Proces Rm014 en P

Download as pdf or txt
Download as pdf or txt
You are on page 1of 574

Reference Manual

Original Instructions

Rockwell Automation Library of Process


Objects: Display Elements
Version 4.0

IMPORTANT This manual applies to the Rockwell Automation Library of Process Objects
version 4.0.
For Rockwell Automation Library of Process Objects version 5.0, see
PROCES-RM200.
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an


explosion in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or
motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor,
to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor
control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or
death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Access the Attachments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Open Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
How to Use Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Chapter 1
Overview Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Basic Attributes and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
State Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Threshold Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Deviation Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Command Source Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Help Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Basic Faceplate Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Quick Display Interaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Using a Display Element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Chapter 2
Cross Functional Family Condition Gate Delay (P_Gate). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Interlocks with First Out and Bypass (P_Intlk) . . . . . . . . . . . . . . . . . . 45
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Interlocks with First Out and Bypass - Advanced (P_IntlkAdv) . . . 53
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Permissives with Bypass (P_Perm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Central Reset (P_Reset) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Graphic Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Common Alarm Block (P_Alarm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Command Source (P_CmdSrc) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Command Source Totem Pole. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 3


Table of Contents

Operator Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Maintenance Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Advanced Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Operator Prompt (P_Prompt) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Graphic Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Faceplates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Boolean Logic with Snapshot (P_Logic). . . . . . . . . . . . . . . . . . . . . . . . . 81
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
View Snapshot Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Gate Configuration Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Chapter 3
I/O Processing Family Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Basic Analog Input (P_AIn) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Operator (Home) Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Advanced Analog Input (P_AInAdv) . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Analog Input Channel (P_AIChan) . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Dual Sensor Analog Input (P_AInDual) . . . . . . . . . . . . . . . . . . . . . . . 117
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Multiple Analog Input (P_AInMulti). . . . . . . . . . . . . . . . . . . . . . . . . . 124
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

4 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Table of Contents

Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129


Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Discrete Input (P_DIn). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Digital Input Advanced (P_DInAdv) . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Discrete Output (P_DOut) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Analog Output (P_AOut) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Pressure/Temperature Compensated Flow (P_PTComp) . . . . . . . 166
Tank Strapping Table (P_StrapTbl) . . . . . . . . . . . . . . . . . . . . . . . . . . . 166

Chapter 4
Regulatory and Proportional + Integral + Derivative Enhanced (P_PIDE). . . . . . . 168
Procedural Control Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Operator (Home) Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Family
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Advanced Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Trends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Analog Fanout (P_Fanout) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 5


Table of Contents

HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197


Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
High or Low Selector (P_HiLoSel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Deadband Controller (P_DBC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Rockwell Automation Sequencer Object (P_Seq) . . . . . . . . . . . . . . . 214
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Dosing (P_Dose). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Lead/Lag/Standby Motor Group (P_LLS) . . . . . . . . . . . . . . . . . . . . . 237
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Motor Configuration Dialog Box . . . . . . . . . . . . . . . . . . . . . . . . . . 243

6 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Table of Contents

HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244


Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245

Chapter 5
Motors Family Common Motors Faceplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Single-speed Motor (P_Motor). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Display Elements (P_Motor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Two-speed Motor (P_Motor2Spd) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Display Elements (P_Motor2Spd) . . . . . . . . . . . . . . . . . . . . . . . . . 258
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Reversing Motor (P_MotorRev). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Display Elements (P_MotorRev) . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Hand-operated Motor (P_MotorHO) . . . . . . . . . . . . . . . . . . . . . . . . . 276
Display Elements (P_MotorHO) . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Discrete 2-, 3-, 4-state Device (P_D4SD). . . . . . . . . . . . . . . . . . . . . . . 286
Display Elements (P_D4SD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 7


Table of Contents

Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298


Variable Speed Drive (P_VSD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Display Elements (P_VSD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
PowerFlex 523/525 Variable Frequency Drives (P_PF52x) . . . . . . 314
Display Elements (P_PF52x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
PowerFlex 753 Drive (P_PF753) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Display Elements (P_PF753) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
PowerFlex 755 Drive (P_PF755) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Display Elements (P_PF755) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
PowerFlex 6000 Drive (P_PF6000). . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Display Elements (P_PF6000). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348

8 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Table of Contents

Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348


Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
PowerFlex 7000 Drive (P_PF7000). . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Display Elements (P_PF7000). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
SMC-50 Smart Motor Controller (P_SMC50) . . . . . . . . . . . . . . . . . 366
Display Elements (P_SMC50). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
SMC Flex Smart Motor Controller (P_SMCFlex) . . . . . . . . . . . . . . 376
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382
E1 Plus Electronic Overload Relay (EtherNet/IP) (P_E1PlusE) . . 383
Display Elements (EtherNet/IP) (P_E1PlusE) . . . . . . . . . . . . . . 383
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
E3/E3 Plus Overload Relay (P_E3Ovld) . . . . . . . . . . . . . . . . . . . . . . . 390

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 9


Table of Contents

Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390


Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
E300 Electronic Overload Relay (EtherNet/IP) (P_E300Ovld) . . 396
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
Run Time and Start Counter (P_RunTime). . . . . . . . . . . . . . . . . . . . 405
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
Restart Inhibit for Large Motor (P_ResInh) . . . . . . . . . . . . . . . . . . . . 407
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409

Chapter 6
Valves Family Common Valves Faceplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Analog/Pulsed Control Valve (P_ValveC) . . . . . . . . . . . . . . . . . . . . . 413
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Hand-operated Valve (P_ValveHO) . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428

10 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Table of Contents

HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430


Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
Motor-operated Valve (P_ValveMO) . . . . . . . . . . . . . . . . . . . . . . . . . . 432
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Mix-proof Valve (P_ValveMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Advanced Mix-proof Valve (P_ValveMPAdv) . . . . . . . . . . . . . . . . . . 450
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Solenoid-operated Valve (P_ValveSO) . . . . . . . . . . . . . . . . . . . . . . . . . 460
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
2-state Valve Statistics (P_ValveStats). . . . . . . . . . . . . . . . . . . . . . . . . . 469
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 11


Table of Contents

Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473


Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
n-Position Device (P_nPos) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478
Advanced Properties Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479
Advanced Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
HMI Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 484
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 486
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 486
Discrete 2-, 3-, 4-state Device (P_D4SD). . . . . . . . . . . . . . . . . . . . . . . 487

Chapter 7
Built-in Instructions Proportional + Integral + Derivative Enhanced (PIDE) Autotune 489
Family Autotune Page 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
Autotune Page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
Autotune Page 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 492
Coordinated Control (CC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 494
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505
Coordinated Control (CC) Autotune. . . . . . . . . . . . . . . . . . . . . . 506
Internal Model Control (IMC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 510
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523
Internal Model Control (IMC) Autotune . . . . . . . . . . . . . . . . . . 524
Modular Multivariable Control (MMC) . . . . . . . . . . . . . . . . . . . . . . . 527
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 527
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 541
Proportional + Integral + Derivative Enhanced (PIDE) . . . . . . . . . 545
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 550

12 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Table of Contents

Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559


Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561
Ramp/Soak (RMPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 562
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 564
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
Totalizer (TOT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 566
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 566
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 569
Advanced Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570
Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 572

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 13


Table of Contents

Notes:

14 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Preface

This document explains the visualization files and the Human Machine
Interfaces (HMI) that are contained in Add-On Instructions that comprise the
volume of Rockwell Automation® Library of Process Objects. Sections are
divided into classifications that are based on what criteria the Add-On
Instructions control and monitor, such as motors.

This document is for the visualization files, display elements, global objects,
and HMI information. The visualization files for each instruction family are
PDF in the form of a Microsoft Excel spreadsheet. See Access the Attachments
on page 16 for how to access the attachments.

The operation of the Add-on Instructions and controller code is contained in


publication PROCES-RM013.

Figure 1 - PlantPAx System Implementation and Documentation Strategy

Define and
Install Prep Develop Operate
Procure

• Selection • Virtualization User • Infrastructure User • Application User • Verify and Troubleshoot
Guide Manual Manual Manual User Manual
• Reference • Reference • Reference
Manual Manual Manual
• Library of Process
Objects
PROCES-RM013

• Define and Procure – Helps you understand the elements of the


PlantPAx® system to make sure that you buy the proper components.
• Install – Provides direction on how to install the PlantPAx system.
• Prep – Provides guidance on how to get started before you develop your
application.
• Develop – Describes the actions and libraries necessary to construct
your application that resides on the PlantPAx system.
• Operate – Provides guidance on how to verify and maintain your
systems for operation of your plant.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 15


Preface

Access the Attachments The Microsoft Excel spreadsheets that are attached to this PDF file list the
visualization files required for each Add-On Instruction.

To use a Microsoft Excel file, click the Attachments link (the paper clip) and
double-click the desired file.

Open Content

As a precaution when you open programs or files, select one of the choices
and click OK.

16 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Preface

How to Use Attachments

The Microsoft Excel spreadsheet has five tabs: Process Library, Logix Library,
BuiltIn Library, Sequencer, and LBSM. On each tab, the Add-On Instructions
are at the top of the spreadsheet. The visualization files are located down the
left side of the spreadsheet. An ‘X’ in the column indicates that visualization
file is required. An ‘O’ in the column indicates that the visualization file is the
visualization file is optional.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 17


Preface

Additional Resources These documents contain additional information that concerns related
products from Rockwell Automation.
Resource Description
PlantPAx Distributed Control System Provides basic definitions of system
Selection Guide, publication PROCES- elements and sizing guidelines for
SG001 procuring a PlantPAx system.
PlantPAx Distributed Control System Describes procedures for how to configure
Infrastructure Configuration User Manual, system components that comprise a
publication PROCES-UM001 PlantPAx modern DCS.
PlantPAx Distributed Control System Appli- Describes procedures to start development
cation of your PlantPAx distributed control sys-
Configuration User Manual, publication tem.
PROCES-UM003
PlantPAx Distributed Control System Provides characterized recommendations
Reference Manual, publication PROCES- for implementing your PlantPAx system.
RM001
Rockwell Automation Library of Process Provides an overview of the code objects,
Objects Reference Manuals: display elements, and faceplates that
Publication PROCES-RM013 comprise the Rockwell Automation
Publication PROCES-RM014 Library of Process Objects.

Rockwell Automation Library of Logix Provides information on Add-On


Diagnostic Objects Reference Manual, Instructions that monitor Logix
publication PROCES-RM003 controllers to diagnose issues that include
memory usage, communication, and
control.
Rockwell Automation Library of Steam Table Provides Add-On Instructions for to
Instructions, calculate temperature and pressure steam
publication PROCES-RM004 tables.
Redundant I/O System User Manual, Explains how to install and configure the
publication 1715-UM001 1715 Redundant
I/O system.
Product Compatibility and Download Center Website helps you find product-related
at downloads including firmware, release
http://www.rockwellautomation.com/ notes, associated software, drivers, tools,
rockwellautomation/support/pcdc.page and utilities.
Rockwell Automation Sample Code website Accesses a Rockwell Automation
at http://samplecode.rockwellautomation.com webpage to search for sample code.

You can view or download publications at


http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.

Added P_ValveMPAdv.
Summary of Changes
Updated the attached Excel table.

18 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 1

Overview

This manual compiles the HMI visualization files that comprise the Rockwell
Automation® Library of Process Objects from individual manuals into one
reference manual. Before this software release, each object was documented in
a separate manual. These objects, which are arranged by device family, provide
visual components to enable interaction with instrument data.

There are three visualization files that are associated with each Add-On
Instruction: Images, Global objects, and HMI faceplates. This manual features
the visualization files that control various instructions for motors, valves,
drives, interlocks, permissives, and additional devices that can be used with the
PlantPAx® system.

IMPORTANT To view spreadsheets with parameters and local tags for


each Add-On Instruction, see the Rockwell Automation
Library of Process Objects: Controller Code
Reference Manual, publication PROCES-RM013.

The required visualization files are included in the Process Library download
from the Product Compatibility and Download Center (PCDC). The files
build on one another and must be imported in the following order:
• Images
• Global objects
• Standard display files

Images are external graphic files that can be used in displays. They must be
downloaded from PCDC to be used by FactoryTalk® View software.

Global object files are display elements that are created once and referenced
multiple times on multiple displays in an application. When changes are made
to a global object, all instances in the application are automatically updated.

Global objects serve two purposes:


• Faceplate object files contain common elements that are used to build
faceplate displays.
• Graphics Library files contain device symbols that you can use to build
your application displays. Click the symbol to open the corresponding
faceplate display.

Standard display files, commonly called faceplates, provide a common user


interface.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 19


Chapter 1 Overview

Required Files Visualization files can be downloaded from the PCDC at http://
www.rockwellautomation.com/rockwellautomation/support/pcdc.page.

IMPORTANT The visualization file dependencies require Process


Library content imports to occur in a specific order:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros

The following table describes the visualization file types.


Table 1 - Visualization File Types
File Type FactoryTalk View SE FactoryTalk View Description
Abbreviatio ME
ns
Images All .png files in the images folder. Common icons
(.png) IMPORTANT: FactoryTalk View application that are used in the
renames PNG files when they are imported with a global objects and
.bmp file extension, but the files retain a .png standard displays
format. for all Process
Objects.
Global (RA-BAS) precedes name (RA-BAS-ME) Examples:
objects of the global object. precedes name of (RA-BAS)
(.ggfx) the global object. Common
Faceplate Objects
(RA-BAS-ME)
Common
Faceplate Objects
Standard (RA-BAS) precedes name (RA-BAS-ME) Examples:
displays of the display. precedes name of (RA-BAS) P_AIn-
(.gfx) the display. Faceplate
(RA-BAS-ME)
P_AIn-Faceplate

20 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Table 1 - Visualization File Types


File Type FactoryTalk View SE FactoryTalk View Description
Abbreviatio ME
ns
HMI tags FTViewSE_ProcessLibrary FTViewME_Proces HMI tags are
(.csv) _Tags_4_0_xx.csv sLibrary_Tags_4_0 created in a
where xx = the service _xx.csv FactoryTalk View
release number. where xx = the ME application to
service release support security,
number. tab control, and
other features on
Process Library
faceplates. HMI
tags can be
imported via the
comma-separated
values file (.csv
file type).
Macros NavToBuiltInCCFaceplate. Macros not used In a FactoryTalk
(.mcr file) mcr with FactoryTalk View SE
NavToBuiltInCCQuick.mcr View ME. application, a
NavToBuiltInIMCFaceplate macro is a series of
.mcr commands that are
stored in a text file.
NavToBuiltInIMCQuick.mc
r In a FactoryTalk
View ME
NavToBuiltInMMCFaceplat application, a
e.mcr macro is a list of
NavToBuiltInMMCQuick.m tag assignments
cr that are stored in a
NavToBuiltInPIDEFaceplat text file.
e.mcr
NavToBuiltInPIDEQuick.m
cr
NavToBuiltInRMPSFacepla
te.mcr
NavToBuiltInTotalizerFacep
late.mcr
NavToChildFaceplate.mcr
NavToFaceplate with line of
site.mcr*
NavToFaceplate.mcr
NavToP_LLS_Motor.mcr
NavToQuick with line of
site.mcr*
NavToQuick.mcr
* To restrict the operation of equipment based on line of site
requirements, rename the macros:
"NavToFaceplate with line of site.mcr" to "NavToFaceplate.mcr"
"NavToQuick with line of site.mcr" to "NavToQuick.mcr"

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 21


Chapter 1 Overview

Basic Attributes and This section shows examples of visual tools that are common for global objects
in the Rockwell Automation Library of Process Objects. Visual tools are
Indicators critical to the daily operation of a plant.

Common attributes of global objects typically include:


• Status/quality/threshold indicator
• Maintenance bypass indicator
• Engineering units
• Label
• Command Source indicator (only for non-analog inputs)
• Alarm border that changes color and blinks on unacknowledged alarm
• Alarm indicator symbol that changes with the severity of an alarm

1
2
3 7
4
5 8

Table 2 - Global Objects Description


Item Description
1 Alarm indicator
2 Alarm border
3 Command source indicator (In the example the flag indicates not in normal
command source)
4 Label
5 Process variable
6 Maintenance bypass indicator
7 Not Ready Indicator
8 Engineering units

Each graphic object includes a touch field over it that opens the faceplate. In
addition, there is a tooltip on the graphic symbol that displays the configured
tag and description.

22 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

State Indicators

The State Indicator text and the color change depending on the state of the
drive. The indicators and colors are common across all Add-On
Instructions.

Table 3 - State Indicator Colors


Color State
Dark gray Stopped
Light blue Starting
Light blue Jogging
Light blue Stopping
Light blue Horn
White Running

Status/Quality Indicators

One of these symbols appears on the graphic symbol when the described
condition is true.
Table 4 - Status/Quality Indicators
Graphic Symbol Description
No symbol that is I/O communication and quality good, configuration valid
displayed
Invalid configuration

Data quality bad/failure

Data Quality degraded: uncertain, test, simulation, substitution, or


out of specification

Device not ready to operate

The input or device has been disabled

Alarm Inhibit (Suppressed or Bypassed)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 23


Chapter 1 Overview

Table 4 - Status/Quality Indicators


Graphic Symbol Description
Device in loopback test

At target speed

Speed ref limited to the minimum / maximum

Value infinite or not a number

value is being held at last good value

Input Controlled Variable that is clamped to minimum / maximum

Output Controlled Variable that is clamped to minimum /


maximum

Accelerating

Decelerating

Value is being initialized

Value has not changed (stuck)

Value is being replaced

Input matches target

input does not match target

Auto loop mode

Manual loop mode

Cascade loop mode

24 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Table 4 - Status/Quality Indicators


Graphic Symbol Description
Motor not controllable

Process Variable within setpoint deadband (no control action


occurs)

Raise Process Variable output that is energized

Lower Process Variable output that is energized

TIP When the Invalid Configuration indicator appears, you


can find what configuration setting is invalid by following
the indicators. Click the graphic symbol to open the
faceplate. The Invalid Configuration indicator appears
next to the appropriate tab at the top of the faceplate to
guide you to the configuration error. Once you navigate to
the tab, the misconfiguration is flagged with this indicator.

Threshold Indicators

These indicators show that the process variable has exceeded a threshold.

Table 5 - Threshold Indicators


Graphic Description
Symbol
High-high threshold exceeded

High threshold exceeded

Low threshold exceeded

Low-low threshold exceeded

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 25


Chapter 1 Overview

Deviation Indicators

These indicators warn of exceeding the deviation limits.

Table 6 - Deviation Indicators


Graphic Description
Symbol
High-high deviation exceeded

High deviation exceeded

Low deviation exceeded

Low-low deviation exceeded

Command Source Indicators

The command source indicator displays by exception only. For example, if the
device is operating normally, there is not an indicator. If the device is out of
service (OoS), then the OoS indicator is displayed.

Command source indicators are not used for analog inputs.

Table 7 - Command Source Indicators


Graphic Description
Symbol
No Symbol Device is in normal command source operation
Device is out of service

Device is not in normal command source operation

Device is in program command source operation

Device is in program locked command source

Device is in maintenance command source operation

26 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Table 7 - Command Source Indicators


Graphic Description
Symbol
Device is in operator command source operation

Device is in external command source operation

Device is in operator locked command source operation

Device is in override command source operation

Device is in hand command source operation

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 27


Chapter 1 Overview

Maintenance Bypass Indicator

The maintenance bypass indicator appears to the right of the label to indicate
that a maintenance bypass has been activated. The Maintenance bypass
indicator appears when the Substitute PV function is enabled. A Maintenance-
entered value supersedes the ‘live’ process variable.
Table 8 - Maintenance Bypass Indicator
Graphic Symbol Description
A maintenance bypass is active

No symbol displayed No maintenance bypass is active

TIP When the Maintenance bypass indicator appears, you can


find what condition was bypassed by following the
indicators. Click the graphic symbol to open the faceplate.
The Maintenance bypass indicator appears next to the
appropriate tab at the top of the faceplate to guide you to
the bypass. Once you navigate to the tab, the bypassed
item is flagged with this indicator.

28 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Help Files

The help displays for the Library of Process Objects have been converted to
PDF documents. The PDF documents can be displayed from the FactoryTalk
View displays by clicking the Help button. The help files are downloaded as
part of the Library of Process Objects and are contained in the Documents
folder.

1. Copy the Help files to a folder accessible by the FactoryTalk View


clients.
In this example we have copied the files to
C:\Users\Rockwell\Desktop\HMI Help Files.
2. Open your project in FactoryTalk View Studio.
3. Open the Tags setting in the Folder Tree.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 29


Chapter 1 Overview

4. Click the RALibrary Folder and then Click RALibrary\HelpFilePath to


access the settings for the Help Files.

5. Type the path to the Help Files into the Initial Data Source Field and
click Accept.

6. Close the settings display.

30 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

7. Restart FactoryTalk View Studio for the settings to take effect.


8. The Help Files can now be accessed using the Help button on the HMI
Display.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 31


Chapter 1 Overview

Basic Faceplate Faceplates consist of tabs, and each tab consists of one or more pages. The
Operator (Home) tab is displayed when the faceplate is initially opened. The
Attributes faceplate provides the means for operators, maintenance personnel, engineers,
and others to interact with an instruction instance, which includes a view of its
status and values. Faceplates also manipulate an instruction through its
commands and settings. Click the appropriate icon on the left of the faceplate to
access a specific tab. This section provides an overview of the faceplate
attributes that are common across the objects. More details are supplied in the
individual section for each object.

Operator (Home) Tab

1 7
2

3
4

6 8

Table 9 - Operator Tab Description


Item Action
1 Click to open the operator tab.
2 Click to open the maintenance tab.
3 Click to open the trends tab.
4 Click to open the diagnostics tab.
5 Click to open the alarm tab.
6 Click to open the help file.

32 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Item Action
7 Click to reset and acknowledge all alarms.
8 Click to display more information (the button is only available if
Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A
tag is created for the P_LLS object that is given the alias P101_More. When
the more information button is pressed on the motor, it links to P101_More.
This will open the faceplate for the LLS object.
9 If the object is configured to have permissive and interlock objects (for
example, Cfg_HasPermObj (Fast or Slow) or Cfg_HasIntlkObj is true), the
permissive and interlock indication become buttons. These buttons open the
faceplates of the source objects that are used as a permissive or interlock.
Often this object is a P_Perm or P_Intlk object. If the object is not
configured in this way, the permissive or interlock symbols are indicators
only.
See Permissives with Bypass (P_Perm) on page 58
See Interlocks with First Out and Bypass (P_Intlk) on page 45

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 33


Chapter 1 Overview

Maintenance Tab

In the maintenance tab, there is a button for Advanced properties. There are
also page identifiers at the bottom if there are multiple configuration pages. See
the following diagram for common attributes of the maintenance tab.

Table 10 - Maintenance Tab Attributes


Item Action
1 Click to open the Advanced Properties.
2 Page identifiers. This example shows page 3.

34 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Advanced Properties

The advanced maintenance, engineering, HMI configuration, Diagnostics,


and Faults tabs for the objects are available in the advanced properties
faceplate. The advanced maintenance and engineering tabs have object-specific
configurations that are detailed for each object.

The HMI configuration tab has settings that are common to the objects. See
the following diagram for common attributes of the HMI configuration tab.

1 5
2 6

4
7
8
9

Table 11 - Common HMI Configuration Tab Attributes


Item Action
1 Click to open the HMI Configuration tab.
2 Click to open the engineering tab.
3 Click to open the Advanced Maintenance tab.
4 Type the device description to show on the faceplate title bar.
5 Click to open the diagnostics tab.
6 Click to open the faults tab.
7 Type the label to show on the graphic symbol.
8 Type the tag name to show on the faceplate and Tooltip.
IMPORTANT: Pause the mouse over this field to display a tool tip with the
configured Logix tag/path.
9 Type the Area name for security.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 35


Chapter 1 Overview

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. These problems can include specific reasons a device
is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.

Faults Tab

The faults tab contains specific reasons that the device is not ready.

36 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Trends Display

The Trends display shows trend charts of key device data over time. These
faceplate trends provide a quick view of current device performance to
supplement, but not replace, dedicated historical or live trend displays.

1 2 3 4 5 6 7

Table 12 - Trends Tab Description


Item Description
1 Click to view the oldest data available.
2 Click to move trend data back 2 minutes.
3 Click to move trend data back 1 minute.
4 Click to scroll new data.
5 Click to move trend data forward 1 minute.
6 Click to move trend data forward 2 minutes.
7 Click to move to the most current trend data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 37


Chapter 1 Overview

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page has an outline that changes color to show the current active alarm
status. See Common Alarm Block (P_Alarm) on page 66 for more
information.

Help Button

Press the help button on the faceplates to access help specific to that faceplate.
The help file is in .pdf format and opens in a separate window. See the
following example:

Figure 2 - Help Example

38 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

Quick Display A Quick Display provides means for operators to perform simple interactions
with an instruction that is instance based on a task. From the Quick Display,
Interaction click the Home button to navigate to the faceplate for full access for operation,
maintenance, and configuration. All other buttons function the same as on the
main faceplate. The following figures show examples of quick displays.

Figure 3 - P_ValveMP

Figure 4 - P_Dose

Figure 5 - P_PIDE

Figure 6 - P_PF755

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 39


Chapter 1 Overview

Using a Display Global objects are typically found in the global object file per instruction. For
example: (RA-BAS) P_AIn Graphics Library.ggfx.
Element
Follow these steps to use a global object.

1. Copy the global object from the global object file and paste it in the
display file.

2. In the display, right-click the global object and choose Global


ObjectParameter Values.

The Global Object Parameter Values dialog box appears.

40 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Overview Chapter 1

The global object parameters are as follows.


Paramete Required Description
r
#102 Y Object tag to point to the name of the associated object Add-
On Instruction in the controller.
#103 Y Path that is used for display navigation features to other
objects. Include program scope if tag is a program scope tag.
#120 N Additional parameter to pass to the display command to open
the faceplate. Typically used to define position for the
faceplate.
#121 N Additional parameter to pass to the display command to open
the faceplate. To define X and Y coordinates, separate
parameters so that #120 defines X and #121 defines Y. This
separation lets these same parameters be used in subsequent
display commands that originate from the faceplate.
#122 Y The following are the options for the global object display:
0 = Always show faceplate
1 = Show Quick Display for users without Maintenance
access (Code C)
2= Always show Quick Display

3. In the Value column, type the tag or value as specified in the


Description column.

TIP Click the ellipsis (...) to browse and select a tag.


Values for items that are not required can be left blank.

Figure 7 - Example Parameter Values Dialog Box

4. Click OK.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 41


Chapter 1 Overview

Notes:

42 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 2

Cross Functional Family

The process objects in this group are often used to extend the functionality of
other objects. However, they can also be used as standalone objects when
necessary to implement a desired control scheme. This document is for the
visualization files, display elements, global objects, and HMI information. The
operation of the Add-on Instructions and controller code is contained in
publication PROCES-RM013.

Condition Gate Delay The P_Gate (Condition Gate Delay) Add-On Instruction provides a ‘gate’ for
a discrete signal and provides on-delay and off-delay timing for the gated signal.
(P_Gate)
P_Gate is used within P_DIn, all Analog inputs, and P_PIDE for threshold
and target disagree status processing.

When the gate input is true, the input is passed through to the output with
on-delay and off-delay timing applied. When the gate input is false, the output
is kept off (the off-delay still applies).

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

The P_Gate instruction is used within other device instructions to provide


status and alarm timing functions. There are no dedicated display elements for
this instruction. The faceplate is called from the containing instruction
faceplate.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 43


Chapter 2 Cross Functional Family

Faceplate

From the faceplate, an operator can monitor the device status.

The Operator tab shows the following information:


• Indicators that show the current Input Value and Output Status
• Gate Input status indicator

The following figure shows the P_Gate faceplate.

4
5

Table 13 - Operator Tab Description


Item Description
1 Type the text for the gate condition.
2 Type the text for the input condition.
This text appears on the Maintenance tab of the faceplate from which the P_Gate
faceplate is opened.
3 Type the amount of time (in seconds) the gate input must be turned on for status
outputs to be enabled.
4 Type the minimum time (in seconds) the input must be true to set the status.
On-delay times are typically used to avoid an unnecessary status indication or
alarm when a value briefly overshoots its threshold.
5 Type the amount of time (in seconds) the input must be clear in the status. Off
delay times are typically used to reduce chattering status indicators or alarms.

44 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Interlocks with First The P_Intlk (Interlocks with First Out and Bypass) Add-On Instruction is
used to collect (sum up) the interlock conditions that stop or de-energize a
Out and Bypass running or energized piece of equipment. This Add-On Instruction can also
(P_Intlk) help prevent it from starting or being energized. Interlocks are always evaluated
to de-energize equipment. For permissive conditions that must be made to
start the equipment, but are ignored once the equipment is running, use the
Permissives (P_Perm) Add-On Instruction.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix® system, aid consistency and save engineering time.

Table 14 - P_Intlk Display Element Description


Display Element Name Display Element Description
GO_P_Intlk Standard Interlock Global Object.

Graphic symbols are provided for use on end-user process graphic displays.
Interlock graphic symbols have the following common attributes.

1 2

Table 15 - P_Intlk Graphic Symbol Description


Item Description
1 Status Indicator
2 Bypass Indicator

The Interlock graphic symbol displays the current summary state of the
interlocks and whether the interlocks are bypassed.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 45


Chapter 2 Cross Functional Family

Table 16 - Interlock States


Item Description
Not ready to run or energize. One or more interlock
conditions are not OK

Ready to run or energize. One or more conditions that


can be bypassed are not OK, but these conditions are
bypassed. All conditions that cannot be bypassed are OK.

Ready to run or energize. All interlock conditions are


OK.

Ready to run or energize, and all interlock conditions are


OK, conditions that can be bypassed are being bypassed
and the equipment is not shut down.

The overall graphic symbol includes a touch field that opens the faceplate. In
the SE version of the library, pause the pointing device over the graphic symbol
to display a tooltip that describes the function of the symbol.

46 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Operator Tab

The Faceplate initially opens to the Operator (Home) Tab. From here, an
operator can monitor the device status.

The Operator tab shows the following information:


• Interlock bypass status indicator (Enabled, Bypassed)
• Each configured interlock along with the current state of the interlock

If navigation is enabled, click a condition to open the faceplate of the object


that is associated with the condition.

The following figure shows the Operator tab in a non-bypassed condition with
no faults.

The following figure shows the Operator tab in a non-bypassed condition with
a failure.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 47


Chapter 2 Cross Functional Family

The following figure shows the Operator tab with a failure that is in a bypassed
condition.

48 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Maintenance Tab

The maintenance tab is used to enable bypass of the interlocks that can be
bypassed.

IMPORTANT Only interlocks with white checkboxes can be


individually bypassed. These interlocks are
configured using the 'Can Bypass' column on the
engineering tab.

The following table lists the functions on the Maintenance tab.

Table 17 - Maintenance Tab Descriptions


Item Description
1 Click an interlock condition that can be bypassed, one that has a white
checkbox, to enable bypass of that individual interlock.
See HMI Configuration Tab on page 51 for information on how to
make interlock conditions active.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 49


Chapter 2 Cross Functional Family

Advanced Properties Display

Click the Advanced Properties button to display the engineering and HMI
configuration tabs. The Advanced Properties Display provides access to device
configuration parameters and ranges, and options for device and I/O setup.
The engineering tab and the HMI configuration tab can be reached from the
Advanced Properties Display. This tab is used for initial system commissioning
or later system changes.

Engineering Tab

Up to 16 interlock inputs can be configured.

1 4

The following table lists the functions of the engineering tab.

Table 18 - Engineering Tab Description


Item Description
1 Selects the state of the corresponding interlock that is the OK to Run state.
2 Type the text description of each interlock condition used. Only the interlocks
with text entered appear on the Operator tab of the faceplate.
3 Check to indicate that the corresponding interlock can be bypassed.
4 Check to indicate that the corresponding interlock is latched and must be reset.

50 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.
Navigation for the 16 interlock inputs is configured across each of the HMI
configuration pages. On the third page there is an option to enable navigation
to an object with more information.

1
2

Table 19 - HMI Configuration Tab Page 1 Description


Item Description
1 Check to enable navigation for the corresponding interlock input object.
2 Type the name of the tag to navigate to when the interlock description on the
Operator tab is clicked.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 51


Chapter 2 Cross Functional Family

Table 20 - HMI Configuration Tab Page3 Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

52 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Interlocks with First The P_IntlkAdv (Interlocks with First Out and Bypass - Advanced) Add-On
Instruction has many of the same properties and the P_Intlk Add-On
Out and Bypass - Instruction.
Advanced
(P_IntlkAdv) The first page of the HMI Configuration Tab is changed to define the types of
interlocks that are available. The fourth page has an option to enable
navigation to an object with more information. The Engineering tab contains
an additional field to provide the type of interlock for each condition. See
Interlocks with First Out and Bypass (P_Intlk) on page 45 for additional
information that is related to this Add-On Instruction.

Operator Tab
The Operator (Home) Tab shows the interlock types that are defined on the
Engineering Tab.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 53


Chapter 2 Cross Functional Family

Maintenance Tab

The maintenance tab is used to enable bypass of the interlocks that can be
bypassed.

IMPORTANT Only interlocks with white checkboxes can be


individually bypassed. These interlocks are
configured using the 'Can Bypass' column on the
engineering tab.

54 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

HMI Configuration Tab

Table 21 - HMI Configuration Tab Page 1 Description


Item Description
1 Check to enable the interlock type that can be defined in the Engineering tab.
There are eight types that are configurable. The first three letters define the
short name type followed by ‘:’ and then the full type description.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 55


Chapter 2 Cross Functional Family

Table 22 - HMI Configuration Tab Page 4 Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

56 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Engineering Tab

Table 23 - Engineering Tab Page 1 Description


Item Description
1 Click to define the interlock type. The display opens to select an available
interlock type that was defined in the HMI Configuration.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 57


Chapter 2 Cross Functional Family

Permissives with The P_Perm (Permissives with bypass) Add-On Instruction is used to collect
(sum up) the permissive conditions that allow a piece of equipment to start
Bypass (P_Perm) (run, energize, open, and so forth). Permissive conditions generally must be
true to start the equipment. Once the equipment is running, permissives are
ignored. Use the P_Intlk (Interlocks) Add-On Instruction to collect
conditions that stop equipment that is running and help prevent it from
starting.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 24 - P_Perm Display Element Description


Display Element Name Display Element Description
GO_P_Perm Standard Permissive Global
Object.

Graphic symbols are provided for use on end-user process graphic displays.
Permissives graphic symbols have the following common attributes.

1 2

Table 25 - P_Perm Graphic Symbol Description


Item Description
1 Status Indicator
2 Bypass Indicator

The Permissives graphic symbol displays the current summary state of the
permissives and whether permissives are bypassed.

58 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Table 26 - Permissive States


Item Description
Not ready to run or energize. One or more interlock
conditions are not OK

Ready to run or energize. One or more conditions that


can be bypassed are not OK, but these conditions are
bypassed. All conditions that cannot be bypassed are OK.

Ready to run or energize. All interlock conditions are


OK.

Ready to run or energize, and all interlock conditions are


OK, conditions that can be bypassed are being bypassed
and the equipment is not shut down.

The overall graphic symbol includes a touch field over it that opens the
faceplate. In addition, pause the mouse over the graphic symbol to display a
tooltip that describes the function of the symbol.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 59


Chapter 2 Cross Functional Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status.

The Operator tab shows the following information:


• Permissive bypass status indicator (Enabled, Bypassed)
• Each configured permissive along with the current state of the
permissive

If navigation is enabled, click the condition to open the faceplate of the object
that is associated with the condition.

60 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters. They also troubleshoot and temporarily work
around device problems, and disable the device for routine maintenance.

IMPORTANT Only interlocks with white checkboxes can be


individually bypassed. These interlocks are
configured by using the 'Can Bypass' column on the
engineering tab.

The following table lists the functions on the Maintenance tab.

Table 27 - Maintenance Tab Description

Item Description
1 Click an active permissive, one that has a white checkbox, to enable
bypass of that individual permissive.
See HMI Configuration Tab on page 63 for information on how to
make permissive conditions active.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 61


Chapter 2 Cross Functional Family

Advanced Properties Display

Click the Advanced Properties button to display the engineering and HMI
configuration tabs. The Advanced Properties Display provides access to device
configuration parameters and ranges, and options for device and I/O setup.
The engineering tab and the HMI configuration tab can be reached from the
Advanced Properties Display. This tab is used for initial system commissioning
or later system changes.

Engineering Tab

1 3

The following table lists the functions of the engineering tab.

Table 28 - Engineering Tab Description


Item Description
1 Selects the state of the corresponding permissive that is the OK to Run state.
2 Type the text description of each permissive condition used. Only the
permissives with text entered appear on the Operator tab of the faceplate.
3 Check to indicate that the corresponding permissive can be bypassed.

62 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.
Navigation for the 16 permissive inputs is configured across each of the HMI
configuration tabs. On page 3 there is an option to enable navigation to an
object with more information.

