Simatic Wincc v75 Sp1 Architectures en
Simatic Wincc v75 Sp1 Architectures en
Simatic Wincc v75 Sp1 Architectures en
5 SP1
Architectures
unrestricted © Siemens 2019 siemens.de/wincc-v7
In addition to the standard WinCC packages in European version,
SIMATIC WinCC V7.5 SP1 and SIMATIC WinCC V7.5 SP1 ASIA
will be available at following WinCC V7.5 SP1 Options
• WinCC/Server V7.5 SP1 About the delivery or compatibility test of the following
• WinCC/Redundancy V7.5 SP1 options will be informed separately
• WinCC/Archive V7.5 SP1
• WinCC/UserArchives V7.5 SP1 • SIMATIC TeleControl
• WinCC/WebNavigator V7.5 SP1
• WinCC/DataMonitor V7.5 SP1
• WinCC/Connectivity Pack V7.5 SP1 With the compatibility tool http://www.siemens.com/kompatool
• WinCC/Connectivity Station V7.5 SP1 you could check the compatibility of the products.
• WinCC/WebUX V7.5 SP1
• WinCC/ODK V7.5 SP1
• WinCC/IndustrialDataBridge V7.5 SP1
• WinCC/Audit V7.5 SP1
• WinCC/SESV7.5 SP1
• WinCC/Calendar Scheduler V7.5 SP1
• WinCC/Event Notifier V7.5 SP1
• WinCC/Performance Monitor V7.5 SP1
• WinCC/ProAgent V7.5 SP1
• SIMATIC Energy Manager V7.2
• SIMATIC InformationServer 2014 SP3 upd4
• SIMATIC ProcessHistorian 2014 SP3 upd4
unrestricted © Siemens 2019
Page 2 2019-12-16 DI FA S MP PRO&SW 3
WinCC V7.5 SP1 –
Overview
Standardfeatures
WinCC V7.5 SP1 – basic package Options / PM Add on
or or
PM-ANALYZE PM-ANALYZE
Client/Server- redundancy work with User data Archiv- messages- Centralized Reporting
solution Web-Clients management tags tags data archiving System
siemens.com/process-management
\\ww004.siemens.net\bu01$\NbgM\PROJ\PROMOTOREN_VM\VM_WARE_WORLD_WITHOUT_UCL\Inst_SW\2019_01_Install_PM_AddOn
unrestricted © Siemens 2019
Page 4 2019-12-16 DI FA S MP PRO&SW 3
Analysis + Reporting with PM-ANALYZE
WinCC Server
External database
WinCC Standard-Client Ex
z.B.: SQL, Oracle, Access
Ext
• Notes on installation
• Microsoft .NET Framework
Before installing WinCC, make sure the .NET Framework is enabled
\\ww004.siemens.net\bu01$\NbgM\PROJ\PROMOTOREN_VM\VM_WARE_WORLD_WITHOUT_UCL\Inst_SW\2019_11_Install_WinCC_V75_SP1
\\ww004.siemens.net\bu01$\NbgM\PROJ\PROMOTOREN_VM\VM_WARE_WORLD_WITHOUT_UCL\Inst_SW\2019_11_Install_WinCC_V75_SP1_Optionen
For WinCC WebNavigator and WinCC DataMonitor clients are also released
• Windows 7 SP1 Professional, Enterprise, Ultimate 32-Bit / 64-Bit ( but use if is possible Windows 10 *)
• Windows 8.1 Professional, Enterprise 32-Bit / 64-Bit ( but use if is possible Windows 10 *)
Release Notes
•Support von MS Office 2013 (64bit) & Microsoft Office 2016 (64bit)
•DataMonitor Excel Workbook Wizard nur Unterstützung von Office 32Bit Installationen
• General compatibility
• For integrated operation in the SIMATIC Manager on an engineering station
compatible with
• STEP 7 V5.6 HFx / SP1
• For industrial communication in combination with
• SIMATIC Net V16
Notes on installation Compatible tested virus scanner
• Trend Micro "OfficeScan" Client-Server Suite V12.0
• Symantec Endpoint Protection V14 (Norton Antivirus)
• McAfee VirusScan Enterprise V8.8
• McAfee ePolicy Orchestrator (ePO) V5.3.1
• McAfee Agent V5.5
• McAfee Application Control V8.1 (Whitelisting)
• Kaspersky Anti-Virus 2018
• Windows Defender (in the operating system contained version)
• In order to call the online help of WinCC, it requires Microsoft Internet Explorer
• Internet Explorer from V11.0 32-Bit
• The system requirements vary depending on the type of the selected WinCC installation and
used Operating system.
