1711 Um002 - en pAA PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 190

User Manual

Single Stage Compressor Control


Catalog Numbers 1711-P02NSSCCN12600C, 1711-P02NSSCCN4X600C, 1711-P02NSSCCN121000C, 1711-P02NSSCCN4X1000C
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Allen-Bradley, CompactLogix, PanelView Plus Compact, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents

Preface Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 1
Introduction Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 2
Single Stage Compressor Controller Single Stage Compressor Controller Components . . . . . . . . . . . . . . . . . . 13
Installation Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrostatic Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unpack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Environmental/Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . 15
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Mount the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Power Distribution and Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single Stage Compressor Controller Power Up . . . . . . . . . . . . . . . . . . . . . 17

Chapter 3
SSCC Hardware Description Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
PanelView Plus Compact Graphic Terminal . . . . . . . . . . . . . . . . . . . . 24

Chapter 4
Human Machine Interface Activate the HMI7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Navigation Toolbar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Operator Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Maintenance Screen Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Alarms Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Warnings Screen Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Trend Select Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Interlocks Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Permissives Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Help Screen Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
HMI Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
User Login. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
User Logout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Change the User Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
HMI Functions with Security Privileges. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 3


Table of Contents

Chapter 5
SSCC Configuration Parameter Lists. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
01: AIN - Compressor Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
02: AIN - Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
03: AIN - Discharge Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
04: AIN - Auxiliary Control Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
05: AIN - Suction Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
06: AIN - Discharge Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
07: AIN - Multi-use Signal A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
08: AIN - Multi-use Signal B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
09: Digital Input Channel Configuration . . . . . . . . . . . . . . . . . . . . . . . 61
10: Digital Output Channel Configuration . . . . . . . . . . . . . . . . . . . . . 63
11: Compressor Configuration Information . . . . . . . . . . . . . . . . . . . . 63
12: Surge Map Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
13: Surge and Margin Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
14: Run and Load Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
15: Anti-Surge Control General Configuration . . . . . . . . . . . . . . . . . 69
16: ASC Primary PID Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
17: ASC Primary PID Loop - Adaptive Integral . . . . . . . . . . . . . . . . . 72
18: ASC Primary PID Loop - Adaptive Proportional . . . . . . . . . . . . 73
19: ASC Secondary PID Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
20: Capacity Control General Configuration . . . . . . . . . . . . . . . . . . . 76
21: Capacity Primary PID Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
22: Capacity Secondary PID Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
23: Anti-Surge - Capacity Decoupling Configuration . . . . . . . . . . . . 82
24: AINs - Substitute PV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
25: DINs - Substitute PV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
26: Reserved for Future Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
27: Interlock Bypassable Configuration. . . . . . . . . . . . . . . . . . . . . . . . . 85
28: Permissive Bypassable Configuration . . . . . . . . . . . . . . . . . . . . . . . 86
29: Modbus Serial Port Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 87
30: Application (HMI Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . 88
Parameter List Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Parameter Configuration Screen Overview . . . . . . . . . . . . . . . . . . . . . 90
Parameter List Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Interlock and Permissive Customization . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Interlock Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Permissive Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Chapter 6
SSCC Operation Operation Screen Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Compressor Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Compressor Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Margin Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Anti-Surge Control PID Loops Overview. . . . . . . . . . . . . . . . . . . . . . 104
Capacity Control PID Loops Overview. . . . . . . . . . . . . . . . . . . . . . . . 106

4 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Table of Contents

Checking Interlocks, Permissives, and Warnings . . . . . . . . . . . . . . . . . . . 107


Interlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Permissives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Compressor Start and Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Compressor Running Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Compressor Load/Unload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Device Faceplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Accessing Device Faceplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Device Names and Device Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Analog Input Device Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Analog Output Device Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Digital Input Device Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Digital Output Device Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
PID Loop Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Compressor Details Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Trends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Using the Trend Detail Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

Chapter 7
Modbus Interface Serial Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Modbus Holding Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

Chapter 8
Troubleshooting System Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Hardware Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Controller Major and Minor Fault Status . . . . . . . . . . . . . . . . . . . . . 167
PanelView Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Digital Input Module Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Digital Output Module Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Analog Input Module Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Analog Output Module Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Managing Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Alarm Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Configuration Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Startup or Operating Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180

Index

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 5


Table of Contents

6 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Preface

This manual provides a product and application overview, installation


instructions, hardware description, Human Machine Interface (HMI) operation
instructions, configuration instructions, controller operation instructions,
Modbus configuration instructions, and troubleshooting information for the
Single Stage Compressor Controller.

Who Should Use this Manual This manual is intended for qualified personnel responsible for installing and
operating the Rockwell Automation Single Stage Compressor Controller
(SSCC). You should have previous experience with, and an understanding of,
electrical terminology, procedures, required troubleshooting equipment,
equipment protection procedures and methods, and safety precautions. See
safety related practices contained in publication NFPA 70E, Standard for
Electrical Safety in the Work Place.

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
CompactLogix™ Controllers Specifications Technical Data, Provides controller specifications.
publication 1769-TD005.
CompactLogix Packaged Controllers Quick Start and User Procedures for using your CompactLogix packaged
Manual, publication IASIMP-QS010. controller as well as additional reference information.
Logix5000 Controllers Common Procedures, publication Provides information on developing projects for
1756-PM001. Logix5000 controllers.
PanelView™ Plus Compact Terminals User Manual, Provides instructions for installing, configuring, and
publication 2711PC-UM001. operating PanelView Plus Compact terminals.
Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell
publication 1770-4.1 Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and
other certification details.

You can view or download publications at


http:/www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 7


Preface

Notes:

8 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 1

Introduction

Product Description The Single Stage Compressor Controller (SSCC) from Rockwell Automation is
a packaged solution providing anti-surge and capacity control for a single-stage
centrifugal or axial gas compressor. The SSCC is an economical compressor
controller providing advanced control algorithms allowing for safe and energy
efficient operation across the compressors operating range.

Figure 1 - Typical Compressor Controls

UIC

Anti-Surge
PIC Valve

FT PT TT

Cooler

Suction Valve
(Capacity Control)

Compressor

PT TT

Application Overview The SSCC utilizes a surge control algorithm which calculates a percent flow and
determines the compressor’s head (simplified polytropic or pressure ratio). If the
percent flow is not adequate for the compressor’s head, the recycle valve will be
opened. The algorithm is used to generate a setpoint for the specialized PID
loop. The surge control algorithm executes in less than 25 ms.

The following simplified functional block diagram illustrates the features of the
algorithm. Secondary PID loop over-rides, and capacity control are not shown
for clarity.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 9


Chapter 1 Introduction

Figure 2 - Anti-surge Control Function Block Diagram

OP Adaptive
Tuning
Q
Qmax SP
Td Operating
OP PV 20 mA . . .4 mA
Ts Point
Ps Calc Analog Out AO
PID Loop 1
Pd SV
m’

Feedback

OP
OP Track
OP Track

CLL

OP Surge Count
Margin
Calc

SLL
Ps
Hp
Pd
Head Lookup
Calc Table
m’

Functional aspects of the SSCC control strategy are summarized in the following
table.

Table 1 - Application Function Summary


Function Features
Analog Input Channel usage configuration (not-used, used, and usage type)
Processing Engineering unit calculation of process value (PV), with linear or square-root extraction
Absolute value correction factor, for PVabs (Press & Temp signals)
Under-range and over-range alarms
Configurable PV high and low alarms
Substitute PV mode to replace field signal with a substitute value
Channel health monitoring and reporting
Device faceplate on HMI
Digital Input Channel usage configuration (not-used, used)
Processing Input state (polarity of signal)
Channel health monitoring and reporting
Device faceplate on HMI
Digital Output Output state (polarity of signal)
Processing Operator mode for field device testing
Channel health monitoring and reporting
Device faceplate on HMI

10 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Introduction Chapter 1

Function Features
Analog Output Device action (air-to-open, air-to-close)
Processing Position monitoring option
Operator mode for field device testing
Channel health monitoring and reporting
Device faceplate on HMI
Compressor Head Calculates the “head” of the compressor as simplified polytropic head (HpSim), pressure ratio
(Pratio), and pressure rise (Prise)
Choice of HpSim or Pratio as head type for the surge map
Configuration error and calculation fault reporting
Operating Point Calculates the operating point (OP) as a normalized, compensated representation of flow,
compensated to base conditions of the surge map
Supports four varieties of flow instrumentation for the compressor
• Flow in suction
• Flow in discharge, no cooling (inter-stage or upstream of flow)
• Flow in discharge, downstream of inter-stage or discharge coolers
• Alternate signal used in place of flow - special cases
Configuration error and calculation fault reporting
Surge Map 10-segment surge map defines the surge limit line (SLL)
Minimum flow fallback strategy on head calculation fault
Option for inlet guide vane (IGV) adjustment methods
Minimum IGV fallback on IGV position fault
Dynamic compressor map on human machine interface (HMI)
Surge Detection Compressor surge detection using:
• Positional surge detection: OP falls below SLL
• Rate-of-change surge: OP drops rapidly beyond configured limits
• Incipient surge: Optional SurgeGard signal detection of impending surge
Control Margin Calculation of the control limit line (CLL) using configurable margin
Margin based on offset and percentage methods
Convenient increment and decrement margin features
Automatic margin increment on surge detection
Minimum (base) and maximum margin limits
Operating Point Calculates the surge control line (SCL) using OP tracking methods
Tracking As OP increases above CLL, SCL tracks OP by a track margin
When OP decreases back towards CLL, SCL decays at a track rate
Configurable max limit, and minimum limited by CLL
Adaptive Tuning Dynamic adjustment to PID loop tuning parameters (ASC primary PID loop) using
configurable breakpoints and slopes
When operating between breakpoints, tuning value is at base value
When operating beyond breakpoints, tuning value automatically adjusted based on slopes
PID Controls PID controller features:
• Range configured automatically based on PV selection
• Configurable setpoint management (track in manual, limits, rates)
• PID control direction (direct, reverse)
• Variety of tuning options
• Manual mode override protection for anti-surge PID
• PID faceplate on HMI
Min/Max Selector and When both the primary PID and a secondary (override) PID are configured, the configured
Control/Track min or max control signal is selected
Management Non-selected PID loop tracks the selected PID loop by margin
Control/track mode reporting
Control Slew Rate and Control value (CV) features:
Override Limits • Minimum and maximum limits
• Opening and closing slew rate limits
• Override/tripped/not running value
Anti-Surge and Decoupling between anti-surge and capacity controls
Capacity Decoupling Prevents capacity controls from driving compressor into surge

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 11


Chapter 1 Introduction

Function Features
Surge Test and Capture Built-in surge test methods
Used to validate surge map
Traps operating data on surge detection
Surge point presented on compressor map
Interlock Management Four configurable external interlocks for compressor trip
Management of external and internal interlocks with first-out indication
Configurable interlock bypass features
Compressor trip output for interface to drive controller
Permissive Four configurable external permissives for compressor ready-to-start
Management Management of external and internal permissives with first-out indication
Configurable permissive bypass features
Ready-to-start output for interface to drive controller

12 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 2

Single Stage Compressor Controller Installation

Single Stage Compressor The Single State Compressor Controller (SSCC) is composed of the following
components:
Controller Components
• Enclosure
• CompactLogix controller
• Digital inputs
• Digital outputs
• Analog inputs
• Analog outputs
• PanelView Plus HMI

All the SSCC required components are mounted, wired and installed inside the
unit’s enclosure, from the factory. This section describes the steps for installation.

Figure 3 - SSCC Panel - Interior View


CompactLogix Controller

Internal Power
Distribution

Power from AC
or DC Source

DO Marshalling
DI, AI, and AO Terminals
PanelView Plus Marshalling
Mounted on Terminals
Door Panel

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 13


Chapter 2 Single Stage Compressor Controller Installation

Mechanical Installation Electrostatic Precautions

The electronic components of these systems are susceptible to electrostatic


discharge. Be sure to take the following precautions.
• Always wear an anti-static wrist strap (or equivalent) when handling any
electrostatic sensitive components.
• All electrostatic sensitive components will be packaged in anti-static bags.
Do not remove these components from these bags until you are ready to
install them.
• Controller modules are especially sensitive to electrostatic discharge; pay
special attention not to touch the module connectors or any exposed
printed circuit board (PCB) components.
• Store all shipping materials, especially anti-static bags, to re-use if it
becomes necessary to transport or ship any system components.

Unpack

All items must be removed from their packaging and checked against the packing
list. Verify that all items are correct and contact Rockwell Automation if any
discrepancies are found. Before unpacking any items, the packaging must be
inspected for damage which may have occurred during shipment. See the
“Inspection” section.

If any packaging is damaged, the package identifying marks (box number, crate
number, etc.) must be noted and communicated to Rockwell Automation. The
package must be stored in a suitable storage area in the condition it was received.
Rockwell Automation will contact the shipping agent who may request to inspect
the damage. The package must not be opened without the express written
permission of Rockwell Automation.

