The SCADA system inside TIA Portal – Efficiency and transparency for your plant
• The WinCC OPC servers provide customer-specific OPC clients with data from the WinCC data warehouse, e.g. process values
or messages.
• The WinCC OPC UA server is installed as Windows service and started automatically.
WinCC / OPC-Server The WinCC OPC UA server supports only the communication profile
"UA-TCP UA-SC UA Binary". The used port number is adjustable.
WinCC Logging (1500/5000 Tags) Archiving of process data (including 500 archive tags) 6AV2107-0GB00-0BB0
Control and monitoring via the web (MS Internet Explorer) See WebNavigator
WinCC WebNavigator slides
Platform and browser-independent operator control and monitoring via the web (HTML5)
WebUX See WebUX slides
Monitoring and analyzing of current and historical process data via the web (MS IE) For
WinCC DataMonitor new systems, the information server is recommended
SIMATIC Information Server 2014 SP3 Web-based analysis and historical process data reports (browser dependent)
upd4
SIMATIC Process Historian 2014 SP3 Plant-wide archive for messages and process data
upd4
Industrial Data Bridge1) Configurable connections to databases and IT systems
SIMATIC ProDiag allows selective and fast machine and plant diagnostics for SIMATIC
SIMATIC ProDiag S7-1500 and SIMATIC HMI: 6AV2107-0UB00-0BB0
1)
Unrestricted © Siemens 2019 WinCC RT Prof: as Consumer/Provider as sep. application
Page 4 2/19/2020
WinCC RT Professional V16
Engineering Options
TIA Portal Multiuser Engineering allows several users to work on the same project simultaneously.
MultiUser 6ES7823-1AA06-0YA5
The TIA Portal Teamcenter Gateway permits storage and management of TIA Portal projects and global
libraries in Teamcenter.
TIA Portal Teamcenter Gateway 6ES7823-1EA06-0YA5
The TIA Portal Cloud Connector enables access to local PC interfaces and connected SIMATIC hardware in
the TIA Portal Engineering even though the engineering itself takes place via remote desktop in a private
TIA Portal Cloud Connector cloud. 6ES7823-1CA00-0YA0
The SIMATIC ODK 1500S allows the development of function libraries with the high-level languages C/C++
SIMATIC ODK 1500S for ODK-capable SIMATIC S7-1500 PLCs. 6AV2108-0AA06-0AA5
The SIMATIC Target 1500S TM for Simulink® is an add-on for Simulink from MathWorks. It allows the
SIMATIC Target 1500S TM for integration of Simulink models directly into the program cycle of an ODK-capable S7-1500 PLC.
6AV2107-0PX06-0AA5
Simulink®
1)
Unrestricted © Siemens 2019 WinCC RT Prof: as Consumer/Provider as sep. application
Page 5 2/19/2020
SIMATIC WinCC Professional
WinCC Premium Add-ons for Process Management
Efficient data management Data consistency over the entire production process
siemens.com/process-management
\\ww004.siemens.net\bu01$\NbgM\PROJ\PROMOTOREN_VM\VM_WARE_WORLD_WITHOUT_UCL\Inst_SW\2019_01_Install_PM_AddOn
Unrestricted © Siemens 2019
Page 6 2/19/2020
Analysis + Reporting with PM-ANALYZE
WinCC Server
External Database
WinCC Standard Client e.g.: SQL, Oracle, Access
Ext
3 …
Software to be installed on the
PC without WinCC 1 2
computer
Office
• Excel 2016
• Build 16.0.6769 (32 or 64 Bit)
• Access to Online Office 365
1) The Windows operating system is only released together with a SIMATIC IPC.