1
2

Table 29 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation for the corresponding permissive input object.
2 Type the name of the tag to navigate to when the permissive description on the
Operator tab is clicked.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 63


Chapter 2 Cross Functional Family

Item Description
3 Check to enable navigation to an object with more information.

64 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Central Reset The P_Reset (Central Reset) Add-On Instruction provides a central point to
reset equipment faults. Latched alarms can be reset for a control strategy.
(P_Reset)
This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Graphic Symbols

The following table describes the graphic symbols of the P_Reset.

Table 30 - Graphic Symbols Description

Button Description
The same as the reset buttons used in other Process Library
Faceplates and screens and is for use on end-user process graphic
displays.

The reset button is inactive.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 65


Chapter 2 Cross Functional Family

Common Alarm Block The P_Alarm (Common Alarm Block) Add-On Instruction is used to provide
notification to operators of abnormal conditions or events. This instruction
(P_Alarm) handles alarm acknowledgment, alarm reset, alarm shelving/disabling, and
alarm suppression (for FactoryTalk® Alarms and Events). This instruction
excludes display elements.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Alarm Indicators

One of these symbols appears on the left of the label to indicate the described
alarm condition. The alarm border blinks if acknowledgment of an alarm
condition is required. Once the alarm is acknowledged, the alarm border
remains the color that corresponds to the severity of the alarm and the alarm
symbol is still present.

Table 31 - Alarm Indicators Description


Symbol Border Color Description
Red Urgent-severity alarm

Orange High-severity alarm

Yellow Medium-severity alarm

Magenta Low-severity alarm

White Return to normal (no alarm condition), but a


previous alarm has not been acknowledged

66 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Alarm indicators appear on the Home tab when the corresponding alarm
occurs. The alarm indicator appears in the top banner along with the matching
color border. The colored border blinks when an alarm is identified. The
Alarm tab also has a border with the alarm color when an alarm is identified.
The following diagram provides an example of a PV High alarm on an analog
input device.

2
5

Table 32 - Alarm Identifiers Description


Item Description
1 PV High Alarm Identified
2 Alarm Border Colored
3 Alarm Tab
4 Alarm Tab Border Colored
5 High limit on display has changed to the alarm color to show that the threshold
limit has been exceeded

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 67


Chapter 2 Cross Functional Family

Alarm Tab

The Alarms tab displays each configured alarm for the P_ instruction. The
alarm border blinks if acknowledgment of an alarm condition is required. Once
the alarm is acknowledged, the alarm border remains the color that corresponds
to the severity of the alarm and the alarm symbol is still present.

When the Reset and Acknowledge All Alarms button is enabled, the border
the alarm name blinks. This blinking indicates that the alarm requires
acknowledgment or reset. The Alarm Acknowledge button is enabled if the
alarm requires acknowledgment.

Table 33 - Alarm Tab Description


Item Description
1 Alarm Description
2 Click to reset and acknowledge all alarms.

68 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Alarm Operator Tab

Click the alarm name to open the operator tab for that alarm.

3
1

4
2

Table 34 - Alarm Operator Tab Description


Item Description
1 Alarm status
2 Individual status information indicators
3 Acknowledge Alarm. This command acknowledges an alarm that has been
configured with “Ack Required”.
4 Reset Alarm
5 Unshelve alarm
6 Shelve alarm

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 69


Chapter 2 Cross Functional Family

Alarm Maintenance Tab

Click the alarm box to open the maintenance tab. From this tab, you can test
the alarm, disable the alarm, and set the severity level of the alarm.

Alarms Advanced Settings

Click the advanced properties button for more options.

The advanced properties include both an engineering tab and an HMI


configuration tab. The HMI configuration tab is used to configure the name of
the alarm. The engineering tab sets the parameters for the alarm.

70 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Command Source The P_CmdSrc (Command Source) Add-On Instruction is used to provide
selection of the command source (owner) of an instruction or control strategy.
(P_CmdSrc) This instruction excludes display elements.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

The command source indicator displays by exception only. For example, if the
device is operating normally, there is not an indicator. If the device is out of
service (OoS), then the OoS indicator is displayed.

Command source indicators are not used for analog inputs.


Table 35 - Command Source Indicators
Graphic Description
Symbol
No Symbol Device is in normal command source operation
Device is out of service

Device is not in normal command source operation

Device is in program command source operation

Device is in maintenance command source operation

Device is in operator command source operation

Device is in override command source operation

Device is in local command source operation

Device is in external command source operation

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 71


Chapter 2 Cross Functional Family

Command Source Totem Pole

The Command Source Totem Pole shows the sources that have been requested.
These sources have a white background color. The leftmost source that is
highlighted is the active command source.

In the example that follows, the current command source is Operator Locked.
When Operator Locked is released, the default command source is Operator.
The small black triangle, in the upper left corner of the operator indicator
indicates the normal command source.

Operator Buttons

The Operator Lock buttons on device faceplates are used to lock and unlock
Operator command source. The buttons also show the current command
source status.

Table 36 - Operator Buttons Description


Graphic Description
Symbol
Click to request Operator command source.

Click to lock in Operator command source. The program cannot take


control.

Click to request Program command source.

72 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

External Control

There is a slider on the operator page that allows the operator to place the
device in External Control.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 73


Chapter 2 Cross Functional Family

Maintenance Buttons

The maintenance buttons on device faceplates are used to request and release
Maintenance command source.

Table 37 - Maintenance Buttons Description


Graphic Description
Symbol
Click to acquire Maintenance command source.

Click to release Maintenance command source.

Click to display Advanced Properties command source.

74 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Advanced Properties

Click the Advanced Properties button from the maintenance page to access the
engineering tabs. There are three engineering tabs. The first page is the
configuration for the Cfg_ProgDefault parameter for the object, which sets the
default command source when no command source is being requested.

From the other pages, you can configure the settings for additional command
sources.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 75


Chapter 2 Cross Functional Family

Operator Prompt The P_Prompt (Operator Prompt) Add-On Instruction is a universal


mechanism for operator interaction that can be used within a control scheme.
(P_Prompt) The instruction presents an operator with configurable message or data fields
and accepts operator response data and confirmation. This instruction excludes
display elements.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Graphic Symbols

The following table describes the graphic symbols of the P_Prompt.

Table 38 - Graphic Symbols Description


Graphic Symbol Description
Standalone prompt button that assumes
the P_Prompt instruction is present and
the button is always visible. The Prompt
instruction controls the enabled state and
alert indicator visibility of the button.

Prompt display indicator for use on


faceplates and displays for objects that
possibly do not have a prompt instruction.

76 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Faceplates

The P_Prompt instruction has three faceplates: Selection, Configuration, and


Response.

Selection Faceplate

The Prompt Selection display provides access to the configuration dialog box
for a given prompt configuration in the prompts array by clicking the
corresponding browse button.

1
2

Table 39 - Selection Faceplate Description


Item Description
1 Click the radio button to select a prompt.
2 Click to open the configuration faceplate.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 77


Chapter 2 Cross Functional Family

Configuration Faceplate

The Prompt Configuration dialog box has four sections to configure a prompt.
The sections are Display Values, Input Values, Selection Options, and
Response Prompts.

Figure 8 - Display Values


2 3 4 5 6 7

Table 40 - Display Values Description


Item Description
1 Check to enable a label text field.
2 Type a label.
3 Type an engineering unit.
4 Type the decimal places to display.
5 Check to either display a value from the prompt 'AOI Input' or the value that
you enter in the box that appears.
6 Check to scale the value by the entered value and the Inp_ScalePct.
7 Check to require the operator to verify the displayed value.

78 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Figure 9 - Input Values

2 3 4 5 6 7 8

Table 41 - Input Values Description


Item Description
1 Check to enable a label text box.
2 Type a label for the input value.
3 Type an engineering unit.
4 Type the decimal places to display.
5 Type a minimum value for the entry
6 Type a maximum value for the entry.
7 Check to require an operator to enter a value.
8 If an input is not required, click Minimum or Maximum to be used for the
entry.

Figure 10 - Selection Options


2 3

Table 42 - Selection Options Description


Item Description
1 Check to enable a label text box.
2 Check and type a label for the selection option.
3 Click to designate a selection as the default.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 79


Chapter 2 Cross Functional Family

Figure 11 - Response Prompts

2 3

Table 43 - Response Prompts Description


Item Description
1 Check to enable a label text box.
2 Check and type a label for the response prompt.
3 Check to require an input.

Response Faceplate

This faceplate lets the operator review and record data based on the prompt.
All values are configured on the prompt configuration faceplate. The operator
clicks the checkbox to continue.

80 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Boolean Logic with The P_Logic (Boolean Logic with Snapshot) Add-On Instruction executes up
to eight gates of configurable Boolean logic. Gate types available include AND,
Snapshot (P_Logic) OR, XOR (Exclusive-OR), Set/Reset, Select, and Majority. Each gate provides
up to four input conditions that are individually invertible. (The P_Logic
instruction does not need a NOT gate.)

The P_Logic Add-On Instruction also provides a snapshot capability. This


capability enables it to record its current state with an optional time stamp.
This snapshot can be taken upon change in output state, on Operator or
Program command, or based on a logic loopback input.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

The P_Logic Instruction has display elements (global objects) for use on
process graphic displays. These elements provide you with the following:
• Information on the current state of the object
• Touch field to open the faceplate of the object
• Tooltip to display the configured tag and description of the object

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 81


Chapter 2 Cross Functional Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device.

The Operator tab shows the following information:


• The eight Boolean inputs and eight logic gates, with each gate having a
maximum of four sources.
• Configurable operator snapshot command button creates an image of
the logic.
• Provides a progress indicator for the on-delay time and off-delay time for
the output of the instruction. See Maintenance Tab on page 84 for
On-delay and off-delay configuration.
1 2 3

The following table describes the functions included on the Operator tab.
Table 44 - Operator Tab Description
Item Description
1 Input Name: Click to navigate to the Input object faceplate.
2 Gates: Click one of the gates to access the Gate Configuration display for that
gate.
3 Click to take a snapshot of the current state.
IMPORTANT: When you take a snapshot, the View Snapshot tab is
automatically displayed.

82 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

View Snapshot Tab

The View Snapshot tab shows an image of the Operator faceplate when the
snapshot was taken. The background of the display turns from gray to white to
indicate capture. The View Snapshot has the same functionality as the operator
faceplate plus a Reset button.
1

2 3

Table 45 - View Snapshot Tab Description

Item Description
1 Click to reset the snapshot function so that another snapshot can be triggered.
IMPORTANT: If ‘Allow a new snapshot to overwrite an existing snapshot
without a snapshot reset' is checked on the maintenance tab, a reset is not
required trigger another snapshot.
2 Time stamp
3 Identifies how the snapshot was triggered.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 83


Chapter 2 Cross Functional Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters. They also troubleshoot and temporarily work
around device problems, and disable the device for routine maintenance.

1 2 3

Table 46 - Maintenance Tab Description


Item Description
1 Type a value for the off-delay time and the on-delay time.
2 Check to allow a new snapshot to be triggered without a reset of the previous
snapshot.
3 Check to generate a time stamp whenever a snapshot triggers.
4 Check to trigger a snapshot when the designated condition is met.

84 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Advanced Properties Display

Click the Advanced Properties button to display the engineering and HMI
configuration tabs. The Advanced Properties Display provides access to device
configuration parameters and ranges, and options for device and I/O setup.
The engineering tab and the HMI configuration tab can be reached from the
Advanced Properties Display. This tab is used for initial system commissioning
or later system changes.

Engineering Tab

Table 47 - Engineering Tab Description


Item Description
1 Click to open the faceplate to select the output source. See Output Source on
page 86
2 Check to invert the selected output before it is passed to the output delay
timers
3 Click to open the Gate Configuration faceplate.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 85


Chapter 2 Cross Functional Family

Figure 12 - Output Source

86 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Gate Configuration Display

The gate configuration display appears if a gate is clicked in the Operator, View
Snapshot, or Engineering tabs.
3 4 5

Table 48 - Gate Configuration Display Description


Item Description
1 Displays the gate being configured.
2 Check to select which inputs of the gate are enabled (1…4).
3 Click to select the inputs for the gate. See Gate Input Source on page 87
4 Check to invert the source that enters the gate.
5 Check to select a gate type.

Figure 13 - Gate Input Source

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 87


Chapter 2 Cross Functional Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.
The tab is separated into three pages. Page 1 contains the common information
and name conventions. Page 2 and three allow for navigation to the objects.

Table 49 - HMI Configuration Page 1 Description


Item Description
1 Type the text to display on the faceplate when output = 0 or 1
2 Type a description for each input.

88 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Cross Functional Family Chapter 2

Table 50 - HMI Configuration Page 2 Description


Item Description
1 Check to enable navigation to input object.
2 Type the tag name of the input object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 89


Chapter 2 Cross Functional Family

Table 51 - HMI Configuration Page 3 Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

90 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 3

I/O Processing Family

The Process Objects in this group provide analog and discrete input/output
signal processing. Pressure/temperature compensated flow calculations and
cylindrical tank level interpolations are also provided. This document is for the
visualization files, display elements, global objects, and HMI information. The
operation of the Add-on Instructions and controller code is contained in
publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated.

Use of global objects with tag structures in the ControlLogix® system aid
consistency and save engineering time.

The items in Table 52 are common to the following Add-On Instructions.


• Basic Analog Input (P_AIn)
• Advanced Analog Input (P_AInAdv)
• Dual Sensor Analog Input (P_AInDual)
• Multiple Analog Input (P_AInMulti)

If additional display elements are used, they are documented in the appropriate
section.
Table 52 - I/O Common Display Elements Descriptions
Name Display Element Description
GO_P_AIn Standard analog-input
global object.

GO_P_AIn_Trend Analog input with a trend


of the Process Variable and
limits (high-high, high,
low, and low-low).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 91


Chapter 3 I/O Processing Family

Table 52 - I/O Common Display Elements Descriptions


Name Display Element Description
GO_P_AIn_TrendWCaptur Analog Input with Trend of
e Process Variable and limits
(high-high, high, low, and
low-low) plus a light gray
capture area.

GO_P_AIn_Indicator Process Variable indicated


by a moving triangle. The
graphic display includes
limits that are displayed
with filled bars.

GO_P_AIn_IndicatorWCa This object is the same as


pture the GO_P_Ain_Indicator
plus a light gray minimum/
maximum capture area.

GO_P_AInX Process Variable that is


displayed as a bar graph.
The graphic display
includes limits that are
displayed as lines on the
graph.

92 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all I/O Processing Add-On Instructions. For basic trends tab
functionality, See Trends Display on page 37.

5
3

Table 53 - Trends Tab Description


Item Description
1 High-high threshold value.
2 Process Variable (%) value.
3 Low-low threshold value.
4 High threshold value.
5 Low threshold value.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 93


Chapter 3 I/O Processing Family

Basic Analog Input The P_AIn Add-On Instruction monitors one analog value, typically from a
channel of an analog input module, and provides alarms when the analog value
(P_AIn) exceeds user-specified thresholds (high and low).

The Analog Input instruction also provides capabilities for linear scaling of an
analog input value from raw (input) units to engineering (output) units. The
instruction can enter a substitute process variable, providing handling of an
out-of-range or faulted input.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Operator (Home) Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device.

2
3

1 5
6

The following table describes the functions included on the Home tab.
Table 54 - Operator Tab Description
Item Description
1 Current Process Variable Graph: Bar graph for the current Process Variable.
High-high (HH) and low-low (LL) ranges are shown in dark gray and these
ranges change colors based on alarm severity if the threshold is exceeded.
High and Low ranges are shown in medium gray, and these ranges also change
color based on alarm severity.
2 High-high Thresholds
3 High Threshold
4 Current Process Variable that is shown as an arrow on the graph and
numerically.
5 Low Thresholds
6 Low-low Thresholds
7 Clear capture minimum / maximum extents

94 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance.

5
1

6
3

IMPORTANT Click a threshold name to open the P_Gate


faceplate. From the P_Gate faceplate, you can
configure and perform additional operations for
each alarm, including Gate Delay, Status On-delay,
Status Off-delay, and Threshold Name.

The following table shows the functions on the Maintenance tabs.


Table 55 - Maintenance Tab Page 1 Description
Item Description
1 Click this button to open the advanced properties. The engineering and HMI
configuration settings become available.
2 Threshold Name: Click a threshold name to open the associated P_Gate
faceplate.
3 Page Identifier
4 Use Substitute PV: Click to input a substitute process variable.
5 Type the threshold (trip point) for analog input alarms.
6 Type the deadband (hysteresis) that applies to each alarm limit. Deadband
helps prevent a noisy signal from generating numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 95


Chapter 3 I/O Processing Family

Table 56 - Maintenance Tab Page 2 Description


Item Description
1 Threshold Name: Click a threshold name to open the associated P_Gate
faceplate.
2 Type the threshold (trip point) minimum / maximum
3 Process variable fail deadband. Type the deadband (hysteresis) that is applied
to each alarm limit. Deadband helps prevent a noisy signal from generating
numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.

96 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Engineering Tab

In the engineering settings, you can configure the Process Variable unit for the
device.

1 4

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 97


Chapter 3 I/O Processing Family

The following table lists the functions on the engineering tab.


Table 57 - Engineering Tab Description
Item Description
1 Input (unscaled) minimum and maximum
These parameters must be set to the range of the signal that is connected to the
Inp_Process Variable Input. The raw minimum default is 0.0 and the raw
maximum default is 100.0.
Example: If your input card provides a signal from 4.0…20.0mA, set
Cfg_InpRawMin to 4.0 and Cfg_InpRawMax to 20.0. The raw minimum/
maximum and engineering units minimum/maximum are used for scaling to
engineering units.
2 Check to allow the Substitute Process Variable Maintenance function.
Clear this checkbox to disallow the Substitute Process Variable Maintenance
function (default).
3 PV Source and Quality
Generate SrcQ: This instruction determines the Process Variable quality using
Inp_PVBad, Inp_PVUncertain, and the PV value (out of range, infinite or not a
number)

Pass thru connected Channel’s SrcQ value: This instruction uses the Source
and Quality (SrcQ) value that is provided by an upstream object (such as
P_AIChan) via Inp_PVSrcQ to determine the PV source and quality.
4 EU minimum and maximum for scaling
These parameters must be set to match the Process Variable range of the input
signal that is connected to Inp_PV. The Process Variable engineering units
minimum default is 0.0 and the Process Variable engineering units maximum is
100.0.
Example: If your input card provides a signal from 4…20 mA that represents -
50…+250 °C, set Cfg_PVEUMIN to -50.0 and Cfg_PVEU maximum to 250.0.
The raw minimum/maximum and Process Variable engineering units minimum/
maximum are used for scaling to engineering units.
5 Type engineering units for display on the HMI. Percent (%) is the default.
6 Type the Process Variable filter time constant.
If the time constant is 0, the Process Variable is unfiltered.

98 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. See Basic Faceplate Attributes on
page 32 for the description of the common attributes.

Table 58 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation to an upstream channel object (for example, P_).
IMPORTANT: The name of the Channel object in the controller must be the
name of the object with the suffix ‘_Chan’. For example, if your P_AIn object
has the name ’AIn123’, then its Channel object must be named ‘AIn123_Chan’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that has
HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag is
created for the P_LLS object that is given the alias P101_More. When the more
information button is pressed on the motor, it links to P101_More. This will
open the faceplate for the LLS object.
3 Set the number of decimal places for the Process Variable.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 99


Chapter 3 I/O Processing Family

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data. The initial faceplate shows the raw input process
variable.

Click the raw input button to open the analog channel quality faceplate. This
tab provides an overview of the process variable. For more information on the
analog channel faceplate, See Analog Input Channel (P_AIChan) on page 110.

Alarms Tab
The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

100 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Analog The P_AInAdv Add-On Instruction monitors one analog value, typically from
an Analog Input I/O module. The Add-On Instruction has the same basic
Input (P_AInAdv) features as P_AIn. See Basic Analog Input (P_AIn) on page 94. This
instruction has the following advanced features that are not included in the
basic analog input:
• Square root scaling to provide positive or negative flow values
• Calculation of the Process Variable rate of change and configurable high
rate of change alarming
• Alarms for deviation from a reference value

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures, aid
consistency and save engineering time.
Table 59 - P_AInAdv Display Elements Description
Display Element Name Display Element Description
GO_P_AInAdv_Indicator A moving triangle indicates
the process variable. The
graphic display includes
limits that are displayed with
filled bars plus a cyan target
range (for deviations).

GO_P_AInAdvTrend This graphic symbol


includes a trend with target
lines and is intended to be
used for the Advanced
Analog Input
Add-On Instruction.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 101


Chapter 3 I/O Processing Family

Table 59 - P_AInAdv Display Elements Description


Display Element Name Display Element Description
GO_AInAdv_IndicatorWC A moving triangle indicates
apture the process variable. The
graphic display includes
limits that are displayed with
filled bars plus a cyan target
range (for deviations) and a
light gray minimum/
maximum capture area.

102 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device. The
home page contains the same basic information as the P_AIn Add-On
Instruction. See Basic Analog Input (P_AIn) on page 94. Additional
information is identified in the following diagram.

5
1
6

7
8
2
9
3
1
4

Table 60 - P_AInAdv Home Tab Description


Item Description
1 High Deviation limit: the label background that changes color based on alarm
severity when exceeded.
2 Low Deviation limit: the label background that changes color based on alarm
severity when exceeded.
3 The rate of change bar graph (visible if Rate of Change calculations is enabled
on the engineering tab).
4 The rate of change value (visible if Rate of Change calculations is enabled on
the engineering tab).
5 Control High-High limit
6 Control High limit
7 Process Variable target.
8 Control Low limit
9 Control Low-Low limit
10 Reset Rate of Change value to zero.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 103


Chapter 3 I/O Processing Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems. The maintenance tab for the P_AInAdv Add-On Instruction
has three pages. The first page contains the threshold and deadband
information and is the same as the P_AIn Add-On Instruction. See Basic
Analog Input (P_AIn) on page 94. Additional information for this instruction
is on pages two … four and can be seen in the following diagrams.

Table 61 - Maintenance Tab Page 2 Description


Item Description
1 Process variable high/low deviation threshold. Type the threshold (trip point)
for analog input alarms.
2 Process variable high/low deviation deadband. Type the deadband (hysteresis)
that is applied to each alarm limit. Deadband helps prevent a noisy signal from
generating numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.
3 Process variable fail deadband. Type the deadband (hysteresis) that is applied
to each alarm limit. Deadband helps prevent a noisy signal from generating
numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.
4 Process variable fail threshold in raw units.

104 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 62 - Maintenance Tab Page 3 Description

Item Description
1 Process variable high rate of change threshold. Type the threshold (trip point)
for the rate of change alarm.
2 Process variable high rate of change deadband. Type the deadband (hysteresis)
that is applied to each alarm limit. Deadband helps prevent a noisy signal from
generating numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.

Table 63 - Maintenance Tab Page 4 Description


Item Description
1 Type the deadband (hysteresis) that is applied to each Control Limit.
2 Type the threshold (trip point) for the Control Limit.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 105


Chapter 3 I/O Processing Family

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The engineering
tab and the HMI configuration tab are reached from the Advanced Properties
Display. This tab is used for initial system commissioning or later system
changes.

Engineering Tab

Use the engineering tab to configure the Process Variable unit for the device.

1
6

3
4

Table 64 - Engineering Tab Page 1 Description


Item Description
1 Input (unscaled) minimum and maximum
These parameters must be set to the range of the signal that is connected to the
Inp_Process Variable Input. The raw minimum default is 0.0 and the raw
maximum default is 100.0.
Example: If your input card provides a signal from 4.0…20.0mA, set
Cfg_InpRawMin to 4.0 and Cfg_InpRawMax to 20.0. The raw minimum/
maximum and engineering units minimum/maximum are used for scaling to
engineering units.
2 Check to allow the Substitute Process Variable Maintenance function.
Clear this checkbox to disallow the Substitute Process Variable Maintenance
function (default).
3 Check to use the square root characterization for a differential pressure input to
read flow.
Clear this checkbox (default) to use linear scaling.
4 Check to enable target entry, deviation calculations, display, and alarms.

106 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 64 - Engineering Tab Page 1 Description


Item Description
5 Check to enable Rate of Change calculations, display, and alarms.
6 EU minimum and maximum for scaling
These parameters must be set to match the Process Variable range of the input
signal that is connected to Inp_PV. The Process Variable engineering units
minimum default is 0.0 and the Process Variable engineering units maximum is
100.0.
Example: If your input card provides a signal from 4…20 mA that represents -
50…+250 °C, set Cfg_PVEUMIN to -50.0 and Cfg_PVEU maximum to 250.0.
The raw minimum/maximum and Process Variable engineering units minimum/
maximum are used for scaling to engineering units.
7 Type engineering units for display on the HMI.

Table 65 - Engineering Tab Page 2 Description


Item Description
1 PV Source and Quality
Generate SrcQ: This instruction determines the Process Variable quality using
Inp_PVBad, Inp_PVUncertain, and the PV value (out of range, infinite or not a
number)

Pass thru connected Channel’s SrcQ value: This instruction uses the Source
and Quality (SrcQ) value that is provided by an upstream object (such as
P_AIChan) via Inp_PVSrcQ to determine the PV source and quality.
2 Check the appropriate time base for seconds, minutes, or hours.
3 Type the time in seconds for the process variable filter time constant.
4 Process variable rate of change time base in units.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 107


Chapter 3 I/O Processing Family

HMI Configuration Tab

See Basic Faceplate Attributes on page 32 for the description of the common
attributes.

3
1
2

Table 66 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation to an upstream channel object (for example,
P_AIChan).
IMPORTANT: The name of the Channel object in the controller must be the
name of the object with the suffix ‘_Chan’. For example, if your P_AInAdv
object has the name ‘AInAdv123’, then its Channel object must be named
‘AInAdv123_Chan’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that has
HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag is
created for the P_LLS object that is given the alias P101_More. When the more
information button is pressed on the motor, it links to P101_More. This will
open the faceplate for the LLS object.
3 Set the number of decimal places for the Process Variable.

108 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes specific reasons a device is 'Not Ready', device warnings and faults,
warning and fault history, and predictive/preventive maintenance data. The
initial faceplate shows the raw input process variable.

Click the raw input button to open the analog channel quality faceplate. This
tab provides an overview of the process variable. For more information on the
analog channel faceplate, See Analog Input Channel (P_AIChan) on page 110.

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 109


Chapter 3 I/O Processing Family

Analog Input Channel The P_AIChan Add-On Instruction monitors one analog input channel and
provides one configurable alarm. This instruction is associated with other
(P_AIChan) instructions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
The P_AIChan instruction is used in association with other device
instructions to provide input monitoring functions. There are no dedicated
display elements for this instruction. The P_AIChan faceplate is called from
other faceplates.

Operator Tab

The faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status.

The Operator tab shows the following information:


• Current Process Variable value in raw and engineering units
• Process Variable status
• Input Source and Quality indicator

110 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters. The following faceplate shows an example of
the maintenance tab.

1
5
2

The following table shows the functions on the Maintenance tab.


Table 67 - Maintenance Tab Descriptions
Item Description
1 Type the high clamping limit for the Process Variable. This value clamps
(limits) the Process Variable so it does not exceed this value.
IMPORTANT: Out-of-Range detection uses the Process Variable value
before clamping. This entry does not affect Out-of-Range detection
2 Type the low clamping limit for the Process Variable. This value clamps
(limits) the Process Variable so it does not go below this value.
IMPORTANT: Out-of-Range detection u
3 Type the thresholds that are considered out of range (failed).
If the Process Variable is greater than or equal to the high threshold, it is
considered out of range.
If the Process Variable is less than or equal to the low threshold for the on-
delay time, it is considered out of range.
4 Type the deadband to use with the out-of-range thresholds. If the Process
Variable is less than the high threshold minus the deadband and the Process
Variable is greater than the low threshold plus the deadband for the off-delay
time, it is considered in range (not failed). The deadband must be greater
than or equal to zero.
5 Type the snap-band to use with the Input Clamping Limits.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 111


Chapter 3 I/O Processing Family

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The advanced
maintenance, engineering, and the HMI configuration tabs can be reached
from the Advanced Properties Display. This tab is used for initial system
commissioning or later system changes.

Advanced Maintenance Tab

2
3

Table 68 - Advanced Maintenance Tab Description


Item Description
1 Type the value to output as the process variable when a condition occurs that
has its action set to ‘Replace’.
2 Type the amount of time the input must stay within the range thresholds (with
deadband) to clear the Out of Range (fail) condition. The off-delay time is
used to help prevent a chattering fail detection on a noisy signal near a range
threshold.
3 Type the amount of time the input must stay beyond a range threshold to cause
an Out of Range (fail) condition. The on-delay time is used to avoid an
unnecessary fail detection when the input only momentarily exceeds the
threshold.
4 Type the amount of time the input must remain unchanged to trigger a stuck
input condition. A value of zero means the input must change every
instruction scan to avoid a stuck input condition. Type a large value to disable
stuck input detection.

112 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Engineering Tab

The engineering tab is divided into two pages. On this tab, configure the
Process Variable quality settings.

1 4

2 5

Table 69 - Engineering Tab Page 1 Description


Item Description
1 Type the Raw Value range of the input signal that is connected to Inp_PV.
The Raw minimum default is 0.0 and the Raw maximum is 100.0.
The Raw Min/Max and Process Variable engineering units Min/Max are used
for scaling to engineering units.
2 Type the units of measure for the input signal. “mA DC” is the default.
3 Check to trigger a failure condition and alarm when the Process Variable
status is either Bad or Uncertain.
Clear this checkbox to trigger the failure condition when only the Process
Variable status is Bad.
4 Type the Process Variable range of the input signal that is connected to
Inp_PV. The Process Variable engineering units minimum default is 0.0 and
the Process Variable engineering units maximum is 100.0.
EXAMPLE: If your input card provides a signal from 4…20 mA that
represents -50…+250 °C, set Cfg_PVEUMin to -50.0 and Cfg_PVEUMax to
250.0.
The Raw Min/Max and Process Variable engineering units Min/Max are used
for scaling to engineering units.
5 Type the engineering units for display on the HMI. Percent (%) is the default.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 113


Chapter 3 I/O Processing Family

1
2
3
4
5
6
7
8
9

Table 70 - Engineering Tab Page 2 Description


Item Description
1 Action:
When the P_AInChan configuration is not valid:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When the P_ configuration is not valid:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
2 Action:
When there is a channel fault:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When there is a channel fault:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad

114 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 70 - Engineering Tab Page 2 Description


Item Description
3 Action:
When there is a module fault:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When there is a module fault:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
4 Action:
When the input is not a number:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When the input is not a number:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
5 Action:
When the input is out of range:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When the input is out of range:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
6 Action:
• Use the input to determine value
• Hold value at its last good value
Set value by using Cfg_PVReplaceVal

Quality:
When the input is out of spec:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
7 Action:
When Inp_FuncCheck is set:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When Inp_FuncCheck is set:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 115


Chapter 3 I/O Processing Family

Table 70 - Engineering Tab Page 2 Description


Item Description
8 Action:
When the input is stuck
(no change):
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When the input is stuck
(no change):
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad
9 Action:
When Inp_MaintReqd is set:
• Use the input to determine value
• Hold value at its last good value
• Set value by using Cfg_PVReplaceVal

Quality:
When Inp_MaintReqd is set:
• Set Sts_PVGood
• Set Sts_PVUncertain
• Set Sts_PVBad

HMI Configuration Tab

Configure the description, label, tag, and security area for the device.

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

116 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Dual Sensor Analog The P_AInDual (Dual Analog Input) Add-On Instruction monitors one
analog Process Variable by using two analog input signals (dual sensors, dual
Input (P_AInDual) transmitters, and dual-input channels). The Add-On Instruction has the same
basic features as P_AIn. See Basic Analog Input (P_AIn) on page 94.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

Dual Sensor Analog Input (P_AInDual) uses the same display elements a
P_AIn. See Basic Analog Input (P_AIn) on page 94 for the display elements.

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

1 5
6

Table 71 - Operator Tab Description


Item Description
1 Click to select Sensor A Input Process Variable.
2 Click to select the maximum of Sensor A and Sensor B Input Process Variable.
3 Click to select the minimum of Sensor A and Sensor B Input Process Variable.
4 Click to select Sensor B Input Process Variable.
5 Clear the minimum / maximum extents of the capture.
6 Click to select the average of Sensor A and Sensor B input Process Variables.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 117


Chapter 3 I/O Processing Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems. The maintenance tab for the P_AInDual Add-On
Instruction has two pages. The first page contains the threshold and deadband
information for the high and low limits and is the same as the P_AIn Add-On
Instruction. See Basic Analog Input (P_AIn) on page 94. Additional
information for this instruction on page 2 can be seen in the following
diagram.

Table 72 - Maintenance Tab Description


Item Description
1 Process variable high/low signal difference threshold. Type the threshold (trip
point) for analog input alarms.
2 Process variable deadband. Type the deadband (hysteresis) that is applied to
the alarm limit. Deadband helps prevent a noisy signal from generating
numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.
3 Process variable fail deadband. Type the deadband (hysteresis) that is applied
to each alarm limit. Deadband helps prevent a noisy signal from generating
numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.
4 Process variable high/low fail threshold in raw units.

118 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The engineering
tab and the HMI configuration tab can be reached from the Advanced
Properties Display. This tab is used for initial system commissioning or later
system changes.

Engineering Tab

Use the engineering tab to configure the Process Variable unit for the device.

1
5

Table 73 - Engineering Tab Page 1 Description


Item Description
1 Input (unscaled) minimum and maximum
These parameters must be set to the range of the signal that is connected to the
Inp_Process Variable Input. The raw minimum default is 0.0 and the raw
maximum default is 100.0.
Example: If your input card provides a signal from 4.0…20.0mA, set
Cfg_InpRawMin to 4.0 and Cfg_InpRawMax to 20.0. The raw minimum/
maximum and engineering units minimum/maximum are used for scaling to
engineering units.
2 Check to allow the Substitute Process Variable Maintenance function.
Clear this checkbox to disallow the Substitute Process Variable Maintenance
function (default).
3 PV Source and Quality Input A
Generate SrcQ: This instruction determines the Process Variable quality
using Inp_PVBad, Inp_PVUncertain, and the PV value (out of range, infinite
or not a number)

Pass thru connected Channel’s SrcQ value: This instruction uses the Source
and Quality (SrcQ) value that is provided by an upstream object (such as
P_AIChan) via Inp_PVSrcQ to determine the PV source and quality.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 119


Chapter 3 I/O Processing Family

Item Description
4 PV Source and Quality Input B
Generate SrcQ: This instruction determines the Process Variable quality
using Inp_PVBad, Inp_PVUncertain, and the PV value (out of range, infinite
or not a number)

Pass thru connected Channel’s SrcQ value: This instruction uses the Source
and Quality (SrcQ) value that is provided by an upstream object (such as
P_AIChan) via Inp_PVSrcQ to determine the PV source and quality.
5 EU minimum and maximum for scaling
These parameters must be set to match the Process Variable range of the input
signal that is connected to Inp_PV. The Process Variable engineering units
minimum default is 0.0 and the Process Variable engineering units maximum
is 100.0.
Example: If your input card provides a signal from 4…20 mA that represents
-50…+250 °C, set Cfg_PVEUMIN to -50.0 and Cfg_PVEU maximum to
250.0.
The raw minimum/maximum and Process Variable engineering units
minimum/maximum are used for scaling to engineering units.
6 Type engineering units for display on the HMI.

Table 74 - Engineering Tab Page 1 Description


Item Description
1 Type the time in seconds for the process variable filter time constant.

120 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

HMI Configuration Tab

Configure the description, label, tag, and security area for the device.

See Basic Faceplate Attributes on page 32 for the description of the common
attributes.

4
5

6
1

Table 75 - HMI Configuration Description


Item Description
1 Check to enable navigation to an upstream channel object (for example,
P_AIChan).
IMPORTANT: The name of the Channel object in the controller must be the
name of the object with the suffix ‘_ChanA’. For example, if your
P_AInDual object has the name ‘AInDual123’, then its Channel object must
be named ‘AInDual123_ChanA’.
2 Check to enable navigation to an upstream channel object (for example,
P_AIChan).
IMPORTANT: The name of the Channel object in the controller must be the
name of the object with the suffix ‘_ChanB’. For example, if your
P_AInDual object has the name ’AInDual123’, then its Channel object must
be named ‘AInDual123_ChanB’.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
4 Type the name for Input Tag A to show on the faceplate and Tooltip.
IMPORTANT: Pause the mouse over the field to display a tool tip with the
configured Logix tag/path.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 121


Chapter 3 I/O Processing Family

Item Description
5 Type the name for Input Tag B to show on the faceplate and Tooltip.
IMPORTANT: Pause the mouse over the field to display a tool tip with the
configured Logix tag/path.
6 Set the number of decimal places for the Process Variable.

122 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes specific reasons a device is 'Not Ready', device warnings and faults,
warning and fault history, and predictive/preventive maintenance data. The
initial faceplate shows the raw input process variable.

