Experimental Investigation On Thermal Performance of Copper With Aluminium

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

I S S N 2321-807X

Volume 12 Number12
Journal of Advances in chemistry

Experimental investigation on Thermal Performance of Copper with


Aluminium Based Finned Heat sinks for Electronics Cooling System
1
Arulmurugan L, 2Dr.Ilangkumaran M
1
Assistant Professor, Department of Mechatronics Engineering,K S Rangasamy College of Technology,
Tiruchengode, India.
E-mail ID: [email protected]
2
Professor and Head, Department of Mechatronics Engineering, K S Rangasamy College of Technology,
Tiruchengode, India.
E-mail ID: [email protected]
ABSTRACT
An Experimental investigation on thermal performance of copper with aluminium based finned heat sinks for
electronics cooling system was studied. The heat sinks have different material proportions containing major constituent of
aluminium and minor constituent of copper. Considered with straight finned heat sink for the experiments for its easiness
in fabrication and efficient heat transfer properties. The observational results for aluminium with copper alloy are compared
with pure aluminium heat sink. Heat sink geometry, fin pitch and its height were taken from the commercially available
heat sinks. In this research work best heat sink geometry is chosen and cooked up with different volume of copper added
with aluminium. Selected four different spots of heat sinks and the temperature raising characteristics were measured for
natural convection. Also the temperature is raised to a fixed temperature and the temperature lowering characteristics
were measured in forced convection as the air circulation takes more heat to keep the heat sink temperature within the
desired level.

Indexing terms/Keywords
Heat Sink, Convection, Aluminium, Copper, Electronics cooling system.

1. INTRODUCTION
The heat sinks are designed to solve the heat problems faced by high performance electronics systems. This is
a traditional method to dissipate unwanted heat generated in the system. A computers CPU performs millions of
computations every second. As the process continues to work, it starts to generate heat. If the heat is not kept under
desired level, the processor could overheat and creates a chance for CPU damage. Different methods for cooling the
electronics chips were proposed, use of thermo-electric coolers [1], two phase flow heat transfer with R-134 [2], the use of
R-134 provides a very effective heat transfer when compared to that of the conventional heat transfer rates, R-134 is the
most commonly used refrigerant having good heat transfer characters. but still it is a costly method of cooling and cannot
be applied to a common and MEMS electronics devices, Flow boiling heat transfer of water in micro channel heat sink[3],
two phase thermal transport in micro gap channels[4], the system used a cooling medium that changes its phase when the
temperature difference occurs as in the refrigeration process, influence of surface roughness on natural convection above
a horizontal plate, that analyzed an aluminium plain plate for the convective heat transfer, that prove that the more rough
surface increases the area of contact of the plate with the air, the optimum rough surface would produce effective cooling,
also it affects the heat flux flow directions that affects the heat transfer to air[5-9]. The conventional air-cooled cooling
system uses forced convection system using a simple geometry having optimum efficiency, heat transfer characteristics
[10]. Among other heat sinks parallel plate finned heat sinks are widely used for its own advantages in fabrication and cost
optimization. Also it is having the advantage of independent of direction of fluid flow. Recently, Kim et al (11) exposed that
the effective heat sink type among plate-fin furthermore pin-fin heat sinks might be firm depending on the propelling power
and heat sink length. It is found that at low Reynolds numbers friction factors are reformed for intermediary size tubes.
This has a dynamic allegation for micro scale pin fin heat sinks.
In addition to the above research activities, there has been a new attempt to combine the advantages of plate-fin
and pin-fin heat sinks. The thermal resistance have a considerable effect on the heat sink. The total thermal resistance
(Rtot) can be expressed as the sum of three components that account for conduction through the silicon substrate
excluding the fin region (Rcond), convection to the flow (Rconv), and thermal resistance due to an increase in the flow
temperature as it flows through the fins and absorbs heat (Rheat). Since the substrate thickness is usually small (<500 µm)
-1o
and the thermal conductivity of silicon is large (̴150W m C), Rcond is usually very small and for most practical purposes
can be neglected. Using a simple energy balance Rheat can be expressed as:
Rheat= 1/mcp
Similarly, Rconv can be expressed as
Rconv= 1/hAt
Where At is the total effective heat transfer area, which can be expressed as follows:
At = Ab +ηAfin
Where Ab is the base area, Afin the surface area of the fins, and η the fin efficiency.