Inspection
• Visually inspect the cabinets for mechanical damage, check the painted
surfaces for scratches and abrasions.

• Check that the cabinet door opens and closes, and that all latches operate
smoothly.

• Check all internal components against the detailed layout drawings, and
be sure that these components were not damaged during shipment.

• Check cable assemblies to make sure they were not damaged during
shipment. All wire ducts should be fitted with covers and all cable
assemblies should be appropriately dressed with cable ties and/or spiral
wrap.

14 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Single Stage Compressor Controller Installation Chapter 2

Environmental/Location Requirements

To meet environmental requirements when installing the equipment, it should be


installed in a room with an ambient temperature of -10…+50 °C (14…122 °F)
with a relative humidity of 0% to 95% relative humidity, non-condensing; and
the room must be provided with adequate lighting.

Tools

An adjustable wrench and socket set are required for panel installation.

Mount the Enclosure

1. Determine the mounting location and be sure it is able to support 31.8 kg


(70 lb). Allow sufficient room above and below, or at the left and right
sides, for cable exiting the enclosure, and for opening the door.
2. Mark the wall through the top of the slots in only the top two mounting
key holes. Drill the necessary holes for the bolts.
3. Insert the bolts through the bottom two mounting key holes of the
enclosure and into the wall. DO NOT tighten the bolts at this time.
4. Mark the wall through the holes in the top two mounting holes. Remove
the enclosure from the wall, drill the necessary holes for the bolts, and re-
hang the enclosure onto the bottom two bolts.
5. Insert bolts through the holes in the top two mounting holes of the
enclosure and into the wall. Tighten all the bolts.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 15


Chapter 2 Single Stage Compressor Controller Installation

Power Distribution and System can be powered by 24V DC or 120V AC. Connect power to terminals
shown in the supplied wiring drawings. Terminal locations are identified in this
Grounding photograph.

Alternate DC Sourced
Power Connection AC Sourced Power
(Regulated 24V DC) Connection
(100…240V AC)

Instrument Ground Connection AC Safety Ground Connection

There are two different ground connections that must be connected before
power is applied to the system. The AC safety ground is for all exposed metal
surfaces of cabinets, racks, chassis ground connections, etc. (All individual
ground wiring interconnections are to be a minimum of 16 AWG, copper wire,
green insulation). Instrument ground is for all DC analog/digital, signal cable
shield wires. Reference ground wiring interconnections will be a minimum of 18
AWG, copper wire, green insulation, with yellow tracer.

ATTENTION: Good ground connections must be verified before any work can be
carried out by any Rockwell Automation or client personnel. Failure to comply
may cause serious injury.

Check for a good electrical AC safety ground connection. The electrical ground
connection must be matched to the breakers or fuses used to protect the feeds to
the system. Check the integrity of the connection and the gauge of the wire used,
that it is sufficient to allow the breakers or fuses to trip.

16 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Single Stage Compressor Controller Installation Chapter 2

Single Stage Compressor First time power up must be done in stages to guard against system-wide power
distribution faults. The system’s power distribution must be verified against the
Controller Powerup power distribution drawings.

1. Switch all circuit breakers to the Off position and open all fuses.
2. Energize the 24V DC or 120V AC feed, and verify voltage at the main
incoming terminals.
3. Close each 120V AC circuit breaker, one at a time, and verify that the
corresponding power supply is energized.
4. Measure the output voltage of the power supply and verify it is delivering
24V DC.
5. Close each 24V DC fuse, one at a time, and verify the corresponding
equipment receives 24V DC by measuring at the power terminals of the
receiving equipment.
6. Close all 24V DC fuses, checking that the system powers-up as expected.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 17


Chapter 2 Single Stage Compressor Controller Installation

Notes:

18 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 3

SSCC Hardware Description

Controller The SSCC hardware and software platform is the 1769-L23E-QB1B


CompactLogix system. The controller comes preconfigured with sixteen digital
inputs and sixteen digital outputs. For the SSCC system, two expansion 1769-
Series I/O modules are added for analog inputs (1769-IF8) and analog outputs
(1769-OF4).

Figure 4 - CompactLogix Controller L23E

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 19


Chapter 3 SSCC Hardware Description

Digital Inputs

The SSCC has 16 digital inputs powered by 24V DC. All inputs are prewired
from marshalling terminal blocks (TS1) to the module specific removable
terminal blocks.

Table 2 - Digital Input Channel Assignment and Wiring


Input Description TS1
Channel 0 Compressor Running contact 1-2
Channel 1 Reset push button 3-4
Channel 2 Load Compressor request push button 5-6
Channel 3 Unload Compressor request push button 7-8
Channel 4 Reserved for future use 9-10
Channel 5 Reserved for future use 11-12
Channel 6 Reserved for future use 13-14
Channel 7 Reserved for future use 15-16
Channel 8 External Ready-to-start Permissive 1 17-18
Channel 9 External Ready-to-start Permissive 2 19-20
Channel 10 External Ready-to-start Permissive 3 21-22
Channel 11 External Ready-to-start Permissive 4 23-24
Channel 12 External Trip Interlock 1 25-26
Channel 13 External Trip Interlock 2 27-28
Channel 14 External Trip Interlock 3 29-30
Channel 15 External Trip Interlock 4 31-32

Notes:
• Accessories (push buttons) for use on channels 1, 2, and 3 are not provided
with the unit; the customer must purchase and install accessories
separately, as required. For each of these signals, the equivalent
functionality is provided on the graphic screens of the unit’s HMI.
• Digital input signal function polarity is configurable for each channel.
• Each channel is configurable for “use” or “not-used.” Signals present on
channels configured as “not-used” are ignored.

20 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Hardware Description Chapter 3

Digital Outputs

The SSCC has 16 digital outputs powered by 24VDC. All outputs are prewired
from marshalling terminal blocks (TS2) to the module specific removable
terminal blocks.

Table 3 - Digital Output Channel Assignment and Wiring


Output Description TS2
Channel 0 Compressor Trip/Interlock 1-2
Channel 1 Surge Alarm 3-4
Channel 2 System Trouble Alarm 5-6
Channel 3 Ready-to-start Permissive 7-8
Channel 4 Compressor Running Status Indication 9-10
Channel 5 Compressor Loaded Status Indication 11-12
Channel 6 Reserved for future use 13-14
Channel 7 Reserved for future use 15-16
Channel 8 Reserved for future use 17-18
Channel 9 Reserved for future use 19-20
Channel 10 Reserved for future use 21-22
Channel 11 Reserved for future use 23-24
Channel 12 Reserved for future use 25-26
Channel 13 Reserved for future use 27-28
Channel 14 Reserved for future use 29-30
Channel 15 Reserved for future use 31-32

Notes:
• All digital output channels are 24V DC sourcing outputs.
• Digital output signal function polarity is configurable per channel.
• Compressor trip/interlock (channel 0) is intended for connection to the
compressor driver (motor, turbine, etc.) to shutdown the compressor.
• Read-to-start permissive (channel 1) is intended for connection to the
compressor driver (motor, turbine, etc.) as a permissive to start the
compressor.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 21


Chapter 3 SSCC Hardware Description

Analog Inputs

The SSCC has eight analog inputs (current 4…20 mA). All inputs are prewired
from marshalling terminal blocks (TS1) to the module specific removable
terminal blocks.

Table 4 - Analog Input Channel Assignment and Wiring


Input Description TS1 Configuration Options
Channel 0 Compressor Flow 33-34 Flow Transmitter located:
Compressor Suction, or
Compressor Discharge, or
Alternate Signal when no Flow signal (consult factory for advice)
Channel 1 Suction Pressure 35-36 Pressure Transmitter in Compressor Suction
Channel 2 Discharge Pressure 37-38 Pressure Transmitter in Compressor Discharge
Channel 3 Auxiliary Control Signal 39-40 Auxiliary Process Transmitter. An optional signal that may be used
for capacity control, or anti-surge override control
Channel 4 Suction Temperature 41-42 Temperature Transmitter in Compressor Suction
Channel 5 Discharge Temperature 43-44 Temperature Transmitter in Compressor Discharge
Channel 6 Multi-Use Signal A 45-46 Choose connection to:
Anti-Surge Valve position Transmitter, or
Capacity Valve / Inlet Guide Vane position Transmitter, or
Incipient Surge (SurgeGard) signal
Channel 7 Multi-Use Signal B 47-48 Choose connection to:
Anti-Surge Valve position Transmitter, or
Capacity Valve / Inlet Guide Vane position Transmitter, or
Incipient Surge (SurgeGard) signal

Notes:
• Each channel has configurable engineering unit scaling, linearization type,
and alarm limits.
• Flow, suction pressure and discharge pressure (channels 0, 1, and 2)
represent the minimum required signals for anti-surge control.
• Temperatures (channels 4 and 5) are often optional, but are required when
flow is measured in discharge and the compressor has inter-stage cooling or
discharge cooling upstream of flow measurement.
• SurgeGard for incipient surge detection is sold separately. Space is
allocated in the panel for mounting and wiring to the system.

22 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Hardware Description Chapter 3

Analog Outputs

The SSCC has four analog outputs (current 4…20 mA). All outputs are prewired
from marshalling terminal blocks (TS1) to the module specific removable
terminal blocks.

Table 5 - Analog Output Channel Assignment and Wiring


Input Description TS1 Device
Channel 0 Anti-Surge Control Valve 49-50 Typically Recycle Valve or Blow-Off
Valve.
Channel 1 Capacity Control Device 51-52 Typically Suction Valve, Inlet Guide
Vanes, Discharge Valve, or Cascade
setpoint to Speed Controller.
Channel 2 Reserved for future 53-54 None
Channel 3 Reserved for future 55-56 None

Note: For each analog output, the application control signal 0…100% open can
be configured to actuate the device as air-to-open or air-to-close.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 23


Chapter 3 SSCC Hardware Description

PanelView Plus Compact Graphic Terminal

The SSCC is equipped with a PanelView Plus Compact color graphic terminal
for a HMI. This device is used as the interface for operation and configuration of
the SSCC. The HMI is installed on the door of the unit control panel and wiring
for power and communication are provided from factory. The standard HMI is
the PanelView Plus Compact 600 with 5.5 in. color touchscreen. The PanelView
Plus Compact 1000 with 10.4 in. color touchscreen can be ordered as an option
for the SSCC.

Figure 5 - PanelView Plus Compact 600 Graphic Terminal

Figure 6 - PanelView Plus Compact 1000 Graphic Terminal

24 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 4

Human Machine Interface

The human machine interface (HMI) provides a single interface for


configuration, operation, maintenance and troubleshooting the SCCC system.
This chapter familiarizes you with these general features and how to access them.
Further details are found later in this manual.

Activate the HMI The operator interface requires entry of an Activation Key ID to activate the
HMI for use. Until the HMI has been successfully activated the HMI will only
display the following screen.

Figure 7 - HMI Activation Screen

Each SSCC requires a unique, eight-character HMI activation Key ID. The Key
ID can be provided from an Authorized Rockwell Automation agent. You will
need to provide them the System Serial Number and Product ID Number as
shown on your Activation screen.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 25


Chapter 4 Human Machine Interface

Follow these steps to activate the HMI.

1. On the Activation screen, press the Enter Activation Key ID entry line.

The following keypad appears.

2. Enter the Key ID using the touch keypad.

Note: The characters in the Key ID are NOT case sensitive. Only enter the
eight character ID. Do not enter any dashes, spaces, or other symbols. For
example, if your agent provides the Key ID of 23F4-60BC, only enter the
eight characters, 23F460BC (or 23f460bc), omitting the dash symbol.

If the Key ID you entered is not valid, the Activation screen remains on the
HMI. In this case, verify the Key ID entered and correct if necessary. If
activation problems continue, contact Rockwell Automation for further
assistance.

If the Key ID is valid and the HMI activation is successful, the toolbar is
displayed at the top of the screen and the Application Information screen
appears.

26 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Navigation The HMI application facilitates user navigation through a centralized icon
toolbar. The toolbar icons access the following eight main screens.
• Operator
• Maintenance
• Alarms
• Warnings
• Trends
• Interlocks
• Permissives
• Help

Each of the main screens accesses additional screens that allow you to fully
configure the SSCC. A navigational hierarchy is presented in Figure 8 on page
28.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 27


Chapter 4 Human Machine Interface

Figure 8 - HMI Screens Navigational Hierarchy

Startup Screen Main Screens Popup Screens Popup Screens

Application Operator
Start Screen

Maintenance Parameter
Screen Configuration

Alarm Interlock
Screen Configuration

Warning Permissive
Screen Configuration

Trend Select
Screen Hardware I/O
Status Status

Interlock
Screen
Device Analog
Configuration Input
Permissive Analog
Screen Output
Trend
Detail
Digital
Help Input
Screen
Digital
Output

PID Loop
Faceplate

Compressor
Details

28 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Navigation Toolbar

Each main screen contains at least one page, where pages are equivalent to
displays. In order to access a main screen, press the corresponding button on the
upper navigation toolbar.