Click the raw input button to open the analog channel quality faceplate. This
tab provides an overview of the process variable. For more information on the
analog channel faceplate, See Analog Input Channel (P_AIChan) on page 110.

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 123


Chapter 3 I/O Processing Family

Multiple Analog Input The P_AInMulti (Multiple Analog Input) Add-On Instruction monitors one
analog process variable (Process Variable) by using up to eight analog input
(P_AInMulti) signals (sensors, transmitters, input channels).The Add-On Instruction has
the same basic features as P_AIn. See Basic Analog Input (P_AIn) on
page 94.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 76 - P_AInMulti Display Elements Description
Display Element Name Display Element Description
GO_P_AInMulti_8V The object displays eight
inputs (A-H), with each
input a moving line on a
horizontal axis. The graphic
display includes indicators
for disabled and rejected
inputs.

GO_P_AInMulti_6V The object displays six


inputs (A-F), with each input
a moving line on a
horizontal axis. The graphic
display includes indicators
for disabled and rejected
inputs.

GO_P_AInMulti_4V The object displays four


inputs (A-D), with each
input a moving line on a
horizontal axis. The graphic
display includes indicators
for disabled and rejected
inputs.

124 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 76 - P_AInMulti Display Elements Description


Display Element Name Display Element Description
GO_P_AInMulti_8H The object displays eight
inputs (A-H), with each
input a moving line on a
vertical axis. The graphic
display includes indicators
for disabled and rejected
inputs.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 125


Chapter 3 I/O Processing Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

Table 77 - Operator Tab Description


Item Description
1 Process Variable
2 Clear minimum/maximum extents of the capture
3 Display of the input signals that are being rejected.

126 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems. The maintenance tab for the P_AInMulti Add-On
Instruction has three pages. The first page contains the threshold and
deadband information for the high and low limits and is the same as the P_AIn
Add-On Instruction. See Basic Analog Input (P_AIn) on page 94. Additional
information for this instruction on page 2 and three can be seen in the
following diagram.

1
3

Table 78 - Maintenance Tab Page 1 Description


Item Description
1 Click a threshold name to open the associated P_Gate faceplate.
2 Input failure status high/low threshold.
3 Type the deadband (hysteresis) that is applied to each alarm limit. Deadband
helps prevent a noisy signal from generating numerous spurious alarms.
EXAMPLE: If the High Alarm Limit is 90.0 and the High Alarm deadband is
5, once the signal rises above 90.0 and generates a High Alarm. The signal
must fall below 85.0 (90.0 minus 5.0) for the alarm to clear.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 127


Chapter 3 I/O Processing Family

Table 79 - Maintenance Tab Page 2 Description

Item Description
1 Sensor inputs. Check:
• ON if the corresponding input is to be used to calculate the final Process
Variable (average or median).
• OFF to exclude the corresponding input from the Process Variable
calculation.
This configuration is typically used to exclude a particular input when it is
taken out of service for maintenance. If the P_AInMulti instruction has a
Process Variable but is not using it, the Maintenance Bypass Indicator is
displayed.

128 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The engineering
tab and the HMI configuration tab can be reached from the Advanced
Properties Display. This tab is used for initial system commissioning or later
system changes.

Engineering Tab

The engineering tab is divided into three pages.

1 5

6
2

Table 80 - Engineering Tab Page 1 Description

Item Description
1 Enter these parameters within the range of the signal that is connected to the
Inp_PV Input. The Raw Min default is 0.0 and the Raw Max default is 100.0.
EXAMPLE: If your input card provides a signal from 4.0…20.0mA, set
Cfg_InpRawMin to 4.0 and Cfg_InpRawMax to 20.0. The Raw minimum/
maximum and engineering units minimum/maximum are used for scaling to
engineering units.
2 Check to set this parameter:
• ON, if the corresponding Process Variable Input is to be used to calculate
final Process Variable (average or median)
• OFF, to exclude the corresponding Process Variable Input from the Process
Variable calculation
TIP: This configuration determines whether a particular input is intended to
be wired and used. See the Maintenance tab for functions to take an input out
of service for maintenance temporarily.
3 Check to set this parameter to one of the following:
• OFF to allow the Substitute Process Variable Maintenance function
(default).
• ON to disallow the Substitute Process Variable Maintenance function.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 129


Chapter 3 I/O Processing Family

Item Description
4 Check to set this parameter to one of the following:
• ON, an input that is flagged as uncertain is rejected and not used to calculate
the final Process Variable.
• OFF, an input that is flagged as uncertain is not rejected and is still used to
calculate the final Process Variable. The flag causes the final Process
Variable to be flagged as uncertain (default).
5 Enter these parameters within the Process Variable range of the input signal
that is connected to Inp_PVA and Inp_PVB. The Process Variable engineering
units minimum default is 0.0 and the Process Variable engineering units
maximum is 100.0.
EXAMPLE: If your input card provides a signal from 4…20 mA that
represents -50…+250 °C, set Cfg_PVEUMIN to -50.0 and Cfg_PVEUMax to
250.0.
The Raw Min/Max and Process Variable engineering units Min/Max are used
for scaling to engineering Units.
6 Enter the engineering units for display on the HMI. Percent (%) is the default.
7 Type the number of unrejected Process Variable inputs that are required to
have the final Process Variable value show good quality.

Table 81 - Engineering Tab Page 2 Description

Item Description
1 Click:
• 'Outside of rejection region' to reject an input that is more than two standard
deviations from the mean.
• 'Outside of mean +/-' to reject an input that deviates from the mean by more
than the value entered. Value is in PV engineering units.
IMPORTANT: At least four inputs must be used for the 'Outside of rejection
region' selection to be meaningful.

130 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Item Description
2 Click:
• 'Average of good inputs' - the calculated final Process Variable is the
average (arithmetic mean) of the good (non-rejected) Process Variable
inputs.
• 'Median of good inputs' - the calculated final Process Variable is the median
(central value) of the good (non-rejected) Process Variable inputs (default).
The average is the sum of values that are divided by the number of values.
The median is the value of the item in the middle. If there are an even number
of items, the median is the average of the two central values.
3 Click one of the options to determine the output calculation when there are
only two unrejected inputs.

Table 82 - Engineering Tab Page 3 Description

Item Description
1 This parameter sets the filter time constant for the first-order (lag) filter
applied to the Process Variable. The filter is applied after scaling and before
alarm checking and Process Variable display as Val.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 131


Chapter 3 I/O Processing Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.
The HMI Configuration has two tabs for this object.

1
1

Table 83 - HMI Configuration Page 1 Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
2 Type the number of decimal places to show for the Process Variable.

132 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

1 2

Table 84 - HMI Configuration Page 2 Description

Item Description
1 Check to enable navigation to an upstream channel object (for example,
P_AIChan).
IMPORTANT: The name of the Channel object in the controller must be the
name of the object with the suffix ‘_Chan’ plus the input letter (A…H). This
restriction applies to each of the eight channels (A…H). For example, if your
P_AInMulti object has the name’AInMulti123’, then its
Channel A object must be named ‘AInMulti123_ChanA’.
2 Set the number of decimal places for the Process Variable.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 133


Chapter 3 I/O Processing Family

Diagnostics Tab

The Diagnostic tab provides raw input process variables and the scaled process
variable from the inputs.

Alarms Tab
The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

134 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Discrete Input (P_DIn) The P_DIn (Discrete Input) Add-On Instruction is used to receive and process
one discrete condition (the Process Variable) typically for a channel of a
discrete input card. It can be used with any discrete (BOOL) signal.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 85 - P_DIn Display Elements Description
Display Element Name Display Element Description
GO_P_DIn Global object with label.

GO_P_DIn1 Global object without label.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 135


Chapter 3 I/O Processing Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

Table 86 - Operator Tab Description


Item Description
1 Current Process Variable
2 Target Process Variable

136 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance.

1 3

Table 87 - Maintenance Tab Description


Item Description
1 Current Process Variable
2 Click to enable the use of the Substitute Process Variable.
3 Target Process Variable
4 Gate condition
5 Target status
6 Click to choose Process Variable to be used.

Click Gate Condition to open the P_Gate faceplate. From the P_Gate
faceplate, you can configure and perform additional operations for each alarm,
including Gate Delay, Status On-delay, Status Off-delay, and condition text.

See Condition Gate Delay (P_Gate) on page 43

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 137


Chapter 3 I/O Processing Family

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The Advanced
Maintenance, Engineering, and HMI configuration tabs can be reached from
the Advanced Properties Display. This tab is used for initial system
commissioning or later system changes.

Advanced Maintenance Tab

Table 88 - Advanced Maintenance Tab Description


Item Description
1 Minimum time the Process Variable must maintain the state, in seconds.

138 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Engineering Tab

The engineering tab provides access to device configuration parameters and


ranges, options for device and I/O setup, displayed text, and
faceplate-to-faceplate navigation settings, for initial system commissioning or
later system changes.

Table 89 - Engineering Tab Description


Item Description
1 Check to enable the substitute Process Variable feature.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 139


Chapter 3 I/O Processing Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.

3
4

1
2

Table 90 - HMI Configuration Description


Item Description
1 Check to display state text in normal state
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
3 Type text to display in PV 0 State.
4 Type text to display in PV 1 State.

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

140 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Digital Input Advanced The P_DInAdv (Discrete Input Advanced) Add-On Instruction provides
additional functionality from the P_DIn Add-On Instruction. This Add-On
(P_DInAdv) Instruction can be configured to use warning and failure indicators as well as
identifying the equipment as a speed switch.

P_DInAdv is used to receive and process one discrete condition (the Process
Variable) typically for a channel of a discrete input card. It can be used with any
discrete (BOOL) signal.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time. This Add-On
Instruction uses the same global objects as the P_DIn Add-On Instruction.

Table 91 - P_DInAdv Display Elements Description


Display Element Name Display Element Description
GO_P_DIn Global object with label.

GO_P_DIn1 Global object without label.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 141


Chapter 3 I/O Processing Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

Table 92 - Operator Tab Description


Item Description
1 Current Process Variable
2 Target Process Variable

142 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance.

1 3

Table 93 - Maintenance Tab Description


Item Description
1 Current Process Variable
2 Click to enable the use of the Substitute Process Variable.
3 Target Process Variable
4 Gate condition
5 Target status
6 Click to choose Process Variable to be used.

Click Gate Condition to open the P_Gate faceplate. From the P_Gate
faceplate, you can configure and perform additional operations for each alarm,
including Gate Delay, Status On-delay, Status Off-delay, and condition text.

See Condition Gate Delay (P_Gate) on page 43

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 143


Chapter 3 I/O Processing Family

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The Advanced
Maintenance, Engineering, and HMI configuration tabs can be reached from
the Advanced Properties Display. This tab is used for initial system
commissioning or later system changes.

Advanced Maintenance Tab

Table 94 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Minimum time the Process Variable must maintain the state, in seconds.

144 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 95 - Advanced Maintenance Tab Page 2 Description

Item Description
1 Type the default warning time in seconds.
2 Type the default failure time in seconds.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 145


Chapter 3 I/O Processing Family

Engineering Tab

The engineering tab provides access to device configuration parameters and


ranges, options for device and I/O setup, displayed text, and
faceplate-to-faceplate navigation settings, for initial system commissioning or
later system changes.

1
2
3

4
5

Table 96 - Engineering Tab Page 1 Description


Item Description
1 Check to enable the substitute Process Variable feature.
2 Check if the device has warning and failure indicators.
3 Check to enable the speed switch functionality.
4 Check to enable the speed feedback functionality.
5 Type the low speed threshold. (used as a percentage of maximum speed out of
100%)
6 Check to monitor the run feedback from the equipment. If run feedback is
detected, the P_DInAdv state changes to Run. The “Run” status will be
updated even if the “Accelerating” state timer has not expired.
7 Select to choose when the speed switch shows At Speed.

146 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Table 97 - Engineering Tab Page 2 Description


Item Description
1 Check the feature and enter the maximum number of pulses expected per
minute. The derived speed of the equipment being monitored is indicated as a
percentage out of a 100.
2 Check to maintain Run status while decelerating.
By default the Run status is immediately reset during the state of Decelerating.
For sequence programming, it may be a requirement to maintain the Run
Status while the equipment is coasting to a stop
3 Type the time to report the status in each state. The state will be reported for
the entire duration of the set time.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 147


Chapter 3 I/O Processing Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.

4
5

2
3

Table 98 - HMI Configuration Description


Item Description
1 Check to display state text in normal state
2 Check to always display the symbol. If selected, the Speed Switch states, Acc,
Run, Decc, or Stop will be displayed with the Tag Label on the global symbol.
The default is to only display the Label.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
4 Type text to display in PV 0 State.
5 Type text to display in PV 1 State.

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the

148 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 149


Chapter 3 I/O Processing Family

Discrete Output The Discrete Output (P_DOut) Add-On Instruction controls a device by one
discrete output signal and optionally monitors feedback from the device to
(P_DOut) check for device failures. The P_DOut instruction operates in various
command sources, and can provide steady, single pulsed, or continually pulsed
output.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save time.
Table 99 - P_DOut Display Elements Description
Display Element Name Display Element Description
GO_P_DOut Digital (2-state) device
display element for use on
overview and detail
displays.

150 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

1
2

3 6

4 7

Table 100 - Operator Tab Description


Item Description
1 Feedback Indicator
2 Discrete Output Indicator
3 Output 'Off' Button
4 Single Pulse 'Off' Button
5 Continuous Pulse Button
6 Output 'On' Button
7 Single Pulse 'On' Button

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 151


Chapter 3 I/O Processing Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance.

1
2

Table 101 - Maintenance Tab Description


Item Description
1 Check if the instruction uses the Off device feedback to check for failure.
2 Check if the instruction uses the On device feedback to check for failure.
3 Check if bypassable interlocks and permissives are bypassed in override
command source.

152 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The Advanced
Maintenance, Engineering, and HMI configuration tabs can be reached from
the Advanced Properties Display. This tab is used for initial system
commissioning or later system changes.

Advanced Maintenance Tab

4
2
5

6
3

Table 102 - Advanced Property Tab Description


Item Description
1 Type the amount of time to allow for the device to get feedback for the Off
setting before setting a fault.
2 Type the amount of time before the output deactivates.
3 Type the amount of time to trigger a pulse when the device deactivates.
4 Type the amount of time to allow for the device to get feedback for the On
setting before setting a fault.
5 Type the amount of time before the output activates.
6 Type the amount of time to trigger a pulse when the device deactivates.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 153


Chapter 3 I/O Processing Family

Engineering Tab

The engineering tab provides access to device configuration parameters and


ranges, options for device and I/O setup, displayed text, and faceplate-to-
faceplate navigation settings. This tab is also used for initial system
commissioning or later system changes.

1
2
3

4
5

6
7

8
9

Table 103 - Engineering Tab Page 1 Description


Item Description
1 Check to configure the instruction to use Off feedback signals from the device.
2 Check to configure the instruction to use On feedback signals from the device.
3 Click to Enable fault when both feedback inputs are either ON or OFF.
4 Check to reset a fault upon an operator command.
Clear this checkbox to reset faults by using only the reset code.
5 Check to reset a fault upon an external command.
Clear this checkbox to reset faults by using only the reset code.
6 Check to enable the pulsing functions.
7 Check if bypassable interlocks and permissives are bypassed in override
command source.
8 Check to make the Operator Off command available in any command source.
Clear this checkbox to make the Operator Off command available only in
Operator or Maintenance command source.
9 Check to make the External Off command available in any command source.
Clear this checkbox to make the External Off command available only in
Operator or Maintenance command source.

154 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

2
3
4

6
7

Table 104 - Engineering Tab Page 2 Description

Item Description
1 Check to finish pulse when commanded ON or OFF.
2 Check to de-energize the output to the device and return the device to its fail
position, when an I/O Fault condition occurs.
Clear this checkbox to keep the output to the device in its current stat on an I/O
Fault condition.
IMPORTANT: If a condition is configured to shed the device to the Off state
on a fault, a reset is required to clear the shed fault. This reset commands the
device to a state other than Off.
3 Check to de-energize the output to the device, return it to its fail position,
when a Position Fail condition occurs.
Clear this checkbox to keep the output to the device in its current state (keep
trying) on a Position Fail condition.
IMPORTANT: If a condition is configured to shed the device to the Off state
on a fault, a reset is required to clear the shed fault. This reset commands the
device to a state other than Off.
4 The device outputs are always de-energized on an Interlock Trip. This item
cannot be unchecked. It is displayed as a reminder that the Interlock Trip
function always de-energizes the device.
5 Sets the time delay (in seconds) for the On or Off status to be echoed back
when Simulation is enabled or when On and Off feedbacks are not used.
6 Click to sound an audible on a commanded stage from the OFF State.
7 Click to sound an audible on a commanded stage from any State.
8 Type the time (in seconds) that the audible sounds when there is a commanded
State change.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 155


Chapter 3 I/O Processing Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.

4
5

1
2

Table 105 - HMI Configuration Descriptions


Item Description
1 Check if a permissive instruction is used with this device. This check changes
the Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix '_Perm'. For example, if your P_DOut
object has the name 'DOut123', then its Permissive object must be named
'DOut123_Perm'.
2 Check if an interlock instruction is used with this device. This check changes
the Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix '_Intlk'. For example, if your P_DOut object
has the name 'DOut123', then its interlock object must be named
'DOut123_Intlk'.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
4 Type text to display when device is in Off (0) state.
5 Type text to display when device is in On (1) state.

156 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab
The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 157


Chapter 3 I/O Processing Family

Analog Output The P_AOut (Analog Output) Add-On Instruction is used to manipulate an
analog output to control a field device, such as a control valve or a motorized
(P_AOut) gate positioner. The output responds to an Operator (manual) or Program
setting of the Controlled Variable (CV) signal.

The P_AOut instruction controls the analog output in various command


sources (Operator, Program, Override, Maintenance, Hand), monitoring for
fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 106 - P_AOut Display Elements Description
Display Element Display Element Description
Name
GO_P_AOut Standard analog-output
global object.

GO_ProcessControlVa Normal controlled valve


lve symbol for horizontal
pipe.

GO_ProcessControlVa Inverted controlled


lve1 valve symbol for
horizontal pipe.

GO_ProcessControlVa Controlled valve


lve2 symbol for vertical pipe
(pipe to the left).

GO_ProcessControlVa Controlled valve


lve3 symbol for vertical pipe
(pipe to the right).

158 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

1
4
2

Table 107 - Operator Tab Description


Item Description
1 Analog Output State (At Target, Ramping Down, Ramping Up, Clamped at
Min, Clamped at Max, or Disabled).
2 Control Variable target.
3 Type to change the Controlled Variable output value.
4 Control Variable.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 159


Chapter 3 I/O Processing Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems, and disable the device for routine maintenance.

Table 108 - Maintenance Tab Description


Item Description
1 Click YES to bypass checking of bypassable interlocks and permissives.
2 Type the CV value above which the device shows as 'Active'. When
Val_CVOut is greater than this value, Sts_Active is set to 1, and the HMI
shows the graphic symbol in the active state (for example, control valve shown
as Open). When Val_CVOut is less than or equal to this value, Sts_Active is
set to 0, and the HMI shows the graphic symbol in the inactive state (for
example, control valve shown as Closed).
3 Type the Rate of Change Limit for increasing the Control Variable.
4 Type the Rate of Change Limit for decreasing the Control Variable.
5 Displays the interlocks faceplate P_Intlk.

160 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Advanced Properties Display

The Advanced Properties Display provides access to device configuration


parameters and ranges, and options for device and I/O setup. The advanced
maintenance, engineering tab, and the HMI configuration tab can be reached
from the Advanced Properties Display. This tab is used for initial system
commissioning or later system changes.

Advanced Maintenance Tab

Table 109 - Advanced Properties Display Description


Item Description
1 Controlled Variable clamp limits. Type the clamping limits for the Controlled
Variable in engineering units.
Clamp limits are enforced in Operator and Program command sources only.
2 Type the maximum allowed value for the Rate of Change Limit in engineering
units per second.
A value of zero allows any rate of change to be input by the Program or
Operator.
3 Type the Operator command source Controlled Variable Target in engineering
units.
This entry is available in Operator command source and Maintenance
command source.
4 Check and the Controlled Variable holds at the last good value when an
Interlock trips or an I/O Fault occurs.
Clear this checkbox and the Controlled Variable goes to the Interlock
Controlled Variable value when an Interlock trips or an I/O Fault occurs.
5 Type the interlock target Controlled Variable in engineering units.
This value is used for the Controlled Variable when interlocked or on an I/O
Fault, but only if Hold Last Good Value is not selected.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 161


Chapter 3 I/O Processing Family

Engineering Tab

The engineering tab provides access to device configuration parameters and


ranges, options for device and I/O setup, displayed text, and faceplate-to-
faceplate navigation settings. This tab is also used for initial system
commissioning or later system changes.

1 7

3
4
5

Table 110 - Engineering Tab Page 1 Description


Item Description
1 Type values for the maximum and minimum scaled (engineering units) scaling
ranges.
2 When checked, the operator settings track the program settings when the
command source is Program, and program settings track the operator settings
when the command source is Operator. Transition between command sources
is bumpless.
When not checked, the operator settings and program settings retain their
values regardless of command source. When the command source is changed,
the value of a limit can change, such as from the Program-set value to the
Operator-set value.
3 When checked, the Program and Operator Settings of the CV track the output
CV when the command source is Hand or Override.
4 Check while in Override command source to bypass Interlocks that can be
bypassed.
5 Check to have the CV immediately go to its target value or configured
Interlock CV value when an Interlock trips or the instruction is placed in
Maintenance or Override command source.
Clear this checkbox to have the CV always use rate of change limiting
(ramping) of the CV output.
6 Engineering Units label.
7 Type values for the maximum and minimum output (Raw) scaling ranges.

162 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

1
2

3
4

Table 111 - Engineering Tab Page 2 Description

Item Description
1 Check so that an I/O Fault triggers a shed of the output, to the configured shed
set value or to hold last good output. The shed condition is latched internal to
the Add-On Instruction. When the I/O Fault condition clears, a Reset
command is required to return to normal operation.
Clear this checkbox so that the I/O Fault condition does not affect operation
(but can still generate an alarm).
2 This selection cannot be changed. The configured shed action always takes
place on an interlock trip.
3 Choose this option to set the analog output to the configured shed set value
when a condition configured as a shed trigger occurs.
4 Choose this option to hold the analog output at its last good value when a
condition configured as a shed trigger occurs.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 163


Chapter 3 I/O Processing Family

HMI Configuration Tab

Configure the description, label, tag, and security area for the device. See Basic
Faceplate Attributes on page 32 for the description of the common attributes.

1
2

Table 112 - HMI Configuration Description


Item Description
1 Check if an interlock object is connected to Inp_IntlkOK. The Interlock
indicator becomes a button that opens the P_Intlk faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_AOut
object has the name ‘AOut123’, then its Interlock object must be named
‘AOut123_Intlk.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
3 Check to enable navigation to the faceplate for the PlantPAx® object that is
providing the CV for this object (PSet_CV).
4 Set the number of decimal places for the Control Variable.

164 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


I/O Processing Family Chapter 3

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab
The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 165


Chapter 3 I/O Processing Family

Pressure/Temperature The Pressure/Temperature Compensated Flow (P_PTComp) Add-On


Instruction is used to calculate a flow at standard temperature and pressure.
Compensated Flow This Add-On Instruction essentially calculates a mass flow rate when given a
(P_PTComp) volumetric flow rate or differential pressure measurement. This instruction also
requires measurements of the actual temperature and pressure of the flowing
gas. There is no graphical HMI for this instruction. More details on this
instruction can be found in PROCES-RM003.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Tank Strapping Table The P_StrapTbl (Tank Strapping Table) Add-On Instruction calculates the
volume of product in an upright cylindrical tank when given the level of the
(P_StrapTbl) product and the tank calibration table. This instruction can optionally
compensate for free water at the bottom of the tank (given a product/water
interface level). This instruction can also compensate for thermal expansion of
the tank shell (given the coefficient of linear expansion of the shell material
and product and ambient temperatures). There is no graphical HMI for this
instruction. More details on this instruction can be found in PROCES-
RM003.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

166 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 4

Regulatory and Procedural Control


Family

Library objects in this section comprise two groups of Advanced Process


Control: regulatory and procedural.
• Regulatory control focuses on the process variables (levels, flows,
temperatures, pressures, and so on). The control is designed to improve
loops that perform poorly and automate loops that are typically run in
manual by the operator. These loops include techniques such as ratio,
feed-forward, cascade, and decoupling control. Regulatory control
variables include:
– Proportional + Integral + Derivative Enhanced (P_PIDE)
– Analog Fanout (P_Fanout)
– High or Low Selector (P_HiLoSel)
– Deadband Controller (P_DBC)
• Procedural control focuses on the product being manufactured (cement,
polyethylene, ethanol. paper, and so on). The objects control the various
product specifications and parameters via a series of discrete sequential
actions. Procedural control variables include:
– Sequencer Object (P_Seq)
– Flowmeter Dosing / Weigh Scale Dosing (P_Dose)
– Lead/Lag/Standby Motor Group (P_LLS)

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 167


Chapter 4 Regulatory and Procedural Control Family

Proportional + Integral The P_PIDE (Proportional + Integral + Derivative Enhanced) Add-On


Instruction provides the functionality of the Studio 5000 Logix Designer®
+ Derivative Enhanced PIDE function block. This Add-On Instruction provides a user experience
(P_PIDE) consistent with the rest of the Rockwell Automation Library of Process
Objects.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix® system, aid consistency, and save engineering time.
Table 113 - P_PIDE Display Elements Description
Display Element Name Display Element Description
GO_P_PID Display element with
PV and CV numeric
displays.

GO_P_PID1 Display element with


PV, SP, and CV
numeric displays.

GO_P_PID2 Display element with


SP and CV numeric
displays.

GO_P_PID_Trend Display Element with


PV and CV numeric
displays and a trend
display that plots SP,
PV, High, and Low
Deviations. The trend
is scaled to PV EU
Min and Max.

GO_P_PID_Trend1 Display Element with


PV, SP, and CV
numeric displays and
a trend display that
plots SP, PV, High,
and Low Deviations.
The trend is scaled to
PV EU Min and Max.

168 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Table 113 - P_PIDE Display Elements Description


Display Element Name Display Element Description
GO_P_PID_TrendWTarget Display Element with
PV and CV numeric
displays and a trend
display that plots SP,
PV, High, and Low
Deviations. The trend
is scaled by using the
High and Low
Deviations.

GO_P_PID_TrendWTarget Display Element with


1 PV, SP, and CV
numeric displays and
a trend display that
plots SP, PV, High,
and Low Deviations.
The trend is scaled by
using the High and
Low Deviations.

GO_P_PID_Indicator Bar graph with SP on


the left and PV on the
right that is scaled by
PV EU minimum and
maximum.

GO_P_PID_Valve Proportional Valve


display element with
PV and CV numeric
displays.

GO_P_PID_Valve1

GO_P_PID_Valve2

GO_P_PID_Valve3

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 169


Chapter 4 Regulatory and Procedural Control Family

Table 113 - P_PIDE Display Elements Description


Display Element Name Display Element Description
GO_P_PID_Valve4 Proportional Valve
display element with
PV, CV, and Setpoint
numeric displays.

GO_P_PID_Valve5

GO_P_PID_Valve6

GO_P_PID_Valve7

GO_P_PID_Valve8 Proportional Valve


display element with
SP, CV, and Setpoint
numeric displays.

GO_P_PID_Valve9

GO_P_PID_Valve10

GO_P_PID_Valve11

170 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Operator (Home) Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates. See Basic Faceplate Attributes on page 32.

1
7
8

9
2
3
1

4
11
5

Table 114 - Operator Tab Description


Item Description
1 Current Process Variable (PV).
2 Bar graph for the current Process Variable.
3 Click to open the ramp wizard display. See Ramp Wizard Display on page 172.
4 Cascade loop mode.
5 Auto loop mode.
6 Current Setpoint (SP).
7 Current Control Variable (CV).
8 Type a value for the loop setpoint.
IMPORTANT: This value can be entered only when the instruction command
source is Operator and the Loop mode is Automatic or Manual.
9 Bar graph for the current Control Variable.
10 Loop mode indicator.
11 Cascade loop mode.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 171


Chapter 4 Regulatory and Procedural Control Family

Figure 14 - Ramp Wizard Display

1 4

2 5
3

Table 115 - Ramp Wizard Display Description


Item Description
1 Type new target setpoint.
2 Ramp Time.
3 Stop setpoint ramping.
4 Calculated rate of change.
5 Start setpoint ramping.

172 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

Table 116 - Maintenance Tab Description


Item Description
1 Threshold Name: Click a threshold name to open the associated P_Gate
faceplate.
2 Type the threshold (trip point) for analog input alarms.
3 Type the deadband (hysteresis) that applies to each alarm limit. Deadband
helps prevent a noisy signal from generating numerous spurious alarms.
Example: If the High alarm limit is 90.0 and the High alarm deadband is 5,
once the signal rises above 90.0 and generates a High alarm. The signal must
fall below 85.0 (90.0 minus 5.0) for the alarm to clear.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 173


Chapter 4 Regulatory and Procedural Control Family

Advanced Properties

Click the advanced properties graphic. The tuning, advanced maintenance,


engineering, HMI configuration, and faults settings are available.

Tuning

2 5
3
6

Table 117 - Tuning Tab Description


Item Description
1 Trend display for Process Variable, Setpoint, and Controlled Variable.
2 Setpoint data entry.
3 Process variable data entry.
4 Tuning constant entries.
5 Cascade loop mode.
6 Auto loop mode.
7 Manual loop mode.

174 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Maintenance Tab Page 1

Table 118 - Advanced Maintenance Tab 1 Description


Item Description
1 Type the Operator ratio.
2 Type the maximum and minimum limits for the ratio.
3 Type the Operator Setpoint for the Operator Loop mode.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 175


Chapter 4 Regulatory and Procedural Control Family

Advanced Maintenance Tab Page 2

3 6

Table 119 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Type the maximum and minimum limits for the setpoint.
2 Type the interlock setpoint.
3 Type the operator setpoint rate of decrease limit.
4 Type the maximum setpoint rate of decrease.
5 Type the maximum setpoint rate of increase.
6 Type the operator setpoint rate of increase limit.

176 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Maintenance Tab Page 3

3
4
5

Table 120 - Advanced Maintenance Tab 3 Description


Item Description
1 Type the value for the zero-crossing deadband (in PV engineering units).
When the loop error is less than the zero-crossing deadband, the loop output
does not change.
IMPORTANT: See the PIDE built-in instruction online help for more
information.
2 Type the maximum and minimum values of the PV range (span) (in PV
engineering units). The maximum value must be greater than the minimum.
3 Gains: Proportional

This value depends on the setting of Cfg_Depend.


If Cfg_Depend = 1 (dependent gains, the default), type the Controller Gain
(unitless). This gain is applied to the Proportional, Integral, and Derivative
terms.
If Cfg_Depend = 0 (independent gains), type the Proportional Gain (unitless).
This gain is applied to the Proportional term only.
A value of zero in either case disables the Proportional term of the controller.
Negative values are not valid.
4 Gains: Integral

This value depends on the setting of Cfg_Depend.


If Cfg_Depend = 1 (dependent gains, the default), type the Integral Time
Constant (minutes
pre-repeat).
If Cfg_Depend = 0 (independent gains), type the Integral Gain
(1/minutes).
A value of zero in either case disables the Integral term of the controller.
Negative values are not valid.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 177


Chapter 4 Regulatory and Procedural Control Family

Item Description
5 Gains: Derivative

This value depends on the setting of Cfg_Depend.


If Cfg_Depend = 1 (dependent gains, the default), type the Derivative Time
Constant (minutes).
If Cfg_Depend = 0 (independent gains), type the Derivative Gain (minutes).
A value of zero in either case disables the Derivative term of the controller.
Negative values are not valid.

Advanced Maintenance Tab Page 4

Table 121 - Advanced Maintenance Tab 4 Description


Item Description
1 Type the maximum allowed value of the CV in percent. The CV output is
clamped not to exceed the entered value. This value must be less than or equal
to 100.0 and greater than the CV Low Limit.
Type the minimum allowed value of the CV in percent. The CV output is
clamped not to go below the entered value. This value must be greater than or
equal to 0.0 and less than the CV High Limit.
2 Type the maximum allowed CV rate of change in percent per second. A value
of zero disables rate limiting. Negative values are not valid.

178 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Maintenance Tab Page 5

3
2
4

Table 122 - Advanced Maintenance Tab 5 Description


Item Description
1 Type the value in percent to output as the CV when an Interlock input is not
OK. The CV is held at this value until the interlock inputs are OK (subject to
interlock bypassing).
2 Type the minimum/maximum value for the controlled variable limits.
3 Type the value of the output (in CV engineering units) that correspond to a CV
of 100.0%. This value cannot equal the CV EU minimum.
4 Type the value of the output (in CV engineering units) that correspond to a CV
of 0.0%.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 179


Chapter 4 Regulatory and Procedural Control Family

Table 123 - Advanced Maintenance Tab Page 6 Description


Item Description
1 Type the CV value. When Val_CVOut is greater than this value, Sts_Active is
set to 1, and the HMI shows the graphic symbol in the active state (for
example, control valve shown as Open). When Val_CVOut is less than or
equal to this value, Sts_Active is set to 0, and the HMI shows the graphic
symbol in the inactive state (for example, control valve shown as Closed).

180 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Engineering Tab Page 1

2
3

5
6

7
8

Table 124 - Engineering Tab Page 1 Description


Item Description
1 Type the interval (in seconds) to execute the PID algorithm.
2 Check so that when this parameter is:
• On, the operator settings track the program settings when command source
is Program, and program settings track the operator settings when the
command source is Operator. Transition between command sources is
bumpless.
• Off, the operator settings and program settings retain their values regardless
of command source. When the command source is changed, the value of a
limit can change, such as from the Program-set value to the Operator-set
value.
3 Check so that Program and operator settings track when the command source
is Hand or Override.
4 Check to bypass Interlocks that can be bypassed while in Override command
source.
5 Click to have the Proportional action of the PID algorithm apply only to
changes in the PV and ignore changes in setpoint.
6 Click to have the Proportional action of the PID algorithm apply to changes to
the PV and to the setpoint.
7 Click to have the Derivative action of the PID algorithm apply only to the rate
of change of the PV and ignore changes in setpoint.
8 Click to have the Derivative action of the PID algorithm apply to the rate of
change of the PV and to the setpoint.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 181


Chapter 4 Regulatory and Procedural Control Family

Engineering Tab 2

2
3

5
6
7

Table 125 - Engineering Tab Page 2 Description


Item Description
1 Check to enable Auto Loop mode.
2 Check to enable Manual Loop mode.
3 Check to enable Cascade Loop mode.
4 Check to multiply the Cascade SP input by the ratio value to get the loop
setpoint.
Clear the checkbox to use the Cascade SP input as the loop setpoint directly.
5 Click to disable normal loop made selection
6 Click to choose manual as the normal loop mode
7 Click to choose auto as the normal loop mode
8 Click to choose cascade as the normal loop mode
9 Check to allow the operator to select only the defined normal loop mode.

182 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Engineering Tab Page 3

2
3
4
5
6

7
8

Table 126 - Engineering Tab Page 3 Description


Item Description
1 Check to set the Loop mode to Manual when the Use CVInit Value input is
true. The loop is left in manual with the CV at the initialization value when the
initialization request clears.
Clear this checkbox to leave the loop in its current mode on an initialization
request. When the initialization request clears, the loop resumes controlling in
its previous mode.
2 Click to keep the Loop mode what it was at powerdown.
3 Click to set the Loop mode to Manual on powerup.
4 Click to set the Loop mode to Auto on powerup.
5 Click to set the Loop mode to Cascade on powerup.
6 Click to keep the Loop mode what it was at powerdown.
7 Type a value to apply to the loop CV (in percent) on controller powerup. The
CV is set to this value on controller powerup in Run mode and on controller
transition from Program mode to Run mode.
8 Type a value to apply to the loop setpoint (in PV engineering units) on
controller powerup. The setpoint is set to this value on controller powerup in
Run mode and on controller transition from Program mode to Run mode.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 183


Chapter 4 Regulatory and Procedural Control Family

Engineering Tab Page 4

1
2
3

4
5

Table 127 - Engineering Tab Page 4 Description


Item Description
1 Check to have the current PV copied to the SP (track) whenever the loop is in
Manual mode.
2 Check to skip the setpoint rate of change limiting in Interlock Trip,
Maintenance, or Override.
3 Check to allow navigation to the setpoint Ramp Wizard Display from the
Operator tab. See Operator (Home) Tab on page 171.
4 Click for reverse-acting loop response (default). When the PV increases, the
CV (output) decreases.
5 Click for direct-acting loop response. When the PV increases, the CV (output)
increases.
6 Click to use the Independent Gains form of the PID algorithm. Changes to the
proportional gain do not affect integral or derivative response.
7 Click to use the Dependent Gains form of the PID algorithm (default).
Changes to Cfg_PGain are applied as loop gain changes and affect
proportional, integral, and derivative responses.
8 Type a value for maximum deviation between SP and PV. If the deviation
exceeds this value, the SP ramp pauses until the PV returns to a value within
the set deviation.

