Harmonics
Harmonics
Harmonics
UPS harmonics
on input mains
GE Digital Energy
Via Cantonale, 50
6595 Riazzino, Swizerland
[email protected]
g GE Digital Energy
www.gedigitalenergy.com
111
GE Digital Energy
TechNote no. 4
UPS harmonics on input mains
Preface
“Technical note” is a collection of technical documents focused on the applications of GE Digital Energy SA UPS
system.
These documents are realized for salesmen, engineers, technicians and for all the people who are looking in
more details the information given on the product descriptions.
The latest publication of this document is available via web at the following address:
Address: http://www.geindustrial.com/industrialsystems/gede/ -> Tools\GE DigitalEnergy Interact
The author disclaim all responsibility subsequent to incorrect use of information or diagrams reproduced in this
document and can not be held responsible for any error or oversights, or for consequence of using information,
configuration and diagrams contained in this document.
This document shall not be copied or reproduced without written permission of GE Digital Energy SA.
Document release
Release: July 2002
Author: Diego Toledo
Department: System & Application Engineering
6595 Riazzino (Locarno) - Switzerland
Contents
1 Abstract ....................................................................................................................................................... 4
2 Understanding harmonics problems ........................................................................................................ 4
2.1 Harmonics ..................................................................................................................................................... 4
2.2 Harmonics effects ......................................................................................................................................... 4
2.3 Harmonics theoretical concept ...................................................................................................................... 5
2.3.1 Fourier analysis............................................................................................................................................. 5
2.3.2 Periodic alternating rms value ....................................................................................................................... 5
2.3.3 Current harmonic distortion ........................................................................................................................... 5
2.3.4 Voltage harmonic distortion........................................................................................................................... 6
2.3.5 Power factor for loads affected by harmonics ............................................................................................... 7
2.4 Rectifier harmonics ....................................................................................................................................... 8
2.5 Rectifier Harmonics compensation................................................................................................................ 8
3 Standard requirement ................................................................................................................................ 9
4 SitePro configuration characteristics ..................................................................................................... 10
4.1 SitePro configurations ................................................................................................................................. 10
4.2 SitePro harmonics value ............................................................................................................................. 11
4.3 6 pulse rectifier............................................................................................................................................ 12
th
4.4 6 pulse rectifier and 5 harmonic filter......................................................................................................... 13
4.5 12 pulse rectifier without galvanic separation.............................................................................................. 14
4.6 12 pulse rectifier with galvanic separation................................................................................................... 15
4.7 6 pulse rectifier and DCU ............................................................................................................................ 16
4.8 12 pulse rectifier with galvanic separation and DCU ................................................................................... 17
4.9 Rectifier with phase shift displacement ....................................................................................................... 18
4.9.1 12 pulse configuration by two parallel UPS ................................................................................................. 19
4.9.2 18 pulse configuration ................................................................................................................................. 20
4.9.3 24 pulse configuration (for 6 pulse UPS)..................................................................................................... 21
4.9.4 24 pulse configuration (for 12 pulse UPS)................................................................................................... 22
1 Abstract
As known an UPS thyristorized rectifier generates harmonics on the upstream input mains. These can cause
several problems on the other load connected on the same electrical network and also on the input transformer.
After a short presentation on theoretical harmonics concept and on the effects on the installation involved, the
document describes the possible solutions adapted on the SitePro UPSs to their compensation.
2.1 Harmonics
In an electric energy production and distribution system the mains voltage can be considered as an ideal
sinusoidal wave with a constant frequency. However, in reality the public mains undergoes voltage and frequency
variations. In particular, an increasing actual problem is the perturbations caused by the harmonics generated by
non-linear loads connected to the mains.
Harmonics are perturbations with frequencies multiple of the fundamental frequency, which will be
superimposed (added) to the fundamental generating a distortion.
The presence of non-linear loads connected to mains generates harmonics in current, which by circulating in
the line impedance lead to voltage harmonics distortion.
Therefore, harmonics current depend from the load, while the harmonics voltage depends from the source and
the line’s impedance.
where
• F0 : DC component, normally equal to zero in AC sine wave + 5th harmonic
electrical applications
• F 1 : rms value of the fundamental component at a
frequency f
• ω = 2π f : fundamental angular frequency
• ϕ 1 : phase displacement
• F h : rms of the n harmonic, with frequency n*f
• ϕ h : phase displacement between n harmonic
current and voltage
5th harmonic
sine wave
where
• T is the period of the function.
