System Specifications
US Ton (nominal) 5
Nominal Cooling1 60,000
Capacity (Btu/h)
Nominal Heating1 66,000
Performance System Modulation down to (Btu/h) 7,000
SEER Ducted / Non-Ducted 17.1 / 20.6
EER Ducted / Non-Ducted 10.9 / 11.2
HSPF Ducted / Non-Ducted 10.9 / 11.5
Voltage (ø/V/Hz) 1 / 208-230 / 60
Maximum Circuit Breaker
Power 50
(MCCB/ELB/ELCB)
Minimum Circuit Ampacity (MCA) 32
Total Capacity (%) 50 - 130% Of Outdoor Capacity
Indoor Units Compatibility
Maximum Indoor Unit Quantity 10 Only compatible with Samsung DVM S indoor units (AM****N***H***) that are equal to or less than
Type Flash Injected Scroll X 1 76,000 Btu/h and MCM-D211UN Universal Communication Kit.
Compressor
RLA A 24.5
Construction
Type R410A The unit shall be galvanized steel with a baked on powder coated finish.
Refrigerant
Factory Charge lbs. 8.2
Heat Exchanger
Pipe The heat exchanger shall be mechanically bonded fin to copper tube.
Liquid X Suction X HP Gas (braze) 3/8 X 3/4 X 5/8
Connections
The aluminum fins of the heat exchanger shall have a protective coating.
Max. Distance - ODU to IDU (feet) 492 (574 equivalent)
Salt spray test method: ASTM-B117-18 - the heat exchanger showed no unusual rust or
Installation Vertical Separation ODU to IDU 3 164 / 131 corrosion development to 2,280 hours.
Limitation2 (feet) Highest/Lowest IDU 49
Total Refrigerant Pipe (feet) 984 Controls
The unit shall be operated via NASA Protocol with controls provided by Samsung
Type Propeller X 2
Fan The outdoor unit shall have a removable EEPROM that stores unit serial number, startup
Output (CFM) 4,767 information, system settings, system tag/name, and other information.
Condenser Fan
Type BLDC
Motor Controls shall integrate with Samsung central controllers without additional interface modules.
Output (W) / FLA (A) 139 X 2 / 0.6
Control wiring shall be 16 AWG X 2 shielded wire.
WXHXD Inches 37 X 55 15/16 X 13
Dimensions
Weight lbs. 275.6 Refrigerant System
The compressor shall be Samsung hermetically sealed, inverter driven, direct flash injected, DC
Sound Level dB (A) Max. (cooling / heating) 58 / 59
scroll type with soft-start capability.
Operating Cooling 4 °F(°C) 0 ~ 118°F (-18 ~ 48°C)
Temperature Flash injected compressors provide advanced low ambient heating performance.
Range Heating °F(°C) -13 ~ 75°F (-25 ~ 24°C)
Refrigerant flow shall be controlled by EEV (electronic expansion valve) throughout the system.
Front WBF-6M A flat plate subcooler device will improve capacity at extreme system refrigerant pipe lengths
Wind Baffles
Back WBB-8M and reduce refrigerant noise.
Wi-Fi Adapter MIM-H03UN
The condenser shall be able to provide simultaneous heating and cooling operation.
Accessories Base Pan Heater Kit MHC-015EE
Installation of an HR Changer (MCU-R4NEK0N) is mandatory. If additional Mode Control
External contact control interface module
Unit(s) are needed, the HR Changer must be installed between the outdoor unit and addtional
(operation and error output, night silent mode MIM-B14
MCU's. Please refer to the installation manual for compatible MCU models.
manual activation)
Indoor units that will be used for cooling only year-around may be piped direct to the liquid and
Safety Certifications ETL (UL 1995)
suction pipes after the HR Changer and bypassing MCU connection.
Intelligent logic to ensure proper operation within unit design limitations and
operational parameters Other Features
Protection
Devices High pressure sensor, low pressure sensor, over-voltage protection, Advanced oil recovery cycle logic to ensure adequate oil level is maintained in the compressor.
compressor over-current protection, current transformer, fan motor Oil recovery operation shall not interrupt heating or cooling operation.
voltage protection, fan motor thermal protection, high voltage fuses
Optional night quiet modes to reduce outdoor unit sound (4 levels) with automatic activation or
1 Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification
manual activation (with MIM-B14).
Program which is based on the latest edition of AHRI Standard 210/240.
2 Other pipe restrictions and requirements exist. Please consult installation manuals or technical data book
Optional snow blowing logic to prevent snow accumulation on idle outdoor units
for full details.
3 Vertical separation: 131’ when outdoor unit is lower than the indoor units, 164’ when the outdoor Maximum current control of outdoor unit(s) to limit current (50% - 100% of design current) adjustable
unit is higher than the indoor units. at outdoor unit or central control devices: DMS 2 (MIM-D00AN), DMS 2.5 (MIM-D01AUN), BACnet
4 When cooling in outside temperatures between 0°F ~ 23°F, wind baffles are required. When outside Gateway (MIM-B17N, MIM-B17BUN), LON Gateway (MIM-B18N, MIM-B18BUN).
temperature is between 0°F ~ 23°F, 50% operating capacity should be maintained to ensure reliability while
in cooling mode. Energy savings options to reduce system energy consumption in heating mode when average indoor
room temperatures are greater than average indoor set temperatures.
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
Units: inches
37"
13"
Top
12 5/16"
55 15/16"
5
5
5 4
4
4 3
3
3
Front Rear
24 3/8"
3
6
12 7/8"
15 1/8"
Bottom
2
1
20 11/16"
15 3/8"
15 3/4"
NO Name Description
1 Refrigerant gas pipe 3/4"
2 Refrigerant liquid pipe 3/8"
3 Knockout hole for pipe intake Front / Side / Rear / Bottom
4 Power wiring conduits Front / Side / Rear, 1 3/8"
5 Communication wiring conduits Front / Side / Rear, 7/8"
6 Drain holes Connect with the provided drain plug