Microsoft Browser:
• Google Chrome*
• Microsoft Edge
• Mozilla Firefox, Mozilla Firefox ESR
Android Browser:
• Google Chrome*
• Firefox
• Edge
• WinCC Professional V16 & WinCC Runtime Professional V16 are released
for the following virtualization platforms
Runtime Advanced/
Virtualization platforms Engineering
Professional
VMware vSphere Hypervisor (ESXi) ab, 6.5 or higher ✓ ✓
VMware Workstation 12.5.5 / 15.0.2 ✓
VMware Player 12.5.5/ 15.0.2 ✓
Microsoft Windows Hyper-V Server 2016 or 2019 ✓ ✓
All of the released operating systems can be used as host operating systems
in a virtualization platform.
The parallel installation of WinCC V16 with WinCC V7 is not permitted for:
• WinCC V16 Professional
• WinCC V16 Runtime Professional
Parallel Use
If the software or license key after the installation is named with the affix “Combo”, the use of the following products/versions is permitted:
• With license "STEP 7 Professional Combo": older versions of STEP 7 (STEP 7 Professional 2006 – STEP 7 Professional V16)
• With license "WinCC V16 Comfort Combo": WinCC flexible 2008 Standard
• With license "WinCC V16 Advanced Combo": WinCC flexible 2008 Advanced
Remote-Software → Link
The following options are available for remote access to WinCC stations:
• NC (Real VNC) Enterprise Edition V5.0.1.
• RDP (Remote Desktop Protocol)
The RealVNC software must be used for remote access to the other computers of a distributed WinCC
system (e.g. WinCC Server).
The Remote Desktop Protocol (RDP) may only be used for remote maintenance of WinCC clients.
Furthermore, no server services (e.g. WebNavigator server, DataMonitor server, OPC server) may be
active on these computers. The reason for this is the handling of the remote desktop sessions by the
Microsoft operating system.
You can also use communication via OPC in the released scenarios.
Start Remote Desktop
Access to WinCC systems with a Remote Desktop Client is only possible via a console session.
Access via the Remote Desktop Protocol may only take place via console transfer with the same user or
initial logon.
6AV2105-3BB06-0AE0
WinCC RT Professional 128
6AV2105-3DD06-0AE0
WinCC RT Professional 512
6AV2105-3FF06-0AE0
WinCC RT Professional 2k
6AV2105-0XA00-0AL0
6AV2105-3HH06-0AE0
WinCC RT Professional 4k
6AV2105-3KK06-0AE0
WinCC RT Professional 8k
6AV2105-3MM06-0AE0
WinCC RT Professional 64k-250k
Server
The number of WinCC Runtime Professional PowerTags for the server is
selectable.
Power Packs extend the number of available tags.
The total price remains constant.
Client
The Client is being deployed for
• WinCC RT Professional Client
Or
128 512 2k 4k 8k 64k 100k 150k 256k
• WinCC RT Professional 128
Online Software
… WinCC Professional V11 to V16 SUS
Delivery
• WinCC Professional V16 512 6AV2103-3DA06-0AE5 6AV2103-3DA06-0AK5
• WinCC Professional V16 4096 6AV2103-3HA06-0AE5 6AV2103-3HA06-0AK5
• WinCC Professional V16 max. 6AV2103-3XA06-0AE5 6AV2103-3XA06-0AK5
6AV21030DA000AY0
• WinCC Prof.V16 512 Powertags SUS DL
• WinCC Prof.V16 4096 Powertags SUS DL 6AV21030HA000AY0
• WinCC Prof.V16 max. Powertags SUS DL 6AV21030XA000AY0
When upgrading from V7 RC/RT, ONLY the RT Professional license will be delivered with immediate effect. The
WinCC Professional Engineering software must be ordered separately if required.
Runtime
• WinCC differentiates between RT licenses (Runtime) and ES licenses (Configuration) as well as the number of tags.
• RT licenses permit the operation of WinCC in runtime for an unlimited period of time.
With this license you can use up to 262 144 external tags and up to 500 archive tags (WinCC Logging) in Runtime.
Engineering is not possible.