4582 | P a g e
October 2016 www.cirworld.com
I S S N 2321-807X
Volume 12 Number12
Journal of Advances in chemistry
2. COMPUTATIONAL FLUID DYNAMIC ANALYSIS
Heat sink used in the CFD analysis part is modeled with SOLID WORKS 2010 modeling software and Used Star
CCM+ for CFD analysis to perform. A real time heat sink used in modeled with the same proportion of the heat sink used
in the experimental study. The high temperature input is taken as 100W, which will be the maximum heat energy
dissipated by a high speed microprocessor. The mesh created by Star CCM+ CFD software is shown in the figure 1. An
analysis done for free and natural convection processes.

Fig 1 : Mesh created in Star CCM+

The geometry created for analysis is same as that of dimensions of the heat sink used in the real time
experimental heat sink used. The geometrical dimensions of length 80mm, breath 60mm, height 30mm and the fin
thickness of 4mm is used. The geometry is constrained with an external wall and letting the fluid at the inlet wall to outlet
wall. The result of CFD software between natural and free convection shows considerable difference. The figure shows
the constrains created for the analysis in Star CCM+, used with standard material properties of aluminium and copper as
the input parameter and the fluid flow rate is set as 35 CFM which is the maximum fluid flow rate that can be created with
a real time microprocessor heat sink fan.

Fig 2 : Heat Transfer in Natural and Forced Convection

Since the cooler fan supplies with a lower temperature air into the fins of the heat sink, it removes the heat supplied
into the heat sink at the lower temperature. The figure 2 shows that under natural convection this heat sink removes
o
80Watts of heat energy at a higher temperature of 82 C and the same 80 Watts of heat energy is removed at much lower
o
temperatures of 54 C. This proves that the heat transfer achieved at with natural convections at a higher temperature level
can be achieved even at a lower temperature by just allowing the air to pass through the surface area where the heat is
being transferred to the air. Also the heat transfer characteristics differs in a significant way that the convection rate will be
even throughout the area of the heat sink, but in case of forced convection the heat transfer rate will be high at the air
entrance point and reduces at the exit point of air.

4583 | P a g e
October 2016 www.cirworld.com
I S S N 2321-807X
Volume 12 Number12
Journal of Advances in chemistry
3. EXPERIMENTAL SETUP AND PROCEDURE
This experimental setup is a smaller domain in order to simplify the experiments. The experimental setup is arranged with
an electrical heater that replaces the position of processor in a real-time setup. The size of heater is 65x85 mm which is 5
mm larger than the size of heat sink, it is marked with a tiny scratch over it to ensure the right location of the heat sink to
be placed on it. It is supplied with 220V AC power supply, so that it can generate a heat of 100 Watts. The heater is fixed
o
with heat sink using a anabond compound with thermal conductivity of 0.437 W/m C and wake field thermal compound
o
with thermal conductivity of 0.735 W/m C is used as a mediator between heat sink and the heater, the application of wake
field thermal compound ensure proper contact between heat sink and the heater surface. The system is placed with a
commercially available blower fan to create a forced convection.