When a main screen contains multiple pages, a page navigation bar is presented at
the bottom of the screen, as shown here. When the screen has only one page, the
page navigation bar is not presented.
Left Arrow Number of Pages Right Arrow

The number of pages is represented by the number of dots presented in the center
of the navigation bar. The green dot indicates which page is presently shown on
the screen.

Use the right arrow button to navigate forward and the left arrow button to
navigate backwards through the pages of the screen. Navigation forward from the
last screen returns to the first screen and vice versa.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 29


Chapter 4 Human Machine Interface

Operator Screen Overview

From any main screen, press the home icon on the navigation toolbar to
open the Operator screen. The Operator screen contains six pages for operations.
When the Operator screen appears, the last viewed page is presented.
Table 6 - Operator Screen Pages
Page Example Screen(s) Description
1 Operator Screen – User Login
Display Features:
• Date and time of the HMI

Operational Features:

• Press to log in and obtain user security privileges

• Press to log off (return to Default user, with no security privileges)


2 Operator Screen – Compressor Overview
Display Features:
• Signal values for all configured transmitters (AINs)
• Anti-surge valve control value and location
• Capacity control value and device type/location (if configured)
• Overall unit status indicators (ready, trip, surge, run, load, trouble)

Operational Features:

• Press to load the compressor – security privilege required (O, S, M, or E)

• Press to unload the compressor – security privilege required (O, S, M, or E)

3 Operator Screen – Compressor Map


Display Features:
• Compressor map for Surge Limit Line (SLL), Control Limit Line (CLL) and Surge Control Line (SCL) with live Operating
Point (OP)
• Anti-surge calculated values for Head, OP, SLL, Margin, CLL, SCL and Distance of OP from Control Limit Line
• Summary of anti-surge and capacity PID loop outputs and control values (for configured loops)

Operational Features:

• Press the to open the Compressor Details popup screen for additional anti-surge information and settings

30 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Table 6 - Operator Screen Pages (Continued)


Page Example Screen(s) Description
4 Operator Screen – Margin Control
Display Features:
• Anti-surge margin information

Operational Features:

• Press (margin increment) and (margin decrement) to adjust margin – security privilege required (O,
S, M, or E)
• Modify Base, Max Margin, and Margin Adjustment - security privilege required (M, E, or A)
5 Operator Screen – Anti-Surge Control PID Loops Overview
Display Features:
• Overview of Anti-surge control PID loops (PV, SP, Output, Mode)
• Anti-surge secondary (Override) PID loop is only shown when configured.

Operational Features:

• Press to open individual PID loop faceplates for detailed PID loop operation and tuning

6 Operator Screen – Capacity Control PID Loops Overview


Display Features:
• Overview of Capacity Control PID Loops (PV, SP, Output, Mode)
• Capacity PID loops are only shown when configured

Operational Features:

• Press to open individual PID loop faceplates for detailed PID loop operation and tuning

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 31


Chapter 4 Human Machine Interface

Maintenance Screen Overview

From any main screen, press the Maintenance icon on the navigation
toolbar to open the Maintenance screen. The Maintenance screen has three pages
for configuration and maintenance activities. When the Maintenance screen
opens, the last viewed page is presented.
Table 7 - Maintenance Screen Pages
Page Example Screen(s) Description
1 Maintenance Screen – Configuration and Settings
Display Features:
• Access to configuration, device settings, and hardware status monitoring
• Bypass interlocks and permissives only shown if configured

Operational Features:

• Press to access Parameter Configuration popup screen

• Press to access Interlocks Configuration popup screen

• Press to access Permissives Configuration popup screen

• Press to access Hardware popup screen to access controller and PanelView Plus status information

• Press to disable bypass for interlocks and permissives – security privilege required (M, E, or A)

• Press to enable bypass for the configured Interlocks and permissives – security privilege required (M, E, or A)

• Use to choose a device and press to open a Device Detail popup (for AIN, DIN, AOUT, DOUT, PID Loop,
and Compressor Details)
2 Maintenance Screen – Change Password
Display Features:
• Access to login/logout and change passwords

Operational Features:

• Press to log in with user security privileges

• Press to log off (return to default user, with no security privileges)

• Press to change the password for the current user – security privilege required (O, S, M, E, or A as applicable)
3 Maintenance Screen – Localization
Display Features:
• Language selection
• Units of measure selection

Operational Features:
• Press the flag that represents the language choice for the HMI
• Press for either Primary or Secondary units – security privilege required (E or A). This selection switches the text
for Units between the user configured primary and secondary units text strings.

32 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Alarms Screen Overview

From any main screen, press the Alarm icon on the navigation toolbar to
open the Alarm screen. The Alarm screen has only one page, containing an alarm
list for the unit alarms.
Table 8 - Alarm Screen Pages
Page Example Screen Description
1 Alarm Screen
Display Features:
• List of alarms - current and historical
• Alarm colors represent severity levels
• Flashing indicates “Unacknowledged,” Steady indicates “Acknowledged”
• Scrollable list maintains history of last 128 alarms

Operational Features:

• Use and to choose an individual alarm for acknowledgement.


• Use and to scroll through the list one page at a time

• Press to acknowledge the selected alarm – security privilege required (O, S, M, E, or A)


• Press to acknowledge all the un-acknowledged alarms in the list – security privilege required (O, S, M, E, or A)
• When available, press to send an alarm reset to the application to reset the Summary Alarm icon indication –
security privilege required (O, S, M, E, or A)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 33


Chapter 4 Human Machine Interface

Warnings Screen Overview

From any main screen, press the Warnings icon on the navigation toolbar to
open the Warnings screen. The Warnings screen has two pages for alerting the
user regarding important errors or other operating condition. When the
Warnings screen opens, the last viewed page is presented to the user.
Table 9 - Warnings Screen Pages
Page Example Screen Description
1 Warnings Screen – Level 1: Preventing Operation
Display Features:
• Level 1 warnings are presented by an orange color
• The Warning icon on the top navigation toolbar will change color to alert the operator when a warning condition is
present

Operational Features:
• No user operations required from this screen

2 Warnings Screen – Level 2: Function Disabled/Bypassed


Display Features:
• Level 2 warnings are presented by an yellow color
• The Warning icon on the top navigation toolbar will change color to alert the operator when a warning condition is
present

Operational Features:
• No user operations required from this screen

Trend Select Screen Overview

From any main screen, press the Trend icon on the navigation toolbar to
open the Trend Select screen. The Trend Select screen has only one page,
containing a list of trend groups.
Table 10 - Trend Select Screen Pages
Page Example Screen Description
1 Trend Select Screen
Display Features:
• Trend Group selector

Operational Features:
• Use and to choose the desired trend group.

• Press to open the Trend Detail popup screen for the chosen trend group

34 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Interlocks Screen Overview

From any main screen, press the Interlock icon on the navigation toolbar to
open the Interlocks screen. The Interlocks screen has two pages, presenting the
condition of the compressor interlocks.
Table 11 - Interlocks Screen Pages
Page Example Screen Description
1 Interlocks Screen – Internal Interlocks
Display Features:
• Internal Interlocks organized on page one
• First-Out interlock displayed in yellow color

Operational Features:
• When available, press to reset latched interlocks that have cleared – security privilege required (O, S, M, E, or A)

2 Interlocks Screen – External Interlocks


Display Features:
• External interlocks organized on page two
• First-Out interlock displayed in yellow color

Operational Features:
• When available, press to reset latched interlocks that have cleared – security privilege required (O, S, M, E, or A)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 35


Chapter 4 Human Machine Interface

Permissives Screen Overview

From any main screen, press the Permissive icon on the navigation toolbar
to open the Permissives screen. The Permissives screen has 2 pages, presenting the
condition of the compressor permissives.
Table 12 - Permissives Screen Pages
Page Example Screen Description
1 Permissives Screen – Internal Logic Permissives
Display Features:
• Internal permissives organized on page one
• First-out permissive displayed in yellow color

Operational Features:
• Permissives are non-latching so use of Reset button is not required (O, S, M, E, or A)

2 Permissives Screen – External Permissives


Display Features:
• External permissives organized on page two
• First-Out permissive displayed in yellow color

Operational Features:
• Permissives are non-latching so use of Reset button is not required (O, S, M, E, or A)

36 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Help Screen Overview

From any main screen, press the Help icon on the navigation toolbar to
open the Help screen. The Help screen has eight pages, presenting HMI
operational help organized under a variety of topics.
Table 13 - Help Screen Pages
Page Example Screen Description
1 Help Screen – Product Identification
Display Features:
• Product Description, Catalog Number, Version and Serial Number

Operational Features:
• No operational actions required from this page

2 Help Screen – Navigation


Display Features:
• Navigation icon toolbar items identified
• Page navigation and page scrolling identified

Operational Features:
• No operational actions required from this page

3 Help Screen – Interlocks/Permissives


Display Features:
• Interlock and permissive icon symbols identified
• Interlock and permissive signal status indications identified

Operational Features:
• No operational actions required from this page

4 Help Screen – Alarms/Warnings


Display Features:
• Alarm icon severity/classification colors identified
• Alarm screen operation buttons identified
• Warning icon classification colors identified

Operational Features:
• No operational actions required from this page

5 Help Screen – Maintenance/Configuration


Display Features:
• Configuration buttons identified
• Bypass Enable/Disable buttons identified
• Parameter list configuration and management identified

Operational Features:
• No operational actions required from this page

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 37


Chapter 4 Human Machine Interface

Table 13 - Help Screen Pages (Continued)


Page Example Screen Description
6 Help Screen – Trends/Security/Hardware Status
Display Features:
• Trend popup screen operational buttons identified
• Security access buttons identified
• Hardware status management buttons identified

Operational Features:
• No operational actions required from this page

7 Help Screen – Indicators


Display Features:
• Compressor operation summary indicators identified

Operational Features:
• No operational actions required from this page

8 Help Screen – Commands


Display Features:
• Operating buttons identified

Operational Features:
• No operational actions required from this page

HMI Security The HMI includes a security model to restrict access to specific functions. The
model relies on user roles which are defined in the following table.

Table 14 - HMI User Roles and Passwords


User Name Initial Password Security Privilege Abbr.

Operator operator O

Supervisor supervisor S

Maintenance maintenance M

Engineer engineer E

Administrator password A

Notes:
• User names ARE NOT case sensitive. For example, “operator”, “Operator”,
and “OPERATOR” are all valid for the Operator user name.
• Passwords ARE case sensitive. For example, the default password for the
Operator user is “operator”, all lower-case.
• User names cannot be changed.

38 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

• Passwords can be changed. Follow the instructions later in this section to


change the password for a user role.
• The security model includes a default user, which has no security
privileges. When the HMI is powered up, or when logged out, the security
access returns to the default level.
• Security privilege abbreviations (O, S, M, E, A) are used in other parts of
this manual to indicate the user role required to perform an action on the
HMI.

User Login

User login is available from either the Operator or Maintenance screen within the
HMI. Follow the appropriate steps to access the desired screen.

Log in from the Operator Screen

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Operator screen appears.

3. Press to page forward, or to page backward, as required to


navigate to page one of the Operator screen.
4. Continue with Log In on page 40.

Log in from the Maintenance Screen

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

3. Press to page forward, or to page backward, as required to


navigate to page two of the Maintenance screen.
4. Continue with Log In on page 40.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 39


Chapter 4 Human Machine Interface

Log In

1. Click .

The Login dialog box appears.

2. Press .

The on-screen keypad appears.


3. Enter the User name. Note: User names are not case sensitive.

4. Press .

The Login dialog box re-appears.

5. Press .

The on-screen keypad appears.


6. Enter the Password. Note: Passwords are case sensitive.

7. Press .

The Login dialog box closes and the Main screen appears. If login was
successful, the current user name shown on the main screen will reflect the
new login. Note: If the current user does not reflect the new Login, repeat
steps 1…7 of this procedure.

40 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

User Logout

When logged in, the HMI provides you with particular security privileges based
on your user role. In order to safeguard against unauthorized changes to
configuration or operational modes, it is recommended that you logout and
return to the default user role, which has no security privileges, when the unit is
unattended.

You can logout from either the Operator or Maintenance screen. Follow these
steps to log out of the HMI.

1. Complete the steps in User Login on page 39 to access either the Operator
or Maintenance screen.

2. Press to return to the default user access level.

Change the User Password

The HMI application has initial passwords set for each user role as presented
earlier in this chapter. From the HMI, it is possible to change the password for
each user role. Changing the user password requires the following two main
processes.

• Login as the desired user

• Change the password for the user.

Follow these steps to change the user password.

1. Complete the steps in User Login on page 39 to access the Maintenance


screen - Login/Change Password page.

2. Press .

The Change Password dialog box appears.

3. Press .

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 41


Chapter 4 Human Machine Interface

The on-screen keypad appears.


