Alup Allegroi AIR CONTROL 3 PDF
Alup Allegroi AIR CONTROL 3 PDF
Alup Allegroi AIR CONTROL 3 PDF
ALLEGRO 30 - 210
2001
All particulars in this manual are specified to our best knowledge, but without
guarantee.
We reserve the right to make changes to information on hardware and
firmware documentation at any time without previous announcement.
Safety instructions You are reading this manual in order to learn about the screw compressor.
It contains information that is required for safe, malfunction-free operation
of the system. Please keep in mind that damages incurred due to improper
usage may not fall under the conditions of guarantee!
For this reason, please keep this manual where all users can have free
access to it at any time.
DANGER
NOTICE
Italic text is employed when we would like to draw your attention to particu-
lar information.
Any other utilization must be regarded as not in compliance with the design
purpose!
The manufacturer/vendor is fundamentally not liable for damages incurred
if the system is not used according to its design purpose!
The generated compressed air may not be used for human respiration. In
case the compressed air is used for pharmaceutical or sanitary purposes, it
must undergo further treatment. The same is true when the compressed air
is used in production plants and comes into direct contact with foodstuffs.
1.3 Qualified personnel This manual is directed to qualified personnel, who are commissioned
with the transport, installation, operation or service of the system. These
individuals must read the chapter relevant to their duties.
Activities that are not described in this manual may only be carried out by
our customer service department or by authorized technical personnel.
5
1. Safety instructions
1.4 General safety instructions
Document all the activities carried out (e.g. in some table format).
7
Carry out the activities in all of the following chapters in the order given.
2. Functional description
2.1 Drive The frequency converter in the switching cabinet supplies the electric mo-
tor with power. For the operating principle of the frequency converter, please
refer to the instructions in the switching cabinet.
The electric motor drives the compressor stage via a flexibly supported
coupling.
2.2 Air path Fresh air supplied by the integrated cooling air ventilator is filtered through
the intake filter(s). The air is then directed via the intake regulator into the
compressor stage, where it is compressed to the final compression pres-
sure together with injected coolant.
In the coolant reservoir, the compressed air is separated 98 % from the
cooland and the downstream coolant separator removes the remaining
coolant from the compressed air. The air then flows via the minimum pres-
sure one way valve into the compressed air aftercooler and is cooled down
to 10 - 15 C above the ambient temperature before it leaves the compres-
sor through the compressed air port.
The intake regulator opens shortly after the compressor has started up for
generating compressed air. It closes when the compressor changes over
to off-load operation and/or comes to a standstill and unloads the system
via the relief valve.
2.3 Coolant circulation The coolant is sprayed into the compression stage and has the following
functions:
sealing lubrication of the rotors to each other and to the housing with a
coolant film
bearing lubrication
noise dampening
The coolant leaves the compression stage together with the compressed
air as a hot coolant return air mixture.
The coolant is separated from the compressed air into the coolant con-
tainer by the coolant separator and when separated, it streams to the cool-
ant heat exchanger. The coolant temperature regulator mixes the cooled
down coolant with the coolant heat exchanger-bypass hot coolant as de-
8 fined by the setpoint temperature. Lastly, the coolant filter cleans the cool-
ant, before it is again injected in the compression stage.
If desired by the customer, an additional heater can be installed in the
coolant container either originally or subsequent to purchase. It prevents
condensation damages in the case ofcold or damp compressor plant envi-
ronments, for example.
2.4 Cooling The compressed air after-cooler of the coolant heat exchanger is cooled
either by
water cooling.
The electric motor is always cooled by its own ventilator fan.
In the case of water-cooled compressors, a fresh air ventilator additionally
ensures sufficient fresh intake air for the removal of radiated heat.