• F (t) is the periodic function under analysis
Using the harmonic analysis, the rms value may be represented as follow
n
F rms = ∑
h =1
F h2
∑ h =1
I h
2
THDI % = 100
I1
that represents the ratio between the whole harmonics content respect to the fundamental sine-wave value.
taking into consideration the harmonic analysis the formula may be expressed as
2
n n
Ih n
I rms = I 12 + ∑h=2
I h2 = I 1 1 + ∑
h=2 I1
= I1 1 + ∑i
h=2
2
h
where
- ih : individual current harmonic, expressed in p.u..
∑h =1
U 2
h
THDU % = 100
U 1
that represents the ratio between the whole harmonics voltage respect to the fundamental sine-wave value.
THDU = Total Harmonics Voltage Distortion; this value is used to indicate the voltage harmonics contents.
The maximum THDU value are regulated by EN-50160-3, EN-61000-2-2 and IEC 61000-2-2 Standard.
taking into consideration the harmonic analysis the formula may be expressed as
2
n n
Uh n
U rms = U 12 + ∑U 2
h = U1 1 + ∑ U
h=2
= U 1 1 + ∑u 2
h
h=2 1 h=2
where
- uh : individual voltage harmonic, expressed in p.u..
power)
sinusoidal form, it is not possible to apply the traditional
concept of a phase displacement in electrical degrees.
) D (harmonics distortion
The Power Factor (PF) is the ratio of power
consumption in kW to kVA. er)
ow
ntp
PF = kW / kVA. par
e
ap
In an electrical system four are the electrical power: tal
A (to
90°
P = active power
ower)
Q= reactive power arent p
S (app
r
we
S = apparent power =
po
2 2
P + Q
e
tiv
90°
ac
D = harmonic power
(re
P (active power)
Q
A = total apparent power = S 2
+ D 2
3 Standard requirement
Harmonics compatibility with public low-voltage supplies is defined by IEC61000-2-2.
th
The input total voltage distortion factor D< 8% with the following maximum level of individual voltage (up to 40
harmonic):
As above showed the Standard requirement is related to the the THDU (Total Voltage Harmonics Distortion); this
is related to the current harmonics by the Input Mains reactancetata are different for any application, therefore in
common use the THDI (Total Current Harmonics Distortion) is request. In fact this value can be easily measured
an less influenced by the Input Mains reactance.
Lk =
12 pulse without galvanic separation 1.9 1.3 7.2 5.7 0.4 0.3 1.4 1.0 -- -- 9.7 %
DCU 3.8 2.6 1.4 1.1 3.6 2.7 1.4 1.0 0.8 0.6 7.0 %
12 pulse with galvanic separation + <5%
-- -- 1.4 1.1 -- -- 1.4 1.0 -- --
DCU (2.5÷4.5)
The above table shows the harmonics value measured on some applications. The value is influenced by input
mains characteristics; therefore in practical applications the values measured on the application could be different
from the values above indicated.
UPS
EBP
INPUT
RECTIFIER INVERTER
LOADS
MAINS
Lk
BATTERY
Characteristics 100
100
• standard UPS configuration
90
Harmonics compensation
80
• THD(I) ca. 27%
current harmonics %
70
Power factor THDI = 27%
• 0.80 approximately 60
Benefit 50
• simple solution 40
UPS
EBP
INPUT
RECTIFIER INVERTER
LOADS
MAINS
Lk
BATTERY
5th
5th HARMONIC
Characteristics 100
th 100
• the filter is realized in order to limit the effect of 5
th
and partially 7 harmonics on rectifier input mains 90
70
power on the electrical network at partial load, due to THDI = 10%
the fact that the utility supplier does not allow it. 60
• 0.90 approximately 1 4 7 10 13 16 19 22 25 28 31
harmonic order (n)
Benefit
• best price/ performance compromise
Limitation
• as capacitive load might have resonance
• possible problems with GenSet. Regulation.
For this reason the filter PCB (Power Contro Board)
is equipped by a GenOn contact; this can be
connected to the GenSet customer interface relay
contact, causing the filter disconnection when the
generator is running.
