SAC Technical Data Book: Accessories Book For Global

Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

SAC

Technical
Data Book
Accessories Book for
Global

1. MCU (Mode Control Unit)


2. EEV (Electronic Expansion Valve ) kit
3. AHU (Air Handling Unit) kit
4. FCU (Fan Coil Unit) Kit
5. UCK (Universal Communication Kit)
6. Drain Pumps
7. Low Ambient Cooling kit (For North America)
8. PDM (Pressure Drop Modulation) Kit
9. Branch kit
10. ERV Kit (Modbus Interface Module, For North America only)
11. Differential Pressure Switch( for Europe only)
12. MERV Filter(MF-C6A0) for N.A 4Way Cassette
3.
 AHU (Air Handling Unit) kit
3.1 Feature (For VRF outdoor unit)

Optimize performance and energy savings with seamless AHU connectivity


Samsung AHU kit allows DVM S outdoor units to connect to air handling units (AHUs), which results in energy
savings and improved performance and efficiency.
Features includes:
•• IP54 waterproof certification
•• Variable capacity
•• 2.5 HP - 40 HP
•• Simple BMS application(0~10V, MXD-K/X Series)
•• Discharge air temperature control

Outdoor unit
Communication F1, F2

EEV kit

EEV Control

Liquid Pipe

EVA. IN AHU Fan Control


Sensor Sensor
Return Air Exhaust Air Fresh Air Supply Air

Room
Sensor

AHU Controller
(Optional)
Gas pipe
EVA. OUT Sensor

40
3. AHU (Air Handling Unit) kit
3.1 Feature (MXD-K100XN, for single outdoor unit)

Optimize performance and energy savings with seamless AHU connectivity


Samsung AHU kit allows CAC outdoor units to connect to air handling units (AHUs), which results in energy savings
and improved performance and efficiency
Features includes:
•• IP54 waterproof rated
•• Variable capacity
•• 2.6kW - 25kW
•• Simple BMS application (0~10V, MXD-K100XN)
•• Air temperature control (Location : A or B)

Outdoor unit
Communication F1, F2

EEV Kit

Liquid Pipe

Eva. in AHU Fan Control


Sensor B

Return Air Exhaust Air Fresh Air Supply Air

A Eva. out
Sensor

AHU Controller
(Optional)
Gas pipe

41
3.
 AHU (Air Handling Unit) kit
3.1 Feature (MXD-K100XN, for single outdoor unit)

MXD-K***AN / MXD-X000AN

EEV kit

No. Parts and components


EEV body
(Coil wire: 2.5/5.0 HP = 2 m
7.5/10.0 HP = 7 m)

Lower insulation

Upper insulation

Holder

Cover

Clamp

•• Out (to AHU heat exchanger)


•• In (from outdoor unit)

Out In

* EEV kit is not included in the Model "MXD-X000AN, MCM-D201N, MXD-K100XN".

Control kit

No. Parts and components

Controller board

Case

Cover

42
3. AHU (Air Handling Unit) kit
3.3. Spec Sheet

AHU kit (for VRF outdoor unit)