2.5 Flow diagram 14
20
02 M
08
PD 1 03 PS
12 13 PI
15 16
04 06 22
07 11 PD2
23
05
21
19 26 28
09 27
25 24
18
17
01
2.6 Components
20
04 02
05
15
06
12 01
07
08
10
19
DANGER
10
11
4. Installation
4.1 Setting up
Install the system in locations with the following environmental conditions:
max. height above sea level: 1000 m
ambient temperature: +5 to +40 C
ambient temperature for Version T: +5 to +45 C
ambient conditions: cool, dry, dust free
Space requirements and system weights are dependent on the plant type
purchased. Measurements and weights: see Chapter 9.
Open flame or fire as well as welding work in the vicinity of the system
are forbidden!
DANGER
4.2 Ventilation The air entering the intake opening is used for the compression as well as
for plant cooling.
Supply required cooling air amounts as defined in Chapterd 9.2 and 9.3
Make certain that the supply air contains no dangerous explosive gas
12 mixtures, steam, dust or aggressive pollutants.
Make certain that the setup site is dust-free as well as within the prescri-
bed operating temperature limits and as cool as possible. If necessary,
ensure the professional installation of forced air ventilation, filtering, room
cooling or heating.
Make certain that no circulating air short circuit (the intake of the
NOTICE exhausted warm air) can occur.
Cooling air volume currents: see Chapter 9.
4.3 Forced ventilation (op- Forced ventilation must be dimensioned in such a way that the required
tional) fresh and exhaust air, considering the available residual pressure of the
compressor ventilator, can be supplied and expelled.
The exhaust air can also be utilized for the purpose of heat recovery.
4. Installation
4.4 Water cooling (optional) For water-cooled plants, the temperature of the compressed air after-cooler
of the coolant heat exchanger is lowered with external cooling water.
12 13 PI
15 16
22
PD2
23
21
17
26 28
14 27
25 24
01
4.7 Electrical connections The system is designed for connections to a three-phase supply network
(clockwise phase sequence). The mains supply contains professionally
dimensioned fuse protection devices (for human and plant system
protection), an appropriate mains switch (switching on/off of the supply
current) is required.
Electrical voltage!
Only trained electricians may connect the system to the electrical sup-
ply network.
DANGER
The plant main switch must be switched off for all service or installa-
tion work and protected from illicit or accidental switching on (e.g.
affix a warning sign to the main switch forbidding its being turned on)!
DANGER
5.2 Emergency OFF The system may be stopped with EMERGENCY OFF in the case of a real
emergency!
Enable system:
1. pull key
F1 F2 F3 F4 Function keys
Switch on compressor.
Integrated green LED
Blinking: compressor is not running, can at any time 17
be automatically started up.
Lighted: Compressor is running.
Momentary com-
Momentarily available grid pressure at com-
pression final tem-
pressed air output
perature
5.3.3 Function key reservation In the basic display, the following informative pictures can be accessed
in the basic display with the function keys:
Mode 1 = reservation 1
18
F1 F2 F3 F4
Capacity Service
utilization Plant pass
With the key and , the mode and therefore the reservation of the
function keys in the basic display can be changed.
Mode 2 = reservation 2
F1 F2 F3 F4
Diagram Diagram
grid pressure air amounts
daily profile
Diagram Diagram
compression air amounts
temperature weekly profile
5.3.3.1 Capacity utilization This diagram represents the operating run, full load run, idling run, and
(Mode 1 - F1) standstill hours in the form of bar diagrams. The respective current hour
Change of mode 5.3.3 count is also displayed in the bars.
Example:
Load hours
With the exception of the idling time hours, all bars are represented from
the left and growing to the right. The sum of the load hours and the idling
time hours yields the total service hours.
The scaling units of this diagram are according to the service hours. If the
number of the standstill hours is larger than the service hours, the bars of
the standstill hours will be cut off. In this case note the displayed hour
count in the bars.
5. Displays and operating elements
5.3.3.2 Service The Service diagram shows the remaining residual time in hours until the
(Mode 1 - F3) respective service interval is due.