184 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Engineering Tab Page 5

1
2
3

4
5
6

Table 128 - Engineering Tab Page 5 Description


Item Description
1 Check to enable derivative smoothing. Derivative smoothing can help reduce
output jitter due to noise on the PV signal.
Clear this checkbox to disable derivative smoothing. When derivative
smoothing is disabled, it can result in quicker loop response at high derivative
gain.
2 Check to disable the zero-crossing function. Once the error is within the
deadband, the output does not change, even if the sign of the error has not
changed (error has not crossed zero).

Clear this checkbox to use the zero-crossing deadband. The error must change
signs (cross zero) for the deadband function to be activated and stop changes to
loop output.
3 Check to limit the CV to the range specified by Cfg_MinCV and Cfg_MaxCV
when the Loop mode is Manual.
Clear this checkbox to allow CV values anywhere in the 0.0%…100.0% range
in Manual Loop mode.
4 Check to keep control of loop mode commands with the Operator, Program,
External, or Follow the Source even if the instruction is in Program mode.
5 Check to keep control of the controlled variable quantity setting with the
Operator, Program, External, or Follow the Source even if the instruction is in
Program mode.
6 Check to keep control of the setpoint settings with the Operator, Program,
External, or Follow the Source even if the instruction is in Program mode.
7 Check to keep control of the ratio settings with the Operator, Program,
External, or Follow the Source even if the instruction is in Program mode.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 185


Chapter 4 Regulatory and Procedural Control Family

Engineering Tab Page 6

2
3
4

5
6
7
8

9
1
1

Table 129 - Engineering Tab Page 6 Description

Item Description
1 Possible Failures
2 For the given failure, do not change the CV operation, keep controlling.
3 For the given failure, hold the CV at the current value.
4 For the given failure, set the CV to the configured value.
5 For the given failure, do not change the SP operation.
6 For the given failure, hold the SP at the current value.
7 For the given failure, set the SP to the configured value.
8 For the given failure, have SP track the current PV value.
9 For the given failure, keep current loop mode.
10 For the given failure, set the loop mode to manual.
11 For the given failure, If loop made is cascade set to auto.

TIP To have the loop mode return to the previous control


operation when the failure clears, set Loop Mode Action
to None.

186 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

HMI Configuration Tab 1

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2

3
4

Table 130 - HMI Configuration Tab 1 Description


Item Description
1 Type the PV engineering units for display on the HMI.
2 Type the CV engineering units for display on the HMI. Percent (%) is the
default.
3 Type in the number of decimal places that are displayed for the Process
Variable
4 Type in the number of decimal places that are displayed for the Control
Variable

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 187


Chapter 4 Regulatory and Procedural Control Family

HMI Configuration Tab 2

1 6
2 7
3
4

Table 131 - HMI Configuration Tab 2 Description


Item Description
1 Check to enable navigation to the CV object.
2 Check to enable navigation to the PV object.
3 Check to enable navigation to Cascade SP object.
4 Check to enable navigation to the Interlock object.
5 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag is
created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
6 Type the name of the CV Object to navigate to.
7 Type the name of the PV Object to navigate to.

188 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Faults Tabs

Page 1 of the Diagnostics tab displays PID Instruction faults.

Page 2 of the Diagnostics tab displays PID Instruction Configuration Faults.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 189


Chapter 4 Regulatory and Procedural Control Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

190 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Trends

On the upper part of the Trends tab, you can view the SP (blue line) and PV
(green line).

On the lower part of the Trends tab, you can view the Output CV (black line)
and the Target CV (orange line).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 191


Chapter 4 Regulatory and Procedural Control Family

Analog Fanout The Analog Fanout (P_Fanout) Add-On Instruction fans one 'primary' analog
output signal out to multiple 'secondary' users or devices. Each secondary
(P_Fanout) output has configurable gain, offset, and clamping limits.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 132 - P_Fanout Display Element Description


Display Element Name Display Element Description
GO_P_Fanout P_Fanout global object
(horizontal layout).

GO_P_Fanout1 P_Fanout global object


(vertical layout).

192 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

If outputs 6, 7, and 8 are used by the instruction (in other words, if


Cfg_HasCV6… Cfg_HasCV8 are 1), the global object has a second page of the
faceplate that displays the information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 193


Chapter 4 Regulatory and Procedural Control Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1 3

Table 133 - Maintenance Tab Description


Item Description
1 Type a value that sets the ratio to calculate each individual output.
This value either sets the operator ratio (for example, OSet_CV1Ratio) or the
configuration ratio (for example, Cfg_CV1Ratio) depending on the ratio source
selection.
2 Type a value that sets the offset to calculate each individual output.
This value either sets the operator offset (for example, OSet_CV1Offset) or the
configuration offset (for example, Cfg_CV1Offset) depending on the ratio
source selection.
3 Operator setting for the Input CV rate of change limit (increasing or
decreasing).
If Cfg_MaxCVRoC = 0.0, then this parameter can be set to zero, which means
the rate of change is not limited.

194 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Engineering Tab

1 3

2 4

Table 134 - Engineering Tab Page 1 Description


Item Description
1 Check to enable use of the corresponding output.
2 Type a value for the minimum value to be used to clamp CV (in engineering
units).
3 Type a rate the CV is to change to a calculated value after initialization to
provide bumpless transfer from initialization.
4 Type a value for the maximum value to be used to clamp CV (in engineering
units).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 195


Chapter 4 Regulatory and Procedural Control Family

1
2

3
4

Table 135 - Engineering Tab Page 2 Description


Item Description
1 Click to use the CV1 initialization value (Inp_CV1InitVal) to set the
initialization output (Out_CV_InitVal) when initialization is requested.
2 Click to use a fixed value (Cfg_FixedInitVal) to set the initialization output
(Out_CV_InitVal) when initialization is requested.
Type a value to set the initialization value (Out_CVInitVal) if initialization is
requested and a fixed value option is selected.
3 Click to hold last good value.
4 Click to pass through the bad value.
5 Type values to set the limits to use to clamp the CV.
6 Type values to set the limits to display for the CV.

196 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2
1 3

Table 136 - HMI Configuration Tab Page 1 Description


Item Description
1 Type the description of the output name.
2 Type the units that are used with the CV.
3 Sets the CV engineering units to use for display.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 197


Chapter 4 Regulatory and Procedural Control Family

4
2

Table 137 - HMI Configuration Tab Page 2 Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that has
HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag is
created for the P_LLS object that is given the alias P101_More. When the more
information button is pressed on the motor, it links to P101_More. This will
open the faceplate for the LLS object.
2 Check to permit navigation to a faceplate for which you typed a tag name. For
example, ‘MyCVObject.’.
3 Type the number of decimal places to be shown for CV.
4 Type the text that is displayed on the HMI.

198 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 199


Chapter 4 Regulatory and Procedural Control Family

High or Low Selector The P_HiLoSel (High or Low Selector Add-On Instruction) selects the lowest
of the (up to six) incoming CVs (if Cfg_HiLoSel = 0), or the highest of the
(P_HiLoSel) incoming CVs (if Cfg_HiLoSel =1) and outputs it (Out_CV).

The unselected CVs are flagged to track the selected CV.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 138 - P_HiLoSel Display Elements Description
Display Element Name Display Element Description
P_HiLoSel Standard High or Low
Selector global object.

200 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

The Operator tab shows the following information:


• Current operation (High or Low Select)
• Currently selected input (white highlight)
• Bar graph for clamp limits from minimum to maximum plus Output
CV indicator
• Input CV values and Output CV value

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 201


Chapter 4 Regulatory and Procedural Control Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

Table 139 - Maintenance Tab Description


Item Description
1 Check to use a CV input.
Clear a checkbox not to use the input and put the instruction in Maintenance
Bypass.

202 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Engineering Tab

4
1

Table 140 - Engineering Tab Description


Item Description
1 Check 'Has Input' (CV1…CV6) where an input is connected.
2 Type in the minimum and maximum to set the range for the selected input CV.
If the selected input CV is below the minimum, it is clamped to the minimum
value.
If the selected input CV is above the maximum, it is clamped to the maximum
value.
3 Click High Select to select the highest input CV value to pass to the output.
Click Low Select to select the lowest input CV value to pass to the output.
4 Check a 'Use Offset' (CV1…CV6) to include the Kp*E offset in initialization
calculation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 203


Chapter 4 Regulatory and Procedural Control Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Table 141 - HMI Configuration Tab Page 1 Description


Item Description
1 Type the engineering units for display on the HMI. Percent (%) is the default.
2 Type in the number of decimal places that are displayed for the CV.

204 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

2 3

Table 142 - HMI Configuration Tab Page 2 Description

Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
2 Check an input (CV1…CV6) or the Output CV to allow navigation to a
specified object.
3 Type the tag name for the corresponding input (CV1…CV6) or Output CV.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 205


Chapter 4 Regulatory and Procedural Control Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

206 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Deadband Controller The P_DBC (Deadband Controller) Add-On Instruction provides control of
a process variable within limits by using one or two discrete outputs. A
(P_DBC) deadband controller is also known as a 'bang-bang' or 'on-off ' controller.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aids consistency and saves engineering time.
Table 143 - P_DBC Global Object Loop Symbol
Global Object Name Global Object Description
GO_P_DBC Standard deadband controller
global object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 207


Chapter 4 Regulatory and Procedural Control Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode.Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

1 9
1

2
1
1
3
1
4
1
5
6 1
7
1
8
1

Table 144 - Operator Tab Description


Item Description
1 Drive PV Lower Limit
2 PV EU maximum
3 Drive PV Lower Value
4 Current PV Value
5 Drive PV Higher Value
6 PV EU minimum
7 Current PV Value
8 Drive PV Higher Limit
9 High Rate of Change Decreasing Limit
10 High Rate of Change Increasing Limit
11 Rate of Change Indicator
12 Current Rate of Change
13 Controlled Variable Indicator
14 Auto/Manual Mode Indicator
15 Drive PV buttons. From left to right: drive PV lower, don’t drive PV, drive PV
higher
16 Manual Mode Command Button
17 Auto Mode Command Button

208 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1 7
2 8
9
3
1
4

1
5
1
6

Table 145 - Maintenance Tab Description


Item Description
1 Enter the value of the PV at which the output turns off and PV starts to
decrease.
2 Enter the value of the PV at which the output turns on and PV starts to
increase.
3 Type the number that is used to establish the high deviation limit. When the
PV reaches this limit, a High Deviation alarm is generated.
EXAMPLE: In the examples, the Lower setpoint is 67 and the PV Hi Dev
Status is 5. We add 67 and 5 to get the high deviation limit of 72.
4 Type the number that is used to establish the low deviation limit. When the PV
reaches this limit, a Low Deviation alarm is generated.
EXAMPLE: In the examples, the Raise setpoint is 30 and the PV Lo Dev
Status is -5. We add 30 and -5 to get the low deviation limit of 25.
5 Type the number to set the high Rate of Change (decrease) limit (83 in the
example). When the Rate of Change reaches this level, a Hi Rate of Decrease
alarm is generated.
6 Type the number to set the high Rate of Change (increase) limit (17 in the
example). When the Rate of Change reaches this level, a Hi Rate of Increase
alarm is generated.

7 Type a number that is the size of the deadband for the Lower output (below
Lower limit)
8 Type a number that is the size of the deadband for the Raise output (above
Raise limit)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 209


Chapter 4 Regulatory and Procedural Control Family

Item Description
9 Type the number that PV must decrease to reset a High Deviation alarm.
EXAMPLE: The high deviation limit is 72 and the deadband is 1. The PV
must decrease 1 unit to 71 to reset the High Deviation alarm.
IMPORTANT: The deadband can be set so that the PV must decrease below
the Lower setpoint before the High Deviation alarm is reset. For example, the
deadband can be set to 10 so that the PV must decrease to 62 to reset the
alarm.
10 Type the number that PV must increase to reset a Low Deviation alarm.
EXAMPLE: The low deviation limit is 30 and the deadband is 1. The PV
must increase 1 unit to 26 to reset the Low Deviation alarm.
IMPORTANT: The deadband can be set so that the PV must increase above
the Raise setpoint before the Low Deviation alarm is reset. For example, the
deadband can be set to 10 so that the PV must decrease to 35 to reset the
alarm.
11 Type the number that the Rate of Change must decrease to reset a Hi Rate of
Decrease alarm.
12 Type the number that the Rate of Change must increase to reset a Hi Rate of
Increase alarm.

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Engineering Tab

3
4

210 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Table 146 - Engineering Tab Description


Item Description
1 Check, the operator settings track the program settings when mode is
Program, and program settings track the operator settings when the mode is
Operator. Transition between modes is bumpless.

Clear the checkbox, this instruction does not modify the operator settings and
program settings. The operator settings and program settings retain their
values regardless of mode. When the mode is changed, the value of a limit can
change, such as from the Program-set value to the Operator-set value.
2 Click the PV rate of change time base used.
3 Type the lower limit for the Loop PV Higher point.
4 Type the upper limit for the loop PV Lower point.
5 Minimum and maximum values for PV input.
These values are reflected on the PV bar graph on the Operator tab and the
graph on the Trends tab.
6 Type the number of units per x seconds, where x equals the number of seconds
selected for the PV rate of change time base.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 211


Chapter 4 Regulatory and Procedural Control Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2 6
7
3

Table 147 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
2 Check to enable navigation to the PV object.
3 Check to enable navigation to the Output object.
4 Type the text of the engineering units for the PV.
5 Type the number of decimal places that are used for the PV.
6 Type the name of the PV object to navigate to.
7 Type the name of the Output object to navigate to.

212 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 213


Chapter 4 Regulatory and Procedural Control Family

Rockwell Automation The Rockwell Automation® Sequencer Object (P_Seq) provides a flexible
controller-based step sequencing solution that reduces engineering time by
Sequencer Object automating common operator procedures. The step-by-step configuration
(P_Seq) makes it easy to adjust procedures directly from the HMI displays without
having to create or modify custom code in the controller. The Sequencer can be
employed in simple and complex sequences without costly tests and
re-engineering. You add, delete, or modify steps that are required accomplish
the objective of the sequence.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode.Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

1
2 6
3 7
8
4
9

Table 148 - Operator Tab Description


Item Description
1 Displays the current sequence state.
2 Displays the current step.
3 Displays the time in current step.
4 Displays the time in current sequence.
5 Click to hold the sequence.
6 Displays the step number, name, time, and the conditions that the sequence is
waiting to qualify.
7 Click to start a sequence.

214 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Item Description
8 Click to stop a sequence.
9 Click to reset a sequence.
10 Click to display the runtime sequence window.
11 Click to restart a sequence.

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1
2

Table 149 - Maintenance Tab Description


Item Description
1 Displays an indicator if there is an active wait in the current step.
2 Displays the inputs per the current step of the sequence. Inputs 0…31.
3 Click to force step complete.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 215


Chapter 4 Regulatory and Procedural Control Family

Advanced Properties Display

The Advanced Properties Display opens to the Advanced Maintenance


settings. The Advanced Properties Display provides access to device
configuration parameters and ranges, and options for device and I/O setup.
This tab is used for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 150 - Advanced Maintenance Tab Page 1 Description


Item Description
1 All inputs are available for use and are checked. Each input is qualified as part
of the step.
Clear an input if there is a maintenance issue with the input. All steps then
ignore the input and it is not used for qualification. The Sequencer goes into
Maintenance Bypass.

216 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Table 151 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Click to toggle the given output.
An output cannot be toggled if:
• It’s actively driven by the sequence
• Track Input is enabled for that input (black numbers)
A dark gray slider is an indication of the 'Off' state (0).
A white slider is an indication of the 'On' state (1).
IMPORTANT: Maintenance personnel can manipulate the output directly
from this tab if 'Track Input' on the Discrete Output Configuration page is
turned off for a particular output AND (the current Sequencer step is not using
a particular output OR the sequence is in a Held state).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 217


Chapter 4 Regulatory and Procedural Control Family

Table 152 - Advanced Maintenance Tab Page 3 Description


Item Description
1 Type a setpoint or value for the analog outputs that are configured for the
Sequencer.
Outputs that are being actively driven by the sequence cannot be written.
These outputs are unavailable.
IMPORTANT: An output can be written only if 'Track Input' on the Analog
Output Configuration page for that particular output is turn off.

218 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Engineering Tab

1
6
2
7
3
8

Table 153 - Engineering Tab Description


Item Description
1 Check to enable the manual prompt queue.
2 Check to put the sequence in a Held State if the step timer expires.
3 Check the box to indicate the Sequencer action when an interlock trips.
4 Click the Display Sequence Configuration Window button to access the
Discrete Inputs, Discrete Outputs, and Analog Outputs configuration dialog
boxes.
5 Click to configure either the Running State or the Stopping State.
6 Type a maximum value for a quantity.
7 Type a default quantity for a sequence.
8 Type a minimum value for a quantity.
9 Type a time in milliseconds that the sequence must be complete or a timeout
occurs.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 219


Chapter 4 Regulatory and Procedural Control Family

There are faceplates that open from the engineering tab that enable input and
output configuration and configuration of both individual and multiple steps.
The following figures show examples of those configuration faceplates.

Figure 15 - I/O Configuration Inputs

Figure 16 - I/O Configuration Digital Outputs

220 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Figure 17 - I/O Configuration Analog Outputs

Figure 18 - State Configuration

Figure 19 - Single Step Configuration Page 1

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 221


Chapter 4 Regulatory and Procedural Control Family

Figure 20 - Single Step Configuration Page 2

Figure 21 - Single Step Configuration Inputs

222 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Figure 22 - Single Step Configurations Digital Outputs

Figure 23 - Single Step Configurations Analog Outputs

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 223


Chapter 4 Regulatory and Procedural Control Family

Figure 24 - Multiple Step Configuration

Figure 25 - Multiple Step Configuration Inputs

224 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3

Table 154 - HMI Configuration Tab Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_Seq
object has the name ’Seq123’, then its Permissive object must be named
‘Seq123_Perm’.
2 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Seq object
has the name ’Seq123’, then its Interlock object must be named
‘Seq123_Intlk’.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
4 Type the engineering units for the quantity.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 225


Chapter 4 Regulatory and Procedural Control Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

226 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

The P_Dose Add-On Instruction controls ingredient addition to measure the


Dosing (P_Dose) quantity of ingredient that is being added. The instruction can be used for a
flowmeter or weigh scale.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 155 - P_Dose Display Elements Description
Display Element Name Display Element Description
GO_P_DoseFM Vertical Orientation
Top

GO_P_DoseFM1 Vertical Orientation


Bottom

GO_P_DoseFM2 Horizontal Orientation


Right

GO_P_DoseFM3 Horizontal Orientation


Left

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 227


Chapter 4 Regulatory and Procedural Control Family

Table 155 - P_Dose Display Elements Description


Display Element Name Display Element Description
GO_P_DoseWS Vertical orientation up.

GO_P_DoseWS1 Horizontal orientation


right.

GO_P_DoseWS2 Horizontal orientation


left.

228 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates. See Basic Faceplate Attributes on page 32.

1
2

7
3
4 8

5 9

6 1

Table 156 - Operator Tab Description


Item Description
1 Dosing Equipment Commanded State.
2 Delivery Progress Bar.
3 Configure the quantity to deliver.
4 Click to stop the Totalizer.
5 Click to clear the totalized quantity.
6 Click to stop the Totalizer flow.
7 Delivery progress.
8 Click to start the Totalizer.
9 Click to check tolerances.
10 Click to bump the Totalizer flow.
11 Click to start the Totalizer flow.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 229


Chapter 4 Regulatory and Procedural Control Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1
2

3
4

Table 157 - Maintenance Tab Description


Item Description
1 Configure the quantity before the end of delivery, when a switch to a reduced
flow rate (dribble) for finer control of the final quantity is made.
2 Configure the quantity before reaching the Setpoint Quantity when a
command the delivery equipment to stop to allow equipment to react. The
preact quantity helps prevent overshooting the delivery Setpoint.
3 Type the quantity by which delivery can exceed the setpoint. If the delivered
quantity is more than the setpoint plus this value, a tolerance check shows over
tolerance.
4 Type the quantity by which delivery can fall short of the setpoint. If the
delivered quantity is less than the setpoint minus this value, a tolerance check
shows under tolerance.

230 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Advanced Properties Display

The Advanced Properties Display opens to the Advanced Maintenance


settings. The Advanced Properties Display provides access to device
configuration parameters and ranges, and options for device and I/O setup.
This tab is used for initial system commissioning or later system changes.

Advanced Maintenance Tab

2
3

4
5

Table 158 - Advanced Maintenance Tab Description


Item Description
1 Type a value so that when the flow rate is less than this value, it is treated as
zero. This value helps prevent totalizing the transmitter error when flow is
stopped.
2 Type the percentage of delivery error.
When the delivery tolerance is checked, if no bump has occurred and if the
delivery is in tolerance, the error (difference between delivery setpoint and
actual delivery) is multiplied by this percentage and applied to the preact. The
preact self tunes and learns the correct value of the preact over time.
3 Configure the Time (in seconds) to Pulse the Clear Output to clear an external
totalizer, such as one in an intelligent flowmeter.
4 Type the amount of time to command the controlled equipment to run flow
when the bump command button is pressed. If this value is set to zero, Bump
is treated like a Jog: flow starts when the button is pressed and stops when the
button is released. If this value is greater than zero, flow is bumped for the
configured time.
5 Type the amount of time in seconds after flow is stopped for the scale reading
to settle before a tolerance check can be commanded.
6 Type the maximum allowed feedback time.
If equipment feedback is being used, the instruction allows this much time
after commanding the equipment for feedback to show the equipment in the
commanded state before raising a fault status.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 231


Chapter 4 Regulatory and Procedural Control Family

Engineering Tab

1
2
3

4
5

6
7

8
9

Table 159 - Engineering Page 1 Description


Item Description
1 Check to adjust the Preact automatically based on the actual versus setpoint
Quantity after each successful delivery.
Clear this checkbox to leave the Preact as entered.
2 Check if the flowmeter provides a Rate input but no Quantity input. The Rate
is totalized (integrated) to calculate Quantity.
3 Check if the flowmeter provides a Quantity input but no Rate input. The rate
of change in the Quantity is used as the Rate.
4 Check to command the equipment to a slower Dribble rate as delivery nears
completion to improve the accuracy of Quantity delivered.
5 Check if the controlled equipment provides feedback of its running, dribbling,
and stopped status to this instruction. This instruction checks that the
equipment is performing the commanded function and provides a status (and
optional alarm) if the equipment fails to respond as commanded within a
configurable time.
IMPORTANT: The feedback fault time is configured on the Advanced
Maintenance tab.
Clear this checkbox if the controlled equipment does not provide feedback of
its status. The instruction assumes that the equipment is performing the
commanded function and no equipment failure-to-respond checks occur.
6 Check if you want the dosing instruction to attempt to stop the controlled
equipment if an equipment fault is reported (Inp_CtrldEqupFault) or detected
(via feedbacks).
Clear this checkbox if you want the dosing instruction to keep performing its
current function, even if an equipment fault occurs.
7 Check to enable bumpless Program/Operator transition of Quantity Setpoint,
Dribble Quantity, Preact, and Tolerance Threshold settings (tracking).
8 Check to designate as a Transfer In instance.
9 Check to designate as a Transfer Out instance.

232 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

2
3

4
5

Table 160 - Engineering Tab Page 2 Description


Item Description
1 Type the maximum allowed quantity to deliver. The quantity setpoint is
clamped not to exceed this value.
2 Type the number of counts in Inp_QtyPV that equal one engineering unit of
quantity delivered. This value is used with pulse output flowmeters and a
pulse input I/O card.
3 Type the rate to quantity engineering units multiplier. This value is used if the
input is in one unit of measure, such as gallons per minute, and the total is in
another that requires conversion above and beyond time units, such as barrels.
4 Type the quantity rollover. This value is used when a quantity or pulse count
input rolls over to zero at some value, such as 999,999 counts.
5 Type the filter time constant for calculated rate.
6 Click to set the time base for rate.
7 Type the number of units per x seconds, where x equals the number of seconds
selected for the time base for rate.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 233


Chapter 4 Regulatory and Procedural Control Family

2
3

Table 161 - Engineering Tab Page 3 Description

Item Description
1 Check to keep control of dosing Start and Stop commands with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
2 Check to keep control of the Setpoint quantity setting with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
3 Check to keep control of the Dribble and Preact quantity settings with the
Operator, Program, External, or Follow the Source even if the instruction is in
Program command source.
4 Check to keep control of the high and low Tolerance settings with the
Operator, Program, External, or Follow the Source even if the instruction is in
Program command source.
5 Type the normal running delivery rate that is used when the P_Dose
instruction is in simulation (Inp_Sim = 1).
6 Type the dribble (slow) delivery rate that is used when the P_Dose instruction
is in simulation (Inp_Sim = 1).

234 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

3
4

5
6

1
2

Table 162 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation to the Rate Input object faceplate.
IMPORTANT: The name of the Channel Rate object in the controller must be
the name of the object with the suffix ‘_ChanRate’. For example, if your
P_Dose object has the name ‘DoseFM123’, then its Channel Rate object must
be named ‘DoseFM123_ChanRate’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
3 Type the units of measure descriptor for the Quantity delivered.
4 Type the units of measure descriptor for the Rate of delivery.
5 Type in the number of decimal places that are displayed for the Quantity
Process Variable
6 Type in the number of decimal places that are displayed for the Rate Process
Variable

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 235


Chapter 4 Regulatory and Procedural Control Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

236 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Lead/Lag/Standby The P_LLS (Lead/Lag/Standby motor group) Add-On Instruction provides


control of a parallel group of motors. Such groups are commonly used for a
Motor Group (P_LLS) group of pumps that maintain pressure on a header despite wide changes in
demand, such as in municipal-scale or plant-scale water distribution.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 163 - P_LLS Display Elements
Display Element Display Element Description
Name
GO_P_LLS_Motors A group of motors.

GO_P_LLS_Blowers A group of blowers.

GO_P_LLS_Pumps A group of pumps.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 237


Chapter 4 Regulatory and Procedural Control Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates. See Basic Faceplate Attributes on page 32.

3 5

4 6

Table 164 - Operator Tab Description


Item Description
1 Motor state indicator.
2 Individual motor state indicators.
3 Click to rotate motor assignments. The lead motor is demoted to the end of the
list. Motors are started or stopped to satisfy Number of Motors to Run.
4 Type a number between 0 and the maximum demand to indicate the number of
motors to run.
5 Click to start group.
6 Click to stop group.
IMPORTANT: Motors stop in reverse order of starting unless First Started is
First Stopped on the engineering tab is checked.

238 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

Table 165 - Maintenance Tab Description


Item Description
1 Check to place a motor in service (not in maintenance bypass).
Clear the checkbox to place a motor out of service (maintenance bypass)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 239


Chapter 4 Regulatory and Procedural Control Family

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Maintenance Tab

1
2

Table 166 - Advanced Maintenance Tab Description


Item Description
1 Type the number of seconds after a start or stop that the next start is allowed.
2 Type the number of seconds after a start or stop that the next stop is allowed.

240 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Engineering Tab

7
8
9

1
2

3
4
5
6

Table 167 - Engineering Tab Page 1 Description


Item Description
1 Check to allow the Rotate command to rotate motor assignments.
2 Check to rotate the lead motor to the end of list upon stopping all motors.
3 Check so that the first motor that is started is the first motor that is stopped.
4 Check to allow the Operator Start or Stop command to reset any previous
faults (Interlock Trip), then start or stop the group.
Clear this checkbox to reset faults by using only the reset commands.
5 Check to allow the External Start or Stop command to reset any previous
faults (Interlock Trip), then start or stop the group.
Clear this checkbox to reset faults by using only the reset commands.
6 Check to bypass interlocks and permissives that are bypassable when in
Override command source.
7 Type the number of motors (2…30) in the group.
8 Type the highest number of motors that can be running.
9 Type the lowest number of motors that can be running.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 241


Chapter 4 Regulatory and Procedural Control Family

1
2

3
4

Table 168 - Engineering Tab Page 2 Description


Item Description
1 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
2 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
3 Check to have Program settings (such as Speed Reference) track Operator
settings in Operator command source, and have Operator settings track
Program settings in Program command source.
4 Check to have Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.
5 Click a number to open the corresponding Motor Configuration dialog box.

242 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Motor Configuration Dialog Box

1
2

Table 169 - Motor Configuration Dialog Box Description


Item Description
1 Check to enable navigation to a motor object.
2 Type the name of the motor object to navigate to.
IMPORTANT: This field is only visible when Enable Navigation to Motor
Object is checked.
3 Type the start priority within the list of the motors selected.
Motors start in order of priority (0...31) and the higher numbers start first.
4 Type the starting preference of the motor selected.
When two or more motors have the same priority, these motors start in the
order of preference (0...31) and the higher numbers start first.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 243


Chapter 4 Regulatory and Procedural Control Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2

Table 170 - HMI Configuration Tab Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_LLS
object has the name ’LLS123’, then its Permissive object must be named
‘LLS123_Perm’.
2 Check if an Interlock object is used with this group. Checking this box
changes the Interlock indicator to a clickable button to open the Interlock
faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
object name with the suffix ‘_Intlk’. For example, if your P_LLS object has
the name’LLS123’, then its Interlock object must be named ‘LLS123_Intlk’.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

244 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Regulatory and Procedural Control Family Chapter 4

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 245


Chapter 4 Regulatory and Procedural Control Family

Notes:

246 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 5

Motors Family

The Process Objects in this group provide control and monitoring for smart
motor controllers, drives, and overload relays. This document is for the
visualization files, display elements, global objects, and HMI information. The
operation of the Add-on Instructions and controller code is contained in
publication PROCES-RM013.

Common Motors Faceplate attributes are common to several Add-On Instructions in the motors
family. Attributes specific to a motor are detailed in the individual sections. If a
Faceplates functionality is not enabled, the buttons are not visible. Common attributes
for motors are detailed in this section. Basic attributes are described in the
overview. See Basic Faceplate Attributes on page 32

Common Operator Tab - Motors

4
5

2 6

Table 171 - Common Operator Tab Attributes


Item Description
1 Motor state (stopping, stopped, starting, or running)
2 Motor stop
3 Current command source (Program, Operator, Override, Maintenance, or Hand)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 247


Chapter 5 Motors Family

Item Description
4 Click to start motor slow (motor run for single speed motors)
5 Click to start motor fast
6 Click to jog Motor

Common Maintenance Tab - Motors

1 3

Table 172 - Common Maintenance Tab Attributes


Item Description
1 Click to open the runtime faceplate.
IMPORTANT: This option is only available if 'Enable navigation to run time
object' on the HMI Configuration tab is checked.
See Run Time and Start Counter (P_RunTime) on page 405
2 Click Yes to bypass checking of bypassable interlocks and permissives. Click
No to enable checking of all interlocks and permissives.
3 Click to open the Restart Inhibit faceplate.
IMPORTANT: This option is only available if 'Enable navigation to restart
inhibit object' on the HMI Configuration tab is checked.
See Restart Inhibit for Large Motor (P_ResInh) on page 407
4 Click to open the Overload faceplate.
IMPORTANT: This option is only available if 'Enable navigation to overload
object' on the HMI Configuration tab is checked.
5 Check to have this instruction use run feedback to check for motor Fail to Start
or fail to Stop.
IMPORTANT: This option is only available if 'Motor has Run Feedback' on
page 1 of the Engineering tab is checked.

248 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Common Trends Tab - Motors

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions

1
2

3 4 5 6 7 8 9

Table 173 - Common Trends Tab Description


Item Description
1 Setpoint
2 Process Variable
3 Click to view the oldest data available.
4 Click to move trend data back 2 minutes.
5 Click to move trend data back 1 minute.
6 Click to scroll new data.
7 Click to move trend data forward 1 minute.
8 Click to move trend data forward 2 minutes.
9 Click to move to the most current trend data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 249


Chapter 5 Motors Family

Single-speed Motor The P_Motor (Single-speed Motor) Add-On Instruction controls a


non-reversing, single-speed motor in various command sources and monitors
(P_Motor) for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_Motor)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix® system, aid consistency and save engineering time.
Table 174 - P_Motor Display Elements
Display Element Name Display Element Description
GO_P_Motor_R Motors operate in different
positions: right, up, and down.
GO_P_Motor_U

GO_P_Motor_D

GO_P_Motor_Blower_R Blowers operate in different


positions: right, left, up, and
GO_P_Motor_Blower_L down.

GO_P_Motor_Blower_U

GO_P_Motor_Blower_D

250 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 174 - P_Motor Display Elements


Display Element Name Display Element Description
GO_P_Motor_Conveyer Conveyor that is shown as a
_R display element.

GO_P_Motor_Inline_U Inline motors operate in several


positions: up, right, left, and
GO_P_Motor_Inline_R down.

GO_P_Motor_Inline_L

GO_P_Motor_Inline_D

GO_P_Motor_Pump_R Pumps operate in several


positions: right, left, and up.
GO_P_Motor_Pump_L

GO_P_Motor_Pump_U

GO_P_Motor_Agitator_ Agitator that is shown as a


D display element.

GO_P_Motor_Mixer_U Mixer that is shown as a


display element.

GO_P_Motor_RPump_U Rotary gear pump that is


shown as a display element.

GO_P_Motor_Fan_D Fan that is shown as a display


element.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 251


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

252 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 175 - Advanced Maintenance Tab Description


Item Description
1 Type the time, in seconds, to allow the run feedback to show that the motor has
started before raising a fail to start alarm.
2 Type the time, in seconds, to allow the run feedback to show that the motor has
stopped before raising a fail to stop alarm.
3 Type the time, in seconds, for the maximum jog time for the motor.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 253


Chapter 5 Motors Family

Engineering Tab

1
2
3

4
5
6

7
8

Table 176 - Engineering Tab Page 1 Description


Item Description
1 Check if the motor provides a run feedback to Inp_RunFdbk.
Clear this checkbox if there is no run feedback.
IMPORTANT: This check places the device in Maintenance Bypass unless
'Use Run Feedback' on the Maintenance tab is checked.
2 Check to allow the Operator Start or Stop command to reset any previous faults
(I/O fault, Fail to Start, Fail to Stop, or Interlock Trip), then start or stop motor.
Clear this checkbox to reset faults by using only the reset commands.
3 Check to allow the External Start or Stop command to reset any previous faults
(I/O fault, Fail to Start, Fail to Stop, or Interlock Trip), then start or stop motor.
Clear this checkbox to reset faults by using only the reset commands.
4 Check to enable the jog feature of the motor.
5 Check to allow the Operator Start or Stop command to reset any previous faults
(I/O fault, Fail to Start, Fail to Stop, or Interlock Trip), then start or stop motor.
Clear this checkbox to reset faults by using only the reset commands.
6 Check to have the Operator Stop command available in any command source.
Clear this checkbox to have the Operator Stop command available only in the
Operator and Maintenance command sources.
7 Check to have the External Stop command available in any command source.
Clear this checkbox to have the External Stop command available only in the
Operator and Maintenance command sources.
8 Check to allow local Start/Stop without alarm.
Clear this checkbox to allow start/stop by using only Program or Operator
commands or Override Logic.

254 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2
3

Table 177 - Engineering Tab Page 2 Description


Item Description
1 Check to stop the motor if an I/O fault is detected.
Clear this checkbox to show only the I/O fault status/alarm and not stop the
motor if an I/O fault is detected.
2 Check to stop the motor if a fail to Start fault is detected.
Clear this checkbox to show only the Fail to Start status/alarm and not stop the
motor if a fail to Start fault is detected.
3 The motor always stops on an interlock trip. This item cannot be unchecked. It
is displayed as a reminder that the Interlock Trip function always trips the
motor.
4 Type the time (in seconds) the audible alarm sounds on a commanded start.
5 Set the time delay (in seconds) for running or stopped status to be echoed back
when the simulation is enabled or when run feedback is not used.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 255


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. Configure the description, label, tag,
and security area for the device. See Basic Faceplate Attributes on page 32 for
the description of the common attributes.

1
2
3

4
5
6

Table 178 - HMI Configuration Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_Motor
object has the name ’Motor123’, then its Permissive object must be named
‘Motor123_Perm’.
2 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
3 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
4 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.

256 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
5 Check if an Overload object is used with this motor. This check makes the
Overload button visible.
IMPORTANT: The name of the Overload object in the controller must be the
name of the object with the suffix ‘_Ovld’. For example, if your P_Motor
object has the name ‘Motor123’, then its Overload object must be named
‘Motor123_Ovld’
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 257


Chapter 5 Motors Family

Two-speed Motor The P_Motor2Spd (Two-speed Motor) Add-On Instruction controls a


non-reversing, two-speed motor (fast/slow/stopped) in various command
(P_Motor2Spd) sources and monitors for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_Motor2Spd)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
P_Motor2Spd uses the same Display Elements as P_Motor. See Display
Elements (P_Motor) on page 250

258 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source.