Type AHU kit Control kit EEV kit (Option)
MCM-D201N MXD-A64K100E
Model MXD-K025AN MXD-K050AN MXD-K075AN MXD-K100AN MXD-X000AN
(10/20/30/40HP) (10HP)
Ø, #, 1,2,220- 1,2,220- 1,2,220- 1,2,220- 1,2,220- 1,2,220-
Power Supply -
V, Hz 240,50/60 240,50/60 240,50/60 240,50/60 240,50/60 240,50/60
Connectable Outdoor - HP/HR HP/HR HP/HR HP/HR HP/HR HP HP
35/70 /
kW 8.8 17.5 24.9 35 - 35
105/140
Max.
119/239 /
MBH 30 60 85 120 - 119
AHU Capacity 358/478
Allowance 25.2/50.4/
kW 6.3 12.6 18.9 25.2 - 25.2
Design 75.6/100.8
Min.
Recommendation 86.4/172.8/
MBH 21.6 43.2 64.8 86.4 - 86.4
259.2/345.6
AHU Internal 8,000/16,000 /
Max. cm3 2,000 4,000 6,000 8,000 - 8,000
Heat Exchanger 24,000/32,000
Volume 6,100/12,200/
Min. cm3 1,200 2,400 4,100 6,100 - 6,100
Allowance 18,300/24,400
High pressure pipe Ø, mm 9.52 9.52 9.52 9.52 - - 12.7
Piping
from outdoor unit Ø, inch 3/8" 3/8" 3/8" 3/8" - - 1/2"
Connections
(EEV kit) High pressure pipe Ø, mm 9.52 9.52 9.52 9.52 - - 12.7
to AHU Ø, inch 3/8" 3/8" 3/8" 3/8" - - 1/2"
Type / Ø 103HW / 6Ø 103HW / 6Ø 103HW / 6Ø 103HW / 6Ø - 103HW / 6Ø -
EVA. IN 10m / 10m/2 * 10m/2 * 10m/2 *
m /mm2 - 7m/2 * 0.75mm² -
2*0.75mm² 0.75mm² 0.75mm² 0.75mm²
Type / Ø 103HW / 7Ø 103HW / 7Ø 103HW / 7Ø 103HW / 7Ø - 103HW / 7Ø -
EVA. OUT 10m/2 * 10m/2 * 10m/2 * 10m/2 *
m /mm 2
- 7m/2 * 0.75mm² -
0.75mm² 0.75mm² 0.75mm² 0.75mm²
PT 1000Ω /
103HW / 103HW / 103HW / 103HW /
Type / Ø - 4~20mA -
Sensor Molding Molding Molding Molding
Room Field Supply
10m/2 * 10m/2 * 10m/2 * 10m/2 *
m /mm2 - -
0.75mm² 0.75mm² 0.75mm² 0.75mm²
PT 1000Ω /
Type / Ø 103HW / 7Ø 103HW / 7Ø 103HW / 7Ø 103HW / 7Ø - 4~20mA -
Discharge Field Supply
10m/2 * 10m/2 * 10m/2 * 10m/2 *
m /mm2 - -
0.75mm² 0.75mm² 0.75mm² 0.75mm²
Refrigerant Type - R410A R410A R410A R410A R410A R410A R410A
Type - INCLUDED INCLUDED INCLUDED INCLUDED NOT INCLUDED NOT INCLUDED -
EEV kit m 2 2 7 7 - - 7
EEV Wire length
ft 6.6 6.6 23 23 - - 23
Accessory for
MCM-D201N,
mm 415 x102 x 170 415 x102 x 170 415 x102 x 170 415 x102 x 170 - - Ordering
Separately
EEV kit (W×HxD)
(1EA per 10HP)
Dimensions [1'-3 1/4"] x [3 [1'-3 1/4"] x [3 [1'-3 1/4"] x [3 [1'-3 1/4"] x [3
inch
1/2"] x [6 3/4"] 1/2"] x [6 3/4"] 1/2"] x [6 3/4"] 1/2"] x [6 3/4"]
inch 6.7 x 16.3 x 4 6.7 x 16.3 x 4 6.7 x 16.3 x 4 6.7 x 16.3 x 4
mm 380 x 130 x 280 380 x 130 x 280 380 x 130 x 280 380 x 130 x 280 380 x 130 x 280 385 x 53 x 275 -
Control Box (W×HxD)
inch 15.0 x 5.1 x 11.0 15.0 x 5.1 x 11.0 15.0 x 5.1 x 11.0 15.0 x 5.1 x 11.0 15.0 x 5.1 x 11.0 15.2 x 2.1 x 10.8 -

•• Specifications may be subject to change without prior notice for product improvement.
•• The AHU design SPEC are base on 10HP test result under Evaporating Temperature:
7˚C, Superheat: 1˚C, Air temperature: 27˚CDB/19˚CWB
•• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
•• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
•• In terms of AHU, there is a no limitation in capacity.

43
3.
 AHU (Air Handling Unit) kit
3.3. Spec Sheet

AHU kit (for single outdoor unit)


Type AHU Kit
Model MXD-K100XN
Ø, #,
Power Supply 1,2,220-240, 50/60
V, Hz
AC100MXADKH/EU
Connectable Outdoor - AC026MXADKH/EU AC035MXADKH/EU AC052MXADKH/EU AC071MXADKH/EU
AC100MXADNH/EU
Nominal kW 2.6 3.5 5 7.1 10
AHU Capacity (Cool) MBH 8.87 11.9 17 24.2 34.1
Allowance Nominal kW 3.4 4 6 8 11.2
Design (Heat) MBH 11.6 13.6 20.5 27.3 38.2
Recommendation
AHU Internal
Max. cm3 800 900 1210 1620 2430
Heat Exchanger
Volume
Allowance Min. cm3 550 620 840 1130 1690