4. Enter the Old Password. Note: Passwords are case sensitive.

5. Press .

The Change Password dialog box re-appears.

6. Press .

The on-screen keypad appears.


7. Enter the New Password. Note: Passwords are case sensitive.

8. Press .

The Change Password dialog box re-appears.

9. Press .

The on-screen keypad appears.


10. Enter the New Password again to confirm. Note: Passwords are case
sensitive.

11. Press .

The Change Password dialog box re-appears.

12. Press .

If you successfully changed the password, the Main screen appears. An error
message is displayed to indicate when the password change was not successful.
Follow the guidance presented in the error message and repeat the procedure.

42 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

HMI Functions with Security The following tables list the functions on the HMI screens that require security
privileges, and the corresponding user roles that can perform the function.
Privileges
User Roles are: O = Operator
S = Supervisor
M = Maintenance
E = Engineer
A = Administrator
Table 15 - Operator Screen
Page Function Requiring Security Privilege User Roles
Page 2 – Compressor Overview Load button O, S, M or E
Unload button O, S, M or E
Page 4 – Margin Control Margin Increment button O, S, M or E
Margin Decrement button O, S, M or E
Base Offset Margin value M, E, or A
Base Percent Margin value M, E, or A
Maximum Margin value M, E, or A
Margin Adjust Amount value M, E or A
Margin Adjust Type value M, E, or A

Table 16 - Maintenance Screen


Page Function Requiring Security Privilege User Roles
Page 1 – Configuration and Settings Bypass Enable button M, E, or A
Bypass Disable button M, E, or A
Page 3 – Localization Unit of Measure select E or A

Table 17 - Alarm Screen


Page Function Requiring Security Privilege User Roles
Page 1 - Alarms Alarm Acknowledge button O, S, M, E or A
Alarm Acknowledge All button O, S, M, E or A
Alarm Reset button O, S, M, E or A

Table 18 - Interlocks Screen


Page Function Requiring Security Privilege User Roles
Page 1 – Internal Interlocks, and Interlock Reset button O, S, M, E or A
Page 2 – External Interlocks

Table 19 - Permissives Screen


Page Function Requiring Security Privilege User Roles
Page 1 – Internal Permissives, and Permissive Reset button Not used,
Page 2 – External Permissives permissives
do not latch

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 43


Chapter 4 Human Machine Interface

Table 20 - Interlocks Configuration Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Internal Interlocks, and Interlock Bypassable select E or A
Page 2 – External Interlocks Interlock Description string E or A

Table 21 - Permissives Configuration Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Internal Permissives, and Permissive Bypassable select E or A
Page 2 – External Permissives Permissive Description string E or A

Table 22 - Parameter Configuration Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 - Parameter Configuration Restore button O, S, M, E or A
Upload button E or A
Download button E or A
Edit Parameter button E or A
Save button E or A

Table 23 - Hardware Status Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 2 – Controller Fault Status Details Fault Reset button O, S, M, E or A
Page 3 – PanelView Plus Information Set Clock button E or A
Exit to PanelView Config button E or A

Table 24 - Digital Input Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Operator Use Input PV button M, E or A
Use Substitute PV button M, E or A
Substitute PV state buttons M, E or A
Page 2 – Configuration Disallow Substitute PV setting E or A
Use this Signal setting E or A
Device Description string E or A

44 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Table 25 - Digital Output Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Operator Operator Mode button O, S, M or E
Program Mode button O, S, M or E
Output Command buttons O, S, M or E
Page 2 – Configuration Fail On setting E or A
Device Description string E or A

Table 26 - Analog Input Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Operator Use Input PV button M, E or A
Use Substitute PV button M, E, or A
Substitute PV value M, E or A
Page 2 – Configuration PV EU Minimum value E or A
PV EU Maximum value E or A
Has Extended Scaling setting E or A
Square-root Extract setting E or A
Has Hi Alarm setting E or A
Has Lo Alarm setting E or A
Hi Alarm Limit value E or A
Lo Alarm Limit value E or A
Alarm Deadband value E or A
Primary Units of Measure string E or A
Secondary Units of Measure string E or A
Device Description string E or A

Table 27 - Analog Output Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Operator Operator Mode button O, S, M or E
Program Mode button O, S, M or E
Operator Control value O, S, M or E

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 45


Chapter 4 Human Machine Interface

Table 27 - Analog Output Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 2 – Configuration CV EU Minimum value Value set by
logic
CV EU Maximum value Value set by
logic
Fail Open setting Value set by
logic
Has Low Resolution AO setting Value set by
logic
Has Position Feedback setting Value set by
logic
Deviation DB value Value set by
logic
Deviation Minimum Duration value Value set by
logic
Primary Unit of Measure string E or A
Secondary Unit of Measure string E or A
Device Description string E or A

Table 28 - PID Loop Device Screen (popup)


Page Function Requiring Security Privilege User Roles
Page 1 – Operator Auto Mode button O, S, M or E
Manual Mode button O, S, M or E
Setpoint value O, S, M or E
Manual CV value O, S, M or E
Page 2 – Configuration (All Loops) Device Description string E or A
Primary PV Unit of Measure string E or A
Secondary PV Unit of Measure string E or A
Primary CV Unit of Measure string E or A
Secondary CV Unit of Measure string E or A

46 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Table 28 - PID Loop Device Screen (popup) (Continued)


Page Function Requiring Security Privilege User Roles
Page 2 – Configuration (ASC Primary Loop with Proportional Break Point 1 value E or A
Adaptive Tuning)
Proportional Break Point 2 value E or A
Proportional Slope 1 value E or A
Proportional Slope 2 E or A
Proportional Maximum Limit value E or A
Proportional Minimum Limit value E or A
Integral Break Point 1 value E or A
Integral Break Point 2 value E or A
Integral Slope 1 value E or A
Integral Slope 2 value E or A
Integral Maximum Limit value E or A
Integral Minimum Limit value E or A
Proportional Base value M, E or A
Integral Base value M, E or A
Page 2 – Configuration (Other Loops with Setpoint Minimum Limit value M, E or A
Conventional Tuning)
Setpoint Maximum Limit value M, E or A
Setpoint Increase Rate value M, E or A
Setpoint Decrease Rate value M, E or A
SetPoint Track PV in Manual setting E or A
Proportional Tuning value M, E or A
Integral Tuning value M, E or A
Derivative Tuning value M, E or A
Interactive Tuning setting E or A

Table 29 - Compressor Details Screen (popup)


Page Function Requiring Security Privilege User Roles
Tab 1 – Compressor Head Ratio of Specific Heats value E or A
Polytropic Efficiency value E or A
Polytropic Exponent Type setting E or A
Max Polytropic Exponent Limit value E or A
Min Polytropic Exponent Limit value E or A

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 47


Chapter 4 Human Machine Interface

Table 29 - Compressor Details Screen (popup) (Continued)


Page Function Requiring Security Privilege User Roles
Tab 2 - Base Conditions Orifice Base Pressure value E or A
Orifice Base Temperature value E or A
Orifice Maximum Flow value E or A
Compressor Base Pressure value E or A
Compressor Base Temperature value E or A
Gas Molecular Weight value E or A
Gas Compressibility E or A
Use IGV Position for Map setting E or A
IGV Minimum Position Limit value E or A
Tab 3 – Surge Map Surge Map – X-axis OP values E or A
Surge Map – Y-Axis Head values E or A
Surge Map – IGV Position values E or A
Tab 4 – OPTrack/Decoupling OP Track – Max Track Limit value M, E or A
OP Track – Track Margin value M, E or A
OP Track – Track Rate value M, E or A
Decoupling – Initiate Point 1 value M, E or A
Decoupling – Release Point 2 value M, E or A
Use Decoupling setting E or A
Tab 5 – ASC and CAP valves ASCV – Open Slew Rate value M, E or A
ASCV – Close Slew Rate value M, E or A
ASCV – Max CV Limit value M, E or A
ASCV – Min CV Limit value M, E or A
ASCV – CV NotRun/Unload/Trip value M, E or A
ASCV – Position Deviation DB value M, E or A
ASCV – Position Deviation Time value M, E or A
CapCV – Open Slew Rate value M, E or A
CapCV – Close Slew Rate value M, E or A
CapCV – Max CV Limit value M, E or A
CapCV – Min CV Limit value M, E or A
CapCV – CV NotRun/Unload/Trip value M, E or A
CapCV – Position Deviation DB value M, E or A
CapCV – Position Deviation Time value M, E or A
Tab 6 – Surge Configuration Multi-Surge Trip Quantity value E or A
Multi-Surge Trip Time value E or A
Rate-of-Change Low value M, E or A
Rate-of-Change Deadband value M, E or A
Rate-of-Change Time value M, E or A
Positional Surge Margin value M, E or A
Reset Surge Count button E or A

48 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Human Machine Interface Chapter 4

Table 29 - Compressor Details Screen (popup) (Continued)


Page Function Requiring Security Privilege User Roles
Tab 7 – Surge Test Activate Surge Test button E or A
DeActivate Surge Test button E or A
Use Pos. Surge for Test setting E or A
Use RoC Surge for Test setting E or A
Use Incip Surge for Test setting E or A
Reset Trapped Data button E or A

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 49


Chapter 4 Human Machine Interface

Notes:

50 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 5

SSCC Configuration

This section contains the steps required to configure the SSCC. The SSCC can
be applied to a variety of control requirements including anti-surge control,
capacity/performance control, additional protection/override controls, as well as
unit interlocks and permissives.

Parameter Lists Because of the wide range of control capabilities, there is a large amount of
configuration choices which can be made in order to meet the requirements of
the application. Configuration choices have been organized into groups called
“parameter lists.” Thus, the configurable parameters grouped together in a
parameter list represent a device (for example, a transmitter), or a control
function (for example, a PID loop) or a common theme (for example, the
compressor surge map).

Each parameter list contains the parameter number, description, range, and
initial value. A User-configured Value column is also provided in each table for
recording purposes. To use this feature, print the lists and record any values
changed during configuration in this column.

Table 30 identifies the parameter lists and provides a summary of the


configuration parameters that make up the list.
Table 30 - Available Configuration Parameter Lists
Parameter List Name Summary of Parameters
01: AIN - Compressor Flow on page 53 Usage, engineering unit scaling, and alarm configuration.
02: AIN - Suction Pressure on page 54 Usage, engineering unit scaling, and alarm configuration.
03: AIN - Discharge Pressure on page 55 Usage, engineering unit scaling, and alarm configuration.
04: AIN - Auxiliary Control Signal on page 56 Usage, engineering unit scaling, and alarm configuration.
05: AIN - Suction Temperature on page 57 Usage, engineering unit scaling, and alarm configuration.
06: AIN - Discharge Temperature on page 58 Usage, engineering unit scaling, and alarm configuration.
07: AIN - Multi-use Signal A on page 59 Usage, engineering unit scaling, and alarm configuration.
08: AIN - Multi-use Signal B on page 60 Usage, engineering unit scaling, and alarm configuration.
09: Digital Input Channel Configuration on page 61 DI channel usage and signal state configuration.
10: Digital Output Channel Configuration on page 63 DO channel control state configuration.
11: Compressor Configuration Information on page 63 Base properties for the compressor map, flow
measurement, gas properties, head calculation method,
inlet guide vane usage.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 51


Chapter 5 SSCC Configuration

Table 30 - Available Configuration Parameter Lists (Continued)


Parameter List Name Summary of Parameters
12: Surge Map Definition on page 65 Compressor surge map (10-segment lookup table) values
(head vs. operating point, plus inlet guide vane positions
if applicable).
13: Surge and Margin Configuration on page 66 Anti-surge control margin properties, surge detection
properties, and operating point tracking properties.
14: Run and Load Configuration on page 68 Compressor run determination, and manual/auto load
configuration.
15: Anti-Surge Control General Configuration on page 69 Anti-surge control and valve properties including control
value limits, slew rates, position deviation alarming. Anti-
surge PID loop min/max selection and tracking.
16: ASC Primary PID Loop on page 70 Configuration properties for the primary anti-surge PID
loop. This loop is always configured to control the anti-
surge valve.
17: ASC Primary PID Loop - Adaptive Integral on page 72 Adaptive integral tuning parameters for the primary anti-
surge PID loop.
18: ASC Primary PID Loop - Adaptive Proportional on page Adaptive proportional tuning parameters for the primary
73 anti-surge PID loop.
19: ASC Secondary PID Loop on page 74 Configuration properties for the secondary anti-surge PID
loop. This is the optional protection/override PID loop
which may be used to control the anti-surge valve.
20: Capacity Control General Configuration on page 76 Capacity control and valve/device properties including
control value limits, slew rates, position deviation
alarming. Capacity PID loop min/max selection and
tracking.
21: Capacity Primary PID Loop on page 78 Configuration properties for the primary capacity PID
loop. When capacity control is required, this is the PID
loop used to control the capacity valve/device.
22: Capacity Secondary PID Loop on page 80 Configuration properties for the secondary capacity PID
loop. This is the optional protection/override PID loop
which may be used to control the capacity valve/device.
23: Anti-Surge - Capacity Decoupling Configuration on Configures the use of decoupling between the anti-surge
page 82 and capacity controls.
24: AINs - Substitute PV on page 83 Configure each analog input channel to allow/disallow
the use of substitute PV.
25: DINs - Substitute PV on page 84 Configure each digital input channel to allow/disallow the
use of substitute PV.
26: Reserved for Future Use on page 84 Intentionally omitted from the HMI, reserved for future
use only.
27: Interlock Bypassable Configuration on page 85 Configure the bypass option for individual interlocks.
28: Permissive Bypassable Configuration on page 86 Configure the bypass option for individual permissives.
29: Modbus Serial Port Configuration on page 87 Configure, set and read the configuration for the Modbus
serial port of the controller.
30: Application (HMI Configuration) on page 88 HMI application configuration properties (consult factory
before making any changes).
Configure whether bypasses are permitted for the unit.

