DATA SHEET
FIREMIKS® 1000-0,5-1-3-PP-M
WATER DRIVEN VOLUMETRIC PROPORTIONER - WITH PISTON PUMP FOR MOBILE USE
0,5%-1%-3% % selectable dosing system for fire- In-house designed multi-vane water motor giving early
fighting – for mobile use. Extinguishing water drives volumetric function, without using moving elastomer
the volumetric water motor, which in its turn drives the sealings. Correct dosing at system pressures from 2 to
single positive displacement piston pump that doses the 16 bar and from min flow* up to 1000 lpm.
correct amount of concentrate in the extinguishing water.
Available also in different water motor materials
Equipped with an Automatic air relief valve, (no 5 on Flow (Ni-Al-Bronze, AISI 316L) and with an optional Dosing
chart) to speed up priming of dosing pump (alt. Manual air return valve, DRV, that allows for testing the system
relief valve). Flushing of dosing pump is done automati- without mixing the concentrate, a Pressure Relief valve
cally when the concentrate inlet is closed with Selector PRV, also included. More options towards the end of this
valve Dosing/Flushing, (no 4 on Flow chart). Supplied document.
with Strainer on water inlet (no 12 on Flow chart) to ensure
clean water enterring the water motor and Wrench to Easy to select 0,5%, 1% and 3%, even while unit is in action,
rotate the unit by hand at maintenance. with three Selector valves (no 9 on Flow chart) placed on
dosing pump.
Complete with sturdy Stainless-Steel Frame (optional with
lockable wheels), separate suction pipe and pressure Lower pressure losses compared with inductors giving
reducing valve in flushing line. Version with handle and longer throw length. Dosing is also immediate which
bottom bracket also available. allows quickly opening and closing the nozzles (pulsing).
Selectable 0,5%-1%-3%
with just one piston pump.
TECHNICAL DATA
Max water flow rate @rpm: 1000 lpm (264 US gpm) @ 1050 rpm
Min water flow rate @ 8 bar 1-20 cP *: 250 lpm (66 US gpm) @3% (@ 0,5% and 1% the min flow is reached earlier)
Min water flow rate @ 4 bar 1-20 cP *: 200 lpm (53 US gpm) @3% (@ 0,5% and 1% the min flow is reached earlier)
Viscosity range:** 1-1800 cP (60 rpm), 1-3600 cP (30 rpm) with Brookfield viscometer #4
Nominal dosing rate: Selectable 0,5%. 1% and 3%
Dosing tolerance:*** -15%/+15% of nominal value (e.g 3% is 2,55% - 3,45%)
Max inlet operating pressure: 16 bar (232 psi)
Factory tested pressure: 24 bar (350 psi), 20 bar (292 psi) with DRV option incl PRV set at 20 bar
Suction height: 0 meters (0 ft) Gravity feed
Operation temperature: 1°C to 55 °C (34°F to 131°F)
Storage temperature, dry condition: -30°C to 55°C (-22° to 131°F)
Connections water motor G (ISO 228-1) male: G 2 1/2” - DN 65 - Hose couplings in customers choice
Connection pump G (ISO 228-1) female: 1” Cam-lock – DN 25 - Equipped with Suction pipe
MATERIALS
FIREMIKS Aluminium – For fresh water/salt water occasional use FIREMIKS Bronze – For salt water/offshore
Wetted: Brass (head), ceramics, NBR (seals), Wetted: Brass (head), ceramics, NBR (seals),
stainless steel. Other: aluminium (body), hardened Dosing pump: stainless steel. Other: aluminium (body),
Dosing pump:
steel with corrosion protection (crankshaft), hardened steel with corrosion protection
AISI 316 Fasteners (crankshaft), AISI 316 Fasteners Note: water motor
made from Stainless
Flexible hoses: High grade stainless steel + PTFE Flexible hoses: High grade stainless steel + PTFE steel AISI 316L
(housing/rotor) also
Fittings: Stainless steel AISI 316L Fittings: Stainless steel AISI 316L available, remaining
Ball valves: Nickel-plated brass, brass, PTFE SS Ball valves: Stainless Steel AISI 316, PTFE spec same as bronze.
