Iron Removal-Softener & Drinking Water Treatment Plant - Drawing

You are on page 1of 1

WATER TREATMENT PLANT Pressure Gauge Expansion Joint

LEGEND :
(1) Iron Removal Plant : 15m3/hr.
(2) Softener Plant : 2m3/hr. SS Ball Valve Non-Return Valve
(3) Drinking Water : 0.5m3/hr. Butterfly Valve Water Flow Meter
H2O2 Salt Dosing Tank
Capacity:500Ltr Capacity:300Ltr
Suction Foot Valve Φ Pipe line as per design

Dosing Pump Dosing Pump

1m3/hr. to DM Plant
IRON REMOVAL FILTER MULTIGRADE FILTER SOFTENER FILTER ACTIVATED CARBON FILTER
Top Manhole Top Manhole Top Manhole Top Manhole

Panel board

Butterfly Valve

Non-Retunr Valve

Expansion Joint

Raw Water Feed Pump


(02- Set)

Drain Line Drain Line Drain Line


Drain Line

Foot Valve

Pre Treatment Water Tank Iron Free Water Tank Soft Water Tank Drinking Water Tank

ITEM Dimension(mm) Dish Body ITEM Dimension(mm) Dish Body Design Data: Pipe Line
I.R.F Ø 1200xH-2000mm 6mm 5mm S.F Ø 776xH-1800mm 5mm 4mm Operation Hour : 24hr. Iron Removal : DN-50mm
6mm 5mm 5mm 4mm Capacity : 15/3/.5m3/hr. Softener : DN-40mm
M.G.F Ø 1200xH-2000mm A.C.F Ø 500xH-1800mm
Hardness : 120ppm Drinking : DN-25mm
M.O.C M.S Capacity: 15m3/hr. M.O.C M.S Q: SF-3m3/hr., ACF-0.5m3/hr. Iron : 5.5ppm Iron/Hardness : 0.05/0-5ppm
CLIENT NAME & ADDRESS CONSULTANT NAME:
Water Treatment Plant for Akij Bicycle & Engineering Ltd. Engr. M.M Sanjidul Islam Engr. Md. Suruz Zaman - -
MIEB-M/31346 (BSc in Civil)
Akij Bicycle & Engineering Ltd.
Tangail, Bangladesh.
Engr. Naimatun Jannat 03/09/2023
Alom Nagor, Shugondha Housing, Hemayetpur, Hydraulic Process Flow Drawing for WTP (BSc in Civil) 01