Type / Φ 103HW / Φ6
EVA. IN
m/mm² 10m/2 * 0.75mm²
Type / Φ 103HW / Φ7
Sensor EVA. Out
m/mm² 10m/2 * 0.75mm²
Type / Φ 103HW / Molding
Room
m/mm² 10m/2 * 0.75mm²
Refrigerant Type - R410A
mm 380 x 130 x 280
Dimensions Control Box (W x H x D)
inch 15.0 x 5.1 x 11.0

•• Specifications may be subject to change without prior notice for product improvement.
•• The AHU design SPEC are base on test result under Air temperature as below.
Cooling : Indoor 27℃DB/19℃WB, Outdoor 35℃DB/24℃WB
Heating : Indoor 20℃DB/15℃WB, Outdoor 7℃DB/6℃WB
•• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
•• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
•• In terms of AHU, there is a no limitation in capacity.

44
3. AHU (Air Handling Unit) kit
3.3. Spec Sheet

5.3. Spec Sheet

AHU kit (for single outdoor unit)


Type AHU Kit
Model MXD-K100XN
Ø, #,
Power Supply 1,2,220-240, 50/60
V, Hz
AC120MXADKH/EU AC140MXADKH/EU
Connectable Outdoor - AC180JXAPNH/EU AC200KXAPNH/EU AC250KXAPNH/EU
AC120MXADNH/EU AC140MXADNH/EU
Nominal kW 12 13.4 18 20 25
AHU Capacity (Cool) MBH 40.9 45.7 61.4 68.2 85.3
Allowance Nominal kW 13 15.5 20 23 27
Design (Heat) MBH 44.3 52.9 68.2 78.5 92.1
Recommendation
AHU Internal
Max. cm3 2830 3240 3700 4600 5400
Heat Exchanger
Volume
Allowance Min. cm3 1970 2250 2700 3200 4000

Type / Φ 103HW / Φ6
EVA. IN
m/mm² 10m/2 * 0.75mm²
Type / Φ 103HW / Φ7
Sensor EVA. Out
m/mm² 10m/2 * 0.75mm²
Type / Φ 103HW / Molding
Room
m/mm² 10m/2 * 0.75mm²
Refrigerant Type - R410A
mm 380 x 130 x 280
Dimensions Control Box (W x H x D)
inch 15.0 x 5.1 x 11.0

•• Specifications may be subject to change without prior notice for product improvement.
•• The AHU design SPEC are base on test result under Air temperature as below.
Cooling : Indoor 27℃DB/19℃WB, Outdoor 35℃DB/24℃WB
Heating : Indoor 20℃DB/15℃WB, Outdoor 7℃DB/6℃WB
•• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
•• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
•• In terms of AHU, there is a no limitation in capacity.

45
3.
 AHU (Air Handling Unit) kit
3.4. Dimensional drawings

Dimensional drawings

MCM-D201N

[Unit: mm(inch)]

4 5/ .6
X 8"
(Φ 6
Ø8 )
4 Φ1/
X 4"

.2
(
Ø )

275.0(10-13/16")
250.0(9-13/16")
175.0(6-7/8")
300.0(10-13/16" )
356.0(14" )
385.0(15-3/16" )
65.1(9" )

EEV kit : Accessory (Ordered separately)

For detailed information of EEV installation, refer to the installation manual of ASS’Y EEV (MXD-A64K100E) which
you need to purchase additionally.

MXD-A64K100E

EEV Unit: mm (inch)


254(10")
185(7-5/16")

Filter

EEV wire (7m)

IN IN/OUT Pipe Diameter :


79 Ø12.7(1/2" )
OUT (3-1/8")
※ IN : From outdoor unit
※ OUT : To AHU heat exchanger

46
3. AHU (Air Handling Unit) kit

Wiring drawings

MXD-K***AN / MXD-X000AN / MXD-K100XN

EEV Electronic Expansion Valve EEV1 Electronic Expansion Valve Vd Defrost Signal(AC)
TR Room Temperature TEI EVAP. IN Temperature TEO EVAP. OUT Temperature
Com/HP/CO/AV/OV Simple BMS

NOTE
•• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
•• Protective earth(SCREW) ), CN *: connector, : The quantity

47
3.
 AHU (Air Handling Unit) kit

Wiring drawings

MCM-D201N

EEV1/2/3/4 Electronic expansion valve Sensor(mA) 4~20mA Sensor(-50~50℃, Field Supply)