Fig 3 : Block Diagram of Experimental setup


The area occupied by the resistance coil is lower than that of the area occupied by the heat sink over the heater, so
that the heating area completely covers the heat sink placed over it, so that the total heat energy output from heat heater
will be transferred to the heat sink. Eight K-type thermocouple is paced at different places of the heat sink and temperature
raise at four different places are considered and others are used as reference, since those points are symmetric about the
axis of the heat sink geometry. The first thermocouple is placed at the top corner left side to the axis of the geometry, the
second thermocouple is placed at bottom lower corner right side to the axis of the geometry and the third thermocouple is
placed at the exact center of the heat sink and the fourth point for locating the thermocouple is fixed at 20mm behind T3
and 10mm from the bottom of the heat sink. Since the setup is placed at a open space, the atmospheric temperature is the
temperature of air blown to the heat sink for forced convection experiments. In these experiments other external heat
sources or not considered in order to simplify the experiments. The flow rate of the air for forced convection is maintained
at a constant level by assuring the suction and delivery fan speed. The volume flow rate of the system is maintained at 35
o
CFM. The saturation temperature was recorded when the system maintains the temperature difference with in ± 1 C for a
duration of 10 minutes. The temperatures are recorded and used to calculate the heat transfer rate of the heat sink

4. DATA ACQUISITION SYSTEM


The data acquisition system is responsible for the accuracy and reliability of the experimental readings. The
o o
parameter to be measured is temperature will not cross beyond 200 C and will not enter below 20 C level. For the data
acquisition the experimental setup is interface with USB-6221 DAQ card. USB-6221 is a data acquisition card form
national instruments having 15 analog and digital input ports and 3 analog and digital output ports. The K-type
thermocouple is used in experimental setup; the thermocouples are directly interfaced with the DAQ card at the analog
input ports ai5, ai6, ai7 and ai8. For data logging labview 2011 is used to interface the DAQ card with the computer
system. Labview 2011 has pre-loaded calibration settings for K-type thermocouple, with a temperature compensation of
o
25 C. Hence no external calibration is required for K-Type thermocouple when interfaced with USB-6221 and
Labview2011.

Fig 4 : LabVIEW Panel Block Diagram

4584 | P a g e
October 2016 www.cirworld.com
I S S N 2321-807X
Volume 12 Number12
Journal of Advances in chemistry
The figure 4 shows the back panel block diagram of the labview system. The back panel uses with the tools of DAQ Assist
that fetches the data sent by the DAQ card and brings in to the computer for data manipulation, since the DAQ brings in
data at a frequency 100Hz, the arithmetic mean reduce it into 10Hz by providing the arithmetic mean of every 10 values at
the output. The signal splitter is used to split the data from four input channels. A graph tool along with a thermocouple
and numerical display tool is placed to display the temperature raise characteristics and a temperature at a particular time.
A signal merge tool is used to merge the signal so that the data from DAQ can be logged into a single Excel File with the
help of Write to measurement file tool in the labview system. Since the data Acquisition takes place in a continues loop,
the entire circuitry is placed inside a while loop. Placing the Write to measurement file tool outside the while loop will
create a new file for every iterations for the readings to log. The function of thermocouple tool and the integer display tool
is for the easy understanding and verification of the system, whether the experimental setup is performing with desired
values.

5. RESULTS AND DISCUSSIONS


The graph shows the temperature raise characteristics of the heat sink with various copper mixture ratios. Since the
airflow rate is very low the heat flow around the heat sink will be low, also the air circulating around the heat sink area.
Also because of the lower temperature raise it takes about 10 minutes to 15 minutes to reach the saturation level after
which it reaches the saturation level and starts maintaining at that level with one or two degree fluctuations. If the system
maintains with this least fluctuation for about 10 minutes then it is considered that the system reaches its saturation level.
5.1 Natural convection