Refer to the following sections for details on each of the parameter lists, and the
configuration settings and options for the parameters that make up each list.

52 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

01: AIN - Compressor Flow

List 01 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 0 for compressor flow. The
compressor flow input is the primary input used to calculate the operating point
(OP) value of the compressor.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 31 - Parameter List 01: AIN – Compressor Flow
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 1…4 1
1 = Qs, suction flow
2 = Qd, discharge flow, and no inter-stage or discharge coolers
3 = Qdd, discharge flow downstream of any inter-stage or discharge coolers (requires suction and
discharge temperatures to be configured)
4 = Qalt, an alternate measurement signal is used instead of Flow (special case, requires special
considerations to determine surge map)
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 1
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment, Engineering Units (applicable to pressure and temperature signals). 0…999999 0
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering Units. -999999…999999 100
10 Low Alarm Limit Value. Engineering Units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 53


Chapter 5 SSCC Configuration

02: AIN - Suction Pressure

List 02 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 1 for suction pressure. The suction
pressure input is used for the following purposes.

• A variable in calculating the compressor “head”

• As pressure compensation in the operating point calculation (when flow


usage is Qs, Qd, or Qdd)

• As the process variable (PV) for the anti-surge secondary (override) PID
loop, or capacity primary or capacity secondary PID loops (if selected)

The following table identifies the configuration parameters, range limits, and
initial values.
Table 32 - Parameter List 02: AIN – Suction Pressure
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0 or 1 1
0 = Not configured
1 = Suction Pressure
Usage should always be configured = 1. In rare cases where the compressor has no suction
pressure transmitter, configure = 1 and use substitute PV to set the value equal to the compressor
base pressure.
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
If transmitter is a gauge transmitter, enter the amount to convert to absolute pressure.
If the transmitter is an absolute transmitter, enter 0.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

54 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

03: AIN - Discharge Pressure

List 03 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 2 for discharge pressure. The
discharge pressure input is used for the following purposes.

• A variable in calculating the compressor “head”

• As pressure compensation in the operating point calculation (when flow


usage is Qd or Qdd)

• As the process variable (PV) for the anti-surge secondary (override) PID
loop, or capacity primary or capacity secondary PID loops (if selected)

The following table identifies the configuration parameters, range limits, and
initial values.
Table 33 - Parameter List 03: AIN – Discharge Pressure
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0 or 1 1
0 = Not configured
1 = Discharge Pressure
Usage should always be configured = 1.
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
If transmitter is a gauge transmitter, enter the amount to convert to absolute pressure.
If the transmitter is an absolute transmitter, enter 0.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 55


Chapter 5 SSCC Configuration

04: AIN - Auxiliary Control Signal

List 04 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 3 provided for an auxiliary control
signal. The auxiliary input signal is used for the following purposes.

• As the process variable (PV) for the anti-surge secondary (override) PID
loop, or capacity primary or capacity secondary PID loops (if selected)

The following table identifies the configuration parameters, range limits, and
initial values.
Table 34 - Parameter List 04: AIN – Auxiliary Control Signal
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0 or 1 0
0 = Not configured
1 = Configured for use
The auxiliary control signal is optional.
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
If transmitter is a gauge transmitter, enter the amount to convert to absolute value.
If the transmitter is an absolute transmitter, enter 0.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

56 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

05: AIN - Suction Temperature

List 05 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 4 for suction temperature. The
suction temperature input is used for the following purposes.

• A variable in calculating the compressor “head” (when variable polytropic


exponent is configured)

• As temperature compensation in the operating point calculation (when


flow usage is Qdd)

The following table identifies the configuration parameters, range limits, and
initial values.
Table 35 - Parameter List 05: AIN - Suction Temperature
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0 or 1 0
0 = Not configured
1 = Suction temperature configured for use
The suction temperature configuration is required when the flow usage is configured as Qdd.
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
For internal calculations, the temperature must be converted into absolute units. Enter the
absolute adjustment value:
For DegF transmitters: set to 460 to convert to DegR
For DegC transmitters: set to 273 to convert to DegK
Suction and discharge transmitters must be in the same units.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 57


Chapter 5 SSCC Configuration

06: AIN - Discharge Temperature

List 06 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 5 for discharge temperature. The
discharge temperature input is used for the following purposes.

• A variable in calculating the compressor “head” (when variable polytropic


exponent is configured)

• As temperature compensation in the operating point calculation (when


flow usage is Qdd)

The following table identifies the configuration parameters, range limits, and
initial values.
Table 36 - Parameter List 06: AIN – Discharge Temperature
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0 or 1 0
0 = Not configured
1 = Discharge temperature configured for use
The discharge temperature configuration is required when the flow usage is configured as Qdd.
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
For internal calculations, the temperature must be converted into absolute units. Enter the
absolute adjustment value:
For DegF transmitters: set to 460 to convert to DegR
For DegC transmitters: set to 273 to convert to DegK
Suction and discharge transmitters must be in the same units.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

58 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

07: AIN - Multi-use Signal A

List 07 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 6 for multi-use signal A. The multi-
use signal input can be used for the following purposes.

• A valve position feedback transmitter, for either the anti-surge valve, or the
capacity control valve/guide vanes.

• The incipient surge detection signal from the optional SurgeGard device.

The following table identifies the configuration parameters, range limits, and
initial values.

Note: Multi-use signal A and multi-use signal B usage should not be configured
for the same signal type.
Table 37 - Parameter List 07: AIN – Multi-use Signal A
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0…3 0
0 = Not configured
1 = PosA, anti-surge valve position transmitter
2 = PosCap, capacity valve/guide vane position transmitter
3 = SG, SurgeGard incipient surge detection signal.
Note: When configured for SurgeGard incipient surge detection signal, the High Alarm is used as
the signal threshold that triggers the incipient surge control value increment action (see parameter
09 in list 15: Anti-Surge Control General Configuration on page 69).
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
Not applicable for this signal, set to 0.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 59


Chapter 5 SSCC Configuration

08: AIN - Multi-use Signal B

List 08 defines the usage, engineering unit scaling and linearization, and alarm
configuration for the analog input channel 7 for multi-use signal A. The multi-
use signal input can be used for the following purposes.

• A valve position feedback transmitter, for either the anti-surge valve, or the
capacity control valve/guide vanes.

• The incipient surge detection signal from the optional SurgeGard device.

The following table identifies the configuration parameters, range limits, and
initial values.

Note: Multi-use signal A and multi-use signal B usage should not be configured
for the same signal type.
Table 38 - Parameter List 08: AIN – Multi-use Signal B
No. Description Range Initial Value User-configured
Value
01 Channel Usage Configuration. Choices: 0…3 0
0 = Not configured
1 = PosA, anti-surge valve position transmitter
2 = PosCap, capacity valve/guide vane position transmitter
3 = SG, SurgeGard incipient surge detection signal
Note: When configured for SurgeGard incipient surge detection signal, the High Alarm is used as
the signal threshold that triggers the incipient surge control value increment action (see parameter
09 in list 15: Anti-Surge Control General Configuration on page 69).
02 Engineering Unit Scale Max Limit (EU). -999999…999999 100
The scaled engineering unit value at 20 mA input.
03 Engineering Unit Scale Min Limit (EU). -999999…999999 0
The scaled engineering unit value at 4 mA input.
04 Scaling Type. Choices: 0 or 1 0
0 = Linear
1 = Square-root extraction (applicable to flow signals)
05 Extrapolate Scaling, if input beyond normal limits. 0 or 1 0
0 = No, clamp EU value at min and max limits
1 = Yes, extrapolate EU value beyond limits
06 Absolute Adjustment. Engineering units. 0…999999 0
Not applicable for this signal, set to 0.
07 Has Alarm High Level. 0 or 1 0
0 = No, high level alarm not to be used
1 = Yes, high level alarm to be used
08 Has Alarm Low Level. 0 or 1 0
0 = No, low level alarm not to be used
1 = Yes, low level alarm to be used
09 High Alarm Limit Value. Engineering units. -999999…999999 100
10 Low Alarm Limit Value. Engineering units. -999999…999999 0
11 Alarm Deadband. Engineering units. 0…999999 0

60 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

09: Digital Input Channel Configuration

List 09 defines the usage and signal state for the all of the digital input channels.
The following table identifies the configuration parameters, range limits, and
initial values.
Table 39 - Parameter List 09: Digital Input Channel Configuration
No. Description Range Initial Value User-configured
Value
01 Use Compressor Run Signal input (DI Channel 0). 0 or 1 0
0 = No, do not use this signal
1 = Yes, Use this signal for compressor run detection
02 Compressor Run State (DI Channel 0). 0 or 1 1
0 = Compressor running state when input is Off
1 = Compressor running state when input is On
03 Use Reset Push Button Signal Input (DI Channel 1). 0 or 1 0
0 = No, do not use this signal
1 = Yes, Use this signal for Reset push button
04 Reset Push Button State (DI Channel 1). 0 or 1 1
0 = Trigger reset action when input is Off
1 = Trigger reset action when input is On
05 Use Load Push Button Signal Input (DI Channel 2). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for Load push button
06 Load Push Button State (DI Channel 2). 0 or 1 1
0 = Trigger load request when input is Off
1 = Trigger load request when input is On
07 Use Unload Push Button Signal Input (DI Channel 3). 0 or 1 0
0 = No, do not use this signal
1 = Yes, Use this signal for Unload push button
08 Unload Push Button State (DI Channel 3). 0 or 1 1
0 = Trigger unload request when input is Off
1 = Trigger unload request when input is On
09 Use External Ready-To-Start-1 Signal Input (DI Channel 8). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for Ready-To-Start-1 condition
10 External Ready-To-Start-1 State (DI Channel 8). 0 or 1 1
0 = Ready-To-Start state when input is Off
1 = Ready-To-Start state when input is On
11 Use External Ready-To-Start-2 Signal Input (DI Channel 9). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for Ready-To-Start-2 condition
12 External Ready-To-Start-2 State (DI Channel 9). 0 or 1 1
0 = Ready-To-Start state when input is Off
1 = Ready-To-Start state when input is On
13 Use External Ready-To-Start-3 Signal Input (DI Channel 10). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for Ready-To-Start-3 condition
14 External Ready-To-Start-3 State (DI Channel 10). 0 or 1 1
0 = Ready-To-Start state when input is Off
1 = Ready-To-Start state when input is On

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 61


Chapter 5 SSCC Configuration

Table 39 - Parameter List 09: Digital Input Channel Configuration (Continued)


No. Description Range Initial Value User-configured
Value
15 Use External Ready-To-Start-4 Signal Input (DI Channel 11). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for Ready-To-Start-4 condition
16 External Ready-To-Start-4 State (DI Channel 11). 0 or 1 1
0 = Ready-To-Start state when input is Off
1 = Ready-To-Start state when input is On
17 Use External Compressor Trip-1 Signal Input (DI Channel 12). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for compressor Trip-1 condition
18 External Compressor Trip-1 State (DI Channel 12). 0 or 1 0
0 = Compressor Trip state when input is Off
1 = Compressor Trip state when input is On
19 Use External Compressor Trip-2 Signal Input (DI Channel 13). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for compressor Trip-2 condition
20 External Compressor Trip-2 State (DI Channel 13). 0 or 1 0
0 = Compressor Trip state when input is Off
1 = Compressor Trip state when input is On
21 Use External Compressor Trip-3 Signal Input (DI Channel 14). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for compressor Trip-3 condition
22 External Compressor Trip-3 State (DI Channel 14). 0 or 1 0
0 = Compressor Trip state when input is Off
1 = Compressor Trip state when input is On
23 Use External Compressor Trip-4 Signal Input (DI Channel 15). 0 or 1 0
0 = No, do not use this signal
1 = Yes, use this signal for compressor Trip-4 condition
24 External Compressor Trip-4 State (DI Channel 15). 0 or 1 0
0 = Compressor Trip state when input is Off
1 = Compressor Trip state when input is On

62 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

10: Digital Output Channel Configuration

List 10 defines the signal state for the all of the digital output channels. The
following table identifies the configuration parameters, range limits, and initial
values.
Table 40 - Parameter List 10: Digital Output Channel Configuration
No. Description Range Initial Value User-configured
Value
01 Compressor Trip Output (DO Channel 0). 0 or 1 1
0 = Normally de-energized, energize for compressor Trip
1 = Normally energized, de-Energize for compressor Trip
02 Compressor Run Output (DO Channel 1). 0 or 1 0
0 = Normally de-energized, energize for compressor Run
1 = Normally energized, de-energize for compressor Run
03 Ready-To-Start Output (DO Channel 2). 0 or 1 0
0 = Normally de-energized, energize for Ready-To-Start
1 = Normally energized, de-energize for Ready-To-Start
04 System Trouble Output (DO Channel 3). 0 or 1 0
0 = Normally de-energized, energize for system trouble
1 = Normally energized, de-energize for system trouble
05 Surge Alarm Output (DO Channel 4). 0 or 1 0
0 = Normally de-energized, energize for surge alarm
1 = Normally energized, de-energize for surge alarm
06 Compressor Load Output (DO Channel 5). 0 or 1 0
0 = Normally de-energized, energize for compressor Load
1 = Normally energized, de-energize for compressor Load

11: Compressor Configuration Information

List 11 defines general properties for the compressor configuration. These


properties represent the following items.
• Base pressure and temperature of the manufacturer’s compressor map
• Gas properties of the manufacturer’s compressor map
• Base properties of the compressor Flow measurement
• Head calculation type for surge map data (polytropic or pressure ratio)
• Inlet guide vane usage and associated map technique.