Change of mode 5.3.3
Intake filter
Coolant filter
Coolant separator
Motor lubrication
Compressor
If the remaining residual time is less than 100 hours until the next service,
the respective bar begins to blink and a defined warning appears on the
display.
5.3.3.3 Plant pass The individual machine data stored in the plant pass are required for our
(Mode 1 - F4) customer service.
Change of mode 5.3.3
20
5.3.3.4 Diagram grid pressure In this diagram, the current process of the grid pressures is displayed.
(Mode 2 - F1)
Change of mode 5.3.3
5.3.3.5 Diagram compression In this diagram, the current process of the compression end temperature is
end temperature displayed.
(Mode 2 - F2)
5.3.3.6 Diagram compressed air In this diagram, the current process of the compressed air-delivery amounts
amount / day profile for a day are displayed.
(Mode 2 - F3)
Change of mode 5.3.3
21
5.3.3.7 Diagram compressed air In this diagram, the current process of the compressed air-delivery amounts
amounts / week profile for a week are displayed.
(Mode 2 - F4)
Change of mode 5.3.3
5. Displays and operating elements
5.3.3.8 Modify diagram settings The scale divisions of the axis can be changed by editing the axis values.
Axis value x-axis (time point 1) Axis value x-axis (time point 2)
The key F2 X/Y-Init is for resetting the scale division for the default values
preset in X-AUTO.
The sub-menu can be selected with the keys and .The selection is
confirmed with ENTER.
In every operating level, F4 will lead you to the next higher operating level.
23
1. The selection of the desired menu position is carried out with the keys
and .
Selection of the menu position Switch-on pressure Lower value for the pressure regulation Can be edited
Modification of the blinking values
Switch-off pressure Upper value for the pressure regulation Can be edited
ENTER Confirm selection/modification
Safety pressure Maximum permissible pressure for Display
F4 Back to the next higher level malfunction triggering (always 0.8 bar
greater than switch-off pressure)
Compression end Minimum permissible compression Display
temperature min end temperature
Compression end Maximum permissible compression Display
temperature max end temperature
5.3.4.2 Sub-menu This menu contains parameters which influence the temporal regulation of
Operating parameters the compressor:
Selection of the menu position After-run time After-run time of the motors in Display
Modification of the blinking values automatic operation
ENTER Confirm selection/modification Standstill time After-run time of the motor for manual Display
F4 Back to the next higher level switching-off delay and for automatic
restart
Run-up time Run-up time Display
Automatic Start after voltage return Can be
restart edited
Operation mode: Behavior on load switching Can be
Setting range: AUTOMATIC edited
LOAD/IDLING
AUTOMATIK OPT.
Max. pressure drop Maximum pressure drop Display
Max. switching cycles Maximum switching cycles of the motor Display
per hour per hour
5.3.4.3 Sub-menu In this menu, all service intervals are displayed, or acknowledged after
Service intervals carrying out the specific service (see Chapter 5.3.5).
Service work acknowledged With the acknowledgement, the displayed residual time for the value of the
5.3.5
respective service intervals (see Chapter 8.1) is reset.
25
5. Displays and operating elements
5.3.4.4 Sub-menu Timer The adjustment of the integrated real-time clock, as well as all switching
processes dependant upon it are in this menu.
Selection of the menu position
Modification of the blinking values Date/time Setting the current date Edit
and time
ENTER Confirm selection/modification
Attention: The adjustment is entered
F4 Back to the next higher level to the real-time clock when the
seconds are confirmed with ENTER
Compressor switching Branch to the sub-menu Edit
times
Compressor pressure Branch to the sub-menu Edit
times
Switching times BLS Branch to the sub-menu Edit
Pressure times BLS Branch to the sub-menu Edit
26
For the activation of the timer, the parameter of the timer channels must be
set to ON in the highest menu line.
If the timer channel is set to ON and
if the timer output is not activated, a blinking clock appears in the dis-
play
If the timer for switching times is activated, then the compressor only
works during the switching times entered!