Vd Defrost Signal (AC) Sensor(PT1000) PT1000Ω Sensor (-30~50℃, Field Supply)

NOTE
•• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
•• Protective earth(SCREW), CN *: connector, : The quantity

48
5. UCK (Universal Communication Kit)
5.1. Feature

1 Provides a communication kit that enables normal operation when connecting an outdoor unit (VRF) to a
3rd party indoor unit.
Components: Control kit + EEV kit

2 Enhances the compatibility with a 3rd party indoor unit and provides advanced functions.

Optimized to perform the following functions:


: Control the Fan (H/M/L)
: Connect to an economizer.
: Control the variable outputs of a ventilation damper.
: Control an enthalpy sensor.
: Provide an applicability to any additional loads.
: Use 24 VAC power supply.

3 System Diagram

Universal comm kit

Simple BMS
Control Economizer

Wired
Remote 1 Control Kit Ventilation
Control Damper
EEV Kit /
2 Temp. Sensor

Outdoor Enthalpy
Unit Sensor

Upper
controller
DMS 2.5/
BACnet/
Lonwork

Indoor Unit
(Ex: Unit Ventilator)

57
 UCK (Universal Communication Kit)
5.
5.2. Combination & Line-up Table

1 Setting of the indoor unit capacity and EEV model selection


(SEG 20 of the installation option 05 series)

Reated
Capacity Range Heat Exchanger Number of Number of
Display Capacity Control kit EEV kit
(Btu/h) (Btu/h) Volume(in3) Control kit EEV kit
0 12k 7k to 18k 28 to 71 1 1
MXD-A24K100E
1 12k 7k to 18k 28 to 71 1 1
2 24k 7k to 30k 71 to 118 1 MXD-A32K100E 1
3 36k 30k to 42k 118 to 165 1 1
MXD-A40K100E
4 48k 42k to 60k 165 to 236 1 1
5 60k 60k to 72k 236 to 283 1 1
6 72k 72k to 96k 283 to 378 1 1
MCM-D211UN
7 96k 96k to 144k 378 to 566 1 1
8 144k 144k to 192k 566 to 755 1 2
9 192k 192k to 240k 755 to 944 1 MXD-A64K100E 2
A 240k 240k to 288k 944 to 1133 1 3
B 288k 288k to 336k 1133 to 1322 1 3
C 336k 336k to 384k 1322 to 1510 1 4
D 384k 384k 1510 to 1725 1 4

2 Outdoor unit combination

Universal Comm. kit


HP HR

DVM S

DVM S water

DVM S Eco

3 Part combination

Part combination of the universal Comm. Kit


Simple
EEV Thermister Fan Motor Fan check Economizer Damper Enthalpy Heater PT 1000 Defrost
BMS
Mandatory
(Product supplied)
Mandatory
(Field supplied)
Optional
(Field supplied)

58
5. UCK (Universal Communication Kit)
5.3. Product Specification

1 Composed of a single Control kit and 4 EEV kits

Type Control Kit EEV Kit EEV Kit EEV Kit EEV Kit
Model Name MCM-D211UN MXD-A24K100E MXD-A32K100E MXD-A40K100E MXD-A64K100E
Φ, #,
Power Supply 24VAC - - - -
V, Hz
Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat
Applied outdoor unit Type -
Recovery Recovery Recovery Recovery Recovery
EEV(EDM) - - Φ 2.4mm Φ 3.2mm Φ 4.0mm Φ 6.4mm

Refrigeration Ton TON 1/2/4/8/17/25/34 1 2 4 8

Cooling kW - - - - -
(Min) Btu/h 7000 7000 18000 30000 60000
Performance Cooling kW - - - - -
(Max) Btu/h 384000 18000 30000 60000 144000
Capacity
Heating kW - - - - -
(Min) Btu/h 8500 8500 22000 34000 64000
Heating kW - - - - -
(Max) Btu/h 432000 22000 34000 64000 108000
AHU Internal
Heat Exchanger Min in3 28 28 71 118 236
Volume
Allowance Max in3 1725 71 118 236 566
EEV in/out Liquid Pipe Φ, inch - 3/8 1/2 3/8 1/2
Connection Gas Pipe Φ, inch - 3/8 1/2 3/8 1/2
Power Source Wire mm2 - - - - -
Field Wiring
Transmission Cable mm2 - - - - -