The following table identifies the configuration parameters, range limits, and
initial values.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 63


Chapter 5 SSCC Configuration

Table 41 - Parameter List 11: Compressor Configuration Information


No. Description Range Initial Value User-configured
Value
01 Compressor Base Temperature, Tbc. 0…999999 0
Enter in absolute temperature units (i.e. Kelvin or Rankin), matching the absolute correction units
of any temperature transmitters.
02 Compressor Base Pressure, Pbc. 0…999999 0
Enter in absolute pressure units, matching the absolute correction units of the pressure
transmitters.
03 Design Gas Ratio of Specific Heats, k (Cp/Cv). 0…2 0
04 Compressor Polytropic Efficiency, Peff. 0…1 0
Polytropic efficiency at surge point.
05 Compressor Flow Device (Orifice) Base Temperature, Tbo. 0…999999 0
Enter in absolute temperature units (i.e. Kelvin or Rankin), matching the absolute correction units
of any temperature transmitters, and the compressor base temperature.
06 Compressor Flow Device (Orifice) Base Pressure, Pbo. 0…999999 0
Enter in absolute pressure units, matching the absolute correction units of the pressure
transmitters, and the compressor base pressure.
07 Max Flow Range, used for surge map Flow normalization. 0…999999 0
From the Rockwell Automation compressor toolset surge map definition.
08 Head Type, for surge map. Choices: 0 or 1 0
0 = HpSim, simplified polytropic Head
1 = Pratio, pressure ratio (Pd/Ps)
09 Polytropic Exponent Calculation Type. Choices: 0 or 1 0
0 = Fixed/constant, calculated from k, and Peff
1 = Variable, calculated from actual pressures/temperatures using log ratios
10 Variable Polytropic Exponent Max Limit. 0…10 0
Used when polytropic exponent type set to “Variable.”
Sets the max limit for the calculated value.
11 Variable Polytropic Exponent Min Limit 0 to 10 0
Used when polytropic exponent type set to “Variable.”
Sets the min limit for the calculated value.
12 Adjust Surge Map Using Inlet Guide Vanes. Choices: 0 or 1 0
0 = No, use the surge map without adjustment
1 = Yes, use inlet guide vane adjustment technique
13 Inlet Guide Vane (IGV) Min Limit for Adjustment. 0…100 0
Used when IGV adjustment technique is configured for use.
Sets the min limit for the IGV adjustment.
14 Design Gas Molecular Weight, MW. 0…200 0
From compressor map, for reference only, not used in calculations.
15 Design Gas Compressibility, Z. 0…2 0
From compressor map, for reference only, not used in calculations.

64 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

12: Surge Map Definition

List 12 defines the surge map for the compressor. The SSCC utilizes a ten-
segment lookup table to represent the surge map plotting Head vs. Flow
(normalized as %Q2). When the compressor includes inlet guide vanes (IGV),
the IGV position is also configured for each point on the surge map.

The surge map values for Head and normalized Flow are typically generated
using the Rockwell Automation compressor toolset. The toolset allows the user
to enter values taken directly from the manufacturer’s compressor map, and
generates the Head (HpSim or Pratio) and Flow (%Q2) values required by the
anti-surge control algorithms in the SSCC.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 42 - Parameter List 12: Surge Map Definition
No. Description Range Initial Value User-configured
Value
01 X-axis Values (%Q2, 11 points), for compressor surge map. 0…100 0
02 Values represent the Flow-squared, normalized over a Flow max range (referred to as %Q-squared,
03 or %Q2).
04 Values typically generated using the Rockwell Automation compressor toolset.
05 Values must be ascending:
06 Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
07 When not all points are required, set each point in the list to 0.0, as required. For example, if only
08 four points are defined, enter them at parameters 8…11 (%Q2 Pt-7…Pt-10), and prefill
09 parameters 1…7 (%Q2 Pt-0…Pt-6) = 0.0.
10
11
12 Y-axis Values (Head, 11 points), for compressor surge map. 0…100 0
13 Values represent Head expressed in simplified polytropic Head, or pressure ratio (as identified in
14 List 11, parameter 8).
15 Values typically generated using the Rockwell Automation compressor toolset.
16 Values must be ascending:
17 Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
18 When not all points are required, pre-fill the list as required. For example, if only four points are
19 defined, enter them at parameters 19…22 (Head, Pt-7…Pt-10), and prefill parameters 12…18
= 0.0 (for HpSim) or = 1.0 (for Pratio).
20
21
22
23 Inlet Guide Vane Values (IGV, 11 points), for compressor surge map. Applicable only for compressor 0…100 0
24 with inlet guide vanes (IGV). Values represent IGV position expressed in %-open.
25 Values typically generated using the Rockwell Automation compressor toolset.
26 Values must be ascending:
27 Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
28 When not all points are required, pre-fill the list as required. For example, if only four IGV points are
29 defined, enter them at parameters 30…33 (IGV, Pt-7…Pt-10), and prefill parameters 23…32 =
0.0 (IGV Pt-0…Pt-6).
30
31
32
33

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 65


Chapter 5 SSCC Configuration

13: Surge and Margin Configuration

List 13 defines the surge detection and control margin properties. These
properties establish the following items.

• Control margin calculations which set the distance between the surge
limit line (SLL) and the control limit line.

• Surge detection methods, which detect surge based on changes to the


operating point, either positionally (it falls below the SLL by a defined
amount) or rate-of-change (it decreases rapidly, exceeding a falling low
threshold).

• Operating point tracking, which establishes the surge control line (SCL)
used as the setpoint for the anti-surge primary PID loop.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 43 - Parameter List 13: Surge and Margin Configuration
No. Description Range Initial Value User-configured
Value
01 Base Offset Margin, %. 0…100 10
The offset margin is one form of margin used to establish the distance from the surge limit line
(SLL) to the control limit line (CLL).
The base offset margin represents the min offset margin that will be used.
The offset margin in use can be incrementally adjusted manually by the operator, or automatically
on surge detection.
02 Base Percent Margin, %. 0…100 20
The percent margin is a second form of margin used to establish the distance from the SLL to the
CLL.
This margin contributes a percentage of the SLL value towards the total margin. Thus, the lower the
SLL value, the smaller the percent margin contribution, and the higher the SLL value, the larger the
percent margin contribution.
Combining the percent margin with the offset margin provides great flexibility in total margin
determination.
The base percent margin represents the minimum percent margin that will be used.
The percent margin in use can be incrementally adjusted manually by the operator, or
automatically on surge detection.
03 Maximum Margin Limit, %. 0…100 30
This limit is applied individually to the offset margin in use, the percent margin in Use, as well as
the calculated total margin in use.
004 Margin Adjustment Amount, %. 0…10 1
The margin in use can be incrementally adjusted by the operator or automatically when surge is
detected. This parameter sets the amount of adjustment.
05 Margin Adjustment Type. 1…3 1
When margin in use is incrementally adjusted, this parameter specifies what form of margin is
adjusted. Choices:
1 = Offset margin in use
2 = Percent margin in use
3 = Both offset and percent margin in use
06 Backup Margin, %. 0…100 3
The backup margin determines the limit for manual control of the anti-surge primary PID loop. If
the distance between the operating point (OP) and the surge limit line (SLL) is less than the backup
margin, then the anti-surge primary PID loop mode is forced to automatic to prevent the operator
from driving the compressor into surge.

66 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 43 - Parameter List 13: Surge and Margin Configuration (Continued)


No. Description Range Initial Value User-configured
Value
07 Backup and Surge Deadband, %. 0…100 1
Sets the deadband used for the backup margin condition, and the positional surge alarm condition.
08 Surge Trip Quantity. 0…10 4
Quantity of surges for the multiple surge trip interlock.
09 Surge Trip Time, seconds. 0…600 30
The duration of time for the multiple surge trip interlock.
If the quantity of surges (parameter 8) occur within this amount of time, the multiple surge trip
interlock is generated, which triggers the compressor trip output.
10 Surge Detection – Rate of Change Low Threshold (-%/sec). -99999…0 -25
Establishes the rate-of-change (RoC) low threshold for operating point which is reported as a
surge.
11 Surge Detection – Rate of Change Deadband (%/sec). 099999 10
A deadband used by the RoC calculation to clear the RoC surge condition.
12 Surge Detection – Rate-of-Change Time, milliseconds. 0…1000 200
Parameters 10, 11, and, 12 are used together to specify a surge detection method for rate-of-
change (RoC) on the operating point (OP). The RoC of the OP is calculated every scan of the
controller (set to 20 msec). The RoC maintains up to 50 samples of RoC values spanning up to 1
second (50 * 20 msec = 1000 msec). The RoC function calculates the average RoC over the time
defined by parameter 12 by averaging the relevant quantity of samples. When this calculated
average RoC is lower than the low threshold value (parameter10) a surge detection based on RoC is
determined. This condition remains until the average RoC is greater than the RoC low threshold
plus RoC deadband (parameter 11).
13 Surge Detection – Position Surge Margin, %. -100…0 -2
Positional surge is detected when the operating point falls below the surge limit line by this
amount.
14 Operating Point Track Margin, %. 0…100 5
OP tracking establishes the surge control line (SCL). As the OP increases and moves to the right of
the control limit line, the SCL may track the OP by this track margin.
15 Operating Point Track Rate, %/sec. 0…100 1
When the OP decreases back towards the CLL, this parameter determines the rate that the SCL is
reduces back towards the CLL.
16 Operating Point Track Max SP Limit, %. 0…100 75
This parameter sets the maximum limit for the SCL.
For example, with OP track max limit set to 75%, and the OP track margin set to 5.0%, the SCL will
track the OP by 5% up to an OP value of 80%. At this point the SCL is tracking the OP at 75%. If the
OP increases beyond 80%, the SCL remains limited at 75%.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 67


Chapter 5 SSCC Configuration

14: Run and Load Configuration

List 14 defines the properties used for compressor running determination and for
manual/automatic loading for the compressor. Compressor running
determination is normally based on the digital input (DIN) for compressor
running (when a DI channel is configured for use).

Compressor running determination can also optionally be base on the following


conditions.

• A head threshold

• An auxiliary control signal (e.g. motor amps) threshold

• An on-delay timer preset and off-delay timer preset for confirmed run
status

The following table identifies the configuration parameters, range limits, and
initial values.
Table 44 - Parameter List 14: Run and Load Configuration
No. Description Range Initial Value User-configured
Value
01 Automatically Load compressor on Run condition. Choices: 0 or 1 0
0 = No
1 = Yes
02 Use Auxiliary Control Signal for Run determination. Choices: 0 or 1 0
0 = No
1 = Yes
03 Auxiliary Control Signal Threshold for Running, EU. -999999…999999 0
When parameter 2 is set to “Yes,” this parameter defines the threshold for the Run determination.
Run condition if (AuxCntrlSig > Threshold)
Example: For a motor driven compressor, the aux control signal analog input signal could be wired
to a motor-amps transducer. If motor amps are greater than a set threshold, then the compressor is
running.
04 Use Head for Run determination. Choices: 0 or 1 0
0 = No
1 = Yes
05 Head Value Threshold for Running, EU. 0…100 0
When parameter 4 is set to “Yes,” this parameter defines the threshold for the Run determination.
Run condition if (Head > Threshold)
06 Confirmed Run Status On-delay Timer Preset, seconds. 0…600 10
This value is the preset for the confirmed run status on-delay time. Until the compressor is
confirmed running, loading is not permitted, and the anti-surge and capacity control devices are
held at their override/unload/not running position.
This on-delay timer applies to all options for Run condition, in other words, the Comp Run DI,
AuxCntrlSig threshold, and Head threshold.
07 Confirmed Run Status Off-delay Timer Preset, seconds. 0…60 1
This value is the preset for the confirmed run status off-delay time. Once confirmed run status is
set, running condition(s) must clear for this off-delay time before the confirmed run status is
cleared.