NOTICE
In this menu, the pressure times of the compressors are defined (increasing
pressure / decreasing pressure).
In order to activate the timer, the uppermost menu row of the parameter for
the timer channels must be set to ON.
5.3.4.6 Sub-menu In this menu, the parameters for the output to thedisplay are stored.
Display parameter
Selection of the menu position Pressure unit Selection of the unit for the display Edit
Modification of the blinking values of the grid pressure
ENTER Confirm selection/modification Temperature unit Selection of the unit for the display Edit
F4 Back to the next higher level of the compression final temperature
Language Selection of the display language Edit
Pressure offset Readjustment possibility for the Display
grid pressure sensor
Diagrams Settings for diagrams Edit
Texts Texts for the plant pass Display
Diagrams
In this menu, the display parameters (default values X-AUTO - see Chapter
5.3.3.8) for the diagrams can be set:
Storage interval Storage interval for the recording of the grid pressure, the
compression final temperature of the momentary delivery
amounts. The control system always stores the most recent
8000 values. For a storage interval of 12s (basic setting)
there is a logging duration of 12s x 8000 = 96000s = 26.7h
Remote mode
Determines how the compressor is switched on or switched off.
During active remote operation, the signal of the remote control must
be switched off after pressing the key 0.
NOTICE
BLS OK: Is for the notification of the operation ready state of a superior
control system to the compressor. (see also BLS Operation 5.3.4.9)
BLS Operation
29
The control system of the compressors is carried out by a superior control
system. The text BLS OPER. (see also Remote Mode 5.3.4.9) appears in
the basic display
5. Displays and operating elements
5.3.4.8 Sub-menu This menu contains parameters for serial communication
Communication
RS485 Address Participant address for RS484 Display
communication
RS485 Mode Data exchange on the serial Display
interface
5.3.4.9 Sub-menu This menu contains the settings for the operation as the BLS Master.
Base Load Switching
(BLS)
For the utilization of the function base load switching, the Air Control 3
Selection of the menu position
must be fitted with
Modification of the blinking values
ENTER Confirm selection/modification a supplementary module for up to 4 additional compressors
F4 Back to the next higher level
two supplementary modules for up to 8 additional compressors.
30
5.3.4.10 Sub-menu Accessories This menu contains the settings for the connection of accessories. The Air
Control 3 must be fitted with the supplementary module accessories for
the utilization of these functions.
The switching on/off times of an accessory relay output are defined in this
menu.
For the activation of the timer, the uppermost menu row of the parameter
of the timer channels must be set to ON.
Input configuration
31
5. Displays and operating elements
5.3.5 Warnings / service work A warning is current when the red light is blinking.
The compressor is not switched off.
The display contains the additional information:
blinking symbol warning triangle
type of warning
telephone number of the service hotline
1. As described in Chapter 5.3.4, call up the main menu and then the sub-
menu Service Interval.
32
2. Select the service work to be carried out with the keys and .
4. By double clicking the key F4 you will return to the basic display.
5.3.6 Malfunctions A malfunction has occurred when the red light is permanently on.
Malfunctions can only be acknowledged when the cause has been profes-
sionally repaired. Error searches and repair should be done exclusively by
qualified personnel!
1. press key .
33
6. Correcting malfunctions
Compression temperature - Silencing hood not closed - Check and secure sound-
too high (red lamp is on) insulation hood
- Intake or environmental - Ventilate compressor room
temperature too high
- Make sufficient room
- Cooling air inlet or outlet blocked
- Renew coolant filter
- Coolant filter fouled
- Add coolant
- Coolant deficiency
- Clean with compressed air. In the
- Outside coolant heat exchanger case of extensive fouling:
fouled! A t t e n t i o n : Cooler disassemble cooler and clean
screw should always be with high pressure cleaner.
