seconds. See Page 14, Section 4.2.1 "Position of operating
elements".
3. If the LED on the electronic insert lights up briefly, the pressure applied has been accepted
for position adjustment.
If the LED does not light up, the pressure applied was not accepted. Observe the input
limits.
Endress+Hauser 27
Commissioning Deltapilot S PROFIBUS PA
! Note!
See also Page 16, Section 4.2.3 "Function of the operating elements" and Page 17, 4.3 "On-site
operation via on-site display".
MEASURED VALUE
GROUP SELECTION
Pressure Level
DAMPING VALUE
P01-xMx7xxxx-19-xx-xx-de-048
Fig. 9: Quick Setup menu for Pressure measuring mode
On-site operation
GROUP SELECTION
Select MEASURING MODE.
MEASURING MODE
Select "Pressure" option.
GROUP SELECTION
Select QUICK SETUP menu.
DAMPING TIME
Enter damping time (time constant ). The damping affects the speed at which all subsequent elements, such as the
on-site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.
28 Endress+Hauser
Deltapilot S PROFIBUS PA Commissioning
! Note!
• The operation must be unlocked. See page 22, Section 4.5 "Locking/unlocking operation".
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
Carry out position adjustment:
1. Pressure is present at device.
2. Press key for at least 3 seconds. See Page 14, Section 4.2.1 "Position of operating
elements".
3. If the LED on the electronic insert lights up briefly, the pressure applied has been accepted
for position adjustment.
If the LED does not light up, the pressure applied was not accepted. Observe the input
limits.
Endress+Hauser 29
Commissioning Deltapilot S PROFIBUS PA
30 Endress+Hauser
Deltapilot S PROFIBUS PA Commissioning
Endress+Hauser 31
KA01023P/00/EN/16.14
71270391
CCS/FM+SGML 9.0