68 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

15: Anti-Surge Control General Configuration

List 15 defines general properties for anti-surge control that are independent
from the primary and secondary anti-surge PID loops. These general
configuration properties are used for the following controls.

• Anti-surge valve control value limits

• Anti-surge valve slew rate limits

• Ant-surge valve position deviation alarming

• Anti-surge PID loop min/max selection

• Anti-surge PID loop tracking

The following table identifies the configuration parameters, range limits, and
initial values.
Table 45 - Parameter List 15: Anti-Surge Control General Configuration
No. Description Range Initial Value User-configured
Value
01 Anti-surge PID Loop Output Min/Max Select Type. Choices: 0 or 1 1
0 = Minimum select
1 = Maximum select
02 Not Running Control Value, % open. 0…100 100
The anti-surge valve is set to this control value whenever the compressor is “Not Running” or
“Unloaded.” This value overrides the PID output values calculated by the primary or secondary anti-
surge PID loops.
If this value exceeds the min or max CV limits expressed in parameters 7 and 8, the min/max
limited value is used under the “Not Running” or “Unloaded” condition.
03 PID Track Margin, % Open. 0…100 5
When both the primary and secondary anti-surge PID loops are configured, this value sets the
tracking limit for the PID loop that is not producing the selected output. This keeps the non-
controlling loop from winding up and moving away from the control value by more than a PID track
margin.
For example, if the PID track margin is set to 10%, the select type is set to “Maximum,” the
compressor is Running and Loaded, the primary PID loop output is max selected and at 60%, and
the secondary PID loop output is 55% and reducing. If the secondary loop output reduces below
50% (60% - 10%) the secondary output is limited (tracks) at 50%. If the primary loop output
increases to 61%, the secondary loop tracking rises to 51% (61% - 10%).
04 Anti-surge Valve Location. Choices 0 or 1 1
0 = Blow-Off valve
1 = Recycle Valve
This setting is used to modify the representation of the anti-surge valve connections on the Process
Overview page of the Operator screen.
05 Open Slew Rate, %/sec. 0…999999 100
Limits the opening rate of the control value.
Normally, the anti-surge opening slew rate is set to allow fast opening.
06 Close Slew Rate %/sec. 0…999999 2
Limits the closing rate of the control value.
Normally, the anti-surge closing slew rate is set to close the valve slowly.
07 Control Value Max Limit % Open. 0…100 100
Sets the max limit for the control value for the valve.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 69


Chapter 5 SSCC Configuration

Table 45 - Parameter List 15: Anti-Surge Control General Configuration (Continued)


No. Description Range Initial Value User-configured
Value
08 Control Value Min Limit, % Open. 0…100 0
Sets the min limit for the control value for the valve.
09 Incipient Surge Control Value Increment, % Open. 0…100 10
On incipient surge detection, this control value is incremented by this amount. This increment is
not subject to open slew rate limits.
This increment serves to “bump” the anti-surge valve open more than the PID calculations are
doing themselves when an incipient surge is detected.
Note: This Incipient Surge Increment action requires that one of the multi-use analog input
channels be configured for the SurgeGard signal input (see list 07: AIN - Multi-use Signal A on page
59 and list 08: AIN - Multi-use Signal B on page 60). Use the High Alarm of the configured channel
for the incipient surge detection threshold.
10 Valve Fail Direction. Choices: 1 1
0 = Closed (i.e. valve is air-to-open)
1 = Open (i.e. valve is air-to-close)
Typically, the anti-surge valve is air-to-close, and fails open.
This setting is used to generate the analog output signal direction from the control value which is
always expressed as % open.
11 Valve Position Deviation Alarm Deadband, %. 0…100 100
When one of the multi-signal analog input channels is configured for anti-surge valve position
feedback, the controller supports a position deviation alarm. This parameter sets the deadband
limit for the alarm. When the difference between the control value and position feedback exceed
this deadband, the deviation alarm timer is activated.
12 Valve Position Deviation Alarm Time, seconds. 0…60 60
This parameter is the preset for the deviation alarm timer. If the position deviation remains active
for this time, the position deviation alarm is generated.

16: ASC Primary PID Loop

List 16 defines the configuration settings for the anti-surge control primary PID
loop. This PID loop is always configured and used for anti-surge control.

The process variable for this loop is always the calculated operating point (OP)
value. The setpoint for this loop is always the surge control limit (SCL) value.
Adaptive tuning is used for this loop (refer to List 17: ASC Primary PID Loop -
Adaptive Integral on page 72 and List 18: ASC Primary PID Loop - Adaptive
Proportional on page 73 for adaptive tuning configuration parameters).

The following table identifies the configuration parameters, range limits, and
initial values. The initial values for these settings will usually not require
changing.

70 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 46 - Parameter List 16: ASC Primary PID Loop


No. Description Range Initial Value User-configured
Value
01 Setpoint Tracks PV in Manual Mode. Choices: 0 or 1 0
0 = No
1 = Yes
Keep this parameter set to 0. The setpoint is always set by the surge control line (SCL) value.
02 Setpoint Maximum Limit, Engineering Units (% Operating Point). 0…100 100
Keep this parameter set to 100.
The SCL calculation by operating point tracking has its own maximum limit for OP tracking. Use
that parameter to limit the maximum SCL and thus the setpoint for this loop. See 13: Surge and
Margin Configuration on page 66, parameter 16.
03 Setpoint Minimum Limit, Engineering Units (% Operating Point). 0…100 0
Keep this parameter set to 0.
The SCL calculation by OP tracking is always lower limited by the control limit line (CLL) value.
There is no need to specify any other limitations on the setpoint for this loop.
04 Setpoint Increment Rate Limit, EU/sec. 0…999999 10000
Keep this parameter set to a large value.
The SCL is allowed to increase as fast as possible, so there is no need to limit this setpoint increasing
rate.
05 Setpoint Decrement Rate Limit, EU/sec 0…999999 10000
Keep this parameter set to a large value.
The SCL decreasing rate is set by the OP track rate (See 13: Surge and Margin Configuration on page
66, parameter 15). There is no need to further limit this setpoint decreasing rate.
06 PID Loop Deadband, Engineering Units (% Operating Point). 0…100 0
Defines a deadband about the setpoint which treats error as 0, and thus no change to control value
output.
If used, normally kept small <= 1%
07 Proportional Action Calculation Type. Choices: 0 or 1 1
0 = Calculate proportional based on change in PV
1 = Calculate proportional based on error
Keep this parameter set to 1 for this loop.
08 Use Interactive Tuning. Choices: 0 or 1 0
0 = No, Tuning parameters are non-interacting
1 = Yes, Tuning parameters are interacting (traditional)
Use for the ASC primary PID loop, which uses adaptive tuning. Keep this parameter set to 0.
09 Control Action. Choices: 0 or 1 0
0 = Reverse
1 = Direct
Used for the ASC primary PID loop. Keep this parameter set to 0 for “Reverse.”
10 PID Control Value (CV) Maximum Limit, % Open. 0…100 100
Sets the maximum limit for the calculated PID control value output.
Normally this parameter will be kept at 100.
11 PID Control Value (CV) Minimum Limit, % Open 0…100 0
Sets the minimum limit for the calculated PID control value output.
Normally this parameter will be kept at 0.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 71


Chapter 5 SSCC Configuration

17: ASC Primary PID Loop - Adaptive Integral

List 17 defines the adaptive integral tuning properties used for the anti-surge
control primary PID loop. The adaptive tuning parameters include the following
feaetures.

• A base tuning value used when operating between breakpoints

• Tuning value minimum and maximum limits

• Breakpoints and slopes used to calculate the adaptive tuning value based
on operating conditions

The following table identifies the configuration parameters, range limits, and
initial values.
Table 47 - Parameter List 17: ASC Primary PID Loop – Adaptive Integral
No. Description Range Initial Value User-configured
Value
01 Base Integral, Kbase, Repeats/minute. 0…100 20
The base integral is the value used when operating within the breakpoints BP1 and BP2.
02 Maximum Limit for Adaptive Integral, Kmax, Repeats/minute. 0…100 100
The calculated adaptive integral is limited to this maximum value.
03 Minimum Limit for Adaptive Integral, Kmin, Repeats/minute. 0…100 1
The calculated adaptive integral is limited to this minimum value.
04 Breakpoint 1, BP1, %. -20…0 -1
The distance below (negative) the CLL where adaptive tuning calculation adjustment begins.
05 Breakpoint 2, BP2, %. 0…100 5
The distance above (positive) the CLL where adaptive tuning calculation adjustment begins.
06 Slope 1, S1, Repeat/min / % . 0…100 10
The slope used for adaptive tuning adjustment below breakpoint 1.
07 Slope 2, S2, Repeat/min / % . -100…100 2
The slope used for adaptive tuning adjustment above breakpoint 2.

72 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

18: ASC Primary PID Loop - Adaptive Proportional

List 18 defines the adaptive proportional tuning properties used for the anti-
surge control primary PID loop. The adaptive tuning parameters include the
following features.

• A base tuning value used when operating between breakpoints

• Tuning value minimum and maximum limits.

• Breakpoints and slopes used to calculate the adaptive tuning value based
on operating conditions.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 48 - Parameter List 18: ASC Primary PID Loop – Adaptive Proportional
No. Description Range Initial Value User-configured
Value
01 Base Proportional, Kbase, Gain. 0…100 0.25
The base proportional is the value used when operating within the breakpoints BP1 and BP2.
02 Maximum Limit for Adaptive Proportional, Kmax, Gain. 0…100 10
The calculated adaptive proportional is limited to this maximum value.
03 Minimum Limit for Adaptive Proportional, Kmin, Gain. 0…100 0.1
The calculated adaptive proportional is limited to this minimum value.
04 Breakpoint 1, BP1, %. -20…0 -1
The distance below (negative) the CLL where adaptive tuning calculation adjustment begins.
05 Breakpoint 2, BP2, %. 0…100 5
The distance above (positive) the CLL where adaptive tuning calculation adjustment begins.
06 Slope 1, S1, Gain / %. 0…100 2
The slope used for adaptive tuning adjustment below breakpoint 1.
07 Slope 2, S2, Gain / %. -100…100 -0.05
The slope used for adaptive tuning adjustment above breakpoint 2.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 73


Chapter 5 SSCC Configuration

19: ASC Secondary PID Loop

List 19 defines the configuration settings for the anti-surge control secondary
PID loop. This PID loop is optional, and must be configured for use using this
parameter list. The configuration parameters for this loop include the following
settings.

• Selection of a process variable (PV) signal for the loop

• Setpoint and associated limits, ramp rates and behaviors

• Control settings (direct/reverse action, CV limits, deadband)

• Loop tuning configuration and values

When this loop has been configured for use, the loop output is available to the
min/max selection for the anti-surge control. The selector chooses the
configured min/max output of primary and secondary ASC PID loop outputs.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 49 - Parameter List 19: ASC Secondary PID Loop
No. Description Range Initial Value User-configured
Value
01 Process Variable Selection. Choices: 0…4 0
0 = Not configured
1 = Q, Compressor Flow (AIN Channel 0)
2 = Ps, Suction Pressure (AIN Channel 1)
3 = Pd, Discharge Pressure (AIN Channel 2)
4 = Aux, Auxiliary Control Signal (AIN Channel 3)
The scaled engineering unit value is used for the PV of the PID loop, and the engineering unit range
of the analog input channel is used for the PID loop PV engineering units.
02 Setpoint (EU). -999999…999999 0
The setpoint for the PID loop. This value can be set here or using the PID loop faceplate. It is
included here to allow it to be saved to the non-volatile memory of the HMI with the other
parameters.
03 Setpoint Tracks PV when Loop is in Manual. Choices: 0 or 1 0
0 = No, Setpoint remains at its last value
1 = Yes, Setpoint tracks the PV value when loop is in manual
04 Setpoint Maximum Limit (EU). -999999…999999 0
Sets the maximum limit for the loop setpoint.
05 Setpoint Minimum Limit (EU). -999999…999999 0
Sets the minimum limit for the loop setpoint.
06 Setpoint Increase Limit (EU/sec). 0…999999 10
Sets the increase ramp rate for the setpoint, in engineering units per second. For example, if set to
0.1, and the SP is changed from 70 to 80 psi, the SP in use will ramp from 70 to 80 at 0.1 psi-per-
second. After 100 seconds, the SP will reach the value of 80 psi.
07 Setpoint Decrease Limit (EU/sec). 0…999999 10
Sets the decrease ramp rate for the setpoint, in engineering units per second. For example, if set to
2 and the SP is changed from 300 to 280 Amps, the SP in use will ramp from 300 down to 280 at 2
Amps-per-second. After 10 seconds, the SP will reach the value of 280.