worked with a counter wrench;
Attention: Danger of short
keep from applying torque to
circuit! Do not put electrical
the cooler
elements under power
- Compressed air consumption - A compressor with larger delivery
Grid pressure falls greater than delivery amounts of amounts is required
the compressor
- Air filter is fouled - Replace air filter
- Relief valve blows air during - Check relief valve; if necessary,
compression replace seals
- Intake regulator does not open - Check magnet valve regulator
piston and if necessary, replace
- Leakage in the piping grid - Make piping grid airtight
System pressure released on - Grid pressure set too high - Adjust grid pressure anew
safety valve
- Safety valve defective - Check safety valve; if necessary,
exchange
- Minimum pressure valve blocked - Exchange magnet valve
- Coolant separator cartridge - Exchange coolant separator
fouled cartridge
34
Malfunction over- - Coolant separator fouled - Replace coolant separator
pressure or Grid
pressure too high (red
- Equalize outside pressure or
lamp is on) - Higher outside pressure in the
remove from grid
compressed air grid
Error Cause Measures
Compressor does not start - Grid pressure set too high - Adjust grid pressure anew
automatically or does not
- Interruption in the control current - Check current loop for interrup-
deliver after previous
circuit tion (only by an trained electri-
switching off upon reaching
cian)
the final pressure or from
idling state. - Ambient temperature under +1 - Build in an additional heater or
C; message Coolant tempera- keep compressor room at right
ture too low temperature
- Switching times have been - Check switching times and
activated in the Air Control 3 pressure times in the Air Control
System does not start on - Grid pressure greater than - Note grid pressure value
pressing the start button switch-on pressure
- Remote control activated - Symbol remote is blinking
Compressed air containing - Coolant return flow piping is - Clean coolant feedback piping
large amount of coolant congested
(coolant consumption too
- Defective coolant separator - Replace coolant separator
great)
35
Water in the piping grid - Dryer switched off - Switch on dryer
- Condensation diverter is not - Clean / exchange drain
functioning
- Bypass open - Close bypass
- Dew point too high - Demand customer service
7.2 Check coolant 1. Make certain that escaping coolant can be collected.
level
Check coolant level/ 2. Check the coolant level at the sight glass which is located on the front
coolant refill 8.3 side of the coolant container: the sight glass must be totally filled with
coolant. Unscrew the the filling screw. Do not misplace the seal. For
new compressors, the coolant level must reach up to the lower level of
the inlet fitting.
3. If required, refill the coolant (see Chapter 8 Check coolant level / refill
coolant)
7.3 Start-up lubrication of the After an extended standstill time, for example between factory delivery
compressor stage and commissioning or during a longer company vacation, there might no
longer be any coolant in the rotor chamber of the compression stage. This
coolant is absolutely necessary for bearing and rotor lubrication in the start-
up phase.
1. Before switching on the compressor plant, fill approx. 0.2 liter coolant
into the filler screw of the intake regulators.
36
If no extra coolant is available (only coolant of the same variety may be
employed!), the coolant can be taken from the coolant drain.
If the system is employed only very irregularly or shut down weeks on end,
it should run an hour in idling mode once a week in order to avoid corrosion
damage caused by standing condensation.
7.4 Rotational direction control The rotational direction of the plant ventilators must be checked.
The rotational direction of the main motor is determined by the frequency
converter and must conform with the affixed rotational direction arrow.
1. Remove the cover panels of the system, so that the electric motor of the
ventilator is visible.
3. Switch the system on with the key Switch the system off again with
the key , when the ventilator starts running.
In order to supply the system with sufficient cooling air, the rotational direc-
tion of the ventilator motors must concur with the rotational direction arrow.
In the case of incorrect rotational direction of the plant ventilators, a trained
electrician should correct the phase sequence of the electrical supply in
the switching cabinet by exchanging the two supply phases. This should
be carried out in a switched-off state secured against accidental switching
on.