kg 1.7 0.29 0.46 0.36 0.66


Net Weight
lb 3.75 0.64 1.01 0..79 1.46
kg 3.54 0.48 0.64 0.56 0.85
Shipping Weight
External lb 7.8 1.06 1.41 1.23 1.87
Dimension Net Dimensions mm 385*275*56 243*70*42 250*70*42 250*70*42 259*117*42
(WxHxD) in 15.16*10.83*2.2 9.57*2.76*1.65 9.84*2.76*1.65 9.84*2.76*1.65 10.20*4.61*1.65
Shipping Dimensions mm 399*289*138 276*121*69 276*121*69 276*121*69 276*121*69
(WxHxD) in 15.71*11.38*5.43 10.87*4.76*2.72 10.87*4.76*2.72 10.87*4.76*2.72 10.87*4.76*2.72

59
 UCK (Universal Communication Kit)
5.
5.4. Technical drawings

Dimensional Drawings

1 Control Kit

Unit: mm[inch]

56 [2-1/4”]
385 [1’3-3/6”]

50 [1-15/16”]

4 - Φ6.6 (Φ 1/4) half slots

4 - Φ8.3 (Φ 5/16) holes

275 [10-13/16”]
175 [6-7/8”]

14.2 [9/16”]
50 [1-15/16”]

42.5 [1-11/16”]
12.5 [1/2”]

42.5 [1-11/16”]

300 [11-15/16”]

60
5. UCK (Universal Communication Kit)
5.4. Technical drawings

1 EEV Kit (Electronic Expansion Valve)

MXD-A64K100E MXD-A40K100E
MXD-A32K100E MXD-A24K100E

EEV EEV

(D)
(D)

(B)
(B)

EEV coil(A) EEV coil(A)

Filter (C) (C)


Filter

Model A [ft(m)] B [inch(mm)] C [inch(mm)]


MXD-A64K100E 22.97 (7) 7.28 (185) 3.03 (77)
MXD-A40K100E 6.56 (2) 6.57 (167) 1.34 (34)
MXD-A32K100E 6.56 (2) 7.28 (185) 2.91 (74)
MXD-A24K100E 3.28 (1) 6.38 (162) 1.18 (30)

61
 UCK (Universal Communication Kit)
5.
5.4. Technical drawings

Piping Drawings

1 Cooling operation

High Temperature & Pressure Gas


High Temperature & Pressure Liquid
Low Temperature & Pressure Gas
Low Temperature & Pressure Liquid

COOL
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)

Thermistor -
Discharge air Temperature
(T_DT)

Ball Valve - Electronic Expansion


Liquid pipe (BV_L) Valve - Main
(E_M)

62
5. UCK (Universal Communication Kit)
5.4. Technical drawings

Piping Drawings

1 Heating operation

High Temperature & Pressure Gas


High Temperature & Pressure Liquid
Low Temperature & Pressure Gas
Low Temperature & Pressure Liquid

HEAT
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)

Thermistor -
Discharge air Temperature
(T_DT)

Ball Valve - Electronic Expansion


Liquid pipe (BV_L) Valve - Main
(E_M)

63
 UCK (Universal Communication Kit)
5.
5.4. Technical drawings

Piping Drawings

1 Free cooling operation

High Temperature & Pressure Gas


High Temperature & Pressure Liquid
Low Temperature & Pressure Gas
Low Temperature & Pressure Liquid

COOL
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)

Thermistor -
Discharge air Temperature
(T_DT)

Ball Valve - Electronic Expansion


Liquid pipe (BV_L) Valve - Main
(E_M)

64
5. UCK (Universal Communication Kit)
5.4. Technical drawings

Wiring Drawings

EEV Electric expansion valve FAN MID FAN Output(Step Mid ON) NC NO CONNECTION
Checking fan operation status of input
AIR (10K) Thermistor () FAN LOW FAN-Output(Step Low ON) FAN CHECK
signal
FREE
EVA-OUT (10K) Thermistor (EVA.-OUT_10K) FAN OUT FAN-Output(ON/OFF) Blowing wind from outside(Input)
COOL_IN
EVA-IN (10K) Thermistor (EVA.-IN_10K) HEATER Heater-Output(ON/OFF) PT1000 PT1000Ω sensor(Input)
DISCHARGE
Thermistor (Discharge_10K) DEFROST Defrost-Output(ON/OFF) TB100 Terminal Block100(Power)
(10K)
EXT CTRL EXTERNAL CONTROL COOL_T Coolling Thermo-Output(ON/OFF) TB800 Terminal Block800(control/Dry Contact)
COMP ERROR Error check output THERMO Thermo-Output(ON/OFF) F100 Fuse
FAN HIGH FAN-Output (Step High ON) OPERATION O(ON/OFF)