• New :... the license for sporadic use:50h of actual use – where the usage can be interrupted as often as required
Activation 50 h
Engineering
A license key is required for:
• WinCC Engineering System, e.g. WinCC Professional
• Options for WinCC Engineering System
Web options
• The license type of the web options (WEBNAVIGATOR, DATAMONITOR and WebUX ) becomes consistently countable.
• 1500 -> 5000 Logging Tag Not applicable due to conversion to additive licenses!
*) Number of tags are additive, i.e. total archive tags = sum of individual licenses
SIMATIC WinCC Runtime Professional … PowerTags V16 Basis Package (RT incl. 500 Archive Variables)
(RT incl. 500 Archive Variables and one WebUX Monitor Client)
128 PowerTags 6AV2105-0BA06-0AA0 6AV2105-0BA06-0AH0 6AV2105-0BA16-0AA0
512 PowerTags 6AV2105-0DA06-0AA0 6AV2105-0DA06-0AH0 6AV2105-0DA16-0AA0
2048 PowerTags 6AV2105-0FA06-0AA0 6AV2105-0FA06-0AH0 6AV2105-0FA16-0AA0
4096 PowerTags 6AV2105-0HA06-0AA0 6AV2105-0HA06-0AH0 6AV2105-0HA16-0AA0
8192 PowerTags 6AV2105-0KA06-0AA0 6AV2105-0KA06-0AH0 6AV2105-0KA16-0AA0
65536 PowerTags AV2105-0MA06-0AA0 6AV2105-0MA06-0AH0 6AV2105-0MA16-0AA0
102400 PowerTags 6AV2105-0PA06-0AA0 6AV2105-0PA06-0AH0 6AV2105-0PA16-0AA0
153600 PowerTags 6AV2105-0RA06-0AA0 6AV2105-0RA06-0AH0 6AV2105-0RA16-0AA0
262144 PowerTags 6AV2105-0TA06-0AA0 6AV2105-0TA06-0AH0 6AV2105-0TA16-0AA0
WinCC Client for RT Prof V15 6AV2107-0DB06-0AA0 6AV2107-0DB06-0AH0 6AV2107-0DB16-0AA0
Please note the price advantage for Online Software Delivery!
Unrestricted © Siemens 2019 Note: WinCC Professional V16 can also be configured with a WinCC Unified Engineering (max license).
Page 22 2/19/2020
SIMATIC WinCC Professional
Order Data Engineering / Trial
• Perfect integration into the TIA Portal => customer good SCADA solution for small to medium solutions
has been using and is familiar with the TIA Portal
for a long time 1 server (optional redundant) maximum 32 clients
• WinCC integrated
• System diagnosis, time stamping at source
• Process diagnosis
• SIMATIC Energy Suite
• Generierung from pictures with SiVArc
• Intelligentes Lastmanagement
1 Basis Paket =
Single-user system SIMATIC WinCC Runtime
Engineering Station+ Professional PowerTags V16
WinCC RT Prof
WinCC RT Prof n
e. g.:
1 • 512 PowerTags
2 • 2048 PowerTags
• 4096 PowerTags
• 8192 PowerTags
• 65 536 PowerTags
• 102 400 PowerTags
• 153 600 PowerTags
• 262 144 PowerTags
SIMATIC Net V16
1 Base Package
Engineering 2
Station WinCC RT Prof n
SIMATIC Net V16
3 1 1 2 WinCC Redundancy
Redundant WinCC
Single-user systems MLFB: 6AV2107-0FB00-0BB0
3 WinCC Engineering
• 512 PowerTags
• 4096 PowerTags
• max PowerTags
Additional information
• The two stations run in parallel (both are connected to the process). In the event of a fault
• in one of the two WinCC stations, the other takes over the archiving of messages,
and the process/user data (recipe). Automatic synchronization of all archives
• after restoration of the normal operating state.
1 Base Package
Engineering 2
Station WinCC RT Prof n
SIMATIC Net V16
3 2 WinCC Redundancy
1 1 Redundant WinCC
single-user systems MLFB: 6AV2107-0FB00-0BB0
3 WinCC Engineering
• 512 PowerTags
• 4096 PowerTags
• max PowerTags
IMPORTANT
Changes can be made in the two WinCC servers via the engineering station.