37
7. Initial commissioning
7.5 Basic settings In order to understand plant basics, please read the chapter 5 Plant
operating elements .
7.5.1 Control system of the More precise instructions on the basic settings of the system can be found
system with Air Control 3 in the following chapters :
Chapter 5.3 Operating screen,
Chapter 5.3.1 Basic display
Chapter 5.3.4 Menu system
If your Air Control 3 has been fitted with the supplementary module BLS,
carry out settings as in point 5.3.4.7 5.3.4.9 of the description.
If your Air Control 3 has been fitted with the supplementary module acces-
sories, carry out settings as in point 5.3.4.10 of the description.
38
7.6 Switch on compressed air 1. Before switching on the system, make certain that no one can be en-
generation dangered by doing so. The sound-insulation hood serves as a part of
the contact protection, among other things for the cooling air conduits
of the compressor plant. It must be closed during operation.
2. Carefully open the shut-off slide valve after the compressed air connec-
tor and between system compressed air grid (container). The system is
now connected to the grid.
4. Make certain that no tools or loose objects are lying on or in the system.
The green LED in the key lights up when the compressor is working.
Check on the operating display desk for the grid pressure.
The grid pressure will slowly rise if the compressed air consumption is less
than the delivery amounts of the compressors.
On blinking green LED, the compressor can start by itself at any time!
DANGER
7.7 Concluding activities 1. Check all piping of cooling liquids and pressure air conduits for leak-
age.
39
2. Check the coolant level of the compressors after 10 and until 20 min-
utes operation time. If the coolant level is too low, refill coolant as de-
fined in Chapter 8 Check coolant level /coolant refill.
6. Check the standard operation of the functions carried out weekly ac-
cording to Chapter 8 Overview of service intervals
8. Service
8.1 Overview Necessary service work appears in the display as warnings (see Chapter
Service intervals 7.1)
Preparatory activities 8.2
Check coolant level / refill coolant Service activities Chapter After the first After the first Every Every 4000
8.3 100 operating 500 operat- week operating h.
Check for leakage 8.4 hours ing hours but at least
Check the compressor once a year
temperature 8.5
Check the cooler for fouling 8.6 Check coolant level 8.3
Check for condensation 8.7
Replace coolant / Replace Check for leakage 8.4
coolant filter 8.8
Replace coolant separator 8.9 Check compressor
Replace air filter 8.10 temperature 8.5
Check safety valve 8.11 Check of the cooler
Check drive 8.12 for fouling 8.6
Lubrication of electric motor 8.13
Concluding activities 8.14 Check for
condensation 8.7
Coolant replacement 8.8
and replacing coolant
filter
Replacing cooling liquid
separator 8.9
Replacing air filter 8.10
Check safety valve 8.11
8.2 Preparatory activities 1. Press key in order to switch off compressed air generation. Please
wait until the compressor has been switched off after an idling or venti-
lation phase. The symbol M for the main motor is then no longer visi-
ble in the display.
2. Switch the plant main switch off and make certain that it cannot be turned
on by mistake or intentionally (e.g. warning signs prohibiting switching).
4. Make certain that the pressure grid side shut-off valve is closed and
cannot be opened accidentally or intentionally.
If the complete sight glass is not full of coolant, coolant must be added as
follows:
2. Use an appropriate funnel for filling. Coolant can be filled up to the filling
rim of the fitting.
3. Take care that the seal is correctly seated and screw the fitting screw
closed.
8.5 Check the compressor The compressor temperature, which can be viewed in the display, should
temperature be between 75 C and 105 C.
8.7 Check for condensate The absorption capacity of water humidity in the air
development falls with increasing pressure
Preparatory activities 8.2
Concluding activities 8.14 rises with increasing temperature.
Sufficiently high compressor temperature guarantees that the intake air
humidity does not precipitate as condensation. The frequent switching on
and off of the compressor can result in the compressor not achieving the
required operating temperature.