UPS
EBP
RECTIFIER
INPUT
INVERTER
LOADS
MAINS
BATTERY
Characteristics
• realized by two input rectifier 30° el. shifted. One 100
rectifier is connected to the input mains by a Dy 100
transformer; the other one by an input coil. 90
• available for power range >40 kVA 80
current harmonics %
Harmonics compensation 70
th th th th th st
• suppression of 5 , 7 , 17 , 19 , 29 , 31 ,….. 60
harmonics THDI = 9.7%
50
• THD(I) ca. 9.7%
40
Power factor compensation
30
• none (standard p.f.=0.80)
20
Benefit 7.2 5.7
10 1.9 1.3 1.4 1
• good THDI compensation 0.4 0.3
0
• no influence with GenSet. regulation 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Limitation harmonic order (n)
• no galvanic separation
• no power factor correction
UPS
EBP
RECTIFIER
INPUT
INVERTER
LOADS
MAINS
BATTERY
Characteristics 100
100
• realized by two input rectifier 30 el. degr. shifted.
The two rectifiers are connected to the input mains 90
by a Ddy transformer. 80
current harmonics %
UPS
EBP
INPUT
RECTIFIER INVERTER
LOADS
MAINS
Lk
BATTERY
Characteristics
100
• the DCU is a filter with a special dynamic feature. 100
Depending of the percentage of the load it will
90
automatically disconnect, in part or totally, in order
that with a partial load the input power factor never 80
current harmonics %
UPS
EBP
RECTIFIER
INPUT
INVERTER
LOADS
MAINS
BATTERY
Characteristics. 100
100
• this solution add the feature of 12 pulse and DCU
filter 90
• available for power range >40 kVA 80
current harmonics %
Harmonics order
5 7 11 13 17 19 23 25 29 31 THD(I)
Configuration
6 pulse rectifier 24 7.7 6.3 4.2 2.3 2.2 0.7 0.9 0.3 0.2 27.0 %
quasi 12 pulse rectifier 1.9 1.3 7.2 5.7 0.4 0.3 1.4 1.0 -- -- 9.7 %
INPUT
MAINS
RECTIFIER MAINS
BYPASS MAINS
UPS 1 UPS 2
INVERTER INVERTER
EBP EBP
BATTERY BATTERY
OUTPUT BUSBAR
LOADS
Characteristics 100
100
• the required phase shift is 30 el. degr.; this is
realized by using: 90
- no. 1 Dy11 transformer (30 el. degr.) 80
current harmonics %
RECTIFIER MAINS
BYPASS MAINS
OUTPUT BUSBAR
LOADS
Characteristics
100
• the required phase shift is 20 el. degr.; this is 100
realized by using:
90
- no. 2 zig-zag transformers (20°el. degr.)
current harmonic %
Limitation
• zig-zag transformer is more expensive than normal
Dy or Dd transformer
• in case of extension units, the same input mains harmonics characteristics are available by adding 3 (or
multiple) units
• in case of one UPS shut down, the rectifier bridge became unbalanced and even harmonics will be product
INPUT
MAINS
RECTIFIER MAINS
BYPASS MAINS
OUTPUT BUSBAR
LOADS
Characteristics
100
• the required phase shift is 15 el. degr.; this is 100
realized by using: 90
- no. 2 zig-zag transformers (15 el. degr.)
80
- no. 1 Dy11 transformer (30 el. degr.)
current harmonics %
INPUT
MAINS
RECTIFIER MAINS
BYPASS MAINS
UPS 1 UPS 2
INVERTER INVERTER
EBP EBP
BATTERY BATTERY
OUTPUT BUSBAR
LOADS
Characteristics
• the required phase shift is 15 el. degr.; this is 100
realized by using: 100
- no. 1 Ddy transformer (0° - 30 el. degr.) 90
- no. 1 Dzz transformer (-15 - +15 el. degr.)
80
• available for 2 or multiple UPSs
current harmonics %
70
Harmonics compensation
th th th th th th th st
60
• elimination of 5 , 7 , 11 , 13 , 17 , 19 , 29 , 31 , THDI = 2.3%
50
……harmonics
40
• THD(I) ca.2.3%
30
Power factor compensation
20
• none (standard p.f.=0.80)
10
Benefit 1.4 1
0
• elimination of most harmonics
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Limitation harmonic order (n)
• practically this configuration is difficult to realize;
realize four rectifier system with a perfect 15 el.
degree shift is not easy due to the tolerance in the
transformer wiring connections
• zig-zag transformer is more expensive than normal transformer
• in case of extension units, the same input mains harmonics characteristics are available by adding 2 (or
multiple) units