The requirement for this is that the engineering station must be configured, for example, with:
• WinCC Prof V16 or
• WinCC Prof V16 + STEP 7 Basic V16 (S7-1200) or STEP 7 Prof V16 (S7-1500)
4 WinCC Recipes
MLFB: 6AV2107-0JB00-0BH0
With WinCC Recipes, the user can manage his archives in tabular form,
E. g.: Recipe management – managing the batch parameters, ...
The recipe license is located on the server.
4 WinCC Logging
e. g.: 1500 archive tags
MLFB: 6AV2107-0GB00-0BB0
The number of the archive tags can be increased with WinCC Logging. e. g.: 5000 archive tags
(countable licenses) MLFB: 6AV2107-0GD00-0BB0
• The license for 500 archive tags is included in the basic package.
• The logging license is located on the server.
• With a license for 1500 archive tags and the basic license for 500 archive tags, you then have
2000 archive tags at your disposal
WinCC RT Prof n
2 WinCC 2 WinCC 2 WinCC
SIMATIC Net V16
… 2 WinCC Client
MLFB: 6AV2107-0DB06-0AA0
1 – 32 WinCC Clients
1 3
WinCC RT Prof Server 3 WinCC Server
MLFB: 6AV2107-0EB00-0BB0
Please note
A standard client does not have a WinCC project. It is connected to a specific server
from which it receives data and views.
4 WinCC Engineering
• 512 PowerTags
• 4096 PowerTags
• max PowerTags
To be observed – Differences compared to the preceding scenario:
An engineering license is also required on the server.
TIA is possible (i.e. STEP 7 can be installed on the server.)
4 WinCC Engineering
• 512 PowerTags
• 4096 PowerTags
• max PowerTags
IMPORTANT
Changes can be made on the WinCC server via the engineering station.
The requirement for this is that the engineering station must be configured.
4 WinCC Engineering
WinCC Prof (512 / 4096 / max )
IMPORTANT
Changes can be made on the WinCC server via the engineering station.
The requirement for this is that the engineering station must be configured.
*Installation on a separate server requires a Microsoft SQL Server 2008, 2014,2016 (32/64).
PM-ANALYZE Client
(With/Without WinCC PM-ANALYZE Server
Client) (Without WinCC)
WinCC Server
PM-AGENT
Distributed System
Internet
2 WinCC IS 2014 SP3 upd4
Base Package
MLFB: 6AV6361-2AA01-4AA0
LAN
The base package contains:
1 • 1 x data source access
WinCC single-user
2 system with (connection with a WinCC database)
IS2014 SP3 upd4 • 3 x client access
(three simultaneous client accesses)
Note:
Information Server 2014 SP3 upd4
is compatible with
Additional Information -WinCC RT Prof V13 SP1 or higher
-WinCC 7.0 SP3 or higher
Standard and user-specific reports (via Report Builder of MS SQL Reporting Services)
-WinCC OA 3.14 or higher
Transparent access to WinCC-Archive in Excel and Word (2007, 2010, 2013 and 2016).
-SIMATIC Process Historian 2014 SP2
PH and Information Server can be installed on the same computer. MLFB: 6AV6361-2AA01-4AA0
If IS is connected to PH, no "IS DataSource Access" license is needed.
7 WinCC IS Client Access (1)
MLFB: 6AV6361-2BD00-0AD0
With Internet Explorer or WinCC ViewerRT 1 – 100 Web Clients 1 Base Package
WinCC RT Prof n
Internet/intranet
SIMATIC Net V16
2
WinCC WebNavigator
LAN
1
RT Prof Web z. B.: for three clients
2 Server Single-User MLFB: 6AV6362-1AD00-0BB0
System
Additional Information
WinCC/WebNavigator allows operator control and monitoring from a remote operator station via a local intranet or the Internet.