2
3
4
5

Table 179 - Operator Tab Description


Item Description
1 Motor state indicator.
2 Click to stop motor.
3 Click to start motor slow.
4 Click to start motor fast.
5 Click to jog motor.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 259


Chapter 5 Motors Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems, and disable the device for routine maintenance.

Table 180 - Maintenance Tab Description


Item Description
1 Click Yes to bypass checking of bypassable interlocks and permissives. Click
No to enable checking of all interlocks and permissives.
2 Click to open the Overload faceplate.
IMPORTANT: This option is only available if 'Enable navigation to overload
object' on the HMI Configuration tab is checked.
3 Check to have this instruction use run feedback to check for motor Fail to Start
or fail to Stop.
IMPORTANT: This option is only available if 'Motor has Run Feedback' on
page 1 of the Engineering tab is checked.

260 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

Advanced Maintenance Tab

Table 181 - Advanced Maintenance Tab Description


Item Description
1 Type the time to allow the run feedback to show that the motor has started
before raising a fail to start alarm.
2 Type the time to allow the run feedback to show that the motor has stopped
before raising a Fail to Stop alarm.
3 Type the time to allow the motor to jog.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 261


Chapter 5 Motors Family

Engineering Tab

The Engineering tab is divided into two pages.

Engineering Tab Page 1

1
2
3

4
5
6

7
8

Table 182 - Engineering Page 1 Description


Item Description
1 Check if the motor provides run feedback to Inp_SlowRunFdbk and
Inp_FastRunFdbk.
Clear this checkbox if there is no run feedback.
IMPORTANT: This check places the device in Maintenance Bypass unless
'Use Run Feedback' on the Maintenance tab is checked.
2 Check to allow the Operator commands for Start Slow, Start Fast, or Stop to
reset any previous faults (I/O fault, Fail to Start, Fail to Stop, Interlock Trip).
Then start or stop motor.
Clear this checkbox to reset faults only using the reset code.
3 Check to allow the External commands for Start Slow, Start Fast, or Stop to
reset any previous faults (I/O fault, Fail to Start, Fail to Stop, Interlock Trip).
Then start or stop motor.
Clear this checkbox to reset faults only using the reset code.
4 Check to allow motor to be jogged.
5 Check to bypass bypassable interlocks and permissives in Override command
source.
6 Check to have the Operator Stop command available in any command source.
Clear this checkbox to have the Operator Stop command available only in the
Operator and Maintenance command sources.
7 Check to have the External Stop command available in any command source.
Clear this checkbox to have the External Stop command available only in the
Operator and Maintenance command sources.
8 Check to allow local Start/Stop without alarm.
Clear this checkbox to allow start/stop only using Program or Operator
commands or Override Logic.

262 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab Page 2

1
2
3

Table 183 - Engineering Page 2 Description


Item Description
1 Check to stop the motor if an I/O fault is detected.
Clear this checkbox to show only the I/O fault status/alarm and not stop the
motor if an
I/O fault is detected.
2 Check to stop the motor if a fail to Start fault is detected.
Clear this checkbox to show only the Fail to Start status/alarm and not stop the
motor if a fail to Start fault is detected.
3 The motor always stops on an interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always trips the motor.
4 Type the amount of time to sound the audible alarm when the motor starts.
5 Type the time delay between when the run output has turned off for one speed
and when it is turned on for the other speed.
6 Type the time delay (in seconds) for the running or stopped status to be echoed
back when the simulation is enabled or when run feedback is not used.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 263


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. Configure the description, label, tag,
and security area for the device. See Basic Faceplate Attributes on page 32 for
the description of the common attributes.

5
6

Table 184 - HMI Configuration Page 1 Description


Item Description
1 Check if a run slow or run fast permissive object is used with this motor.
IMPORTANT: The name of the Slow or Fast Permissive object in the
controller must be the name of the object with the suffix ‘_FastPerm’ or
‘_SlowPerm’. For example, if your P_Motor2Spd object has the name
’Motor123’, then its Slow Permissive object must be named
‘Motor123_SlowPerm’ or its Fast Permissive object must be named
‘Motor123_FastPerm’.
2 Check if an interlock object is used with this motor.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor2Spd
object has the name ’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
3 Check if a restart inhibit object is used with this motor.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor2Spd object has the name ’Motor123’, then its Restart Inhibit object
must be named ‘Motor123_ResInh’.
4 Check if a run time object is used with this motor.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your
P_Motor2Spd object has the name ‘Motor123’, then its Run Time object must
be named ‘Motor123_RunTime’.
5 Type the text to display when the motor is running fast.
6 Type the text to display when the motor is running slow.

264 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Page 2 Description

Item Description
1 Check if an overload object is used with this motor.
IMPORTANT: The name of the Overload object in the controller must be the
name of the object with the suffix ‘_Ovld’. For example, if your P_Motor2Spd
object has the name ‘Motor123’, then its Overload object must be named
‘Motor123_Ovld’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 265


Chapter 5 Motors Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab
The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

266 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Reversing Motor The P_MotorRev (Reversing Motor) Add-On Instruction controls a reversing,
motor (forward/reverse/stopped) in various command sources and monitors
(P_MotorRev) for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_MotorRev)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time. P_MotorRev
uses the same Display Elements as P_Motor. See Display Elements (P_Motor)
on page 250

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 267


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

This instruction also includes a reverse button.

Table 185 - Operator Tab Description


Item Description
1 Click to start motor in reverse direction.

268 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 269


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 186 - Advanced Maintenance Tab Description


Item Description
1 Type the time, in seconds, to allow the run feedback to show that the motor has
started before raising a fail to start alarm.
2 Type the time, in seconds, to allow the run feedback to show that the motor has
stopped before raising a fail to stop alarm.
3 Type the time, in seconds, for the maximum jog time for the motor.

270 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

1
2
3

4
5
6

7
8

Table 187 - Engineering Page 1 Description


Item Description
1 Check if the motor provides run feedback to Inp_SlowRunFdbk and
Inp_FastRunFdbk.
Clear this checkbox if there is no run feedback.
IMPORTANT: This check places the device in Maintenance Bypass unless
'Use Run Feedback' on the Maintenance tab is checked.
2 Check to allow the Operator commands for Start Slow, Start Fast, or Stop, to
reset any previous faults (I/O fault, Fail to Start, Fail to Stop, Interlock Trip).
Then start or stop motor.
Clear this checkbox to reset faults only using the reset code.
3 Check to allow the External commands for Start Slow, Start Fast, or Stop, to
reset any previous faults (I/O fault, Fail to Start, Fail to Stop, Interlock Trip).
Then start or stop motor.
Clear this checkbox to reset faults only using the reset code.
4 Check to allow motor to be jogged.
5 Check to bypass bypassable interlocks and permissives in Override command
source.
6 Check to have the Operator Stop command available in any command source.
Clear this checkbox to have the Operator Stop command available only in the
Operator and Maintenance command sources.
7 Check to have the External Stop command available in any command source.
Clear this checkbox to have the External Stop command available only in the
Operator and Maintenance command sources.
8 Check to allow local Start/Stop without alarm.
Clear this checkbox to allow start/stop only using Program or Operator
commands or Override Logic.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 271


Chapter 5 Motors Family

1
2
3

Table 188 - Engineering Page 2 Description


Item Description
1 Check to stop the motor if an I/O fault is detected.
Clear this checkbox to show only the I/O fault status/alarm and not stop the
motor if an I/O fault is detected.
2 Check to stop the motor if a fail to Start fault is detected.
Clear this checkbox to show only the Fail to Start status/alarm and not stop the
motor if a fail to Start fault is detected.
3 The motor always stops on an interlock trip. This item cannot be unchecked. It
is displayed as a reminder that the Interlock Trip function always trips the
motor.
4 Type the time (in seconds) the audible alarm sounds on a commanded start.
5 Set the time delay (in seconds) for running or stopped status to be echoed back
when the simulation is enabled or when run feedback is not used.

272 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. Configure the description, label, tag,
and security area for the device. See Basic Faceplate Attributes on page 32 for
the description of the common attributes.

6
7

1
2

3
4
5

Table 189 - HMI Configuration Page 1 Description


Item Description
1 Check if a run forward permissive object is used with this motor. This check
changes the Permissive indicator to a clickable button to open the Permissive
faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_Motor
object has the name ’Motor123’, then its Permissive object must be named
‘Motor123_Perm’.
2 Check if a run reverse Permissive object is used with this motor. This check
changes the Permissive indicator to a clickable button to open the Permissive
faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_Motor
object has the name ’Motor123’, then its Permissive object must be named
‘Motor123_Perm’.
3 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
4 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 273


Chapter 5 Motors Family

Table 189 - HMI Configuration Page 1 Description


Item Description
5 Check if a RunTime object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the RunTime object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.
6 Type the text to display when the motor is running forward.
7 Type the text to display when the motor is running reverse.

1
2

Table 190 - HMI Configuration Page 2 Description


Item Description
1 Check if an Overload object is used with this motor. This check makes the
Overload button visible.
IMPORTANT: The name of the Overload object in the controller must be the
name of the object with the suffix ‘_Ovld’. For example, if your P_Motor
object has the name ‘Motor123’, then its Overload object must be named
‘Motor123_Ovld’
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

274 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 275


Chapter 5 Motors Family

Hand-operated Motor The P_MotorHO (Hand-operated Motor) Add-On Instruction monitors a


locally controlled (hand-operated) motor.
(P_MotorHO)
This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_MotorHO)

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

276 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

The P_MotorHO instruction has graphic symbols for motors, blowers,


agitators, and pumps for use on process graphic displays.

Table 191 - P_MotorHO Display Elements


Display Element Name Display Element Description
GO_P_MotorHO_R Motors operating in
GO_P_MotorHO_U different positions.
GO_P_MotorHO_D

GO_P_MotorHO_Blower_ Blowers operating in


R different positions.
GO_P_MotorHO_Blower_
L
GO_P_MotorHO_Blower_
U
GO_P_MotorHO_Blower_
D

GO_P_MotorHO_Conveyo Conveyor shown as a


r_R display element.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 277


Chapter 5 Motors Family

Table 191 - P_MotorHO Display Elements


Display Element Name Display Element Description
GO_P_MotorHO_Inline_U Inline motors operating in
GO_P_MotorHO_Inline_R different positions.
GO_P_MotorHO_Inline_L
GO_P_MotorHO_Inline_D

GO_P_MotorHO_Pump_R Pumps operating in


GO_P_MotorHO_Pump_L different positions.
GO_P_MotorHO_Pump_U

GO_P_MotorHO_Agitator_ Agitator shown as a display


D element.

GO_P_MotorHO_Mixer_U Mixer shown as a display


element.

GO_P_MotorHO_RPump_ Rotary gear pump shown as


U a display element.

GO_P_MotorHO_Fan_D Fan shown as a display


element.

278 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 279


Chapter 5 Motors Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instruction faceplates for the motors family.

See Common Maintenance Tab - Motors on page 248

280 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 192 - Advanced Maintenance Tab Description


Item Description
1 Enter the amount of time to allow motor run feedback to show that the motor
stopped after a trip is commanded. If the motor does not show stopped in the
allowed time, a Trip Fail alarm is raised.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 281


Chapter 5 Motors Family

Engineering Tab

1
2

3
4

5
6

Table 193 - Engineering Tab Description


Item Description
1 Check if a trip output is connected to the P_MotorHO instruction to stop the
motor on an interlock or trip command. This check makes the trip (stop)
command button visible on the Operator tab.
2 Check to allow the operator trip command to reset any previous faults (I/O fault,
fail to trip, interlock trip) then trip motor.
Clear this checkbox to reset faults by using only the reset command.
3 Check for a two speed (fast/slow) motor.
IMPORTANT: This option is unavailable if 'Motor is reversing' is checked.
Clear this checkbox for a reversing motor or a single-speed motor.
4 Check for a reversing (forward/reverse) motor.
IMPORTANT: This option is unavailable if 'Motor is 2 speed' is checked.
Clear this checkbox for a two-speed motor or a single-speed motor.
5 Check to send the trip output to the motor if an I/O fault is detected.
Clear this checkbox to show only the I/O fault status/alarm and not trip the
motor if an I/O fault is detected.
6 The motor always trips on an Interlock Trip. This item cannot be unchecked. It
is displayed as a reminder that the interlock trip function always trips the motor.
7 Check to keep sending the trip output to the motor on a trip, even if position
feedback does not confirm the motor stopped.
Clear this checkbox to stop sending the trip output to the motor when the motor
trip times out and the fail to trip status is set.
8 Type the amount of time (in seconds) the motor status shows tripping before
showing a stopped or running status when the motor is tripped and the I/O are
being simulated (Inp_Sim = 1).

282 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

5
6

1
2

Table 194 - HMI Configuration Tab Description


Item Description
1 Check if an interlock object is connected to Inp_Intlk. This check changes the
interlock indicator on the Operator tab to a button that opens the interlocks
faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_MotorHO
object has the name’MotorHO123’, then its Interlock object must be named
‘MotorHO123_Intlk’.
2 Check if a Run Time instruction is connected to the status of this instruction for
accumulating total motor run time and number of starts. This check displays the
‘hour meter’ button, which opens the run time faceplate, visible on the Operator
tab.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your
P_MotorHO object has the name ‘MotorHO123’, then its Run Time object must
be named ‘MotorHO123_RunTime’.
3 Check if an Overload object is connected. This check displays the button, which
opens the Overload faceplate, visible on the Operator tab.
IMPORTANT: The name of the Overload object in the controller must be the
name of the object with the suffix ‘_Ovld’. For example, if your P_MotorHO
object has the name ‘MotorHO123’, then its Overload object must be named
‘MotorHO123_Ovld’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 283


Chapter 5 Motors Family

Item Description
4 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that has
HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag is
created for the P_LLS object that is given the alias P101_More. When the more
information button is pressed on the motor, it links to P101_More. This will
open the faceplate for the LLS object.
5 Type the text to show after ‘running’ when a 2-speed motor is running fast.
6 Type the text to show after ‘running’ when a 2-speed motor is running slow.

284 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 285


Chapter 5 Motors Family

Discrete 2-, 3-, 4-state The P_D4SD (Discrete 2-, 3-, 4-state Device) Add-On Instruction controls
and monitors feedback from a discrete 2-state, 3-state, or 4-state device in
Device (P_D4SD) various command sources, monitoring for fault conditions. These devices
include multiple-speed motors or multiple-position valves.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_D4SD)

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 195 - P_D4SD Display Elements Description
Display Element Name Display Element Description
GO_P_D4SD_4Way Three/Four-Way Valve.
The Three/Four-way Valve
parameters define the inlet and
output ports of the valve:
• No. 110 - Top port open state
• No. 111 - Right port open state
• No. 112 - Bottom port open
state
• No. 113 - Left port open state

• 0 = Inlet (always shown as


open)
• 1 = Open when Val_Sts = 1
(state 0)
• 2 = Open when Val_Sts = 2
(state 1)
• 3 = Open when Val_Sts = 3
(state 2)
• 4 = Open when Val_Sts = 4
(state 3)
GO_P_D4SD_3Way_SO Two-Way Solenoid-operated
Rt Diverter Valve in different
positions: right, left, bottom, and
top.
Parameters define the inlet and
output ports of the Two-way
GO_P_D4SD_3Way_SO Solenoid-operated Diverter
Lt Valve.

GO_P_D4SD_3Way_SO
Btm

GO_P_D4SD_3Way_SO
Top

286 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 195 - P_D4SD Display Elements Description


Display Element Name Display Element Description
GO_P_D4SD_Diverter Two Way Diverter Valve in open
top-left and open top-right
positions.
The Two-way Diverter Valve
parameters define the state of the
GO_P_D4SD_Diverter1 valve:
• State 0: Open top-left
• State 1: Open top-right
• State 2: —
• State 3: —
GO_P_D4SD_3WayMO Two-Way Motor-operated
_Rt Diverter Valve in different
positions: right, left, bottom, and
top.
Parameters define the inlet and
output ports of the Two-way
GO_P_D4SD_3WayMO Motor-operated Diverter Valve.
_Lt

GO_P_D4SD_3WayMO
_Btm

GO_P_D4SD_3WayMO
_Top

GO_P_D4SD_R Motors in different positions:


right, up, and down.

GO_P_D4SD_U

GO_P_D4SD_D

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 287


Chapter 5 Motors Family

Table 195 - P_D4SD Display Elements Description


Display Element Name Display Element Description
GO_P_D4SD_Blower_R Blowers in different positions:
right, left, up, and down.

GO_P_D4SD_Blower_L

GO_P_D4SD_Blower_U

GO_P_D4SD_Blower_D

GO_P_D4SD_Conveyor Conveyor
-R

GO_P_D4SD_Inline_U Inline Motors in different


positions: up, left, down, and
right.

GO_P_D4SD_Inline_L

GO_P_D4SD_Inline_D

GO_P_D4SD_Inline_R

288 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 195 - P_D4SD Display Elements Description


Display Element Name Display Element Description
GO_P_D4SD_Pump_R Pumps in different positions:
right, left, and up.

GO_P_D4SD_Pump_L

GO_P_D4SD_Pump_U

GO_P_D4SD_Agitator_ Agitator in down position.


D

GO_P_D4SD_Mixer_U Mixer in up position.

GO_P_D4SD_RPump_ Rotary Gear Pump in up position.


U

GO_P_D4SD_Fan_D Fan in down position.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 289


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

Table 196 - Operator Tab Description


Item Description
1 Device state indicator
2 Move to state command buttons

290 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 291


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 197 - Advanced Maintenance Tab Description


Item Description
1 Type a value (0…2,147,483.647) to indicate the time (seconds) to energize
outputs to the device to be sure that they are latched in.
(0 = output held continuously)
2 Type a value (0…2,147,483.647) to indicate the time (seconds) to allow the
device to reach the commanded state before issuing a fault.

292 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

The engineering tab is divided into three pages.

3
4
5

Table 198 - Engineering Page 1 Description


Item Description
1 Click to select the number of states.
2 Check to reset a fault upon a new operator command.
3 Check to reset a fault upon a new external command.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 293


Chapter 5 Motors Family

Item Description
4 Check (= 1) to make Operator State 0 (OCmd_St0) available in any command
source.
Clear this checkbox (= 0) to make Operator State 0 (OCmd_St0) available
only in Operator or Maintenance command source.
5 Check (= 1) to make External State 0 (XCmd_St0) available in any command
source.
Clear this checkbox (= 0) to make External State 0 (XCmd_St0) available only
in Operator or Maintenance command source.
6 Click a state to open the P_D4SD State Configuration display for that state.

This display directs how the P_D4SD instruction commands the device state
via outputs and determines the actual device state via feedback inputs. The
first two columns for output set parameters, Cfg_OutSt[x]Write, and
Cfg_OutSt[x]Value, determine how outputs are written to command to a state.
The second two columns for feedback set parameters, Cfg_FdbkSt[x]Check,
and Cfg_FdbkSt[x]State, determine how the state is interpreted from the
input values.

1
2
3
4
5

294 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 199 - Engineering Page 2 Description


Item Description
1 Check to shed if a Device Fault is detected.
2 Check to shed if an I/O Fault is detected.
3 Check to shed if target state is not reached.
4 The device always sheds an Interlock Trip. This item cannot be unchecked. It
is displayed as a reminder that the Interlock Trip function always triggers a
shed.
5 Click to determine whether you hold position or go to state 0 upon a shed
condition.
6 Type a value (seconds) to indicate the delay to echo back reaching the state
when in simulation.

1
2

Table 200 - Engineering Page 3 Description


Item Description
1 Click to sound an audible on a commanded stage from State 0.
2 Click to sound an audible on a commanded stage from any State.
3 Type the time (in seconds) that the audible sounds when there is a commanded
State change.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 295


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Table 201 - HMI Configuration Page 1 Description


Item Description
1 Check if the corresponding north, south, east, or west Permissive object is
used with this device. This check changes the Permissive Indicator to a button
that accesses the Permissive faceplate.
IMPORTANT: The name of the Permissives object in the controller must be
the name of the object with the suffix ‘_Perm#’, where ‘#’ is the permissive
number (0…3) For example, if your P_D4SD object has the name
’D4SD123’, then its Permissives object must be named ‘D4SD123_Perm0’.
2 Type text to describe the state.

296 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2

Table 202 - HMI Configuration Page 2 Description


Item Description
1 Check if an interlock object is connected to Inp_Intlk. This check changes the
interlock indicator on the Operator tab to a button that opens the interlocks
faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_D4SD
object has the name’D4SD123’, then its Interlock object must be named
‘D4SD123_Intlk’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 297


Chapter 5 Motors Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

298 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Variable Speed Drive The P_VSD (Variable Speed Drive) Add-On Instruction is used to operate one
variable speed motor by using a drive (AC variable frequency or DC) in various
(P_VSD) command sources, monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_VSD)

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 203 - P_VSD Display Elements Description
Display Element Name Display Element Description
GO_P_VSD Motors operate in different
positions: right, up, and
GO_P_VSD_1 down.

GO_P_VSD_4

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 299


Chapter 5 Motors Family

Table 203 - P_VSD Display Elements Description


Display Element Name Display Element Description
GO_P_VSD_Blower_1 Blowers operate in
different positions: right,
GO_P_VSD_Blower_2 left, up, and down.

GO_P_VSD_Blower_3

GO_P_VSD_Blower_4

GO_P_VSD_Conveyer_ Conveyor shown as a


Lt2Rt display element.

GO_P_VSD_Inline_1 Inline Motors operate in


several positions: up, right,
GO_P_VSD_Inline_2 left, and down.

GO_P_VSD_Inline_3

GO_P_VSD_Inline_4

300 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 203 - P_VSD Display Elements Description


Display Element Name Display Element Description
GO_P_VSD_Pump_1 Pumps operate in several
positions: right, left, and
GO_P_VSD_Pump_2 up.

GO_P_VSD_Pump_3

GO_P_VSD_Agitator Agitator shown as a display


element.

GO_P_VSD_Mixer Mixer shown as a display


element.

GO_P_VSD_RotPump Rotary Gear Pump shown


as a display element.

GO_P_VSD_Fan Fan shown as a display


element.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 301


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

2
3

Table 204 - Operator Tab Description


Item Description
1 Current speed of drive
2 Setpoint for the speed of the drive
3 Start motor in reverse

302 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Table 205 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 303


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

3
4

Table 206 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time to allow for the run feedback on the drive to confirm
that the drive has started before raising a Fail to Start alarm.
3 Type the amount of time to allow for the run feedback on the drive to confirm
that the drive has stopped before raising a Fail to Stop alarm.
TIP: Allow extra time for the drive to decelerate or coast to zero speed before
it returns a confirmed Stopped status.
4 Type the maximum amount of time allowed to jog the motor.

304 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

The engineering tab has five pages.

1
2
5
6

7
8

3
4
9
10

If Speed Feedback is disabled on page 2 of the Engineering tab, the Speed


Feedback part (above dashed line) of the preceding image is not displayed and
the loopback options are not available.

Table 207 - Engineering Tab Page 1 Description


Item Description
1 Enter the raw input count that corresponds to the maximum speed feedback
from the drive
2 Enter the raw input count that corresponds to the minimum speed feedback
from the drive. (This value is usually zero.)
3 Enter the engineering unit value for the maximum speed reference sent to the
drive.
4 Enter the engineering unit value for the minimum speed reference sent to the
drive. (This value is usually zero. Do not enter a negative value for reversing
drives. Reversing is handled separately.)
5 Enter the engineering unit value for the maximum speed feedback from the
drive.
6 Enter the engineering unit value for the minimum speed feedback from the
drive.
(This value is usually zero. Do not enter a negative value for reversing drives.
Reversing is handled separately.)
7 Enter the text of the units of measure of the scaled speed feedback. (Units of
measure are often Hz, RPM, or Percent.)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 305


Chapter 5 Motors Family

Item Description
8 Enter the text of the units of measure of the scaled speed reference. (Units of
measure are often Hz, RPM, or Percent.)
9 Enter the raw output count that corresponds to the maximum speed reference
sent to the drive.
10 Enter the raw output count that corresponds to the minimum speed reference
sent to the drive. (This value is usually zero.)

1
2
3

5
6

7
8

9
10

Table 208 - Engineering Tab Page 2 Description


Item Description
1 Check if the drive provides a run feedback signal. This check enables
feedback checking for Fail to Start and Fail to Stop.
Clear this checkbox if there is no run feedback.
2 Check if the drive provides speed feedback on Inp_SpeedFdbk.
3 Check if Speed feedback greater than zero is used to signify the drive is
running.
IMPORTANT: This configuration setting is available only if the previous
configuration setting is checked.
4 Check to reset the faults when a new operator command is issued.
Clear this checkbox for ‘reset required’ to clear fault.
5 Check to reset the faults when a new External command is issued.
Clear this checkbox for ‘reset required’ to clear fault.
6 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate.
7 Check to make the forward and reverse direction command buttons visible on
the Operator tab and enable the drive to run forward or reverse.

306 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
8 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
9 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
10 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.

1
2
3

4
5
6

Table 209 - Engineering Tab Page 3 Description


Item Description
1 Check to allow for local command source start and stop without triggering a
fault.
2 Check to have Program settings, such as Speed Reference, track Operator
settings in Operator command source, and have Operator settings track
Program settings in Program command source.
3 Check to have Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 307


Chapter 5 Motors Family

Item Description
4 Check to stop the drive if an I/O Fault is detected.
Clear this checkbox show the I/O Fault Status/Alarm only and not stop the
drive if an I/O Fault is detected.
5 When the bit is on and a motor Fail to Start is detected, the drive is stopped. A
reset is required before another start can be attempted.
If the bit is off and a drive Fail to Start is detected, the instruction sets only the
Sts_FailToStart status (and the Alm_FailToStart alarm, if so configured). The
outputs are not changed, so the instruction continues to start the drive.
6 The drive always stops on an Interlock trip. This item cannot be unchecked. It
is displayed as a reminder that the Interlock Trip function always stops
the drive.

2
3

Table 210 - Engineering Tab Page 4 Description


Item Description
1 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
2 Check to keep control of the drive Start, Stop, and Jog commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.
3 Check to keep control of the Output Datalink Setting (if used) with the
Operator, Program, External, or Follow the Source even if the instruction is in
Program command source.
4 Type the time (in seconds) the audible alarm sounds on a commanded start.
5 Enter the time, in seconds, to ramp speed feedback when in Simulation.

308 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

2 6

4 8

Engineering Tab Page 5 Description

Item Description
1 Check if Inp_Datalink is used. This check makes the Input Datalink
configuration and operation functions visible.
2 Configure the minimum and maximum raw (from the drive) units for the Input
Datalink.
3 Check if Out_Datalink is used. This check makes the Output Datalink
configuration and operation functions visible.
4 Configure the minimum and maximum scaled values for the Output Datalink
in Engineering Units.
5 Enter the text to display the units of measure for the Output Datalink.
6 Configure the minimum and maximum scaled values for the Input Datalink in
Engineering Units.
7 Type the text to display the units of measure for the Input Datalink.
8 Configure the minimum and maximum scaled values for the Output Datalink
in Raw (to the drive) Units. Enter the text to display for the label and units of
measure of the Output Datalink.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 309


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3
4

6
7

Table 211 - HMI Configuration Page 1 Description


Item Description
1 Type a name for forward direction.
2 Type a name for reverse direction.
3 Type the text to display for the label of the Input Datalink.
4 Type the text to display for the label of the Output Datalink.
5 Type the number of decimal places to be shown for actual speed.
6 Type the number of decimal places to be shown for input datalink.
7 Type the number of decimal places to be shown for output datalink.

310 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2
3
4

Table 212 - HMI Configuration Page 2 Description


Item Description
1 Check if a permissive object is connected to Inp_FwdPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Forward Permissive object in the controller
must be the name of the object with the suffix ‘_FwdPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Forward Permissive
object must be named ‘Drive123_FwdPerm’.
2 Check if a permissive object is connected to Inp_RevPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Reverse Permissive object in the controller
must be the name of the object with the suffix ‘_RevPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Reverse Permissive
object must be named ‘Drive123_RevPerm’.
3 Check if an interlock object is connected to Inp_IntlkOK. The Interlock
indicator becomes a button that opens the interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_PF52x
object has the name ’Drive123’, then its Interlock object must be named
‘Drive123_Intlk’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 311


Chapter 5 Motors Family

Item Description
4 Check if a restart inhibit object is connected. The button that opens the Restart
Inhibit faceplate appears.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_PF52x object has the name ’Drive123’, then its Restart Inhibit object must
be named ‘Drive123_ResInh’.
5 Check if a runtime object is connected. The button that opens the runtime
faceplate appears.
IMPORTANT: The name of the runtime object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_PF52x
object has the name ‘Drive123’, then its runtime object must be named
‘Drive123_RunTime’.
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

312 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 313


Chapter 5 Motors Family

PowerFlex 523/525 The P_PF52x (PowerFlex® 523/525 Variable Frequency Drives) object is used
to control and monitor a PowerFlex 523 variable-frequency drive with optional
Variable Frequency EtherNet/IP Interface. The P_PF52x can also control and monitor a
Drives (P_PF52x) PowerFlex 525 variable-frequency drive with embedded or optional add-on
EtherNet/IP Interface.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_PF52x)

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_PF52x instruction uses the same HMI display elements that are used
for the Variable Speed Drive (P_VSD) instruction. See Display Elements
(P_VSD) on page 299

314 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

2 3
4

Table 213 - Operator Tab Description


Item Description
1 Current speed of drive.
2 Setpoint for the speed of the drive.
3 Jog drive in reverse.
4 start drive in reverse.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 315


Chapter 5 Motors Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Table 214 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.

316 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 215 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time for the run feedback of the drive to confirm that the
drive has started before raising a Fail to Start alarm.
3 Type the amount of time for the run feedback of the drive to confirm that the
drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum amount of time allowed to jog the motor.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 317


Chapter 5 Motors Family

Engineering Tab

The Engineering tab has four pages.

4
5

6
2

Table 216 - Engineering Tab Page 1 Description


Item Description
1 Type the raw input count that corresponds to the maximum and minimum
(This value is typically zero.) speed feedback from the drive
2 Type the engineering unit value for the maximum and minimum (typically
zero) speed reference sent to the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
3 Type the engineering unit value for the maximum and minimum (typically
zero) speed feedback from the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
4 Type the text of the units of measure of the scaled speed feedback. (typically
Hz, RPM, or Percent.)

318 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
5 Type the text of the units of measure of the scaled speed reference. (typically
Hz, RPM, or Percent.)
6 Click the Simulation option (left, middle, or right) that corresponds to how the
speed feedback for the drive is to be determined from the speed reference
when the drive is being simulated (Inp_Sim = 1).
Click the left option to copy the speed reference in engineering units to the
speed feedback. (The simulated feedback is ramped to act like a drive that is
accelerating or decelerating.) Use this option if the speed reference and speed
feedback use the same scaling parameters
Click the middle option to scale the simulated feedback from the speed-
reference engineering unit range to the speed-feedback engineering unit range.
Use this setting if the speed reference and speed feedback have different
engineering ranges. For example, percent for reference and Hz for feedback),
but the maximum reference (for example, 100%) corresponds to the maximum
feedback (for example, 3600 RPM.
Click the right option to scale the speed reference to raw units, copy the speed
reference in raw units to speed feedback raw units, and scale to speed
feedback engineering units. Use this setting if the reference and feedback
ranges do not correspond.
7 Type the raw output count that corresponds to the maximum and minimum
(This value is typically zero.) speed reference sent to the drive.

1
2

3
4

5
6

7
8
9
10

Table 217 - Engineering Tab Page 2 Description


Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox if a reset is required to clear faults.
2 Check to reset faults on a new External command.
Clear this checkbox if a reset is required to clear faults.
3 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate.
4 Check to make the forward and reverse direction command buttons visible on
the Operator tab and enable the drive to run forward or reverse.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 319


Chapter 5 Motors Family

Item Description
5 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
6 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
7 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
8 Check (= 1) to let local circuits start/stop the drive without an alarm.
Clear this checkbox (= 0) to start/stop the drive from the HMI or program
only.
9 Check to have program settings, such as Speed Reference, track operator
settings in Operator command source, and have operator settings track
Program Settings in Program command source.
10 Check to have the Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.

1
2
3

4
5

320 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 218 - Engineering Tab Page 3 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
Clear this checkbox to have control of the drive Speed Reference follow the
Instruction command source.
5 Check to keep control of the drive Start and Stop commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.
Clear this checkbox to have control of the drive Start, Stop, and Jog follow
Instruction command source.

Table 219 - Engineering Tab Page 4 Description


Item Description
1 Type the time (in seconds) the audible alarm sounds on a commanded start.
2 Type the time, in seconds, to ramp speed feedback when in Simulation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 321


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

The HMI configuration tab has two pages.

1
2

Table 220 - HMI Configuration Tab Page 1 Description


Item Description
1 Type a name for forward direction.
2 Type a name for reverse direction.
3 Type names for the digital inputs.
4 Type the number of decimal places to be shown for actual speed.

322 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2

3
4

5
6

Table 221 - HMI Configuration Tab Page 2 Description


Item Description
1 Check if a permissive object is connected to Inp_FwdPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Forward Permissive object in the controller
must be the name of the object with the suffix ‘_FwdPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Forward Permissive
object must be named ‘Drive123_FwdPerm’.
2 Check if a permissive object is connected to Inp_RevPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Reverse Permissive object in the controller
must be the name of the object with the suffix ‘_RevPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Reverse Permissive
object must be named ‘Drive123_RevPerm’.
3 Check if an interlock object is connected to Inp_IntlkOK. The Interlock
indicator becomes a button that opens the interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_PF52x
object has the name ’Drive123’, then its Interlock object must be named
‘Drive123_Intlk’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 323


Chapter 5 Motors Family

Item Description
4 Check if a restart inhibit object is connected. The button that opens the Restart
Inhibit faceplate appears.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_PF52x object has the name ’Drive123’, then its Restart Inhibit object must
be named ‘Drive123_ResInh’.
5 Check if a runtime object is connected. The button that opens the runtime
faceplate appears.
IMPORTANT: The name of the runtime object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_PF52x
object has the name ‘Drive123’, then its runtime object must be named
‘Drive123_RunTime’.
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

324 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions. See Common Trends
Tab - Motors on page 249

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 325


Chapter 5 Motors Family

PowerFlex 753 Drive The P_PF753 (PowerFlex 753 Drive) object is used to operate one
variable-speed motor by using a PowerFlex 753 AC variable frequency drive in
(P_PF753) various command sources, and monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_PF753)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_PF753 instruction uses the same HMI display elements that are used
for the Variable Speed Drive (P_VSD) instruction. See Display Elements
(P_VSD) on page 299

326 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

Table 222 - Operator Tab Description


Item Description
1 Current speed of drive
2 Setpoint for the speed of the drive

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 327


Chapter 5 Motors Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Table 223 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.

328 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 224 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time for the run feedback of the drive to confirm that the
drive has started before raising a Fail to Start alarm.
3 Type the amount of time for the run feedback of the drive to confirm that the
drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum amount of time allowed to jog the motor.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 329


Chapter 5 Motors Family

Engineering Tab

The engineering tab has four pages.

4
5

6
2

Table 225 - Engineering Page 1 Description

Item Description
1 Type the raw input count that corresponds to the maximum and minimum
(This value is usually zero.) speed feedback from the drive
2 Type the engineering unit value for the maximum and minimum (usually zero)
speed reference sent to the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
3 Type the engineering unit value for the maximum and minimum (usually zero)
speed feedback from the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
4 Type the text of the units of measure of the scaled speed feedback. (Often Hz,
RPM, or Percent.)

330 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
5 Type the text of the units of measure of the scaled speed reference. (Often Hz,
RPM, or Percent.)
6 Click the Simulation option (left, middle, or right) that corresponds to how the
speed feedback for the drive is to be determined from the speed reference
when the drive is being simulated (Inp_Sim = 1).
Click the left option to copy the speed reference in engineering units to the
speed feedback. (The simulated feedback is ramped to act like a drive that is
accelerating or decelerating.) Use this option if the speed reference and speed
feedback use the same scaling parameters
Click the middle option to scale the simulated feedback from the speed-
reference engineering unit range to the speed-feedback engineering unit range.
Use this setting if the speed reference and speed feedback have different
engineering ranges. For example, percent for reference and Hz for feedback),
but the maximum reference (for example, 100%) corresponds to the maximum
feedback (for example, 3600 RPM.
Click the right option to scale the speed reference to raw units, copy the speed
reference in raw units to speed feedback raw units, and scale to speed
feedback engineering units. Use this setting if the reference and feedback
ranges do not correspond.
7 Type the raw output count that corresponds to the maximum and minimum
(This value is usually zero.) speed reference sent to the drive.

1
2

3
4

5
6

7
8
9
10

Table 226 - Engineering Page 2 Description

Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox if a reset is required to clear faults.
2 Check to reset faults on a new External command.
Clear this checkbox if a reset is required to clear faults.
3 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate
4 Check to make the forward and reverse direction command buttons visible on
the Operator tab and enable the drive to run forward or reverse.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 331


Chapter 5 Motors Family

Item Description
5 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
6 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
7 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
8 Check (= 1) to let local circuits start/stop the drive without an alarm.
Clear this checkbox (= 0) to start/stop the drive from the HMI or program
only.
9 Check to have program settings, such as Speed Reference, track operator
settings in Operator command source, and have operator settings track
Program Settings in Program command source.
10 Check to have the Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.