NOTE
•• This wiring diagram applies only to Universal Comm. Kit
•• Colors BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue , ORG: orange,
GRN: green
•• When operating, don’t short circuit the protection device (High Pressure switch)
•• Protective earth(screw), : connector, : The wire quantity

65
 UCK (Universal Communication Kit)
5.
5.5. Installation

Structure diagram of an Universal Comm. Kit

Outdoor unit

Communication cable: F1,F2

ASS'Y EEV(Electronic Expansion Valve)

EEV Control
Liquid valve

Communication cable:
F3,F4

Return air Exhaust


Outdoor air
air
Supply air
IN sensor

* Room Temperature

Gas pipe
Wired remote controller
OUT sensor

66
5. UCK (Universal Communication Kit)
5.5. Installation

10.5. Installation

PBA

12 11 10 9 8
(+) (COM)
DIS EXT-CTRL COMP/ERROR EEV1 EEV2 EEV3 EEV4 COOL HEAT AUTO COM TEMP COM ENTHALPY

DAMPER
(COM)
7

(+)
6

AIR
EVA-OUT
5

EVA-IN
4

F1 F2 V1 V2 F3 F4
AC 24V B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26

1 2 3

No. CONNECTOR SIGNAL FUNCTION CONTACT SHORT CONTACT OPEN *SCREW


1 TB100 - AC24V/60Hz - - M4
B1
*DRY CONTACT FAN HIGH FAN STEP HIGH ON FAN OFF M3.5
B2
B3
*DRY CONTACT FAN MID FAN STEP MID ON FAN OFF M3.5
B4
B5
*DRY CONTACT FAN LOW FAN STEP LOW ON FAN OFF M3.5
B6
B7
*DRY CONTACT FAN OUT FAN ON FAN OFF M3.5
B8
B9
*DRY CONTACT HEATER HEATER ON HEATER OFF M3.5
B10
B11
*DRY CONTACT DEFROST DEFROST ON DEFROST OFF M3.5
B12
B13
2 TB800 *DRY CONTACT COOL_T COOL THERMO ON COOL THERMO OFF M3.5
B14
B15
*DRY CONTACT THERMO THERMO ON THERMO OFF M3.5
B16
B17
*DRY CONTACT OPERATION OPERATION ON OPERATION OFF M3.5
B18
B19 - - - - -
B20
ZERO Voltage CONTACT FAN CHECK FAN CHECK ON FAN CHECK OFF M3.5
B21
B22
ZERO Voltage CONTACT FREE COOL_IN FREE COOL ON FREE COOL OFF M3.5
B23
B24 INPUT
B25 INPUT PT1000 - - M3.5
B26 COM

67
 UCK (Universal Communication Kit)
5.
5.5. Installation

No. CONNECTOR SIGNAL FUNCTION CONTACT SHORT CONTACT OPEN *SCREW


F1 -
IN-OUT COMMUNICATION - -
F2 -
F3
3 CN301 DC DC 12V - - M3.5
F4
F5 - WIRED REMOTE
- -
F6 - COMMUNICATION
4 CN400 - EVA IN SENSOR - - M3
5 CN401 - EVA OUT SENSOR - - M3
6 CN402 - AIR SENSOR - - M3
(+) LEVEL OUT DAMPER ALNALOG LEVEL
7 CN804 - - M3
COM COM -
(+) LEVEL IN ENTHALPY IN
8 CN810 - - M3
COM COM -
COOL
- -
HEAT
ZERO Voltage CONTACT SIMPLE BMS MODE IN
AUTO
9 CN305 - - M3.5
COM
TEMP LEVEL IN
SIMPLE BMS TEMP IN - -
COM -
10 CN800~803 - EEV - -
11 CN81,CN83 - EXTERNAL CONTROL - -
12 CN403 - DISCHARGE SENSOR - -

* Use the rated current capacity for the dry contact within AC 250 V/1 A.
* Use the ring terminal that fits the screw.

68
2018. 12
Ver.3.1
Samsung Electronics Co., LTD.