Fig 5 : Temperature raise in Natural convection at point 1 and 2

Fig 6 : Temperature raise in Natural convection at point 3 and 4

As the temperature variation differs between the points, the least temperature difference is considered the actual
difference, however the least difference is not zero at any point and it is showing with the right sign. At all the four points
o
the saturation level between 0% Copper and 5% fine copper dust mixed heat sink has at least 25 C at all the point. Figure
5 show the temperature raise characteristics at point one and two, and Figure 6 show the temperature raise characteristics
at point 3 and 4. The difference in temperature raise characteristics between the saturation level of coarse and fine copper
dust particles is not creating a considerable difference mostly in both 5% and 15% copper added heat sinks. The
o
difference in temperature raise between a 5% and 15% is at least 15 C at all the points of heat sink. Since the heat
removal rate is very low compared to forced convection system of cooling, the natural convection is only for assessing the
performance of the heat sink as it shows with huge saturation temperature difference with a small difference the thermal
properties of the heat sink. Form the result natural convection heat transfer it is taken as the heat transfer rate increases
with the addition of copper dust particles up to optimal level.

4585 | P a g e
October 2016 www.cirworld.com
I S S N 2321-807X
Volume 12 Number12
Journal of Advances in chemistry
5.2 Forced Convection

Fig 7: Temperature raise in Forced convection at point 1 and 2

Fig 8: Temperature raise in Forced convection at point 3 and 4


Figure 7 and 8 shows the temperature raise characteristics at four different points under forced convection heat transfer.
o
In the forced convection, the heat sink is allowed to rise to a particular temperature of 100 C under natural convection and
o
the system is allowed to start the forced convection from 100 C. The data logging takes place 10 seconds after the
process starts. This 10 sec is allowed to stabilize the thermocouple as the sudden start of airflow may create a noise
signal. The response of airflow within the fins of heat sink is highly immediate. Since the airflow takes place at a speed of
35 CFM into the heat sink. The comparison of saturation temperature between the forced convection and natural
convection proves that the temperature characters of heat sink remains same in both the mode of heat transfer. When the
o
temperature difference in the natural convection reduces below 5 C, it produces only a negligible difference in the heat
o
transfer for forced convection system. The maximum temperature difference achieved is only of 10 C at all the points.
This maximum difference is achieved between 0% copper and 15% fine copper Heat sinks. But under forced convection,
the saturation temperature between the Fine and Coarse copper dust particles of both 5% and 15% copper Heat sinks
o
shows only a negligible difference of 2 C.

6. CONCLUSION
The thermal convection characteristics of the heat sinks with Fine and Coarse Copper particles added with aluminium,
about 5% and then added with 15% of copper to pure 6063 Aluminium and the result of heat transfer characteristics is
compared with pure aluminium heat sink. The geometrical characters such as fin thickness, height, and length are copied
from the commercially available conventional heat sink. Simulation is carried with a commercially available CFD software
called Star CCM+. The experimental analysis is carried out to validate the results from simulation. The experiments were
made under natural and forced convection system of heat transfer. Improvements are noted in Heat transfer characters in
o o
the CFD analysis. With the experimental result the saturation temperature lowers by 25 C in natural convection, this 25 C
difference is achieved between 0% copper heat sink and 15% Fine copper dust mixed heat sink. Between Coarse and fine
copper mixed heat sinks the saturation level obtained is 3 to 4 degree in natural convection where it reduces to a
negligible level of temperature difference in forced convection. With the addition of 5% copper the saturation temperature
reduces considerably by creating an effective heat transfer. But the saturation temperature difference is lower than that of
0% and 5% copper heat sink. So the further increase in the copper may have no effect in the heat transfer characteristics.
o
The experiment also proves that the saturation temperature difference of 10 C in natural convection process will create a
considerable effect in the forced convection process. This study will benefit the heat sink designers in the fabrication of
heat sink for electronics cooling.

4586 | P a g e
October 2016 www.cirworld.com
I S S N 2321-807X
Volume 12 Number12
Journal of Advances in chemistry
Acknowledgement
This research is financially supported by FIST (Fund for improvement of science and technology infrastructure)
programme by the Department of Science and Technology (DST) New Delhi. DST-FIST (SR/FST/College-235/2014 dated
21-11-2014) and K S Rangasamy College of Technology, Tiruchengode, India.