1
2
3

4
5

332 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 227 - Engineering Page 3 Description

Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
Clear this checkbox to have control of the drive Speed Reference follow the
Instruction command source.
5 Check to keep control of the drive Start and Stop commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.
Clear this checkbox to have control of the drive Start, Stop, and Jog follow
Instruction command source.

Table 228 - Engineering Tab Page 4 Description


Item Description
1 Type the time (in seconds) the audible alarm sounds on a commanded start.
2 Type the time, in seconds, to ramp speed feedback when in Simulation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 333


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

6
1
2

3
4

Table 229 - HMI Configuration Page 1 Description


Item Description
1 Check if a permissive object is connected to Inp_FwdPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Forward Permissive object in the controller
must be the name of the object with the suffix ‘_FwdPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Forward Permissive
object must be named ‘Drive123_FwdPerm’.
2 Check if a permissive object is connected to Inp_RevPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Reverse Permissive object in the controller
must be the name of the object with the suffix ‘_RevPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Reverse Permissive
object must be named ‘Drive123_RevPerm’.
3 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.

334 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 229 - HMI Configuration Page 1 Description


Item Description
4 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
5 Type the text to display when the motor is running forward.
6 Type the number of decimal places to be shown for actual speed.

1
2

Table 230 - HMI Configuration Page 2 Description


Item Description
1 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 335


Chapter 5 Motors Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions. See Common Trends
Tab - Motors on page 249

336 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

PowerFlex 755 Drive The P_PF755 (PowerFlex 755 drive) object is used to operate one
variable-speed motor by using a PowerFlex 755 AC variable frequency drive
(P_PF755) in various command sources and monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_PF755)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_PF753 instruction uses the same HMI display elements that are used
for the Variable Speed Drive (P_VSD) instruction. See Display Elements
(P_VSD) on page 299

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 337


Chapter 5 Motors Family

Table 231 - Operator Tab Description


Item Description
1 Current speed of drive
2 Setpoint for the speed of the drive

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

1
2

Table 232 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.
2 Drive maintenance data.

338 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 233 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has started before raising a Fail to Start alarm.
3 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum time (in seconds) that the drive can be jogged by using
OCmd_Jog.

IMPORTANT: This value stops drive jogging if HMI communication is lost


during a jog.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 339


Chapter 5 Motors Family

Engineering Tab

The Engineering Tab consists of four pages.

1 8
2 9
10

3
4
5

6
7

Table 234 - Engineering Tab Page 1 Description


Item Description
1 Type the engineering unit value for the maximum speed feedback from the
drive.
2 Type the engineering unit value for the minimum speed feedback from the
drive. (This value is usually zero. Do not enter a negative value for reversing
drives. Reversing is handled separately.)
3 Check to permit the Operator Start or Stop command to reset any previous
faults (I/O Fault, Fail to Start, Fail to Stop, Interlock Trip), then start or stop
the motor.

Clear this checkbox if a reset is required to clear faults.


4 Check to permit the External Start or Stop command to reset any previous
faults (I/O Fault, Fail to Start, Fail to Stop, Interlock Trip), then start or stop
the motor.

Clear this checkbox if a reset is required to clear faults.


5 Check to enable Jog on the Operator tab so that the drive can be jogged from
the faceplate.
6 Check to enable Forward and Reverse directions on the Operator tab so that
the drive can be commanded to run forward or reverse.
7 Check to have the bypassable interlocks and permissives bypassed in Override
command source.
8 Type the engineering unit value for the maximum speed reference sent to the
drive.
9 Type the engineering unit value for the minimum speed reference sent to the
drive. (This value is usually zero. Do not enter a negative value for reversing
drives. Reversing is handled separately.)
10 Type the text of the units of measure Engineering Units of the scaled speed
feedback. (Units of measure are often 'Hz', 'RPM' or 'Percent’.)

340 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2
3

4
5

Table 235 - Engineering Tab Page 2 Description


Item Description
1 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
2 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
3 Check (= 1) to allow local start/stop without an alarm.
Clear this checkbox (= 0) to
start/stop from the HMI or program only.
4 Check to have program settings, such as Speed Reference, track operator
settings in Operator command source, and have operator settings track
Program Settings in Program command source.
5 Check to have the Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.
6 Select the PowerFlex Drive type.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 341


Chapter 5 Motors Family

2
3

4
5

Table 236 - Engineering Tab Page 3 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected.
Clear the checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check so that if a motor fail to start is detected, the motor is stopped. A reset is
required before another start can be attempted.

Clear the checkbox and if a motor fail to start is detected, the instruction sets
only the Sts_FailToStart status (and the Alm_FailToStart alarm, if so
configured). The outputs are not changed, so the instruction continues to start
the motor.
3 The motor always stops on an interlock trip. This item cannot be unchecked. It
is displayed as a reminder that the Interlock Trip function always trips the
motor.
4 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
5 Check to keep control of the drive Start, Stop, and Jog commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.

342 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2

Table 237 - Engineering Tab Page 4 Description


Item Description
1 Type the time (in seconds) the audible alarm sounds on a commanded start.
2 Enter the time, in seconds, to ramp speed feedback when in Simulation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 343


Chapter 5 Motors Family

HMI Configuration Tab

5
6

7
1
2

3
4

Table 238 - HMI Configuration Page 1 Description


Item Description
1 Check if a permissive object is connected to Inp_FwdPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Forward Permissive object in the controller
must be the name of the object with the suffix ‘_FwdPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Forward Permissive
object must be named ‘Drive123_FwdPerm’.
2 Check if a permissive object is connected to Inp_RevPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Reverse Permissive object in the controller
must be the name of the object with the suffix ‘_RevPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Reverse Permissive
object must be named ‘Drive123_RevPerm’.
3 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
4 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
5 Type a name for forward direction.
6 Type a name for reverse direction.
7 Type the number of decimal places to be shown for actual speed.

344 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2

Table 239 - HMI Configuration Page 2 Description


Item Description
1 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 345


Chapter 5 Motors Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions. See Common Trends
Tab - Motors on page 249

346 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

PowerFlex 6000 Drive The P_PF6000 (PowerFlex 6000 drive) object is used to operate one
PowerFlex 6000 Medium Voltage Variable Frequency Drive in various
(P_PF6000) command sources and monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_PF6000)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_PF6000 instruction uses the same HMI display elements that are used
for the Variable Speed Drive (P_VSD) instruction. See Display Elements
(P_VSD) on page 299

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 347


Chapter 5 Motors Family

Table 240 - Operator Tab Description


Item Description
1 Current speed of drive
2 Setpoint for the speed of the drive

Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance
tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

2
1

Table 241 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.
2 Drive maintenance data.

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

348 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Maintenance Tab

Table 242 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has started before raising a Fail to Start alarm.
3 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum time allowed (in seconds) for the I/O communication to
the drive to complete a read/write cycle before declaring a communication
failure.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 349


Chapter 5 Motors Family

Engineering Tab

3
4

5
1

Table 243 - Engineering Tab Page 1 Description


Item Description
1 Type the engineering unit value for the maximum and minimum (usually zero)
speed reference sent to the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
2 Type the engineering unit value for the maximum and minimum (usually zero)
speed feedback from the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
3 Type the text of the units of measure of the scaled speed feedback. (Often Hz,
RPM, or Percent.)
4 Type the text of the units of measure of the scaled speed reference. (Often Hz,
RPM, or Percent.)
5 Click the Simulation option (left, middle, or right) that corresponds to how the
speed feedback for the drive is to be determined from the speed reference
when the drive is being simulated (Inp_Sim = 1).
Click the left option to copy the speed reference in engineering units to the
speed feedback. (The simulated feedback is ramped to act like a drive that is
accelerating or decelerating.) Use this option if the speed reference and speed
feedback use the same scaling parameters
Click the middle option to scale the simulated feedback from the speed-
reference engineering unit range to the speed-feedback engineering unit range.
Use this setting if the speed reference and speed feedback have different
engineering ranges. For example, percent for reference and Hz for feedback),
but the maximum reference (for example, 100%) corresponds to the maximum
feedback (for example, 3600 RPM.
Click the right option to scale the speed reference to raw units, copy the speed
reference in raw units to speed feedback raw units, and scale to speed
feedback engineering units. Use this setting if the reference and feedback
ranges do not correspond.

350 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2

3
4

5
6

7
8

Table 244 - Engineering Tab Page 2 Description


Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox if a reset is required to clear faults.
2 Check to reset faults on a new External command.
Clear this checkbox if a reset is required to clear faults.
3 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
4 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
5 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
6 Check (= 1) to let local circuits start/stop the drive without an alarm.
Clear this checkbox (= 0) to start/stop the drive from the HMI or program
only.
7 Check to have program settings, such as Speed Reference, track operator
settings in Operator command source, and have operator settings track
Program Settings in Program command source.
8 Check to have the Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 351


Chapter 5 Motors Family

1
2
3

4
5

Table 245 - Engineering Tab Page 3 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
Clear this checkbox to have control of the drive Speed Reference follow the
Instruction command source.
5 Check to keep control of the drive Start and Stop commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.
Clear this checkbox to have control of the drive Start, Stop, and Jog follow
Instruction command source.

Table 246 - Engineering Tab Page 3 Description

352 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 247 - Engineering Tab Page 4 Description


Item Description
1 Type the time (in seconds) the audible alarm sounds on a commanded start.
2 Type the time, in seconds, to ramp speed feedback when in Simulation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 353


Chapter 5 Motors Family

HMI Configuration Tab

1
2
3

4
5

Table 248 - HMI Configuration Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_Motor
object has the name ’Motor123’, then its Permissive object must be named
‘Motor123_Perm’.
2 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
3 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
4 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.
5 Check to enable navigation to the Parameter Read/Write object. This check
makes the Parameter Read/Write object visible.

354 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
7 Type the number of decimal places to be shown for actual speed.

Diagnostics Tab
The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions. See Common Trends
Tab - Motors on page 249

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 355


Chapter 5 Motors Family

PowerFlex 7000 Drive The P_PF7000 (PowerFlex 7000 drive) object is used to operate one
PowerFlex 7000 Medium Voltage AC Drive in various command sources and
(P_PF7000) monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_PF7000)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_PF7000 instruction uses the same HMI display elements that are used
for the Variable Speed Drive (P_VSD) instruction. See Display Elements
(P_VSD) on page 299

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

356 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 249 - Operator Tab Description


Item Description
1 Current speed of drive
2 Setpoint for the speed of the drive

Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance
tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

1 2

Table 250 - Maintenance Tab Description


Item Description
1 Type the clamping limits for the speed setpoint. If a speed setpoint outside this
range is entered, the speed is clamped at these limits and Sts_SpeedLimited is
asserted.
2 Drive maintenance data.

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 357


Chapter 5 Motors Family

Advanced Maintenance Tab

Table 251 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has started before raising a Fail to Start alarm.
3 Type the amount of time to allow for the run feedback of the drive to confirm
that the drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum time (in seconds) that the drive can be jogged by using
OCmd_Jog.

IMPORTANT: This value stops drive jogging if HMI communication is lost


during a jog.

358 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

3
4

5
1

Table 252 - Engineering Tab Page 1 Description


Item Description
1 Type the engineering unit value for the maximum and minimum (usually zero)
speed reference sent to the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
2 Type the engineering unit value for the maximum and minimum (usually zero)
speed feedback from the drive.
Do not enter a negative value for reversing drives. Reversing is handled
separately.
3 Type the text of the units of measure of the scaled speed feedback. (Often Hz,
RPM, or Percent.)
4 Type the text of the units of measure of the scaled speed reference. (Often Hz,
RPM, or Percent.)
5 Click the Simulation option (left, middle, or right) that corresponds to how the
speed feedback for the drive is to be determined from the speed reference
when the drive is being simulated (Inp_Sim = 1).
Click the left option to copy the speed reference in engineering units to the
speed feedback. (The simulated feedback is ramped to act like a drive that is
accelerating or decelerating.) Use this option if the speed reference and speed
feedback use the same scaling parameters
Click the middle option to scale the simulated feedback from the speed-
reference engineering unit range to the speed-feedback engineering unit range.
Use this setting if the speed reference and speed feedback have different
engineering ranges. For example, percent for reference and Hz for feedback),
but the maximum reference (for example, 100%) corresponds to the maximum
feedback (for example, 3600 RPM.
Click the right option to scale the speed reference to raw units, copy the speed
reference in raw units to speed feedback raw units, and scale to speed
feedback engineering units. Use this setting if the reference and feedback
ranges do not correspond.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 359


Chapter 5 Motors Family

1
2

3
4

5
6

7
8
9

Table 253 - Engineering Tab Page 2 Description


Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox if a reset is required to clear faults.
2 Check to reset faults on a new External command.
Clear this checkbox if a reset is required to clear faults.
3 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate
4 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
5 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
6 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
7 Check (= 1) to let local circuits start/stop the drive without an alarm.
Clear this checkbox (= 0) to start/stop the drive from the HMI or program
only.
8 Check to have program settings, such as Speed Reference, track operator
settings in Operator command source, and have operator settings track
Program Settings in Program command source.
9 Check to have the Program and Operator Speed Reference track the Override
Speed Reference in Override command source or the actual speed in Hand
command source.

360 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

1
2
3

4
5

Table 254 - Engineering Tab Page 3 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Check to keep control of the drive Speed Reference with the Operator,
Program, External, or Follow the Source even if the instruction is in Program
command source.
Clear this checkbox to have control of the drive Speed Reference follow the
Instruction command source.
5 Check to keep control of the drive Start and Stop commands with the
Operator, Program, External, or Follow the Source, even if the instruction is in
Operator command source.
IMPORTANT: The Program cannot Jog the drive, even if Jogging is enabled.
Clear this checkbox to have control of the drive Start, Stop, and Jog follow
Instruction command source.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 361


Chapter 5 Motors Family

Table 255 - Engineering Tab Page 4 Description


Item Description
1 Type the time (in seconds) the audible alarm sounds on a commanded start.
2 Type the time, in seconds, to ramp speed feedback when in Simulation.

362 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

Table 256 - HMI Configuration Tab Page 1 Description


Item Description
1 Type the text to display when the motor is running forward.
2 Type the number of decimal places to be shown for actual speed.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 363


Chapter 5 Motors Family

1
2

3
4
5

Table 257 - HMI Configuration Tab Page 2 Description


Item Description
1 Check if a permissive object is connected to Inp_FwdPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Forward Permissive object in the controller
must be the name of the object with the suffix ‘_FwdPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Forward Permissive
object must be named ‘Drive123_FwdPerm’.
2 Check if a permissive object is connected to Inp_RevPermOK. The
Permissive indicator becomes a button that opens the permissive faceplate.
IMPORTANT: The name of the Reverse Permissive object in the controller
must be the name of the object with the suffix ‘_RevPerm’. For example, if
your P_PF52x object has the name ’Drive123’, then its Reverse Permissive
object must be named ‘Drive123_RevPerm’.
3 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_Motor
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.

364 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Item Description
4 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_Motor object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
5 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your P_Motor
object has the name ‘Motor123’, then its Run Time object must be named
‘Motor123_RunTime’.
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Trends Tab
The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. The trends displays are
common across all Motors Family Add-On Instructions. See Common Trends
Tab - Motors on page 249

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 365


Chapter 5 Motors Family

SMC-50 Smart Motor The P_SMC50 (SMC™-50 Smart Motor Controller) Add-On Instruction
controls and monitors a motor via an SMC-50 Smart Starter.
Controller (P_SMC50)
This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (P_SMC50)

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 258 - P_SMC50 Display Elements
Display Element Name Display Element Description
GO_P_SMC_R Motors operate in the right,
up, and down positions.
GO_P_SMC_U

GO_P_SMC_D

GO_P_SMC_Blower_R Blowers operate in the right,


left, up, and down positions.
GO_P_SMC_Blower_L

GO_P_SMC_Blower_U

GO_P_SMC_Blower_D

GO_P_SMC_Conveyer_ Conveyor in the up position


U is shown as a display
element.

366 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 258 - P_SMC50 Display Elements


Display Element Name Display Element Description
GO_P_SMC_Inline_U Inline motors operate the up,
right, left, and down
GO_P_SMC_Inline_R positions.

GO_P_SMC_Inline_L

GO_P_SMC_Inline_D

GO_P_SMC_Pump_R Pumps operate in the right,


left, and up positions.
GO_P_SMC_Pump_L

GO_P_SMC_Pump_U

GO_P_SMC_Agitator_D Agitator in the down


position shown as a display
element.

GO_P_SMC_Mixer_U Mixer in the up position


shown as a display element.

GO_P_SMC_RPump_U Rotary gear pump in the up


position shown as a display
element.

GO_P_SMC_Fan_D Fan in the down position


shown as a display element.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 367


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

368 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 369


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 259 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to hold Out_Reset true to reset a drive fault when a
reset command is received.
2 Type the amount of time for the run feedback of the drive to confirm that the
drive has started before raising a Fail to Start alarm.
3 Type the amount of time for the run feedback of the drive to confirm that the
drive has stopped before raising a Fail to Stop alarm.
4 Type the maximum amount of time allowed to jog the motor.

370 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

1
2

3
4

5
6

Table 260 - Engineering Tab Page 1 Description


Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox if a reset is required to clear faults.
2 Check to reset faults on a new External command.
Clear this checkbox if a reset is required to clear faults.
3 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate
4 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
5 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
6 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
7 Check (= 1) to let local circuits start/stop the drive without an alarm.
Clear this checkbox (= 0) to start/stop the drive from the HMI or program
only.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 371


Chapter 5 Motors Family

1
2
3

Table 261 - Engineering Tab Page 2 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Type the time (in seconds) the audible alarm sounds on a commanded start.
5 Set the time delay (in seconds) for running or stopped status to be echoed back
when the simulation is enabled or when run feedback is not used.

372 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3

Table 262 - HMI Configuration Tab Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_SMC50
object has the name ’Motor123’, then its Permissive object must be named
‘Motor123_Perm’.
2 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_SMC50
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
3 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_SMC50 object has the name ’Motor123’, then its Restart Inhibit object must
be named ‘Motor123_ResInh’.
4 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your
P_SMC50 object has the name ‘Motor123’, then its Run Time object must be
named ‘Motor123_RunTime’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 373


Chapter 5 Motors Family

Item Description
5 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

374 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 375


Chapter 5 Motors Family

SMC Flex Smart Motor This instruction controls and monitors a motor via an SMC Flex Smart Starter.
Controller This document is for the visualization files, display elements, global objects,
(P_SMCFlex) and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_SMCFlex instruction uses the same HMI display elements that are used
for the SMC-50 Smart Motor Controller (P_SMC50) instruction.
See Display Elements (P_SMC50) on page 366

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

The operator tab for the P_SMCFlex instruction also shows the average full
load amps and the motor thermal usage.

376 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 377


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

2
3
4

Table 263 - Advanced Maintenance Tab Description


Item Description
1 Type the number of seconds the starter fault reset is pulsed to clear motor
fault.
2 Type the time, in seconds to allow run feedback to show that the motor has
started before raising a fail to start alarm.
3 Type the time, in seconds to allow run feedback to show that the motor has
stopped before raising a fail to stop alarm.
4 Type the time, in seconds for the maximum amount of time to jog the motor.

378 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

1
2

3
4
5
6
7

Table 264 - Engineering Tab Page 1 Description


Item Description
1 Check to reset faults on a new Operator command.
Clear this checkbox for ‘reset required’ to clear fault.
2 Check to reset faults on a new External command.
Clear this checkbox for ‘reset required’ to clear fault.
3 Check to make the Jog command button visible on the Operator tab and enable
the drive to be jogged from the faceplate.
4 Check to have the interlocks and permissives that can be bypassed, bypassed
in Override command source.
5 Check (= 1) so that the OCmd_Stop has priority and is accepted at any time. If
the Command Source is not Operator or Maintenance, the motor or drive
requires a reset.
Clear this checkbox (= 0) so that the OCmd_Stop works only in Operator or
Maintenance command source.
6 Check (= 1) so that the XCmd_Stop has priority and is accepted at any time. If
the Command Source is not External, the motor or drive requires a reset.
Clear this checkbox (= 0) so that the XCmd_Stop only works when the
command source is External.
7 Check to allow local Start/Stop without alarm.
Clear this checkbox to allow start/stop by using only Program or Operator
commands or Override Logic.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 379


Chapter 5 Motors Family

1
2
3

Table 265 - Engineering Tab Page 2 Description


Item Description
1 Check to stop the drive if an I/O Fault is detected. After the I/O Fault clears, a
reset is required before the drive can be started.
Clear this checkbox to show only the I/O Fault Status/Alarm and not stop the
drive if an I/O Fault is detected.
2 Check to stop the drive on a failure to start. A reset is required before another
start can be attempted.
Clear this checkbox to show only the Fail to Start status and alarm on a failure
to start. The outputs are not changed, so the instruction continues to attempt to
start the motor.
3 The drive always stops on an Interlock trip. This item cannot be cleared. It is
displayed as a reminder that the Interlock Trip function always stops the drive.
4 Type the time (in seconds) the audible alarm sounds on a commanded start.
5 Set the time delay (in seconds) for running or stopped status to be echoed back
when the simulation is enabled or when run feedback is not used.

380 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2
3
4

Table 266 - HMI Configuration Tab Description


Item Description
1 Check if a Permissive object is used with this motor. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your
P_SMCFlex object has the name ’Motor123’, then its Permissive object must
be named ‘Motor123_Perm’.
2 Check if an Interlock object is used with this motor. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_SMCFlex
object has the name’Motor123’, then its Interlock object must be named
‘Motor123_Intlk’.
3 Check if a Restart Inhibit object is used with this motor. This check makes the
Restart Inhibit button visible.
IMPORTANT: The name of the Restart Inhibit object in the controller must
be the name of the object with the suffix ‘_ResInh’. For example, if your
P_SMCFlex object has the name ’Motor123’, then its Restart Inhibit object
must be named ‘Motor123_ResInh’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 381


Chapter 5 Motors Family

Item Description
4 Check if a Run Time object is used with this motor. This check makes the Run
Time button visible.
IMPORTANT: The name of the Run Time object in the controller must be the
name of the object with the suffix ‘_RunTime’. For example, if your
P_SMCFlex object has the name ‘Motor123’, then its Run Time object must
be named ‘Motor123_RunTime’.
5 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
6 Select the units, megawatts, or kilowatts, to be used for power.

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

382 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

E1 Plus Electronic The P_E1PlusE (E1 Plus™ Electronic Overload Relay (EtherNet/IP)) Add-On
Instruction controls and monitors an E1 Plus Electronic Overload Relay by
Overload Relay using the 193-ETN EtherNet/IP interface module.
(EtherNet/IP)
(P_E1PlusE) This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements (EtherNet/IP) (P_E1PlusE)


A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 267 - P_E1PlusE Display Element Description


Display Element Name Display Element Description
GO_P_Ovld Standard E1 Plus Electronic
GO_P_Ovld1 Overload Relay (EtherNet/
IP) global objects.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 383


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

1
3

Table 268 - Operator Tab Description


Item Description
1 Full load amps numeric display and sparkline
2 Thermal utilization
3 Input indicator
4 Output indicator

384 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.

See Common Maintenance Tab - Motors on page 248

Table 269 - Maintenance Tab Description


Item Description
1 Trip log

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 385


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 270 - Advanced Maintenance Tab Description


Item Description
1 Type the number of seconds (0…2,147,483) to pulse.

386 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

Table 271 - Engineering Tab Description


Item Description
1 Type the number of seconds (0…2,147,483) to pulse.
2 Type the maximum number of resets (1…3) in a given number of seconds
(0…2,147,483).
IMPORTANT: Setting the time to approximately10 seconds or less allows
unlimited Remote Trip resets

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 387


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2
3
4

Table 272 - HMI Configuration Tab Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
2 Type the names for input 1
3 Type the names for input 2
4 Type the names for output A.

388 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 389


Chapter 5 Motors Family

E3/E3 Plus Overload The P_E3Ovld Add-On Instruction controls and monitors a 193/592-EC1, -
EC2, -EC3, or -EC5 overload relay.
Relay (P_E3Ovld)
This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The P_E3Ovld instruction uses the same HMI display elements that are used
for the E1 Plus Overload Relay (EtherNet/IP) (P_E1PlusE) instruction.
See Display Elements (EtherNet/IP) (P_E1PlusE) on page 383

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family.

Table 273 - Operator Tab Description


Item Description
1 Overload status indicator.
2 Outputs (up to 2).
3 Inputs (up to 4).

390 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 391


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 274 - Advanced Maintenance Tab Description


Item Description
1 Type the number of seconds (0…2,147,483) to pulse.

392 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Engineering Tab

Table 275 - Engineering Tab Description


Item Description
1 Type the maximum number of resets (1…3) in a given number of seconds
(0…2,147,483).
IMPORTANT: Setting the time to approximately10 seconds or less allows
unlimited Remote Trip resets
2 Check to let the Maintenance and/or Operator User use the Remote Trip
function.
3 Check to let the Maintenance and/or Operator User use the Trip Reset
function.
4 Click to select the type of E3 Overload used.
IMPORTANT: E3 Plus has two additional inputs and one additional output.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 393


Chapter 5 Motors Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2
3

Table 276 - HMI Tab Description


Item Description
1 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
2 Type the names for input 1
3 Type the names for input 2
4 Type the names for output A.

394 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 395


Chapter 5 Motors Family

E300 Electronic The P_E300Ovld (E300™ Electronic Overload Relay) Add-On Instruction
controls and monitors a 193-ECM-ETR (E300 on EtherNet/IP) overload
Overload Relay relay.
(EtherNet/IP)
(P_E300Ovld) This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

The (EtherNet/IP) (P_E300Ovld) instruction uses the same HMI display


elements that are used for the E1 Plus Overload Relay (EtherNet/IP)
(P_E1PlusE) instruction. See Display Elements (EtherNet/IP) (P_E1PlusE)
on page 383

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the motors family. See Common Operator Tab -
Motors on page 247.

2
1
3

396 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 277 - Operator Tab Description


Item Description
1 Overload status indicator.
2 Thermal utilization.
3 Motor current indicator.

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the motors family.
See Common Maintenance Tab - Motors on page 248

3
4

Table 278 - Maintenance Tab Description


Item Description
1 Average current.
2 Current imbalance.
3 Control module status.
4 Sensing module status.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 397


Chapter 5 Motors Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

1 5

6
2 7
3

Table 279 - Advanced Maintenance Tab Page 1 Description


Item Description
1 L3-L1 phase voltage.
2 L1 current.
3 Current to ground.
4 L3 current.
5 L3-L2 phase voltage.
6 L2-L1 phase voltage.
7 L2 current.
8 Type the number of seconds (0…2,147,483) to pulse.

398 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 280 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Up to six inputs.
2 Up to three outputs.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 399


Chapter 5 Motors Family

Table 281 - Advanced Maintenance Tab Page 3 Description


Item Description
1 Status of up to four digital I/O modules. Indicators for up to four discrete
inputs and up to two discrete outputs.
2 Status of up to four analog input modules. Indicators for the three analog
inputs.

400 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Table 282 - Advanced Maintenance Tab Page 4 Description


Item Description
1 Indicators for the DeviceLogix™ output status.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 401


Chapter 5 Motors Family

Engineering Tab

Table 283 - Engineering Tab Description


Item Description
1 Type the maximum number of resets (1…3) in a given number of seconds
(0…2,147,483).
IMPORTANT: Set the time to approximately 10 seconds or less to allow
unlimited Remote Trip resets.
2 Check to let the Maintenance and/or Operator User use the Remote Trip
function.
3 Check to let the Maintenance and/or Operator User use the Trip Reset
function.

402 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Table 284 - HMI Configuration Tab Description


Item Description
1 Type the names for inputs Pt00…Pt05.
2 Type the names for outputs 1 and 2.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 403


Chapter 5 Motors Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

404 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Run Time and Start The P_RunTime (Run Time and Start Counter) Add-On Instruction is used
to accumulate the total run time and count of starts for a motor or other
Counter (P_RunTime) equipment. It is a software implementation of the mechanical hour meter that
is often mounted in the door of a Motor Control Center (MCC) cabinet to
show total motor run time. The run time and number of starts are variables
used by maintenance personnel to determine when to perform maintenance
activities on the motor or other equipment.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 285 - P_RunTime Display Element


Display Element Name Display Element Description
GO_P_RunTime Standard Run Time Global
Object.

The graphic symbol in the preceding table is for use on faceplates and end-user
process graphic displays.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 405


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status.

The following table lists the functions on the Operator tab.


Table 286 - P_RunTime Operator Tab Description
Item Description
1 Click to clear maximum continuous running time for any given start.
2 Click to clear total running time.
3 Click to clear total number of motor starts or start attempts.

Advanced Properties Display

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. Configure the description, label, tag,
and security area for the device. See Basic Faceplate Attributes on page 32 for
the description of the common attributes.

406 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Restart Inhibit for The P_ResInh (Restart Inhibit for Large Motor) Add-On Instruction is used
to help prevent damage to a large motor through repeated starts. The high
Large Motor starting current for a large motor causes considerable heating. The thermal
(P_ResInh) mass of a large motor is much smaller relative to its horsepower and starting
current compared to smaller motors. For this reason, repeated starts (or start
attempts) over a short time overheats the motor windings, potentially
damaging the motor permanently.

The P_ResInh instruction provides a rule-based state model for restarts and is
not intended to model or monitor the motor heating. It cannot replace sensor-
based motor monitoring devices. It can, however, be a simple solution to avoid
over stressing a motor without the cost (money or controller resources) of more
extensive modeling and monitoring.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 287 - P_ResInh Display Elements Description
Display Element Name Display Element Description
GO_P_ResInh Standard Restart Inhibit Global
Object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 407


Chapter 5 Motors Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status.

The Operator tab shows the following information:


• A graphical representation of the P_ResInh instruction State Diagram.
• Indication of the current state.
• The status appears at the top and displays either Ready to Start or Time
Until Ready with an animated countdown timer.

7
2

3 5 6

Table 288 - Operator Tab Description


Item Description
1 Type the time, in hours, during which three motor starts turn a cold motor to hot.
2 Type the time, in hours, to wait after failing to start a cold motor the first time.
3 Type the time, in hours, to wait after failing to start a cold motor two or more
times.
4 Type the time, in hours, for a stopped hot motor to cool.
5 Type the time, in hours, to wait after failing to start a hot motor the first time.
6 Type the time, in hours, to wait after stopping a running hot motor.
7 Type the time, in hours, to wait after failing to start a hot motor two or more
times.

408 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Motors Family Chapter 5

Advanced Properties Display

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and


faceplate-to-faceplate navigation settings. Configure the description, label, tag,
and security area for the device. See Basic Faceplate Attributes on page 32 for
the description of the common attributes.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 409


Chapter 5 Motors Family

Notes:

410 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 6

Valves Family

The Process Objects in this group provide an interface to a wide range of


process valve types and valve statistical calculations. This document is for the
visualization files, display elements, global objects, and HMI information. The
operation of the Add-on Instructions and controller code is contained in
publication PROCES-RM013.

Common Valves Faceplate attributes are common to several Add-On Instructions in the valves
family. Attributes specific to a valve are detailed in the individual sections. If a
Faceplates functionality is not enabled, the buttons are not visible. Common attributes
for valves are detailed in this section. Basic attributes are described in the
overview. See Basic Faceplate Attributes on page 32

Common Operator Tab - Valves

2
3

Table 289 - Common Operator Tab Attributes


Item Description
1 Valve state indicator.
2 Click to open valve.
3 Click to close valve.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 411


Chapter 6 Valves Family

Common Maintenance Tab - Valves

Table 290 - Common Maintenance Tab Attributes


Item Description
1 Click yes to bypass checking of interlocks and permissives that can be
bypassed.
2 Click to open Valve Statistics faceplate. See 2-state Valve Statistics
(P_ValveStats) on page 469

412 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Analog/Pulsed Control The P_ValveC (Analog/Pulsed Control Valve) Add-On Instruction


manipulates a control valve by using an analog signal or discrete signals, and
Valve (P_ValveC) monitors the valve by using an analog position feedback.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix® system, aid consistency and save engineering time.
Table 291 - P_ValveC Display Elements Description
Display Element Display Element Description
Name
GO_ProcessControlV Normal controlled valve
alve symbol for horizontal pipe.

GO_ProcessControlV Inverted controlled valve


alve1 symbol for horizontal pipe.

GO_ProcessControlV Controlled valve symbol for


alve2 vertical pipe (pipe to the
left).
GO_ProcessControlV Controlled valve symbol for
alve3 vertical pipe (pipe to the
right).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 413


Chapter 6 Valves Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

1
2

Table 292 - Operator Tab Description


Item Description
1 Controlled Variable bar graph
2 Click to enter the Controlled Variable value.
3 Current Controlled Variable.

414 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

1
2

Table 293 - Maintenance Tab Page 1 Description

Item Description
1 Check to enable the Valve Closed limit switch for failure checking.
2 Check to enable the Valve Open limit switch for failure checking.
3 Type a value to indicate the position, that if exceeded, the valve is assumed
open if limit switches are not used.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 415


Chapter 6 Valves Family

1
2

Table 294 - Maintenance Tab Page 2 Description

Item Description
1 Maximum rate of increase (% Open/sec) for the CV rate of change limit. A
value of zero indicates unlimited.
2 Maximum rate of decrease (% Open/sec) for the CV rate of change limit. A
value of zero indicates unlimited.

416 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

1 3

Table 295 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type the clamping limits for the Controlled Variable in engineering units.
Clamping limits are enforced in Operator and Program command sources
only.
2 Type the CV Rate of Change Limit in engineering units per second. This value
determines the rate at which the CV output changes upon a change in CV
target. A value of zero disables rate of change limiting.
3 Type the CV in engineering units.
This entry is available in Operator command source and Maintenance
command source. It is available in other command sources if Bumpless
Program/Operator Transition is not selected.
4 When checked, the CV holds at the last good value when an Interlock trips or
an I/O Fault occurs.
When cleared, the CV is set to the configured Interlock CV value when an
Interlock trips or an I/O Fault occurs.
5 Type the interlock target CV in engineering units.
This value is used for the CV when interlocked or on an I/O Fault, but only if
Hold Last Good Value is not selected.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 417


Chapter 6 Valves Family

Table 296 - Advanced Maintenance Tab Page 2 Description

Item Description
1 Type a value to indicate the time (in seconds) for an open and close pulse.
2 Type a value to indicate the additional time (in seconds)
on the first pulse after a stop or direction change.
3 Type a value to indicate the maximum pulse output time (in seconds) for
opening and closing a value.
4 Type a value to indicate the minimum pulse output time (in seconds) for
opening and closing a value.
5 Type a value to indicate the amount of time to bump the valve open or closed
when feedback is bad.

418 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Engineering Tab

1 3

2 5

Table 297 - Engineering Tab Page 1 Description


Item Description
1 Type a maximum and minimum range for the raw feedback signal.
2 Type a maximum and minimum range for the controlled variable in
engineering units (for scaling).
3 Type a maximum and minimum range for the controlled variable in
engineering units (for scaling).
4 Type an engineering unit for the controlled variable.
5 Type maximum and minimum range (in raw units) to use for output unscaling
to I/O.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 419


Chapter 6 Valves Family

1
2
3

4
5
6
7

Table 298 - Engineering Tab Page 2 Description


Item Description
1 Check if the valve provides a closed limit switch signal.
2 Check if the valve provides an open limit switch signal.
3 Click to enable a fault when both limit switches are On, or when both switches
are Off.
4 Check so that program settings track operator settings in Operator command
source, and operator settings track program settings in Program command
source for bumpless transfer.
5 Check so that program and operator settings of the CV track the output CV
when the command source is Hand or Override.

6 Check so that bypassable interlocks and permissives are bypassed in Override


command source.
7 Check to have the CV immediately go to its target value or configured
Interlock CV value when an Interlock trips or the instruction is placed in
Maintenance or Override command source.
Clear the checkbox to have the CV always use rate of change limiting
(ramping) of the CV output.

420 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

1
2

3
4

5
6

Table 299 - Engineering Tab Page 3 Description


Item Description
1 Check to have the CV perform the configured Shed Action (hold or go to the
Interlock CV value) when an I/O Fault occurs. When checked, the Shed
Trigger is latched; that is, it is necessary to issue a Reset command to return to
normal operation after the I/O Fault condition clears.
Clear the checkbox to have an I/O Fault not trigger the configured Shed
Action. The output continues to operate normally.
2 The device always performs the shed action on an Interlock Trip.
This item cannot be unchecked. It is displayed as a reminder of the Interlock
Trip function.
3 Click to have the output go to its configured Interlock CV value when an
Interlock trips or an I/O Fault occurs (if configured as a shed trigger).
Type a value for the interlock CV value to be used if shed is configured to go
to a set value.
4 Click to have the output hold its current value when an Interlock trips or an I/
O Fault occurs (if configured as shed trigger).
5 Type a value to indicate the rate that the valve moves when opening.
6 Type a value to indicate the rate that the valve moves when closing.
7 Check to clamp the feedback to the EU Min/Max when using Limit Switch.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 421


Chapter 6 Valves Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

4
1

3 5

Table 300 - HMI Configuration Tab Description


Item Description
1 Check if an interlock instruction is used with this output.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_ValveC
object has the name ’ValveC123’, then its Interlock object must be named
‘ValveC123_Intlk’.
2 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.
3 Check to permit navigation to the faceplate of the object that is the source of
the CV for this object.
4 Type the number of decimal places to be shown for the Control Variable.
5 Type the name of the CV object to navigate to when the CV display on the
Home tab is clicked.