Water flow rate Pressure loss @3% Material water motor Product Name
PRINCIPLE
FLOW CHART
WATER/CONCENTRATE SOLUTION
8.
1. Water motor 1.
2. Dosing pump 12. 40.
4. Selector valve: Dosing/Flushing
5. Air relief valve (Manual or Automatic)
6. Check valve
7. Filter 7.
8. Drain valve
9. Selector valves 0,5% - 1% - 3% 5. 6.
12. Strainer
1.10 Set of vane plates (4 pcs) 2.10 Water seals and plunger kit 3.10 Automatic Air relief valve
1.20 Set of Mechanical Seals (2 pcs) 2.20 In/Out valve kit (3.11 Manual Air relief valve)
Always mention the
1.30 Set of Ball Bearings (2 pcs) 3.20 Check valve
serial number of the
1.40 Set of O-rings (8 pcs) 3.40 Filter flushing line units concerned when
ordering Spare parts.
1.45 Set of Gable inserts (2 pcs)
Reversed water flow direction (right to left) Standard flow direction is from left to right seen from pump
side.
Dosing return valve (DRV) Valve for returning the concentrate to the tank, making it
possible to check the functioning of the unit and to measure
the admixture rate with suitable equipment’s (see below),
without generating water/foam solution. Including pressure
relief valve (PRV) to avoid over-pressure, in case the return line
is blocked for discharge for any reason.
DRV dosing rate measuring equipment Measuring equipment’s consisting of one Mag flow meter for
water flow, one Mag flow meter for pumped concentrate and
a Pressure regulating valve for simulating working pressure in
return line, plus a damped Pressure gauge.
Handheld Tachometer for RPM measurement Used to give an estimate of the water flow through the water
motor and to compare with max flow rpm stated on this Data
sheet, to ensure that unit is not over-speeding.
Note: RPM cannot be used to correctly verify the dosing rate
as the actual unit flow performance is not fully verified with
this method.
High temperature application above 55°C (131°F). Unit adapted with materials for usage up to 80°C (176°F).
Relevant low temperature performance may be affected.
Alternative Water motor connections/Couplings Flanges (ANSI, DIN), Storz couplings, etc.
High-grade stainless-steel ball valves Replacing brass valves (Already standard on Bronze and
SS water motor version and valves with iso5211 interface)
Flap check valve on concentrate inlet To avoid water overflow of the concentrate tank if wrong
handling of the Dosing/Flushing valve occurs.
Certifications / Factory Acceptance tested (FAT) Each unit can be type tested according to applicable parts
of NFPA 11 or EN 13565, Factory Acceptance tested (FAT) or
delivery inspected by DNV-GL or Bureau Veritas.
Check valve on internal flushing line To avoid leakage of concentrate in dry pipe or
non-pressurized water pipe systems if wrong handling of the
Dosing/Flushing valve occurs. (If unit is installed semi-fixed)
Higher spring rate in check valve in internal To avoid leakage of concentrate in dry pipe or
dosing line non-pressurized water pipe systems in combination
with gravity feed. (If unit is installed semi-fixed)
The unit is delivered on a closed EUR pallet, with instruction manual in printed form.
Weight of Aluminium 80 kg
packaged goods:
Bronze and
103 kg
Stainless steel
Note! Weight and dimensions specified here serves only as a guideline, and may vary depending if you choose different
optional equipment. Correct weight and dimension of the goods are given before delivery.
Firemiks AB is SS-EN ISO-9001:2015 certified by Bureau Veritas, cert.no SE008839. Scope of supply:
Development, production and sales of water motor driven dosing systems for firefighting.