V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

10 functions Control elements

10 time ranges Fine adjustment

Setting of time range


Supply voltage 12-240 V AC/DC
Function selector
1 change-over contact
Status indication
Width 22.5mm LED U/t: Supply voltage

LED R: Relay status

TECHNICAL DATA
SUPPLY CIRCUIT

Terminals A1-A2

Supply voltage 12 … 240V AC/DC

Supply voltage tolerance -10 / +10 %

Rated frequency 50 / 60Hz or DC

Rated frequency tolerance 48 … 63Hz

Rated consumption 230 V AC typ. 0,4 W / 0,75 VA

24 V DC typ. 0,25 W / 0,25 VA

Standby consumption 230 V AC typ. 0,16 W / 0,3 VA

24 V DC typ. 0,03 W / 0,09 VA

Duty-cycle 100%

Backup power time < 30 ms

Recovery time > 100 ms

Drop-out voltage ≥7V

CONTROL INPUT

Terminals A1-B1

Function start of function

Type voltage controlled

Control voltage see supply voltage

Minimum control pulse length AC min. 50 ms

DC min. 25 ms

Loadable yes

http://tele-online.com Page 1 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

TIMING CIRCUIT

Time ranges 10 0,05 … 1 s


0,15 … 3 s
0,5 … 10 s
1,5 … 30 s
3 … 60 s
9 … 180 s
0,5 … 10 min
3 … 60 min
0,5 … 10 h
5 ... 100 h

RANGE OF FUNCTIONS

Functions 10 E, R, Wu, Es, Ws, Wa, Ec, Bp, Bi, Wt

STATUS INDICATION

Supply voltage / time lapse LED U/t (green) on supply voltage applied

LED U/t (green)


flashes
indication of lapse of time

Relay status LED R (yellow) on output relay energized

OUTPUT CIRCUIT

Terminals 15-16-18

Kind of output Relay

Number of contacts change-over


1
contact

Contact material AgNi

Rated voltage
250V
(IEC 60947-5-1)

Maximum switching voltage 400V AC

Minimum switching voltage / switching current 12 V / 10 mA

Rated current AC-1 8 A / 250 V


(IEC 60947-5-1)
AC-15 1,5 A / 240 V (B300)

DC-12 8 A / 24 V

DC-13 0,1 A / 250 V

Endurance mechanical 30 x 106 switching cycles

electrical (AC-1) 100 x 103 switching cycles

Rated frequency of operation with load 6/min

without load 1200/min

http://tele-online.com Page 2 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

ACCURACY

Base accuracy < 1 % (of full scale)

Setting accuracy < 5 % (of full scale)

Repeat accuracy < 0,5 % or ±5 ms

Temperature influence < 0,01 % / °C

Voltage influence -

Frequency influence -

ENVIRONMENTAL CONDITIONS

Ambient temperature operation -25 … +60°C

storage -40 … +70°C

Relative humidity 5 … 95 %

Vibration EN 61812-1 10 … 60 Hz: 0,15 mm; 60 … 150 Hz: 20 m/s2

EN 60947-1 2 … 13,2 Hz: 1 mm; 13,2 … 100 Hz: 7 m/s2

Shock EN 60947-1 ±150 m/s2 11 ms

GENERAL DATA

Dimensions W×H×D 22,5 × 67 × 76 mm

Mounting DIN rail (EN60715)

Mounting position any

Housing material PA 66, self-extinguishing plastic, class V-0

Degree of protection housing IP40

terminals IP20

Electrical connection V2ZM10 Screw terminal

Wire size flexible with wire


0,5 … 2,5 mm² (20 AWG … 13 AWG)
end ferrule

flexible without
wire end ferrule
0,5 … 4 mm² (20 AWG … 12 AWG)

rigid 0,5 … 4 mm² (20 AWG … 12 AWG)

Stripping length 8 mm

Tightening torque max. 1Nm

Electrical connection V2ZM10P Push-in terminal

Wire size flexible with wire


0,25 … 1,5 mm² (24 AWG … 16 AWG)
end ferrule

flexible with
plastic ferrule
0,25 … 0,75 mm² (24 AWG … 19 AWG)

flexible without
wire end ferrule
0,2 … 1,5 mm² (24 AWG … 16 AWG)

rigid 0,2 … 1,5 mm² (24 AWG … 16 AWG)

Stripping length 8 mm

http://tele-online.com Page 3 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

GENERAL DATA

Prospective current value 1000 AEff

Fuse rating 8A fast acting

MTTF -

Weight 85 g

ISOLATION DATA

Pollution degree
2
(IEC 61812-1)

Overvoltage category
III
(IEC 61812-1)

Rated insulation voltage supply circuit /


300 V
(IEC 61812-1) output cicuit

Rated impulse withstanding voltage supply circuit /


6 kV
(IEC 61812-1) output cicuit

Insulation test voltage supply circuit /


3200 V
(IEC 61812-1) output cicuit

Degree of protection supply circuit /


protective separation
output cicuit

STANDARDS

Product standard IEC 61812-1

Interference immunity IEC 61812-1 class A

Interference emission IEC 61812-1 class A

Approvals

http://tele-online.com Page 4 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

FUNCTIONS

ON delay (E)
When the supply voltage U is applied, the set interval t begins
(green LED U/t flashes). After the interval t has expired (green U
LED U/t illuminated) the output relay R switches into on-po-
sition (yellow LED illuminated). This status remains until the LED U/t
supply voltage is interrupted. If the supply voltage is inter-
rupted before the expiry of the interval t, the interval already
R t <t
expired is erased and is restarted when the supply voltage is
next applied.