Support for all current IBM / AT PC platforms. WinCC always relies on current operating
systems and high security requirements
https://support.industry.siemens.com/cs/ww/en/view/109745988
unrestricted © Siemens 2019
Page 11 2019-12-16 DI FA S MP PRO&SW 3
WinCC V7.5 SP1
Upgrading WinCC licenses
• Remote-Software (→ Link)
• Remote Desktop Connection (RDP) in console mode (for WinCC clients release)
(If WinCC Server is running in service mode)
• "RealVNC" Enterprise Edition V5.1.0
Client
Server Single system Client with Projekt
without Projekt
Max. 3 Clients
Windows
without redundancy
• 10
Windows Server
• 2012 R2
• 2016
• 2019
•
Windows Server
• 2012 R2
• 2016
• 2019
• RC-Lizenzen berechtigen zum zeitlich unbegrenzten Einsatz von WinCC in Runtime und bei der Projektierung.
RC licenses can be used locally or remotely. If an RC license is on a different computer, use is only permitted
for the configuration. If you want to use Runtime, the RC license must be available locally or you also need an RT license.
How many external variables and archive tags are allowed for the configuration is shown by the number in the parenthesis,
for example: Eg "WinCC RC (65536)". With this license, you can use up to 64 * 1024 external tags and up to 512 archive tags in
runtime.
If you activate a project in which the number of external variables or archive variables exceeds the number of permitted
variables, the demo mode is activated.
The system then behaves as if the licenses were completely missing
description Order number DVD – EU Online Software Download – EU Order number DVD – ASIA
WinCC WebUX Monitor 1 Client 6AV6362-2AB00-0BB0 6AV6362-2AB00-0AH0 6AV6362-2AB00-0BB0
WinCC WebUX Monitor 3 Clients 6AV6362-2AD00-0BB0 6AV6362-2AD00-0AH0 6AV6362-2AD00-0BB0
WinCC WebUX Monitor 10 Clients 6AV6362-2AF00-0BB0 6AV6362-2AF00-0AH0 6AV6362-2AF00-0BB0
WinCC WebUX Monitor 30 Clients 6AV6362-2AJ00-0BB0 6AV6362-2AJ00-0AH0 6AV6362-2AJ00-0BB0
WinCC WebUX Monitor 100 Clients 6AV6362-2AM00-0BB0 6AV6362-2AM00-0AH0 6AV6362-2AM00-0BB0
Please note the limited number of connections for Windows desktop operating systems
• To analyze the WinCC project, WinCC provides the system variables "@PRF _...".
• This allows you to evaluate the time behavior of the server
• The WinCC Tag Management creates the system tags when creating a WinCC project. As soon as you
create a new connection under a communication driver, additional performance variables are created
for this connection.
Windows Performance Monitor
Quantity Comment
WinCC Server-Server 18 Server Connection to a multi-user system with MULIT-Clients has not been approved
communication • One server can access the data from up to 17 other servers or redundant pairs of servers
• The server accessing the data behaves as a client in respect of the configuration and operation,
except that a standard server cannot be configured
WinCC Server or 18 Servers Access to a maximum of 18 WinCC servers or redundant server pairs from WinCC MULTI-Clients
redundant Server pairs
WinCC MULTI-Clients 50 Clients Maximum of 50 WinCC MULTI-Clients in the WinCC distributed system
(with their own project) • A maximum of 36 servers in the form of 18 redundant server pairs is possible
WinCC WebUX-Clients 100 Clients As a typical scenario, we tested the simultaneous access of 100 WebUX clients to one WebUX server
• 100 clients are not a “hard” system limit – it is technically possible to connect more than 100 clients simultaneously
• The performance depends on the employed hardware and the volume of process data
Configuration of mixed systems (means minimum one UNI- & one MULTI-Client exist in the
system)
• Different quantity structures can be realized according to the type and number of client
types used.
Distributed Server-Client System with web-solution
• Mixed systems are possible, meaning the parallel use of clients with and without Web-Web-Client Web-Client Web-Client
Clients
…
within one client/server system.