422 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 423


Chapter 6 Valves Family

Hand-operated Valve The P_ValveHO (Hand-operated Valve) Add-On Instruction monitors a hand
(locally) operated valve and displays its current state. The valve can have any
(P_ValveHO) type of actuator – handwheel, lever, motor, solenoid, pneumatic, hydraulic –
but it is normally operated at the valve. The control system only monitors the
valve via open and closed limit switches. The P_ValveHO instruction cannot
control the valve to both open and closed positions, but provides an optional
Trip output to command the valve to its default (fail) position. If the trip
function is used, the P_ValveHO instruction checks to make sure that the valve
reaches the configured trip position (open or closed) if a trip command is
executed.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 301 - P_ValveHO Display Element Description


Display Element Name Display Element Description
GO_P_ValveHO Hand-operated Valves that
GO_P_ValveHO1 are shown in various
GO_P_ValveHO2 orientations.
GO_P_ValveHO3

424 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 425


Chapter 6 Valves Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

Table 302 - Maintenance Tab Description


Item Description
1 Check to configure the valve to use the closed limit switch.
Clear the checkbox to bypass the closed limit switch temporarily.
2 Click to take the device out of service.

426 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

1
2

Table 303 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time to allow the valve to reach its trip position after a trip
command is received before raising a trip fail alarm.
2 Type the amount of time (in seconds) that the valve is not confirmed open or
closed before a Transit Stall.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 427


Chapter 6 Valves Family

Engineering Tab

The Engineering tab consists of two pages.

2
3

5
6

Table 304 - Engineering Tab Page 1 Description


Item Description
1 Check if the valve has a closed limit switch and the switch is wired to
Inp_ClosedLS for position monitoring.
2 Check if the valve has an open limit switch and the switch is wired to
Inp_OpenLS for position monitoring.
3 Click ‘ON’ if both limit switches are OFF when the valve is moving in normal
operation.
Click ‘OFF’ if both limit switches are ON when the valve is moving in normal
operation.
This selection determines which limit switch combination indicates abnormal
operation.
4 Check to allow the operator trip command to reset any previous faults (I/O
fault, fail to trip, interlock trip), then trip the valve.
Clear this checkbox to reset faults with only the reset command.
5 Check if a trip output is connected to the P_ValveHO instruction to trip the
valve on an interlock or trip command. This check makes the trip command
button visible on the operator tab.
6 Check if sending the trip output to the valve causes it to open (fail open valve).
Clear this checkbox if sending the Trip output to the valve causes it to close
(fail closed valve).

428 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

1
2
3

Table 305 - Engineering Tab Page 2 Description


Item Description
1 Check to send the trip output to the valve if an I/O Fault is detected.
Clear this checkbox to show only the I/O fault status/alarm and not trip the
valve if an I/O fault is detected.
2 The valve always trips on an interlock trip. This item cannot be unchecked. It
is displayed as a reminder that the interlock trip function always trips the
valve.
3 Check to keep sending the trip output to the valve on a trip, even if position
feedback does not confirm the valve reached the trip position.
Clear this checkbox to stop sending the trip output to the valve when the valve
trip times out and the fail to trip status is set.
4 Configure the amount of time the valve status shows ‘tripping’ before
showing an opened or closed status when the valve is tripped and I/O are
being simulated (Inp_Sim = 1).

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 429


Chapter 6 Valves Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3

Table 306 - HMI Configuration Tab Description


Item Description
1 Check if an interlock object is connected to Inp_Intlk. This check changes the
interlock indicator on the operator tab to a button that opens the interlocks
faceplate.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_ValveHO
object has the name ’ValveHO123’, then its Interlock object must be named
‘ValveHO123_Intlk’.
2 Check if a Valve Stats instruction is used with this valve. This check makes the
Valve Statistics button visible; clicking this button opens the valve statistics
faceplate for this valve.
IMPORTANT: The name of the Valve Stats object in the controller must be
the name of the object with the suffix ‘_ValveStats’. For example, if your
P_ValveHO object has the name’ValveHO123’, then its Valve Stats object
must be named ‘ValveHO123_ValveStats’
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

430 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 431


Chapter 6 Valves Family

Motor-operated Valve The P_ValveMO (Motor-operated Valve) Add-On Instruction is used to


operate (open and close) a motor-operated valve in various command sources,
(P_ValveMO) monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Table 307 - P_ValveMO Display Elements Description
Display Element Name Display Element Description
GO_P_ValveMO Standard motor-operated
GO_P_ValveMO1 valve global objects.
GO_P_ValveMO2
GO_P_ValveMO3

432 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 433


Chapter 6 Valves Family

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 308 - Advanced Maintenance Tab Description


Item Description
1 Type the amount of time (in seconds) with no motion after a command for an
alarm to occur.
2 Type the amount of time (in seconds) to reach position after a command before
an alarm occurs.
3 Type the amount of time (in seconds) to pulse the valve outputs.
0 means that the outputs are always on.

434 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Engineering Tab

1
2
3

4
5
6
7
8

Table 309 - Engineering Tab Page 1 Description


Item Description
1 Check if the valve has a closed limit switch and the switch is wired to
Inp_ClosedLS for position monitoring.
2 Check if the valve has an open limit switch and the switch is wired to
Inp_OpenLS for position monitoring.
3 Click ‘ON’ if both limit switches are off when the valve is moving in normal
operation.
Click ‘OFF’ if both limit switches are on when the valve is moving in normal
operation. This selection determines which limit switch combination indicates
abnormal operation.
4 Check to allow operator commands to reset any previous faults (I/O fault,
transit stall, full stall, interlock trip), then move the valve.
Clear this checkbox to reset faults by using only the reset command.
5 Check to allow External commands to reset any previous faults (I/O fault,
transit stall, full stall, interlock trip), then move the valve.
Clear this checkbox to reset faults by using only the reset command.
6 Check if a signal used to stop valve motion is connected to the Out_Stop
output of the instruction. This action makes the Stop command button visible
on the Operator tab.
7 Check to allow the state to change when coasting into the limit switch.
Clear this checkbox keep the state when coasting into the limit switch.
8 Check to bypass permissives that can be bypassed in Override command
source.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 435


Chapter 6 Valves Family

1
2
3
4
5

Table 310 - Engineering Tab Page 2 Description

Item Description
1 Check to send a stop output to the valve and clear the Open and Close outputs
when an I/O Fault condition occurs.
Clear this checkbox to keep the outputs to the valve in their current state on an
I/O Fault condition.
IMPORTANT: When this checkbox is checked and an I/O Fault condition
occurs, a reset is required before the valve can be energized.
2 Check to send a stop output to the valve and clear the Open and Close outputs
when a Transit Stall condition occurs.
Clear this checkbox to keep the outputs to the valve in their current state (keep
trying) on a Transit Stall condition. (A Transit Stall means the valve, when
commanded to move, moved off its original position, but did not reach its
commanded position before the Transit Stall time expired.)
IMPORTANT: When this checkbox is checked and a Transit Stall condition
occurs, a reset is required before the valve can be energized.
3 Check to send a stop output to the valve and clear the Open and Close outputs
when a Full Stall condition occurs.
Clear this checkbox to keep the outputs to the valve in their current state (keep
trying) on a Full Stall condition. (A Full Stall means the valve, when
commanded to move, did not move off its original position before the Full
Stall time expired.)
IMPORTANT: When this checkbox is checked and a Full Stall condition
occurs, a reset is required before the valve can be energized.
4 Check to send a stop output to the valve and clear the Open and Close outputs
when an Actuator Fault condition occurs.
Clear this checkbox to keep the outputs to the valve in their current state on an
Actuator Fault condition.
IMPORTANT: When this checkbox is checked and an Actuator Fault
condition occurs, a reset is required before the valve can be energized.

436 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Item Description
5 The device always de-energizes on an interlock trip. This item cannot be
unchecked. It is displayed as a reminder that the interlock trip function always
causes the valve to de-energize.
6 Type the time delay (in seconds) for the opened or closed status to be echoed
back when Simulation is enabled or when limit switch feedback is not used.
7 Type the seconds to sound an audible alarm when the valve energizes.

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3
4

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 437


Chapter 6 Valves Family

Table 311 - HMI Configuration Tab Description


Item Description
1 Check if you have a P_Perm instruction that is used with this valve for Open
Permissives. This action changes the Permissive indicator to a clickable button
to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_OpenPerm’. For example, if your
P_ValveMO object has the name ‘ValveMO123’, then its Permissive object
must be named ‘ValveMO123_OpenPerm’.
2 Check if you have a P_Perm instruction that is used with this valve for Close
Permissives. This action changes the Permissive indicator to a clickable button
to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_ClosePerm’. For example, if your
P_ValveMO object has the name ‘ValveMO123’, then its Permissive object
must be named ‘ValveMO123_ClosePerm’.
3 Check if an interlock instruction is used with this output.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_ValveMO
object has the name ’ValveMO123’, then its Interlock object must be named
‘ValveMO123_Intlk’.
4 Check if a Valve Stats object is used with this valve. This action makes the
Valve Statistics button visible; click this button to open the Valve Statistics
faceplate for this valve.
IMPORTANT: The name of the ValveStats object in the controller must be
the name of the object with the suffix ‘_ValveStats’. For example, if your
P_ValveMO object has the name ‘ValveMO123’, then its Valve Stats object
must be named ‘ValveMO123_ValveStats’.
5 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

438 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 439


Chapter 6 Valves Family

Mix-proof Valve The Mix-proof Valve (P_ValveMP) Add-On Instruction controls one mix-
proof valve in various command sources and states. This valve can also check
(P_ValveMP) position feedback inputs to verify that the valve reached the commanded
position. An alarm can be provided on failure to reach a target position.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 312 - P_ValveMP Display Element Description


Display Element Name Display Element Description
GO_P_ValveMP2D This Mix-proof Valve
graphic object allows for
numerous orientations on
displays.

GO_P_ValveMP_Orth This 3-D orthogonal Mix-


proof Valve graphic object
provides different valve
angle positions on displays.

GO_P_ValveMP_Orth1 This 3-D orthogonal Mix-


proof Valve graphic object
provides different valve
angle positions on displays.

440 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

2
3
4
5

Table 313 - Operator Tab Description


Item Description
1 Click to go to the CIP/SIP Valve Lower Seat state.
2 Click to go to the CIP/SIP Valve Upper Seat state.
3 Click to go to the CIP/SIP Valve Cavity state.
4 Click to go to the Lift Valve Lower Seat state.
5 Click to go to the Lift Valve Upper Seat state.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 441


Chapter 6 Valves Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

442 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 314 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type a value (seconds) that gives the valve time to achieve state before
triggering a valve failure fault.
2 Type a value (seconds) that the valve seat is held closed when pulsing for
cleaning.
3 Type a value (seconds) that the valve seat is held open when pulsing for
cleaning.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 443


Chapter 6 Valves Family

Table 315 - Advanced Maintenance Tab Page 2 Description

Item Description
1 Click a state box to open the State Configuration display to access
configuration parameters for the valve state

State Configuration Display

1 3

Table 316 - State Configuration Display Description


Item Description
1 Set State of each Output in the selected valve state.
2 Check to require a feedback signals for the selected valve state.
3 Sets the desired value of the feedback signals for the selected valve state.
4 Type a value (seconds) the feedback must match for the valve to achieve the
selected state.

444 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Engineering Tab

1
2

3
4

5
6

Table 317 - Engineering Tab Page 1 Description


Item Description
1 Check to enable the lift lower seat state for the valve.
2 Check to enable pulsing in the lift lower state.
3 Check to enable the lift upper seat state for the valve.
4 Check to enable pulsing in the lift upper state.
5 Check to enable the SIP lower seat state for the valve.
6 Check to enable pulsing in the SIP/CIP lower state.
7 Check to enable the SIP upper seat state for the valve.
8 Check to enable pulsing in the SIP/CIP upper state.
9 Check to enable the SIP cavity state for the valve.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 445


Chapter 6 Valves Family

2
3

4
5
6

Table 318 - Engineering Tab Page 2 Description


Item Description
1 Check to reset a fault on a new Operator command.
2 Check to reset a fault on a new External command.
3 Check to bypass permissives and interlocks in Override command source.
4 Check to close the valve when an I/O Fault occurs. A reset is required to clear
this latched shed condition.
Clear this checkbox to show only the I/O fault status/alarm and not trip the
valve if an I/O fault is detected.
5 Check to close the valve when a Position Fail occurs. A reset is required to
clear this latched shed condition.
Clear this checkbox to show only the Position Fail status/alarm and not trip the
valve if a Position Fail is detected.
6 The device always sheds (closes) on an interlock trip. This item cannot be
unchecked. It is displayed as a reminder that the interlock trip function always
triggers a shed.

446 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

2
3

Table 319 - HMI Configuration Tab Description


Item Description
1 Check if a Permissive object is used with this valve. This check changes the
Permissive indicator to a clickable button to open the Permissive faceplate.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your
P_ValveMP object has the name ’ValveMP123’, then its Permissive object
must be named ‘ValveMP123_Perm’.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 447


Chapter 6 Valves Family

Item Description
2 Check if an Interlock object is used with this valve. This check changes the
Interlock indicator to a clickable button to open the Interlock faceplate.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_ValveMP
object has the name ’ValveMP123’, then its interlock object must be named
‘ValveMP123_Intlk’.
3 Check if the Valve Stats instruction (for example, P_ValveStats) is used with
this device. This check adds a button to the faceplate that opens the Valve Stats
faceplate.
IMPORTANT: The name of the Valve Statistics object in the controller must
be the name of the object with the suffix ‘_ValveStats’. For example, if your
P_ValveMP object has the name ’ValveMP123’, then its Interlock object must
be named ‘ValveMP123_ValveStats’.
4 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

448 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 449


Chapter 6 Valves Family

Advanced Mix-proof The Advanced Mix-proof Valve (P_ValveMPAdv) Add-On Instruction


controls one mix-proof valve in various command sources and states. This
Valve (P_ValveMPAdv) instruction can also check valve position feedback inputs to verify that the
valve reached the commanded position. An alarm can be provided on failure to
reach a target position.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 320 - P_ValveMPAdv Display Element Description


Display Element Name Display Element Description
GO_P_ValveMPAdv2D This Advanced Mix-proof
Valve graphic object allows
for numerous orientations
on displays.

GO_P_ValveMPAdv_Orth This 3-D orthogonal


Advanced Mix-proof Valve
graphic object provides
different valve angle
positions on displays.

GO_P_ValveMPAdv_Orth1 This 3-D orthogonal


Advanced Mix-proof Valve
graphic object provides
different valve angle
positions on displays.

450 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

2
3
4

Table 321 - Operator Tab Description


Item Description
1 Click to go to the Lift Valve Upper Seat state.
2 Click to go to the CIP/SIP Valve Cavity state.
3 Click to go to the CIP/SIP Valve Upper Seat state.
4 Click to go to the CIP/SIP Valve Lower Seat state.
5 Click to go to the Lift Valve Lower Seat state.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 451


Chapter 6 Valves Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

Item Description
1 Select Yes to enable the valve locator. When yes is selected the valve locator
lamp will be illuminated

452 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

2
3

Table 322 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type a value (seconds) that gives the valve time to achieve state before
triggering a valve failure fault.
2 Type a value (seconds) that the valve seat is held closed when pulsing for
cleaning.
3 Type a value (seconds) that the valve seat is held open when pulsing for
cleaning.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 453


Chapter 6 Valves Family

Table 323 - Advanced Maintenance Tab Page 2 Description

Item Description
1 Click a state box to open the State Configuration display to access
configuration parameters for the valve state

State Configuration Display

1 3

Table 324 - State Configuration Display Description


Item Description
1 Set State of each Output in the selected valve state.
2 Check to require a feedback signals for the selected valve state.
3 Sets the desired value of the feedback signals for the selected valve state.
4 Type a value (seconds) the feedback must match for the valve to achieve the
selected state.

454 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Engineering Tab

1
2

3
4

5
6

Table 325 - Engineering Tab Page 1 Description


Item Description
1 Check to enable the lift lower seat state for the valve.
2 Check to enable pulsing in the lift lower state.
3 Check to enable the lift upper seat state for the valve.
4 Check to enable pulsing in the lift upper state.
5 Check to enable the SIP lower seat state for the valve.
6 Check to enable pulsing in the SIP/CIP lower state.
7 Check to enable the SIP upper seat state for the valve.
8 Check to enable pulsing in the SIP/CIP upper state.
9 Check to enable the SIP cavity state for the valve.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 455


Chapter 6 Valves Family

2
3

4
5
6

Table 326 - Engineering Tab Page 2 Description


Item Description
1 Check to reset a fault on a new Operator command.
2 Check to reset a fault on a new External command.
3 Check to bypass permissives and interlocks in Override command source.
4 Check to close the valve when an I/O Fault occurs. A reset is required to clear
this latched shed condition.
Clear this checkbox to show only the I/O fault status/alarm and not trip the
valve if an I/O fault is detected.
5 Check to close the valve when a Position Fail occurs. A reset is required to
clear this latched shed condition.
Clear this checkbox to show only the Position Fail status/alarm and not trip the
valve if a Position Fail is detected.
6 The device always sheds (closes) on an interlock trip. This item cannot be
unchecked. It is displayed as a reminder that the interlock trip function always
triggers a shed.

456 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2
3

4
5

Table 327 - HMI Configuration Tab Description


Item Description
1 Check if a valve Open Interlock object is used with this valve. This check
changes the Open Interlock indicator to a clickable button to open the
Interlock faceplate associated with the Open functions of this valve.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix '_OpenIntlk'. For example, if your
P_ValveMPAdv object has the name 'ValveMP123', then its open interlock
object must be named 'ValveMP123_OpenIntlk'.
2 Check if a valve Lower Seat Interlock object is used with this valve. This
check changes the Lower Seat Interlock indicator to a clickable button to open
the Interlock faceplate associated with the Lower Seat functions of this valve.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix '_LowerSeatIntlk'. For example, if your
P_ValveMPAdv object has the name 'ValveMP123', then its lower seat
interlock object must be named 'ValveMP123_LowerSeatIntlk'.
3 Check if a valve Upper Seat Interlock object is used with this valve. This
check changes the Upper Seat Interlock indicator to a clickable button to open
the Interlock faceplate associated with the Upper Seat functions of this valve.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix '_UpperSeatIntlk'. For example, if your
P_ValveMPAdv object has the name 'ValveMP123', then its upper seat
interlock object must be named 'ValveMP123_UpperSeatIntlk'.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 457


Chapter 6 Valves Family

Item Description
4 Check if a valve Cavity Interlock object is used with this valve. This check
changes the Cavity Interlock indicator to a clickable button to open the
Interlock faceplate associated with the cavity and clean (CIP/SIP) functions of
this valve.
IMPORTANT: The name of the interlock object in the controller must be the
name of the object with the suffix '_CavityIntlk'. For example, if your
P_ValveMPAdv object has the name 'ValveMP123', then its cavity interlock
object must be named 'ValveMP123_CavityIntlk'.
5 Check if the Valve Stats instruction (for example, P_ValveStats) is used with
this device. This check adds a button to the faceplate that opens the Valve Stats
faceplate.
IMPORTANT: The name of the Valve Statistics object in the controller must
be the name of the object with the suffix '_ValveStats'. For example, if your
P_ValveMPAdv object has the name 'ValveMP123', then its Interlock object
must be named 'ValveMP123_ValveStats'.
6 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

458 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 459


Chapter 6 Valves Family

Solenoid-operated The P_ValveSO (Solenoid-operated Valve) Add-On Instruction is used to


operate (open and close) a solenoid-operated valve in various command
Valve (P_ValveSO) sources, monitoring for fault conditions.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 328 - P_ValveSO Display Element Description


Display Element Name Display Element Description
P_ValveSO Standard solenoid-operated
P_ValveSO1 valve global objects.
P_ValveSO2
P_ValveSO3

460 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 461


Chapter 6 Valves Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

1
2

Table 329 - Maintenance Tab Description


Item Description
1 Check if the instruction uses the closed limit switch feedback to check for
valve full stall or transit stall.
2 Check if the instruction uses the open limit switch feedback to check for valve
full stall or transit stall.

462 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 330 - Advance Maintenance Tab Description


Item Description
1 Type the amount of time to allow for the valve to move off the current position
before raising a Full Stall alarm.
2 Type the amount of time to allow for completing valve travel before raising a
Transit Stall alarm.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 463


Chapter 6 Valves Family

Engineering Tab

1
2
3

4
5
6
7

Table 331 - Engineering Tab Page 1 Description


Item Description
1 Check if the valve has a closed limit switch and the switch is wired to
Inp_ClosedLS for position monitoring.
2 Check if the valve has an open limit switch and the switch is wired to
Inp_OpenLS for position monitoring.
3 Click ON if both limit switches are OFF when the valve is in motion.
Click OFF if both limit switches are ON when the valve is in motion. This
selection determines how the instruction detects a stuck limit switch.
4 Check to allow an Operator Open or Close command to reset any previous
faults (I/O Fault, Transit Stall, Full Stall, Interlock Trip), then open or close
the valve.
Clear this checkbox to reset faults by using the Reset command.
5 Check to allow an External Open or Close command to reset any previous
faults (I/O Fault, Transit Stall, Full Stall, Interlock Trip), then open or close
the valve.
Clear this checkbox to reset faults by using the Reset command.
6 Check if the valve fails Open for energize-to-close operation.
Clear this checkbox if the valve fails Closed for energize-to-open operation.
7 Check to bypass interlocks and permissives (that can be bypassed) in Override
command source.

464 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

1
2
3
4

Table 332 - Engineering Tab Page 2 Description


Item Description
1 Check to de-energize the output to the valve and return it to its fail position,
when an I/O Fault condition occurs.
Clear this checkbox to keep the output to the valve in its current state on an I/
O Fault condition.
IMPORTANT: When this checkbox is checked and an I/O Fault condition
occurs, a Reset is required before the valve can be energized.
2 Check to de-energize the output to the valve and attempt to return it to its fail
position, when a Transit Stall condition occurs.
Clear this checkbox to keep the output to the valve in its current state (keep
trying) on a Transit Stall condition. (A Transit Stall means the valve, when
commanded to move, moved off its original position, but did not reach its
commanded position before the Transit Stall time expired.)
IMPORTANT: When this checkbox is checked and a Transit Stall condition
occurs, a Reset is required before the valve can be energized.
3 Check to de-energize the output to the valve, attempting to return it to its fail
position, when a Full Stall condition occurs.
Clear this checkbox to keep the output to the valve in its current state (keep
trying) on a Full Stall condition. (A Full Stall means the valve, when
commanded to move, did not move off its original position before the Full
Stall time expired.)
IMPORTANT: When this checkbox is checked and a Full Stall condition
occurs, a Reset is required before the valve can be energized.
4 The valve outputs are always de-energized on an Interlock Trip. This item
cannot be unchecked. It is displayed as a reminder that the Interlock Trip
function always de-energizes the valve.
5 Sets the time delay (in seconds) for the opened or closed status to be echoed
back when Simulation is enabled or when limit switch feedback is not used.
6 Type the seconds to sound an audible alarm when the valve energizes.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 465


Chapter 6 Valves Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

1
2

3
4

Table 333 - HMI Configuration Tab Description


Item Description
1 Check if a permissive object is connected to the Permissive input. This action
changes the Permissive indicator to a clickable button.
IMPORTANT: The name of the Permissive object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your
P_ValveSO object has the name ’ValveSO123’, then its Permissive object
must be named ‘ValveSO123_Perm’.

466 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Item Description
2 Check if an interlock object is connected to the Interlock input. This action
changes the Interlock indicator to a clickable button.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_ValveSO
object has the name’ValveSO123’, then its Interlock object must be named
‘ValveSO123_Intlk’.
3 Check if a Valve Stats object is used with this valve. This action makes the
Valve Statistics button visible.
IMPORTANT: The name of the Valve Stats object in the controller must be
the name of the object with the suffix ‘_ValveStats’. For example, if your
P_ValveSO object has the name’ValveSO123’, then its Valve Stats object must
be named ‘ValveSO123_ValveStats’
4 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 467


Chapter 6 Valves Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

468 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

2-state Valve Statistics The P_ValveStats (2-state Valve Statistics) Add-On Instruction monitors a
2-state (open and close) valve and records various statistics that are related to
(P_ValveStats) stroke times and stroke counts.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 334 - P_ValveStats Display Element Description


Display Element Name Display Element Description
GO_P_ValveStats This GO_P_ValveStats
object can be added to
application graphics to
access valve statistics. A
similar object is already
included on faceplates for
2-state valves to provide
access to valve statistics.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 469


Chapter 6 Valves Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

The Operator tab shows the following information:


• Completion information and moving average for close and open strokes.
• Count and last stroke information for slow close and slow open strokes.
• Current, last, maximum, and total time in different states.

Table 335 - Operator Tab Description


Item Description
1 Click this symbol to reset an accumulated time or count.

470 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the engineering settings. The


Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Engineering Tab

Table 336 - Engineering Tab Description


Item Description
1 Check when a valve has stopped or other state to monitor.
2 Type the number of seconds to give the valve to close before counting a slow
close stroke.
3 Type the number of seconds to give the valve to open before counting a slow
open stroke.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 471


Chapter 6 Valves Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Table 337 - HMI Configuration Tab Description


Item Description
1 Type a name for the Stopped or other state of the valve.

472 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 473


Chapter 6 Valves Family

n-Position Device The P_nPos (n-Position Device) Add-On Instruction controls a circular or
linear discrete device with 2…8 positions. The P_nPos instruction provides
(P_nPos) outputs to select an individual position and outputs to move toward increasing
positions (‘clockwise’ for a circular device) or decreasing positions
(‘counterclockwise’ for a circular device).

For linear devices, the P_nPos instruction can be configured to return to


Position 1 on every move, approaching the target position from the ‘same side’
on each move to improve position repeatability, or move directly to the
new position.

For circular devices, the P_nPos instruction can be configured to move only
‘clockwise’ to increase positions (for example, 6, 7, 8, 1, 2…). The instruction
can also be configured to move both directions by using the shortest move (for
example, ‘clockwise’ from 6…1: 6, 7, 8, 1; or ‘counterclockwise’ from 2…7: 2, 1,
8, 7).

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

474 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 338 - P_nPos Display Elements Description


Display Element Display Element Description
Name
GO_P_nPos_8SelV These display elements
alve are used for routing
one flow path to many
vertically. These
elements show all 3, 4,
GO_P_nPos_8SelV 6, or 8 ports and
alve1 unused ports are not
hidden.

GO_P_nPos_6SelV
alve

GO_P_nPos_6SelV
alve1

GO_P_nPos_4SelV
alve

GO_P_nPos_4SelV
alve1

GO_P_nPos_3SelV
alve

GO_P_nPos_3SelV
alve1

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 475


Chapter 6 Valves Family

Table 338 - P_nPos Display Elements Description


Display Element Display Element Description
Name
GO_P_nPos_8PosR These display elements
otary are used for rotary
selection from one port
to many ports. Only the
ports that are enabled
are displayed. For
example, if you
configure the P_nPos
instruction with five
GO_P_nPos_6PosR positions, ports 6, 7,
otary and 8 are not displayed.

GO_P_nPos_4PosR
otary

GO_P_nPos_Slide These display elements


Gate show a linear multi-
position device. The
symbol is animated to
GO_P_nPos_Slide show the position that
Gate1
is based on the number
of positions
configured.

GO_P_nPos These display elements


are similar to those
elements shown on the
first page of this table,
but ports that aren’t
configured are not
displayed.
GO_P_nPos1

476 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator command source. Several features are common to all Add-On
Instructions faceplates for the valves family. See Common Valves Faceplates on
page 411.

Table 339 - Operator Tab Description


Item Description
1 Current Device Position.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 477


Chapter 6 Valves Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates for the valves family.
See Common Valves Faceplates on page 411.

1
2

Table 340 - Maintenance Tab Description


Item Description
1 Check to have the instruction use the Position Feedback to check the position
of the device.
2 Check to have the instruction use the index cylinder position feedback.

478 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Advanced Properties Display

The Advanced Properties Display opens to the advanced maintenance settings.


The Advanced Properties Display provides access to device configuration
parameters and ranges, and options for device and I/O setup. This tab is used
for initial system commissioning or later system changes.

Advanced Maintenance Tab

Table 341 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type a value (0…2,147,483) that indicates the maximum time that is allowed
for lock feedback before a fail.
2 Type a value (0…2,147,483) that indicates the maximum time that is allowed
for the device to be in position before a fail.
3 Type a value (0…2,147,483) that indicates the time delay before engaging a
cylinder move.
4 Type a value (0…2,147,483) that indicates the delay time to verify that a
device is in a commanded position.
5 Type a value (0…2,147,483) to indicate the number of retires for a device in
Position 1 before a fault
is set.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 479


Chapter 6 Valves Family

1 4

3 5

Table 342 - Advanced Maintenance Tab Page 2 Description


Item Description
1 This state is highlighted whenever the device is in the position that it was last
commanded.
2 This state is highlighted if the device feedback fails to confirm that the device
is unlocked, moved to position, or locked as requested within the configured
failure times.
3 This state is displayed only if the device is configured with a lock or seal that
must be unlocked or unsealed to move. This state is highlighted when the
device has reached its commanded position and has been commanded to lock,
but locked feedback has not been received yet.
4 This state is displayed only if the device is configured with a lock or seal that
must be unlocked or unsealed to move. This state is highlighted when the
device has been commanded to unlock, but unlocked feedback has not been
received yet.
5 This state is highlighted when the device is being moved to its commanded
position, but that position feedback has not been received yet.

There is an additional state that is not identified in this diagram.


• State 3 - Moving to Position - This state is displayed only if the device
is configured as a linear device that returns to position 1 on every
move. This strategy is used to approach each position from the same
side. This state is highlighted when the device has been unlocked and
is being moved to position 1, but position 1 feedback has not been
received yet.

480 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Engineering Tab

3
4

Table 343 - Engineering Tab Page 1 Description


Item Description
1 Click circular or linear for the device type.
2 For Circular, click either clockwise only or clockwise or counterclockwise.

For Linear, click whether the device returns to Position 1 for every move or
moves directly to the target position.
3 Check to reset a fault on a new Operator command.
4 Check to reset a fault on a new External command.
5 Check to bypass permissives and interlocks in Override command source.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 481


Chapter 6 Valves Family

1
2
3
4

7
8
9

Table 344 - Engineering Tab Page 2 Description


Item Description
1 Check to enable device feedback for all positions.
2 Check to enable a new position command to be received and processed while
a move is in progress.
3 Check to keep a position output On until the next move.
4 Check to enable indexing cylinders with position feedback.
5 Check if the device must be unlocked to move and locked when the move is
complete.
6 Check if the device has feedback for locked/unlocked positions.
7 Type the time (0…2,147,483) to reach a target position in simulation.
8 Type the time (0…2,147,483) to lock/unlock with the device in simulation.
9 Type the time (0…2,147,483) to simulate index cylinder feedback in
simulation.

482 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

3
4

Table 345 - Engineering Tab Page 3 Description


Item Description
1 Check to enable whether an I/O Fault, Failure to Reach Position, or Lock
Failure is considered a shed condition.
The device always sheds on an Interlock Trip. This item cannot be unchecked.
It is displayed as a reminder that the Interlock Trip function always triggers a
shed.
If a condition causes the device to shed, a reset is required to operate the
device.
2 Click to determine whether the device holds the hold position or goes to
position 1 upon a shed condition.
3 Click to sound an audible on a commanded stage from Position 1.
4 Click to sound an audible on a commanded stage from any State.
5 Type the time (in seconds) that the audible sounds when there is a commanded
State change.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 483


Chapter 6 Valves Family

HMI Configuration Tab

The HMI configuration tab provides access to displayed text, and faceplate-to-
faceplate navigation settings. Configure the description, label, tag, and security
area for the device. See Basic Faceplate Attributes on page 32 for the
description of the common attributes.

Table 346 - HMI Configuration Page 1 Description


Item Description
1 Type a name for each device position that is based on the number of positions.

484 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

1
2
3

Table 347 - HMI Configuration Page 2 Description


Item Description
1 Check to indicate that a permissive object is connected to the permissive
inputs of this object.
IMPORTANT: The name of the Permissives object in the controller must be
the name of the object with the suffix ‘_Perm’. For example, if your P_nPos
object has the name ’nPos123’, then its Permissives object must be named
‘nPos123_Perm’.
2 Check to indicate that an interlock object is connected to the interlock inputs
of this object.
IMPORTANT: The name of the Interlock object in the controller must be the
name of the object with the suffix ‘_Intlk’. For example, if your P_nPos object
has the name ’nPos123’, then its Interlock object must be named
‘nPos123_Intlk’.
3 Check to enable navigation to an object with more information
(Cfg_HasMoreObj is set to true.)
This can be configured to navigate to an AOI backing tag or a UDT tag that
has HMI_Type and HMI_Lib defined.
For example, there is a motor with the tag name P_101 and there is a need to
have the more information button navigate to the parent P_LLS object. A tag
is created for the P_LLS object that is given the alias P101_More. When the
more information button is pressed on the motor, it links to P101_More. This
will open the faceplate for the LLS object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 485


Chapter 6 Valves Family

Diagnostics Tab

The Diagnostic tab provides indications that are helpful to diagnose or help
prevent device problems. The device problems can include specific reasons a
device is 'Not Ready', device warnings and faults, warning and fault history, and
predictive/preventive maintenance data.

The Diagnostics tab displays possible reasons for the device not being ready.
See Diagnostics Tab on page 36

Alarms Tab

The Alarms tab displays each configured alarm. The icon on the tab for the
alarms page changes color to show the current active alarm status. A blinking
alarm icon indicates that one or more alarms must be acknowledged or the
device must be reset. See Common Alarm Block (P_Alarm) on page 66 for
more information.

486 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Valves Family Chapter 6

Discrete 2-, 3-, 4-state The P_D4SD (Discrete 2-, 3-, 4-state Device) Add-On Instruction controls
and monitors feedback from a discrete 2-state, 3-state, or 4-state device in
Device (P_D4SD) various command sources, monitoring for fault conditions. These devices
include multiple-speed motors or multiple-position valves.

See Discrete 2-, 3-, 4-state Device (P_D4SD) on page 286

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-on Instructions and
controller code is contained in publication PROCES-RM013.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 487


Chapter 6 Valves Family

Notes:

488 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Chapter 7

Built-in Instructions Family

The faceplates that appear in this section are designed to let the function
blocks and built-in firmware instructions for the Logix 5000 controllers
interface with the Process Library Add-On Instructions. This document is for
the visualization files, display elements, global objects, and HMI information.
The operation of the Add-On Instructions and controller code is contained in
publication PROCES-RM013.

For details on built-in instructions, see the Logix 5000 Controllers Advanced
Process Control and Drives Instructions Reference Manual, publication 1756-
RM006.

Proportional + Integral The Studio 5000 Logix Designer® application PIDE autotuner provides an
openloop autotuner that is built into the PIDE instruction. This function
+ Derivative Enhanced filters a signal to assist with the calculation of control variables. You can
(PIDE) Autotune autotune from PanelView™ Plus terminals or any other operator interface
devices and Logix Designer application.

The PIDE block has an Autotune Tag (type PIDE_AUTOTUNE) that you
specify for those PIDE blocks that you want to autotune.

IMPORTANT The PIDE autotuner is installed with the Logix


Designer application, but you need an activation
key to enable the autotuner. The autotuner is
supported only in function block programming; it is
not available in relay ladder or structured text
programming.

The Autotune function is accessed through the Advanced Maintenance tab of


the Built-in PIDE faceplate.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 489


Chapter 7 Built-in Instructions Family

Autotune Page 1

1 3

4
2

Table 348 - Autotune Page 1 Description


Item Description
1 Tag Status Indicator
2 Click the item that best describes the process.
3 Click to acquire the Autotune tag.
4 Click to release the Autotune tag.
5 Type a value for the PV Change Limit. The autotune is aborted if the PV
changes by more than this amount.