REFERENCES
1. Akhilesh.R, Arunn Narasimhan, Balaji.C, ―Method to improve geometry for heat transfer enhancement in PCM
composite heat sinks‖, International Journal of Heat and Mass Transfer 48 (2005) 2759–2770, April 2005.
2. Avram Bar-Cohen, Jessica R. Sheehan, Emil Rahim, ―Two-Phase Thermal Transport in Microgap Channels—
Theory, Experimental Results, and Predictive Relations‖, Microgravity Sci. Technol. (2012) 24:1–15, September
2011.
3. Kuznetsov.V.V and Shamirzaev A. S.,‖Flow Boiling Heat Transfer of Water in Microchannel Heat Sink‖. Journal of
Engineering Thermophysics, 2012, Vol. 21, July, 2011.
4. Mohan.R and Govindarajan.P, ―Expermiental and CFD analysis of heat sinks with base plate for CPU
cooling,‖Journal of mechanical science and technology , vol. 25(8)(2011), April 2011.
5. Mousa M. Mohamed, ―Air cooling characteristics of a uniform square modules array for electronics device heat
sink‖, Applied Thermal Engineering 26 (2006) 486–493, September 2005.
6. Prashant Reddy.G and Navneet Gupta, ―Material selection for microelectronics heat sink: An application of the
Ashby approach‖, Journal of Material and design, July 2009.
7. Qu Z.G., Li W.Q., Wang J.L., Tao W.Q., ―Passive thermal management using metal foam saturated with phase
change material in a heat sink‖. International Communications in Heat and Mass Transfer, September 2012.
8. Venugopal Gandikota, Gerard F. Jones, Amy S. Fleischer, ―Thermal performance of a carbon fiber composite
material heat sink in an FC-72 Thermosyphon, Experimental Thermal and Fluid Science 34 (2010) 554–561,
November 2009.
9. Wanga Q., Han X.H., Sommers A., Parkc Y., Joen C.T, Jacobi A., ―A review on application of carbonaceous
materials and carbon matrix composites for heat exchangers and heat sinks‖, international journal of refrigeration
35 (2012), September 2011.
10. Yoav Peles, Ali Kos_ar, Chandan Mishra, Chih-Jung Kuo, Brandon Schneider, ―Forced convective heat transfer
across a pin fin micro heat sink., International Journal of Heat and Mass Transfer 48 (2005) 3615–3627, May
2005
11. Yun Wook Hwang and Min Soo Kim, ―Two-phase flow heat transfer of R-134a in microtubes‖. Journal of
Mechanical Science and Technology 23 (2009), July 2009.

Author’ biography with Photo


L.Arulmurugan was born in India in 1983. He is presently working as Assistant Professor(SG),
Department of Mechatronics Engineering, K S Rangasamy College of Technology, Tiruchengode,
India. He is pursuing his Ph.D in the faculty of information and communication engineering from
Anna University Chennai and he holds a ME degree in Applied Electronics from Anna university,
Chennai. and BE in Electronics and Communication Engineering from Bharathiar University,
Coimbatore. He has published two international journals and four papers in international and
national conferences. He is a life member of ISTE. His research interest is Electronics cooling
system and Decision Support System.

Dr. M. Ilangkumaran was born in India in 1978. He is presently working as Professor and Head,
Department of Mechatronics Engineering, K.S.Rangasamy College of Technology, Tiruchengode,
India. His research interest is optimization in IC engines and maintenance management. He
completed his graduation in Mechanical Engineering from K.S.Rangasamy College of Technology,
Tiruchengode in 1999 and Masters in Industrial Engineering from Kumaraguru College of Technology,
Coimbatore in 2001. He received his Ph.D in maintenance management from Anna University,
Chennai in 2010. He has published more than Forty three international and national journals and he
presented six papers in national conferences. He is a life member of ISTE.