• When configuring a mixed system, the following rule* of thumb should
Client as
be observed to achieve the maximum quantity structures: Web-Server
… HTML 5 Client
• Each client type has one value:
• WebNavigator-Client / Thin-Client = 1 Server
Multi-User Project
WebUX-Client / MULIT & UNI-Client = 2
…
UNI-Client with the "Configure remote" function = 4
• The total of all values of all clients should not exceed 120 per
server in the case of WinCC servers without operating function
• In the case of servers with operating function, …
Increased availability and reliability through redundant automation systems with S7-1500R / H controllers
Communication with R / H
Systems by using the
"System IP Address" For R / H (1st delivery level
IM 155-6PN HF
ET 200SP
unrestricted © Siemens 2019
Page 27 2019-12-16 DI FA S MP PRO&SW 3
WinCC V7.5 SP1 Communication
S7-1500 H/R - with the System-IP
The System-IP has to be configured. The HMI-Connection will be configured with the IP-Address.
Additional Information
Quantity:
Process Variables: Up to 262 144 (depending on the license selected)
Archiving variables: Max. 80 000 (based on the WinCC Tag Logging option)
(Reminder: The WinCC V7.5 SP1 base includes 512 archiving variables)
1 1
Redundant
WinCC V7.5 SP1
single-user stations 2 WinCC Redundancy
MLFB: 6AV6371-1CF07-5AX0
Additional Information
Both stations work in parallel (both are connected to the process). In case of a breakdown of one
of the 2 WinCC stations, the other takes over the archiving of messages, process Data and user archive
data (Recipe). Automatic synchronization of all archives after resumption of normal operation.
MLFB: 6AV6371-1CF07-5AX0
3 WinCC Engineering
Please note
WinCC V7.5 SP1 RC license hast to be installed at one station to implement modifications WinCC V7.5 SP1 RC n
(longer than 1h) to the WinCC project.
2 WinCC Client
…
MLFB: 6AV6381-2CA07-5AX0
1 3 WinCC V7.5 SP1 1 – 64 WinCC UNI-Clients
Server
3 WinCC Server
MLFB: 6AV6371-1CA07-5AX0
Please note
A Standard Client has no WinCC project and is connected to a very specific server
from which he retrieves data and views.
MULTI-
Client 2 WinCC Client
…
MLFB: 6AV6381-2CA07-5AX0
1 3 WinCC V7.5 SP1 1 3 WinCC V7.5 SP1 1 – 50 WinCC Multi-Clients
Server Server
3 WinCC Server
MLFB: 6AV6371-1CA07-5AX0
Please note
A MULTI Client with their own WinCC project and is connected to a very specific server
from which he retrieves data and views.
2 2 2
WinCC WinCC WinCC
Remote Engineering Client
Standard-
Clients 2 WinCC Client
…
MLFB: 6AV6381-2CA07-5AX0
1 3
WinCC V7.5 SP1
RT Server
3 WinCC Server
MLFB: 6AV6371-1CA07-5AX0
1 3 1 3 1 – 64 WinCC Clients
Redundancy 3 WinCC Server
WinCC V7.5 SP1
RT servers 4 MLFB: 6AV6371-1CA07-5AX0
4 WinCC Redundancy
MLFB: 6AV6371-1CF07-5AX0
Please note
Due to the redundancy of the servers, the Clients can continue to work in case of a server crash.
The data are synchronized across the servers and the database is entirely replicated
5 WinCC Engineering
when operations return to normal.
WinCC V7.5 SP1 RC n
2
2 SIMATIC ProcessHistorian 2014 SP3 upd4
Access to short and
long-term archiving Long-term archiving
MLFB: 6AV6361-1AA01-4AA0
WinCC 1 The WinCC station has transparent access Operating system, MS SQL Server
WinCC
Single-user station to the PH server archives (display of • Windows Server 2008 R2 SP1
data in the trend and alarm objects) (no strings) 64 Bit Standard/Enterprise
Short-term archiving • Windows Server 2012 R2 /2016
64 Bit Standard/Enterprise
Additional Information
Process Historian is installed only on one OS Server 2008 R2 SP1 or 2012 R2 /2016 .
WinCC is not required (and must not be installed) on a PH server.
The Alarm Logging and Tag Logging archives are transferred to the PH server
in real time with a secure connection. If the communication is interrupted,
the data is buffered on the WinCC computer (Store & Forward Cache)
4 MLFB: 6AV6371-1CF07-5AX0
4 MLFB: 6AV6371-1CF07-5AX0
MLFB: 6AV6361-2AA01-4AH0
Additional Information
IS and DataMonitor can be installed and used on the same computer.
Standard- and user-sepcific reports (with report builder of MS SQL reporting services)
Transparent accesses on WinCC Archive in excel and word (2007, 2010, 2013 and 2016)
MLFB: 6AV6361-2BD00-0AJ0
Additional Information
6 WinCC IS Datasource Access (2)
The client access- and data source access-licenses are required parallel.