490 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Autotune Page 2

1 3

Table 349 - Autotune Page 2 Description


Item Description
1 Autotune Status Indicator
2 Type a value for CV step size in percent for the tuning step test.
3 Click to start the Autotune process for CV1, CV2, and CV3.
4 Click to stop the Autotune process.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 491


Chapter 7 Built-in Instructions Family

Autotune Page 3

4
2 5

3 6

Table 350 - Autotune Page 3 Description

Item Description
1 Click an option for response speed.
2 Press the ‘Use Gains’ button to copy the selected gains into the current PIDE
gain tags.
3 Autotune Status Indicator
4 Type a value for Proportional gain.
5 Type a value for Integral gain.
6 Type a value for Derivative gain.

492 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Coordinated Control The Coordinated Control (CC) function block controls one process variable
by manipulating as many as three different control variables. As an option, any
(CC) of the three outputs can be used as an input to create feed forward action in the
control variable. The CC function block calculates the control variables (CV1,
CV2, and CV3) in the Auto mode based on the PV - SP deviation, internal
models, and tuning.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix® system, aid consistency and save engineering time.
Table 351 - Coordinated Control Display Elements Description
Display Element Name Display Element Description
GO_BuiltIn_CC Coordinated Control object
with a Process Variable and
three Control Variables.

GO_BuiltIn_CC1 Coordinated Control object


with a Process Variable,
Setpoint, and three Control
Variables.

GO_BuiltIn_CC2 Coordinated Control object


with a Process Variable and
a Setpoint.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 493


Chapter 7 Built-in Instructions Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

5 6

1 7

8
2

Table 352 - Operator Tab Description

Item Description
1 Current setpoint
2 Current process variable
3 Setpoint slider
4 Process variable indicator
5 Type a value for control variable output (CV1, CV2, CV3).
6 Control variable sliders
7 Manual loop
8 Auto loop

494 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1
2

4
5

Table 353 - Maintenance Tab Description

Item Description
1 Type the setpoint high threshold.
2 Type the setpoint low threshold.
3 Type the CV high and low, in percent (CV1, CV2, CV3).
4 Type the CV Rate of Change positive limit, in percent per second. (CV1, CV2,
CV3).
Rate of change limiting is used only when in Auto mode or in Manual mode if
CVManLimiting is true. A value of zero disables CV1 ROC limiting.
5 Type the CV Rate of Change negative limit, in percent per second. (CV1, CV2,
CV3).
Rate of change limiting is used only when in Auto mode or in Manual mode if
CVManLimiting is true. A value of zero disables CV1 ROC limiting.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 495


Chapter 7 Built-in Instructions Family

Advanced Tab

Tuning

The tuning tab consists of separate pages for each CV. The following example
shows page 1. Pages for the additional CV settings have the same setup
parameters. Click the page numbers to advance to the next CV.

1
2
3
4
5

Table 354 - Tuning Tab Description

Item Description
1 Enter the target value for CV, CV2, or CV3.
2 Enter the CV1, CV2, or CV3 gain.
3 Enter the CV1, CV2, or CV3 time constant.
4 Enter the deadtime forCV1, CV2, or CV3.
5 Enter the CV1, CV2, or CV3 response time constant. This value determines the
speed of the CV in seconds.
6 Click to open the CC Autotune (CV1, CV2, or CV3) faceplate. See Coordinated
Control (CC) Autotune on page 506.
7 Click to request Auto Loop mode.

496 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

2
3
4

Table 355 - Maintenance Tab Page 1 Description

Item Description
1 Type the Operator setpoint.
2 Type the maximum limit for the setpoint.
3 Type the minimum limit for the setpoint.
4 Actual Setpoint
5 Type the maximum and minimum limits for the PV in engineering units.
6 Calculated values that are used on the next page.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 497


Chapter 7 Built-in Instructions Family

This example shows the functions for CV1, CV2, and CV3. The functions for
CV1 are described. The functions for CV2 and CV3 are the same as CV1.

2
3
4
5

Table 356 - Maintenance Tab Page 2 Description

Item Description
1 Type in the value (%) for CV.
2 Type in the maximum limit for the CV.
3 Type in the minimum limit for the CV.
4 Type in the maximum CV Rate of Increase.
5 Type in the minimum CV Rate of Increase.
6 Turn on to enable CV tracking when autotune is off. This parameter is ignored
in Hand and Operator mode.

498 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

This example shows the functions for CV1, CV2, and CV3. The functions for
CV1 are described. The functions for CV2 and CV3 are the same as CV1.

2
3
4
5

Table 357 - Maintenance Tab Page 3 Description

Item Description
1 Type the CV1, CV2, or CV3 Override value.
CV1, CV2, or CV3 is set to this value when in Override mode.
This value is recommended to correspond to a safe state output of the loop.
2 CV output %
3 Type the maximum value for CV1EU, CV2EU, or CV3EU.
The value of CV1EU, CV2EU, or CV3EU that corresponds to 100% CV1,
CV2, or CV3.
4 Type the minimum value for CV1EU, CV2EU, or CV3EU.
The value of CV1EU, CV2EU, or CV3EU that corresponds to 0% CV1, CV2,
or CV3.
5 Current value (EU)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 499


Chapter 7 Built-in Instructions Family

Engineering Tab

1
2
6
3
4 7

5 8

Table 358 - Engineering Tab Page 1 Description


Item Description
1 Check to limit the current value when in Manual mode.
2 Check to set the Loop mode to manual when CV initialization is requested.
Clear the checkbox to leave the Loop mode unchanged when initialization is
requested. When the initialization request clears, the loop resumes control in its
previous Loop mode.
3 Check to reset Program inputs after each execution.
4 Click to Set true to enable PV Tracking when autotune is OFF.
This parameter is ignored in Hand and Override mode.
5 Click to select CV1, CV2, or CV3 to be the first, second, or third to act to
compensate for PV-SP deviation.
6 Type the CV1, CV2, or CV3 target value.
7 Type a value for the Target Response Time Constant.
8 Click to set the PV target action priority for CV1, CV2, and CV3.

500 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 359 - Engineering Tab Page 2 Description


Item Description
1 Click to select the time base execution mode.
2 Click to select the model gain units. (Percent or Engineering Units)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 501


Chapter 7 Built-in Instructions Family

Faults Tab

Page 1 of the Faults tab displays PID Instruction faults.

Page 2 of the Faults tab displays PID Instruction Configuration Faults.

502 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

Table 360 - Trends Tab Description


Item Description
1 Click to open the trends for the PV with Setpoint.
2 Click to open the trend tab for the control variables.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 503


Chapter 7 Built-in Instructions Family

PV with Setpoint Trends Tab

CV Trends Tab

504 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 505


Chapter 7 Built-in Instructions Family

Coordinated Control (CC) Autotune

2
3
4
5

Table 361 - CC Autotune Tab Page 1 Description


Item Description
1 Click either Integrating or Non-integrating.
2 Enter the PV change limit.
3 Type a value for the maximum time for autotune to complete following the CV
step change.
When autotune exceeds this time, tuning is aborted.
4 Type a value for the integrating model approximation factor.
IMPORTANT: You can enter this value only when Integrating is selected as
the Process Type.
5 Click Low, Medium, or High to set the estimate of the noise level that is
expected on the PV to compensate for it during tuning.

506 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

1
2

Table 362 - CC Autotune Tab Page 2 Description


Item Description
1 Type a value for CV1, CV2, or CV3 step size in percent for the tuning step test.
2 Click to start the autotune process.
3 Click to abort the autotune process.
This button also becomes active if the process is aborted due to an error.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 507


Chapter 7 Built-in Instructions Family

1
2
3
4

Table 363 - CC Autotune Tab Page 3 Description


Item Description
1 Type a value for the gain for CV1, CV2, or CV3.
Enter a positive or negative gain depending on process direction.
2 Type a value for CV1, CV2, or CV3 time constant in seconds.
3 Type a value for CV1, CV2, or CV3 deadtime in seconds.
4 Type a value for the tuning parameter that determines the speed of the control
variable action for CV1, CV2, or CV3 in seconds.
5 Click to replace the current model parameters with the calculated Autotune
model parameters.

508 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Internal Model Control The Internal Model Control (IMC) function block controls one process
variable by manipulating one control-variable output. This function block
(IMC) performs an algorithm where the actual error signal is compared against that of
an internal first-order lag plus deadtime model of the process. The IMC
function block calculates the control variable output (CV) in the Auto mode
based on the PV - SP deviation, internal model, and tuning.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements
A display element (global object) is created once and can be referenced
multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 364 - IMC Display Elements Description


Display Element Display Element Description
Name
GO_BuiltIn_IMC Internal Model Control object
with a Process Variable and a
Control Variable.

GO_BuiltIn_IMC2 Internal Model Control object


with a Process Variable,
Setpoint, and a Control
Variable.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 509


Chapter 7 Built-in Instructions Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

4
5
1 6

2 7

3 9

Table 365 - Operator Tab Description


Item Description
1 PV indicator
2 Move this slider to adjust the loop setpoint.
3 Click to request Cascade Loop mode.
IMPORTANT: This button is available only if 'Allow Cascade/Ratio Mode' on
page 1 of the Engineering tab is checked.
4 Type the SP Operator value, scaled in PV units.
SP is set to this value when in Operator control.
5 Type a value for the Ratio Operator multiplier.
Ratio is set to this value when in Operator control.
6 Type a value for CV Operator Manual value.
CV is set to this value when in Operator control and Manual mode.
7 Move this slider to adjust the loop CV output.
8 Click to request Manual Loop mode.
9 Click to request Auto Loop mode.

510 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

Table 366 - Maintenance Tab Page 1 Description


Item Description
1 Type the SP maximum and minimum limits.
2 Type a value for the Ratio high and low limits.
These parameters limit the value of Ratio obtained from RatioProg or
RatioOper.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 511


Chapter 7 Built-in Instructions Family

Table 367 - Maintenance Tab Page 2 Description


Item Description
1 Type values for the CV high and low limits.
It is also used for limiting CV when in Auto or CascadeRatio modes or Manual
mode if CVManLimiting is true.
2 CV increasing or decreasing rate of change limit, in percent per second.
The rate of change limiting is used only when in Auto or CascadeRatio modes
or Manual mode if CVManLimiting is true.
A value of zero disables CV ROC limiting.

512 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Advanced Tab

Tuning

1
6
2
3 7
4

Table 368 - Tuning Tab Description


Item Description
1 Type a value for the internal model gain.
Enter a positive or negative gain depending on process direction.
2 Type a value for the internal model Time Constant in seconds.
3 Type a value for the internal model Deadtime in seconds.
4 Type a value for the tuning parameter that determines the speed of the control
variable action in seconds.
5 Click to request Cascade Loop mode.
6 Click to request Auto Loop mode.
7 Click to request Manual Loop mode.
8 Click to open the CV Autotune faceplate.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 513


Chapter 7 Built-in Instructions Family

Maintenance Tab

1 4

Table 369 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type a value for the Ratio Operator multiplier.
Ratio is set to this value when in Operator control.
2 Type a value for the Ratio high and low limits.
These parameters limit the value of Ratio obtained from RatioProg or
RatioOper.
3 Type the SP maximum and minimum limits.
4 Type a value for the SP Operator value, scaled in PV units.
SP is set to this value when in Operator control.

514 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

2
3
4
5

Table 370 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Type the minimum or maximum limits for the PV in engineering units.
2 Type a value for the internal model gain.
Enter a positive or negative gain depending on process direction.
3 Type a value for the internal model Time Constant in seconds.
4 Type a value for the internal model Deadtime in seconds.
5 Type a value for the tuning parameter that determines the speed of the control
variable action in seconds.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 515


Chapter 7 Built-in Instructions Family

Table 371 - Advanced Maintenance Tab Page 3 Description


Item Description
1 Type the operator CV value.
2 Type values for the CV high and low limits.
It is also used for limiting CV when in Auto or CascadeRatio modes or Manual
mode if CVManLimiting is true.
3 CV increasing or decreasing rate of change limit, in percent per second.
The rate of change limiting is used only when in Auto or CascadeRatio modes
or Manual mode if CVManLimiting is true.
A value of zero disables CV ROC limiting.
4 Check to enable CV Tracking when autotune is OFF.
This parameter is ignored in Hand and Override mode.

516 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 372 - Advanced Maintenance Tab Page 4 Description


Item Description
1 Type the value for the CV Override value.
CV is set to this value when in Override mode.
2 Type the maximum or minimum value for CV EU scaling.
This value corresponds to 100% or 0% CV respectively.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 517


Chapter 7 Built-in Instructions Family

Engineering

1
2

4
5
6

7
8

Table 373 - Engineering Tab Page 1 Description


Item Description
1 Check if Cascade Loop mode is to be used.
IMPORTANT: Checking this option displays the Cascade button on the
Operator tab.
2 Check to enable ratio control when in Cascade Loop mode.
IMPORTANT: Checking this option displays the current ratio multiplier,
Operator ratio multiplier, and Program ratio multiplier on the Operator tab.
Checking this option also displays the Cascade/Ratio portion of the SAMA
diagram on page 1of the Maintenance tab.
3 Check to limit the CV while in Manual mode.
4 Check to set the Loop mode to manual when CV initialization is requested.
Clear the checkbox to leave the Loop mode unchanged when initialization is
requested. When the initialization request clears, the loop resumes control in its
previous Loop mode.
5 Check to reset Program inputs after each execution.
6 Check so that CV cannot increase in value.
7 Check so that CV cannot decrease in value.
8 Click to enable PV Tracking when autotune is OFF.
This parameter is ignored in Hand and Override mode.

518 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 374 - Engineering Tab Page 2 Description


Item Description
1 Click to select the time base execution mode.
2 Click to choose the model gain units. (Percent or Engineering Units)

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 519


Chapter 7 Built-in Instructions Family

Faults Tab

Page 1 of the Diagnostics tab displays PID Instruction faults.

Page 2 of the Diagnostics tab displays PID Instruction Configuration faults.

520 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

Table 375 - Trends Tab Description


Item Description
1 Click to open the trends for the PV with Setpoint.
2 Click to open the trend tab for the control variables.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 521


Chapter 7 Built-in Instructions Family

PV with Setpoint Trends Tab

CV Trends Tab

522 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 523


Chapter 7 Built-in Instructions Family

Internal Model Control (IMC) Autotune

The faceplates in this section let you access all necessary parameters to
autotune the IMC function block and hand-tune the instruction.

2
3
4

Table 376 - IMC Autotune Tab Page 1 Description


Item Description
1 Click either Integrating or Non-integrating.
2 Type a value for the PV limit scaled in PV units.
When Autotune is running and predicted PV exceeds this limit, the tuning is
aborted.
3 Type a value for the maximum time for autotune to complete following the CV
step change.
When autotune exceeds this time, tuning is aborted.
4 Type a value for the non-integrating model approximation factor.
IMPORTANT: You can enter this value only when Integrating is selected as
the Process Type.
5 Click Low, Medium, or High to set the estimate of the noise level expected on
the PV to compensate for it during tuning.

524 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

3
1

Table 377 - IMC Autotune Tab Page 2 Description


Item Description
1 Click to start the autotune process.
2 Type a value for CV1, CV2, or CV3 step size in percent for the tuning step test.
3 Click to abort the autotune process.
This button also becomes active if the process is aborted due to an error.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 525


Chapter 7 Built-in Instructions Family

1
2
3
4

Table 378 - IMC Autotune Tab Page 3 Description


Item Description
1 Type a value for the internal model gain for CV1, CV2, or CV3.
Enter a positive or negative gain depending on process direction.
2 Type a value for CV1, CV2, or CV3 internal model time constant in seconds.
3 Type a value for CV1, CV2, or CV3 internal model deadtime in seconds.
4 Type a value for the tuning parameter that determines the speed of the control
variable action for CV1, CV2, or CV3 in seconds
5 Click to replace the current model parameters with the calculated Autotune
model parameters.

526 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Modular Multivariable The Modular Multivariable Control (MMC) function block controls two
process variables to their setpoints manipulating up to three control variables.
Control (MMC) The MMC function block calculates the control variables (CV1, CV2, and
CV3) in the Auto mode based on the PV1 - SP1, PV2 - SP2 deviation, internal
model, and tuning. The MMC function block is a flexible model-based
algorithm that can be used in two basic configuration modes:
• Three control variables used to control two interacting process variables
• Two control variables used to control two interacting process variables

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 379 - MMC Display Elements Description


Display Element Display Element Description
Name
GO_BuiltIn_MMC Modular Multivariable Control
object with two process
variables and three control
variables.

GO_BuiltIn_MMC1 Modular Multivariable Control


object with two process
variables, two setpoints, and
three control variables.

GO_BuiltIn_MMC2 Modular Multivariable Control


object with two process
variables and two setpoints.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 527


Chapter 7 Built-in Instructions Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

5 6

1 8

2
3

Table 380 - Operator Tab Description


Item Description
1 Current PV value
2 Current SP value
3 Setpoint Slider
4 PV Indicator
5 Operator CV Value
6 CV Slider
7 Click to request Manual Loop mode.
8 Click to request Auto Loop mode.

528 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

Table 381 - Maintenance Tab Description


Item Description
1 Type the high and low SP threshold.
2 Type the high and low CV threshold.
3 Type the positive and negative Rate of Change limit value.
Rate of change limiting is used only when in Auto mode or in Manual mode if
CVManLimiting is true.
A value of zero disables CV1 ROC limiting.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 529


Chapter 7 Built-in Instructions Family

Advanced Tab

Tuning

The following diagram shows the functions for CV1 on page 1. CV2 and CV3
are covered on pages 2 and 3.

1
2
3

4
5
6
7
8
9
1

Table 382 - Tuning Tab Description


Item Description
1 Type the SP 1 value.
2 Type the SP2 value.
3 Type the CV value.
4 Type the Operator model gain for PV1: CV1, CV2, or CV3, PV2: CV1, CV2,
or CV3.
This value is the internal model gain for CV# - PV#. enter a positive or
negative gain depending on the process direction.
5 Type the internal model time constant for PV1: CV1, CV2, or CV3, PV2: CV1,
CV2, or CV3 in seconds.
6 Type the internal model deadtime for PV1: CV1, CV2, or CV3, PV2: CV1,
CV2, or CV3
in seconds.
7 Type the internal Response time constant for PV1: CV1, CV2, or CV3, PV2:
CV1, CV2, or CV3.
This value is the tuning parameter that determines the speed of the control
variable action for CV# - PV# in seconds.
8 Click to select '+' or '-' as the Process Gain sign for PV1: CV1, CV2, or CV3,
PV2: CV1, CV2, or CV3.
This selection is used only for Autotune and is the sign of the process gain
(PV1/CV1).

530 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Item Description
9 Click to show the Autotune (CV1, CV2, or CV3) Operator faceplate.
10 Click to request Manual loop mode.
11 Click to request Auto Loop mode.

Maintenance Tab

Table 383 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type the Operator setpoint.
2 Type the high and low limits for the SP.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 531


Chapter 7 Built-in Instructions Family

Table 384 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Type the minimum and maximum PV configuration. (In engineering units.)

532 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 385 - Advanced Maintenance Tab Page 3 Description


Item Description
1 Type the Operator CV value.
2 Type the CV high and CV low limits.
3 Type the maximum CV rate of increase and decrease configuration values.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 533


Chapter 7 Built-in Instructions Family

Table 386 - Advanced Maintenance Tab Page 4 Description


Item Description
1 Type the override value for the CV. The CV is set to this value when in the
Override mode.
2 Type the CV maximum and minimum values in engineering units.

534 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Engineering Tab

1 6
2

3
4

5 8

Table 387 - Engineering Tab Page 1 Description


Item Description
1 Limit CV1, CV2, or CV3 in Manual mode.
If in Manual mode and CVManLimiting is true, CV1, CV2, and CV3 are
limited by the CV1, CV2, and CV3 HLimit and CV1, CV2, and CV3 LLimit
values.
2 Check to set the Loop mode to manual when CV initialization is requested.
Clear the checkbox to leave the Loop mode unchanged when initialization is
requested. When the initialization request clears, the loop resumes control in its
previous Loop mode.
3 Check to reset Program control values after each execution.
4 Check to enable SP to track PV.
This process is ignored when in Auto modes. SP tracks PV only when all three
outputs are in manual. As soon as any output returns to Auto, PVTracking
stops.
5 Click to select the first CV to act to compensate for PV1-SP1 deviation.
Click to select the second CV to act to compensate for PV1-SP1 deviation.
Click to select the third CV to act to compensate for PV1-SP1 deviation.
6 Click to select the CV to be driven to its target.
7 Type the value that determines the speed with which the control variables
approach their target values.
8 Click to select the first CV to act to compensate for PV2-SP2 deviation.
Click to select the second CV to act to compensate for PV2-SP2 deviation.
Click to select the third CV to act to compensate for PV2-SP2 deviation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 535


Chapter 7 Built-in Instructions Family

Table 388 - Engineering Tab Page 1 Description


Item Description
1 Click to select Periodic, Oversampling, or Real-Time for the execution mode.
2 Select either 'EU' or '%' for the Model Gain units in Engineering Units or
'Percent of span'.

536 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Faults

Page 1 of the Diagnostics tab displays PID Instruction faults.

Page 2 of the Diagnostics tab displays PID Instruction configuration faults.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 537


Chapter 7 Built-in Instructions Family

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

Table 389 - Trends Tab Description


Item Description
1 Click to open the trends for PV 1 with Setpoint.
2 Click to open the trends for PV 2 with Setpoint.
3 Click to open the trend tab for the control variables.

538 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

PV 1 with Setpoint 1 Trends

PV 2 with Setpoint 2 Trends

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 539


Chapter 7 Built-in Instructions Family

CV Trends

540 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 541


Chapter 7 Built-in Instructions Family

Modular Multivariable Control (MMC) Autotune

The faceplates in this section let you access all necessary parameters to
autotune the MMC function block and hand-tune the instruction.

2
3

Table 390 - MMC Autotune Page 1 Description


Item Description
1 Click either Integrating or Non-integrating.
2 Type a value for PV1 and PV2 limit scaled in PV units.
When Autotune is running and predicted PV exceeds this limit, the tuning is
aborted.
3 Type a value for PV1 and PV2 maximum time (in minutes) for autotune to
complete following the CV step change.
When autotune exceeds this time, tuning is aborted.
4 Click Low, Medium, or High to set the estimate of the noise level expected on
PV1 and PV2 to compensate for it during tuning.

542 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

2 4
3

Table 391 - MMC Autotune Page 2 Description


Item Description
1 Type a value for CV1 step size in percent for the tuning step test.
2 PV1 and PV2 Autotune status indicator
3 Click to start the autotune process.
4 Click to abort the autotune process.
This button also becomes active if the process is aborted due to an error.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 543


Chapter 7 Built-in Instructions Family

1
2
3
4

Table 392 - MMC Autotune Page 3 Description


Item Description
1 Type a value for the modular multivariable PV1 and PV2 gain.
Enter a positive or negative gain depending on process direction.
2 Type a value for the modular multivariable PV1 and PV2 time constant in
seconds.
3 Type a value for the modular multivariable PV1 and PV2 deadtime in seconds.
4 Type a value for thePV1 and PV2 tuning parameter that determines the speed of
the control variable action in seconds
5 Click to replace the current PV1 and PV2 model parameters with the calculated
Autotune PV1 and PV2 model parameters.

544 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Proportional + Integral The Proportional + Integral + Derivative Enhanced (PIDE) instruction


provides enhanced capabilities over the standard PID instruction. The
+ Derivative Enhanced instruction uses the velocity form of the PID algorithm. The gain terms are
(PIDE) applied to the change in the value of error or PV, not the value of error or PV.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 393 - MMC Display Elements Description


Display Element Display Element Description
Name
GO_Builtin_PIDE Proportional + Integral +
Derivative Enhanced object
with one Process Variables and
one Control Variable.

GO_Builtin_PIDE1 Proportional + Integral +


Derivative Enhanced object
with one Process Variable, one
Setpoint, and one Control
Variable.

GO_BuiltIn_PIDE_ Proportional + Integral +


CV Derivative Enhanced (normal
Control Valve for horizontal
pipe) object with one Process
Variable and one Control
Variable.

GO_BuiltIn_PIDE_ Proportional + Integral +


CV1 Derivative Enhanced (inverted
Control Valve for horizontal
pipe) object with one Process
Variable and one Control
Variable.

GO_BuiltIn_PIDE_ Proportional + Integral +


CV2 Derivative Enhanced (Control
Valve for vertical pipe to the
left) object with one Process
Variable and one Control
Variable.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 545


Chapter 7 Built-in Instructions Family

Display Element Display Element Description


Name
GO_BuiltIn_PIDE_ Proportional + Integral +
CV3 Derivative Enhanced (Control
Valve for vertical pipe to the
right) object with one Process
Variable and one Control
Variable.
GO_BuiltIn_PIDE_ Proportional + Integral +
CV4 Derivative Enhanced (normal
Control Valve for horizontal
pipe) object with one Process
Variable, one Setpoint, and one
Control Variable.

GO_BuiltIn_PIDE_ Proportional + Integral +


CV5 Derivative Enhanced (inverted
Control Valve for horizontal
pipe) object with one Process
Variable, one Setpoint, and one
Control Variable.

GO_BuiltIn_PIDE_ Proportional + Integral +


CV6 Derivative Enhanced (Control
Valve for vertical pipe to the
left) object with one Process
Variable, one Setpoint, and one
Control Variable.
GO_BuiltIn_PIDE_ Proportional + Integral +
CV7 Derivative Enhanced (Control
Valve for vertical pipe to the
right) object with one Process
Variable, one Setpoint, and one
Control Variable.

546 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Operator Tab

The faceplate initially opens to the Operator (‘Home’) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode.

4
5
1

6
7
2

3 9

Table 394 - Operator Tab Description


Item Description
1 Current PV value
2 PV Slider
3 Click to request Cascade Loop mode.
4 Type a value for the loop Setpoint.
5 Type a value for the ratio operator multiplier.
6 Type a value for CV.
7 Move this slider to adjust the loop CV output.
8 Click to go to request Manual loop mode.
9 Click to request Auto Loop mode.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 547


Chapter 7 Built-in Instructions Family

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot and temporarily work around
device problems, and disable the device for routine maintenance.

Table 395 - Maintenance Tab Page 1 Description


Item Description
1 Type values for the PV high-high, high, low, and low-low alarm limits.
2 Type a value for the PV alarm limit deadband.

Table 396 - Maintenance Tab Page 2 Description


Item Description
1 Type values for the Deviation high-high, high, low, and low-low alarm limits.
2 Type a value for the Deviation alarm limit deadband.

548 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

1
2
3

Table 397 - Maintenance Tab Page 3 Description


Item Description
1 Enter a value for the positive rate of change alarm limit.
2 Enter a value for the negative rate of change alarm limit.
3 Type a value for the PV Rate of change sample period. This value is the time
period, in seconds, over which the rate of change for PV is evaluated.
Type zero to disable the PV rate of change period checking.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 549


Chapter 7 Built-in Instructions Family

Advanced Tab

Tuning Tab

5
1
6
2
3
7
4

Table 398 - Tuning Tab Description


Item Description
1 Type the value for the control variable.
2 Type the value for the proportional gain.
3 Type the value for the integral gain.
4 Type the value for the derivative gain.
5 Click to request Cascade loop mode.
6 Click to request Auto Loop mode.
7 Click to request Manual Loop mode.
8 Click to show the Autotune (CV1, CV2, or CV3) Operator faceplate.

550 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Table 399 - Advanced Maintenance Tab Page 1 Description


Item Description
1 Type a ratio Operator multiplier.
2 Type values for the high and low ratio limits.
These values limit the value of Ratio obtained from Operator or Program Ratio.
3 Type the high and low limits for the setpoint.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 551


Chapter 7 Built-in Instructions Family

1
2

3
4
5

Table 400 - Advanced Maintenance Tab Page 2 Description


Item Description
1 Type a value for the zero-crossing deadband range.
Type zero to disable the zero-crossing deadband checking.
2 Type a value for the maximum and minimum scaled values for PV.
3 Type in a value for Proportional gain
4 Type in a value for Integral gain
5 Type in a value for Derivative gain

552 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 401 - Advanced Maintenance Tab Page 3 Description


Item Description
1 Type a value for CV when in the Operator Manual mode.
2 Type values for the CV high and low limits.
3 Type a value for CV Rate of Change limit.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 553


Chapter 7 Built-in Instructions Family

Table 402 - Advanced Maintenance Tab Page 4 Description


Item Description
1 Type a value for CV when in the Override mode.
2 Type values for the maximum and minimum values for CV in engineering
units.

554 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Engineering

1
2
3

4
5
6

7
8

9
1

Table 403 - Advanced Engineering Tab Page 1 Description


Item Description
1 Check to enable Cascade loop mode.
2 Check to enable ratio control when in Cascade mode.
3 Click to smooth changes in the derivative term.
4 Check to limit CV in the Manual mode.
5 Check to set the Loop mode to manual when CV initialization is requested.
Clear the checkbox to leave the Loop mode unchanged when initialization is
requested. When the initialization request clears, the loop resumes control in its
previous Loop mode.
6 Click to clear all program request inputs after each execution of the instruction.
7 Click to calculate the derivative term by using the change in the process
variable (PVPercent).
Clear this checkbox to use the change in error (EPercent).
8 Click to calculate the proportional term by using the change in process variable
(PVPercent).
Clear this checkbox to use the change in error (EPercent).
9 Click to have SP track PV when in Manual mode.
This setting is ignored when in Cascade or Auto mode.
10 Click to disable zero-crossing for the deadband calculation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 555


Chapter 7 Built-in Instructions Family

Table 404 - Advanced Engineering Tab Page 2 Description


Item Description
1 Click to select the timing execution mode.

556 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 405 - Advanced Engineering Tab Page 3 Description


Item Description
1 Click to select the method of calculating error.
2 Click to select Independent or Dependant for the gains equation.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 557


Chapter 7 Built-in Instructions Family

Faults Tab

Page 1 of the Diagnostics tab displays PID Instruction faults.

Page 2 of the Diagnostics tab displays PID Instruction configuration faults.

558 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

Table 406 - Trends Tab Description


Item Description
1 Click to open the trends for the PV with Setpoint.
2 Click to open the trends tab for the control variables.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 559


Chapter 7 Built-in Instructions Family

PV with Setpoint Trends Tab

CV Trends Tab

560 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

Ramp/Soak (RMPS) The Ramp/Soak (RMPS) instruction provides for a number of segments of
alternating ramp and soak periods.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 407 - RMPS Display Elements Description


Display Element Display Element Description
Name
GO_BuiltIn_RMPS Ramp Soak global object.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 561


Chapter 7 Built-in Instructions Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

2
4

3 6

Table 408 - Operator Tab Description


Item Description
1 Type a value for the Operator Segment.
This value is used if Ramp/Soak is in the Manual mode.
2 Type a value for the Operator Soak Time Left.
This value is used if Ramp/Soak is in the Manual mode.
3 Click to initialize Current Segment and Soak Time Left.
4 Type a value for the Operator output value.
This value is used as the Output when Ramp/Soak is in the
Manual mode.
5 Click to request Manual Loop mode.
6 Click to request Auto Loop mode.

562 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

The Maintenance tab has inputs for Ramp Time, Soak Time, and Soak Value
for each segment. The segments are split between two pages.

1 4

Table 409 - Maintenance Tab Description


Item Description
1 Type a value for Ramp time, in minutes or units/minute, for the desired
segments.
2 Click to select the current segment.
3 Type a value for Soak Time, in minutes, for the desired segments.
4 Type a value for Soak Value for the desired segments.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 563


Chapter 7 Built-in Instructions Family

Advanced Tab

Engineering

Table 410 - Engineering Tab Description


Item Description
1 Check to set for cyclic action.
Clear this checkbox to set for single action.
Cyclic action continuously repeats the ramp/soak profile.
Single action performs the ramp/ soak profile once and then stops.
2 Click to set ramp/Soak in Manual or Program Hold mode after initialization.
Clear this checkbox to have Ramp/Soak remain in its previous mode after
initialization completes.
3 Click to reset program control values.
4 Click so that the RampValue parameter entered is in minutes.
Clear this checkbox if the RampValue parameter is entered in units/minute.
5 Click to set Guaranteed Ramp.
If set and the instruction is in Auto, ramping is temporarily suspended if the PV
differs from the Output by more than RampDeadband.
6 Click to clear the soak timer.
7 Type the number of ramp soak segments.
8 Type a value (Guaranteed Ramp Deadband) in engineering units that PV is
allowed to differ from the output when GuarRamp is on.
9 Type a value in engineering units that the PV is allowed to differ from the
output when GuarSoak is on.

564 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 565


Chapter 7 Built-in Instructions Family

Totalizer (TOT) The TOT instruction provides a time-scaled accumulation of an analog input
value.

This document is for the visualization files, display elements, global objects,
and HMI information. The operation of the Add-On Instructions and
controller code is contained in publication PROCES-RM013.

Display Elements

A display element (global object) is created once and can be referenced


multiple times on multiple displays in an application. When changes are made
to the original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.

Table 411 - TOT Display Element Description


Display Element Display Element Description
Name
GO_BuiltIn_Totalize Totalizer with target,
rTgt horizontal orientation - top

GO_BuiltIn_Totalize Totalizer with target,


rTgt1 horizontal orientation - bottom

GO_BuiltIn_Totalize Totalizer with target, vertical


rTgt2 orientation - right

GO_BuiltIn_Totalize Totalizer with target, vertical


rTgt3 orientation - left

566 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Table 411 - TOT Display Element Description


Display Element Display Element Description
Name
GO_BuiltIn_Totalize Totalizer, horizontal
r orientation - top

GO_BuiltIn_Totalize Totalizer, horizontal


r1 orientation - bottom

GO_BuiltIn_Totalize Totalizer, vertical orientation -


r2 right

GO_BuiltIn_Totalize Totalizer, vertical orientation -


r3 left

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 567


Chapter 7 Built-in Instructions Family

Operator Tab

The Faceplate initially opens to the Operator (Home) tab. From here, an
operator can monitor the device status and manually operate the device when it
is in Operator mode. Several features are common to all Add-On Instructions
faceplates. See Basic Faceplate Attributes on page 32.

7
1 8

6 1

Table 412 - Operator Tab Description


Item Description
1 Totalizer status
2 Flow indicator
3 Type the setpoint value for the totalizer input.
4 Type a value for the large deviation pre-target value of Total compared to
Target.
This value is expressed as a deviation from the Target.
5 Type a value for the small deviation pre-target value of Total compared to
Target.
This value is expressed as a deviation from the Target.
6 Click to reset Totalizer.
7 Large Deviation Pre-Target
8 Small Deviation Pre-Target
9 Click to stop Totalizer.
10 Click to start Totalizer.

568 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Maintenance Tab

Maintenance personnel use the information and controls on the Maintenance


tab to adjust device parameters, troubleshoot, temporarily work around device
problems, and disable the device for routine maintenance. Several features are
common to all Add-On Instructions faceplates. See Basic Faceplate Attributes
on page 32

1
2

Table 413 - Maintenance Tab Description


Item Description
1 Type a value for the low input cutoff.
When the input is set at or below LowInCutoff, totalization stops.
2 Type a value for reset input.
3 Type a value for the setpoint.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 569


Chapter 7 Built-in Instructions Family

Advanced Tab

Engineering

Table 414 - Engineering Tab Description


Item Description
1 Click to select the timing execution mode.
2 Click to select the time base for the time base input.
3 Type a value for the multiplier of the incremental totalized value.

570 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


Built-in Instructions Family Chapter 7

Trends Tab

The Trends tab shows trend charts of key device data over time. These faceplate
trends provide a quick view of current device performance to supplement, but
not replace, dedicated historical or live trend displays. For basic trends tab
functionality, See Trends Display on page 37.

The trend tab is split into two pages.

Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021 571


Chapter 7 Built-in Instructions Family

Diagnostics Tab

The Diagnostic tab provides indications to diagnose device problems. This tab
includes device warnings and faults, warning and fault history, and predictive/
preventive maintenance data.

572 Rockwell Automation Publication PROCES-RM014E-EN-P - December 2021


.

Rockwell Automation Support


Use the following resources to access support information.

Knowledgebase Articles, How-to Videos,


Technical Support Center FAQs, Chat, User Forums, and Product https://rockwellautomation.custhelp.com/
Notification Updates.
Local Technical Support Phone http://www.rockwellautomation.com/global/support/get-
Locate the phone number for your country. support-now.page
Numbers
Find the Direct Dial Code for your product.
Direct Dial Codes Use the code to route your call directly to a http://www.rockwellautomation.com/global/support/direct-
dial.page
technical support engineer.

Literature Library Installation Instructions, Manuals, http://www.rockwellautomation.com/global/literature-library/


Brochures, and Technical Data. overview.page

Product Compatibility and Get help determining how products interact,


check features and capabilities, and find http://www.rockwellautomation.com/global/support/pcdc.page
Download Center (PCDC) associated firmware.

Documentation Feedback

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-

Allen-Bradley, ControlLogix, DeviceLogix, E1 Plus, E300, FactoryTalk, PanelView, PlantPAx, PowerFlex, Rockwell Software, Rockwell Automation, SMC, and Studio 5000
Logix Designer are trademarks of Rockwell Automation, Inc.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication PROCES-RM014E-EN-P - December 2021


Supersedes Publication PROCES-RM014D-EN-P - August 2020 Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like