OFF delay with control input (R)


The supply voltage U must be constantly applied to the device U
(green LED U/t illuminated). When the control contact S is
closed, the output relay R switches into on-position (yellow LED
illuminated). If the control contact is opened, the set interval t LED U/t
begins (green LED U/t flashes). After the interval t has expired
(green LED U/t illuminated) the output relay switches into S <t
off-position (yellow LED not illuminated). If the control contact
is closed again before the interval t has expired, the interval R t <t
already expired is erased and is restarted.

Single shot leading edge with control input (Ws)


The supply voltage U must be constantly applied to the device
(green LED U/t illuminated). When the control contact S is U
closed, the output relay R switches into on-position (green LED
U/t illuminated) and the set interval t begins (green LED U/t LED U/t
flashes). After the interval t has expired (green LED U/t illumi-
nated) the output relay switches into off-position (yellow LED
not illuminated). During the interval, the control contact can
S
be operated any number of times. A further cycle can only be
started when the cycle run has been completed. R t t

Single shot leading edge voltage controlled (Wu)


When the supply voltage U is applied, the output relay R
switches into on-position (yellow LED illuminated) and the set
interval t begins (green LED U/t flashes). After the interval t has U
expired (green LED U/t illuminated) the output relay switches
into off-position (yellow LED not illuminated). This status re- LED U/t
mains until the supply voltage is interrupted. If the supply vol-
tage is interruted before the interval t has expired, the output
relay switches into off-position. The interval already is erased
R t <t
and is restarted when the supply voltage is next applied.

Single shot trailling edge with control input (Wa)


The supply voltage U must be constantly applied to the device
(green LED U/t illuminated). Closing the control contact S has U
no influence on the condition of the output R. When the cont-
rol contact is opened, the output relay switches into on-positi- LED U/t
on (yellow LED illuminated) and the set interval t begins (green
LED U/t flashes). After the interval t has expired (green LED U/t S
illuminated), the ouput relay switches into off-position (yellow
LED not illuminated). During the interval, the control contact
can be operated any number of times. A further cycle can only R t t
be started when the cycle run has been completed.

http://tele-online.com Page 5 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

FUNCTIONS
ON delay with control input (Es)
The supply voltage U must be constantly applied to the device U
(green LED U/t illuminated). When the control contact S is clo-
sed, the set interval t begins (green LED U/t flashes). After the LED U/t
interval t has expired (green LED U/t illuminated) the output
relay R switches into on-position (yellow LED illuminated). This
status remains until the control contact is opened again. If the
S
control contact is opened before the interval t has expired ,
the interval already expired is erased and is restarted with the R t1 <t
next cycle.

Flasher pause first (Bp)


When the supply voltage U is applied, the set interval t begins U
(green LED U/t flashes). After the interval t has expired, the
output relay R switches into on-position (yellow LED illumina-
ted) and the set interval t begins again. After the interval t has
LED U/t
expired, the output relay switches into off-position (yellow LED
not illuminated). The output relay is triggered at a ratio of 1:1 R t t t t
until the supply voltage is interrupted.

Flasher pulse first (Bi)


When the supply voltage U is applied, the output relay R U
switches into on-position (yellow LED illuminated) and the set
interval t begins (green LED U/t flashes). After the interval t has
expired, the output relay R switches into off-position (yellow LED U/t
LED not illuminated) and the set interval t begins again (green
LED U/t flashes). The output relay is triggered at a ratio of 1:1 R t t t t
until the supply voltage is interrupted.

Pulse sequence monitoring (Wt)


When the supply voltage U is applied (green LED U/t illumi-
nated), the output relay R switches into on-position (yellow
U
LED illuminated). When the control contact S is closed, the set
interval t begins (green LED U/t flashes). So that the output LED U/t
relay R remains in on-position, the control contact S must be
opened and closed again within the set interval t. If this does S
not happen, the output relay R switches into off-position and
all further pulses at the control contact are ignored. To restart
the function the supply voltage must be interrupted and R ∞t <t <t t
re-applied.

Additive ON Delay (Ec)


When the supply voltage U is applied, the release for the inter-
val starts (green LED U/t illuminated). When the control contact
S is closed, the set interval t begins (green LED U/t flashes). If
the control contact S is opened during the set interval t, the U
interval stops (green LED U/t illuminated), and the already
expired interval is stored. During the lapse of time the control LED U/t
contact can be opened or closed as often as required. If the
sum of the periods, in which the control contact S is closed
reaches the set interval t the output relay R switches into
S t1 t2 t=t1+t2
on-position (yellow LED R illuminated). The interval is stopped
(green LED U/t illuminated) and a further activation of the R
control contact S remains without effect. By interrupting the
supply voltage, the device will be reset. A possibly expired time
t is deleted.

http://tele-online.com Page 6 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

CONNECTIONS

without control input with control input

UN (+) UN (+)
(-) (-)

A1 A2 B1 A1 A2 B1

16 18 15 16 18 15

16 18 15 16 18 15

http://tele-online.com Page 7 of 8
V2ZM10 12-240V AC/DC

VEO
Art.Nr.: 125100

V2ZM10P 12-240V AC/DC


TIME RELAY / MULTIFUNCTION TIME RELAY Art.Nr.: 125600

DIMENSIONS

67 mm
76 mm 22,5 mm

CONTACT

TELE Haase Steuergeräte Ges.m.b.H. CALL US +43 / 1 / 614 74 - 0


Vorarlberger Allee 38
1230 Vienna ONLINE SUPPORT [email protected]
Austria

http://tele-online.com Page 8 of 8