In each case, a web license for n clients allows a simultaneous connection with the WinCC web server for these n clients
Additional information
In this case, three clients HTML5 can access to the WebUX server without any installation from the client
side.
WebUX is based on a secure connection and needs a certificate.
Note: The security certificate must be renewed after one year.
Because of some limitations in comparison to WebNavigator, please verify that WebUX is suitable for the
required operations.
2 WinCC WebNavigator
As example, a fourth stand-alone client with the Diagnostics License can access to the server anytime!
Unrestricted © Siemens 2019
Page 44 2/19/2020
Web server single-user system – Special case with only one
web connection (WebNavigator Diagnostics)
2 WinCC RT Prof n
Internet SIMATIC Net V16
2 WinCC WebDiagnostics Client
MLFB: 6AV6362-1BA00-0BB0
1
Webserver-
Single-User System
Additional Information
In contrast to the preceding case, the license is installed on a web client.
Thus, no license is necessary on the server(s) for this client.
Several diagnostic clients can be connected to a diagnostics server
3 Thin Client V3 /
Thin Client V3 PRO
6AV6646-1BA15-0AA0 SIMATIC ITC1500 V3
6AV6646-1BA15-0NA0 SIMATIC ITC1500 V3
6AV6646-1BA18-0AA0 SIMATIC ITC1900 V3
With the services of the Windows Terminal Server, the functionalities of the WebNavigator can be used for 6AV6646-1BA18-0NA0 SIMATIC ITC1900 V3
thin clients (limited resources and 6AV6646-1BA22-1AA0 SIMATIC ITC2200 V3
operating system not supported by WinCC) Example: SIMATIC Thin Client 6AV6646-1BA22-1NA0 SIMATIC ITC2200 V3
The ITC V3 supports the protocols RDP, VNC and Sm@rtserver
https://support.industry.siemens.com/cs/ww/en/view/109758315
3 WebPanel
Attention:
Standard ThinClient V3 uses a Mozilla Firefox
Additional Information browser that is not optimal for WebUX
WebPanel (Linux based software ) Please order the new WebPanel based on Thin
Integrated current Chromium Browser v66 (perfect for WebUX) Client V3 with the new Google Chrome
browser
The IWP software supports different hardware architect (Basic Panels / ITC /IPC
ES: 512, 4k, max. RC: 128, 512, 2k, 8k, 64k, 100K, 150K, 256k
PowerTags
RT: 128, 512, 2k, 4k, 8k, 64k, 100K, 150K, 265k RT: 128, 512, 2k, 8k, 64k, 100K, 150K, 265k
Logging *) Archive tags add. 1,500, 5,000 Archive tags add. 1,500, 5,000, 10k, 30k, 80k
500/ 512 archive tags incl.
max. 80,000 (server) max. 80,000 (server)
Recipes: 500 / Recipes: No limit /
Recipes **)
Elements per recipe: 10 000 Elements per recipe: 100,000
WebNavigator
1, 3, 10, 30, 100 clients 1, 3, 10, 30, 100 clients ( in WinCC V7.3 max.150 clients)
WebUX
PLC Connections Up to 128 connections, 128 x S7-1500/ 32 x S7-1200 / 64 x S7-300/400
*) V7.x: Archive tags -max. 128 x S7-1200 / S7-1500 Connections
**) V7.x: UserArchives -max. 64 x S7-300 / 400 Connections
OPC UA OPC UA Server : DA, HA, A&C (Alarm & Condition) UA Server: DA, HA, A&C (Alarm & Condition)
SINUMERIK NO Add-on
2x7D/E
client client
4x7D
547E/G
347E
2x7E
377E
client client
ITP1000
647 / 847C/D/E
127E
? (Worked, but not system tested)
All product designations, product names, etc. may contain trademarks or other rights of Siemens AG, its affiliated
companies or third parties.
Their unauthorized use may infringe the rights of the respective owner.