Since water is heavier than coolant, after extended standstill times (e.g. on
a weekend) the condensation collects in the bottom of the coolant contain-
ers. It can be simply drained off by the discharge drain.
Carry out the following activities only when the system has been turned
off at least overnight.
42 1. Open the discharge drain and carefully observe the escaping liquid.
Close the discharge drain again as soon as coolant appears.
2. By opening the discharge drain, allow the coolant to drain into an ap-
propriate vessel and then close the discharge drain again.
3. Use an appropriate funnel for filling. Coolant can be filled up to the filling
rim of the fitting.
4. Take care that the seal is correctly seated and screw the fitting screw 43
closed.
5. Loosen the coolant filter with a strap wrench and remove possible seal
rests from the coolant filter housing.
7. Screw the new coolant filter to the stop and tighten the coolant filter by
hand another half a revolution.
3. Screw the new coolant separator to the stop. Tighten the coolant filter
by hand another half a revolution.
Preparatory activities 8.2 1. Test manually whether the clutch might have some radial play.
Concluding activities 8.14
2. If so, loosen the cam ring of the clutch, push it back, and replace the
clutch element.
3. Mount the cam ring again on the clutch half and test manually whether
the clutch now has no more radial play.
If there are no grease nipples on the electric motor, then it is equipped with
capsulated permanently greased bearings. These motor bearings must be
replaced when they are worn out.
8.14 Concluding activities 1. Open the stopcock slowly on the pressure grid side.
Service work acknowledged 7.1
2. Switch the plant main switch on.
3. Make certain that no tools or loose objects are lying on or in the system.
5. Check all cooling liquids and compressed air piping for leakage
ALLEGRO 30 1,095
ALLEGRO 40 1,165
ALLEGRO 60 1,265
ALLEGRO 80 1,350
ALLEGRO100 1,675 16,500 17,000 1.50 0.84
ALLEGRO115 1,820 16,800 21,000 1.80 1.00
ALLEGRO130 1,820 16,800 21,000 1.80 1.00
Compressor Weight Cooling air Cooling water current at Cooling water Connection
amountsinlet/return temperature pressure pressure cooling
10/40 C 25/40 C 35/45 C min - max water
kg m3/h m3/h m3/h m3/h bar G
ALLEGRO 30
ALLEGRO 40
ALLEGRO 60
ALLEGRO 80
ALLEGRO100 1,800 2,400 2.44 4.87 7.31 2.5 - 10 1
ALLEGRO115 1,950 2,400 2.80 5.60 8.41 2.5 - 10 1 1/2
ALLEGRO130 1,950 2,400 3.05 6.09 9.14 2.5 - 10 1 1/2
ALLEGRO 30 30
ALLEGRO 40 40
ALLEGRO 60 60
ALLEGRO 80 80
ALLEGRO100 100 295 325 148 194 129 142 5
ALLEGRO115 115 369 406 185 693 161 178 4
ALLEGRO130 130 461 508 231 1083 202 222 4
A
AGRE-Kompressoren GmbH
Tel.: +43/7252/52341-0
Fax: +43/7252/52133
Internet: www.agre.at
E-mail: [email protected]
Werkstrae 2
4451 Garsten-St. Ulrich
STERREICH
NL
ALUP-Kompressoren B.V.
Tel.: +31/30/2809000
Fax: +31/30/2895675
Internet: www.alup.nl
E-mail: [email protected]
Biezenwade 8-10
3439 Nieuwegein
NEDERLANDS
HU
ALUP Magyarorszg Kft.
Tel.: +36/36/423444
Fax: +36/36/516340
Internet: www.alup.hu
E-mail: [email protected]
Szlloda u. 5
3300 Eger
MAGYARORSZG
BG
ALUP-Kompressoren Bulgaria OOD.
Tel.: +359/2/528032
Fax: +359/2/528032
E-mail: [email protected]
Tsar Asen Str. 63
1000 Sofia
BULGARIA