In our example there are max. four clients simultaneously and two WinCC-data sources. MLFB: 2 x 6AV6361-2CD00-0AJ0
*
* The installation on a separate server requires a Microsoft SQL Server 2008, 2014, 2016 (32/64)
PM-ANALYZE Client
with/without
PM-ANALYZE Server
WinCC Client) (without WinCC)
WinCC Server
PM-AGENT
Distributed system
Internet
2 WinCC WebNavigator
Additional Information
WinCC/WebNavigator allows remote PC-stations to behave as monitoring/operating stations via a local Intranet or via the Internet.
WinCC/DataMonitor serves to evaluate the real-time data, archives or alarms of the process and to Distribute them via an Intranet or Internet in
Display mode only!
In all cases, a Web license for n Clients allows n clients to log in at the same time to the WinCC Web server
MLFB: 6AV6362-1BA00-0BB0
1 WinCCV7.5 SP1
Web Server
Single-user station
Additional Information
In contrast to the preceding case, a token is assigned to a Web client station
and only that station will be able to connect to the Web server
(always via Intranet or Internet)
MLFB: 6AV6362-1BA00-0BB0
Additional Information
In the case of 4 connections: It is possible to use a 3-connections package that allows for
the connection of 3 standard clients with the addition of a 4th dedicated client with this Diagnostics license
Web Internet
Clients 3 2 WinCC WebNavigator
By using the services of the Windows Server Terminal, it is possible to use the functions 6AV6646-1BA15-0AA0 SIMATIC ITC1500 V3
of the WebNavigator or DataMonitor for thin Clients (low resources and operating system 6AV6646-1BA15-0NA0 SIMATIC ITC1500 V3
not supported by WinCC) e.g.: SIMATIC webpanel (customiced Thin Client) 6AV6646-1BA18-0AA0 SIMATIC ITC1900 V3
6AV6646-1BA18-0NA0 SIMATIC ITC1900 V3
6AV6646-1BA22-1AA0 SIMATIC ITC2200 V3
6AV6646-1BA22-1NA0 SIMATIC ITC2200 V3
2
2 2 WinCC Client
2
MLFB: 6AV6381-2CA07-5AX0
MLFB: 6AV6371-1CA07-5AX0
MLFB: 6AV6371-1CA07-5AX0
WinCC user archive allows a user to manage his archives in the form of tables; 4 WinCC Userarchiv
E.g.: Management of recipes – management of batch parameters, etc.
The user archive license is on the server. MLFB: 6AV6371-1CB07-5AX0
The user archive component is installed for each Client but no user archive license
is required for these customers.
1 WinCC Runtime
WinCC Clients
WinCC V7.5 SP1 RT n
WinCC 2 WinCC 2 WinCC 2
…
2 WinCC Client
1 WinCC V7.5 SP1
MLFB: 6AV6381-2CA07-5AX0
3 Server
4
3 WinCC Server
MLFB: 6AV6371-1CA07-5AX0
With WinCC archive, the number of archive tags can be increased. 4 WinCC Archive
The base license is valid for 512 archive tags.
The archive license is located on the server. Z.B.: 1500 archive variables
Licenses are countable (which become 512 archive variables of the base package not added to the MLFB: 6AV6371-1DQ17-5AX0
5000 archive tag package) Z.B.: 5000 archive variables
You can increase the number of archive tags that need to be licensed by combining several packages MLFB: 6AV6371-1DQ17-5BX0
ES: 512, 4k, max. RC: 128, 512, 2k, 8k, 64k, 100K, 150K, 256k
PowerTags
RT: 128, 512, 2k, 4k, 8k, 64k1,, 100K, 150K, 265k RT: 128, 512, 2k, 8k, 64k, 100K, 150K, 265k
OPC UA OPC UA Server : DA, HAD, A&C (Alarm & Condition) UA Server: DA, HAD, A&C (Alarm & Condition)
SINUMERIK NO Add-on
Packages
Available for all SIMATIC IPCs that meet the SCADA requirements
2 x order numbers:
• 1 x for the IPC and
• 1 x for the software
Price advantage with simultaneous ordering of the - SIMATIC IPC and
+SIMATIC WinCC Software the WinCC software
2x7D/E
client client
4x7D
6x7 / 8x7 C
547E/G
347E
2x7E
client client
377E
client client
ITP1000
647 / 847E
127E