74 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 49 - Parameter List 19: ASC Secondary PID Loop (Continued)


No. Description Range Initial Value User-configured
Value
08 Proportional Tuning value (Gain). 0…100 1
Tuning value for the proportional action of the PID loop, in units of gain. Gain represents the
percent control value per percent-error. For example, to create a 2% change of output for each %-
error, set the gain to 2. This representation is the reciprocal of proportional band.
09 Proportional Action based on PV or Error. Choices: 0 or 1 1
0 = PV, Proportional action is based on changes in the process variable.
1 = Error, Proportional action is based on error
When based on error, the proportional action responds to changes in setpoint. When based on PV,
the proportional action responds to changes in PV only, and is not affected by setpoint changes.
10 Integral Tuning value (Repeats/minute) 0…100 2
11 Derivative Tuning value (seconds) 0…100 0
12 Interactive Tuning. Choices: 0 or 1 1
0 = Non-Interactive. The proportional gain value does not interact with the integral or derivative
contributions.
1 = Interactive. The proportional gain is used to calculate the integral and derivative contributions.
The setting of 1, “Interactive,” represents the traditional form of PID tuning behavior. In other
words, increasing the gain also increases the integral and derivative contributions.
The setting of 0, “Non-Interactive,” calculates the integral and derivative contributions
independent of the proportional gain. The integral and derivative are calculated as if they have an
effective gain of 1.
13 PID Loop Control Action (a.k.a. Direction). Choices: 0 or 1 1
0 = Reverse Acting
1 = Direct Acting
This parameter determines the direction the output moves in consequence to the direction the PV
moves:
Direct - An increasing PV will cause the output to increase
Reverse - A increasing PV will cause the output to decrease
14 PID Control Value (CV) Maximum Limit (% Open). 0…100 100
The maximum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 100% open, but can be reduced if desired.
15 PID Control Value (CV) Minimum Limit (% Open). 0…100 0
The minimum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 0% open, but can be increased if desired.
16 PID Deadband (EU). 0…999999 0
A deadband in PV engineering units above and below the loop setpoint. When the PV is within the
deadband, the output of the PID loop is held at its present value and not updated.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 75


Chapter 5 SSCC Configuration

20: Capacity Control General Configuration

List 20 defines general properties for capacity control that are independent from
the primary and secondary capacity PID loops. These general configuration
properties are used to define the following settings.

• Capacity device location/representation on Process Overview screen

• Capacity device control value limits

• Capacity device slew rate limits

• Capacity device position deviation alarming

• Capacity PID loop min/max selection

• Capacity PID loop tracking

The following table identifies the configuration parameters, range limits, and
initial values.
Table 50 - Parameter List 20: Capacity Control General Configuration
No. Description Range Initial Value User-configured
Value
01 Capacity PID Loop Output Min/Max Select Type. Choices: 0 or 1 0
0 = Minimum select
1 = Maximum select
02 Not Running Control Value, % Open. 0…100 0
The capacity device is set to this control value whenever the compressor is “Not Running” or
“Unloaded.” This value overrides the PID output values calculated by the primary or secondary
capacity PID loops.
If this value exceeds the min or max CV limits expressed in parameters 7 and 8, the min/max
limited value is used under the “Not Running” or “Unloaded” condition.
03 PID Track Margin, % Open. 0…100 5
When both the primary and secondary capacity PID loops are configured, this value sets the
tracking limit for the PID loop that is not producing the selected output. This keeps the non-
controlling loop from winding up and moving away from the control value by more than a PID track
margin.
For example, PID track margin set to 8%, Select Type is set to minimum, compressor running and
loaded, primary PID loop output is min selected and at 35%, secondary PID loop output is 40% and
increasing. If the secondary loop output increases above 43% (35% + 8%) the secondary output is
limited (tracks) at 43%. If the primary loop output decreases to 32%, the secondary loop tracking
reduces to 40% (32% + 8%).
04 Capacity Device Type and Location. Choices: 0…4 0
0 = Capacity control not required, show no device
1 = Suction valve throttling used for capacity control
2 = Inlet guide vane used for capacity control
3 = Discharge valve throttling used for capacity control
4 = Variable speed used for capacity control
This setting is used to modify the location and representation of the capacity device on the Process
Overview page of the Operator screen.
05 Open Slew Rate, %/sec. 0 …999999 10
Limits the opening rate of the control value.
Normally, the capacity control opening slew rate is set for slow to moderate opening rate.

76 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 50 - Parameter List 20: Capacity Control General Configuration (Continued)


No. Description Range Initial Value User-configured
Value
06 Close Slew Rate %/sec. 0 …999999 10
Limits the closing rate of the control value.
Normally, the capacity control closing slew rate is set for slow to moderate closing rate.
07 Control Value Maximum Limit, % Open. 0…100 100
Sets the maximum limit for the control value for the device.
08 Control Value Minimum Limit, % Open. 0…100 0
Sets the minimum limit for the control value for the device.
09 Valve Fail Direction. Choices: 0 or 1 0
0 = Closed (i.e. Valve is Air-to-Open)
1 = Open (i.e. Valve is Air-to-Close)
Typically, the device is Air-to-Open, and fails closed.
This setting is used to generate the analog output signal direction from the control value which is
always expressed as % open.
10 Device Position Deviation Alarm Deadband, %. 0…100 100
When one of the multi-signal analog input channels is configured for capacity device position
feedback, the controller supports a position deviation alarm. This parameter sets the deadband
limit for the alarm. When the difference between the control value and position feedback exceed
this deadband, the deviation alarm timer is activated.
11 Device Position Deviation Alarm Time, seconds. 0…60 60
This parameter is the preset for the deviation alarm timer. If the position deviation remains active
for this time, the position deviation alarm is generated.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 77


Chapter 5 SSCC Configuration

21: Capacity Primary PID Loop

List 21 defines the configuration settings for the capacity control primary PID
loop. This PID loop is optional, and must be configured for use using this
parameter list. The configuration parameters for this loop include the following
settings.

• Selection of a process variable (PV) signal for the loop

• Setpoint and associated limits, ramp rates and behaviors

• Control settings (direct/reverse action, CV limits, deadband)

• Loop tuning configuration and values

When this loop has been configured for use, the loop output is available to the
min/max selection for the capacity control. The selector chooses the configured
min/max output of primary and secondary capacity PID loop outputs.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 51 - Parameter List 21: Capacity Primary PID Loop
No. Description Range Initial Value User-configured
Value
01 Process Variable Selection. Choices: 0…4 0
0 = Not configured
1 = Q, Compressor Flow (AIN Channel 0)
2 = Ps, Suction Pressure (AIN Channel 1)
3 = Pd, Discharge Pressure (AIN Channel 2)
4 = Aux, Auxiliary Control Signal (AIN Channel 3)
The scaled engineering unit value is used for the PV of the PID loop, and the engineering unit range
of the analog input channel is used for the PID loop PV engineering units.
02 Setpoint (EU). -999999…999999 0
The setpoint for the PID loop. This value can be set here or using the PID loop faceplate. It is
included here to allow it to be saved to the non-volatile memory of the HMI with the other
parameters.
03 Setpoint Tracks PV when Loop is in Manual. Choices: 0 or 1 0
0 = No, Setpoint remains at its last value
1 = Yes, Setpoint tracks the PV value when loop is in manual
04 Setpoint Maximum Limit (EU). -999999…999999 0
Sets the maximum limit for the loop setpoint.
05 Setpoint Minimum Limit (EU). -999999…999999 0
Sets the minimum limit for the loop setpoint.
06 Setpoint Increase Limit (EU/sec). 0…999999 10
Sets the increase ramp rate for the setpoint, in engineering units per second. For example, if set to
0.1, and the SP is changed from 70 to 80 psi, the SP in use will ramp from 70 to 80 at 0.1 psi-per-
second. After 100 seconds, the SP will reach the value of 80 psi.
07 Setpoint Decrease Limit (EU/sec). 0…999999 10
Sets the decrease ramp rate for the setpoint, in engineering units per second. For example, if set to
2 and the SP is changed from 300 to 280 Amps, the SP in use will ramp from 300 down to 280 at 2
Amps-per-second. After 10 seconds, the SP will reach the value of 280.

78 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 51 - Parameter List 21: Capacity Primary PID Loop (Continued)


No. Description Range Initial Value User-configured
Value
08 Proportional Tuning value (Gain). 0…100 1
Tuning value for the proportional action of the PID loop, in units of gain. Gain represents the
percent control value per percent-error. For example, to create a 2% change of output for each %-
error, set the gain to 2. This representation is the reciprocal of proportional band.
09 Proportional Action based on PV or Error. Choices: 0 or 1 1
0 = PV, Proportional action is based on changes in the process variable.
1 = Error, Proportional action is based on error
When based on error, the proportional action responds to changes in setpoint. When based on PV,
the proportional action responds to changes in PV only, and is not affected by setpoint changes.
10 Integral Tuning value (Repeats/minute) 0…100 2
11 Derivative Tuning value (seconds) 0…100 0
12 Interactive Tuning. Choices: 0 or 1 1
0 = Non-Interactive. The proportional gain value does not interact with the integral or derivative
contributions.
1 = Interactive. The proportional gain is used to calculate the integral and derivative contributions.
The setting of 1, “Interactive,” represents the traditional form of PID tuning behavior,. In other
words, increasing the gain also increases the integral and derivative contributions.
The setting of 0, “Non-Interactive,” calculates the integral and derivative contributions
independent of the proportional gain. The integral and derivative are calculated as if they have an
effective gain of 1.
13 PID Loop Control Action (a.k.a. Direction). Choices: 0 or 1 1
0 = Reverse Acting
1 = Direct Acting
This parameter determines the direction the output moves in consequence to the direction the PV
moves:
Direct - An increasing PV will cause the output to increase
Reverse - A increasing PV will cause the output to decrease
14 PID Control Value (CV) Maximum Limit (% Open). 0…100 100
The maximum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 100% open, but can be reduced if desired.
15 PID Control Value (CV) Minimum Limit (% Open). 0…100 0
The minimum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 0% open, but can be increased if desired.
16 PID Deadband (EU). 0…999999 0
A deadband in PV engineering units above and below the loop setpoint. When the PV is within the
deadband, the output of the PID loop is held at its present value and not updated.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 79


Chapter 5 SSCC Configuration

22: Capacity Secondary PID Loop

List 19 defines the configuration settings for the capacity control secondary PID
loop. This PID loop is optional, and must be configured for use using this
parameter list. The configuration parameters for this loop include the following
settings.

• Selection of a process variable (PV) signal for the loop

• Setpoint and associated limits, ramp rates and behaviors

• Control settings (direct/reverse action, CV limits, deadband)

• Loop tuning configuration and values

When this loop has been configured for use, the loop output is available to the
min/max selection for the capacity control. The selector chooses the configured
min/max output of primary and secondary capacity PID loop outputs.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 52 - Parameter List 22: Capacity Secondary PID Loop
No. Description Range Initial Value User-configured
Value
01 Process Variable Selection. Choices: 0…4 0
0 = Not configured
1 = Q, Compressor Flow (AIN Channel 0)
2 = Ps, Suction Pressure (AIN Channel 1)
3 = Pd, Discharge Pressure (AIN Channel 2)
4 = Aux, Auxiliary Control Signal (AIN Channel 3)
The scaled engineering unit value is used for the PV of the PID loop, and the engineering unit range
of the analog input channel is used for the PID loop PV engineering units.
02 Setpoint (EU). -999999…999999 0
The setpoint for the PID loop. This value can be set here or using the PID loop faceplate. It is
included here to allow it to be saved to the non-volatile memory of the HMI with the other
parameters.
03 Setpoint Tracks PV when Loop is in Manual. Choices: 0 or 1 0
0 = No, Setpoint remains at its last value
1 = Yes, Setpoint tracks the PV value when loop is in manual
04 Setpoint Maximum Limit (EU). -999999…999999 0
Sets the maximum limit for the loop setpoint.
05 Setpoint Minimum Limit (EU). -999999…999999 0
Sets the minimum limit for the loop setpoint.
06 Setpoint Increase Limit (EU/sec). 0…999999 10
Sets the increase ramp rate for the setpoint, in engineering units per second. For example, if set to
0.1, and the SP is changed from 70 to 80 psi, the SP in use will ramp from 70 to 80 at 0.1 psi-per-
second. After 100 seconds, the SP will reach the value of 80 psi.
07 Setpoint Decrease Limit (EU/sec). 0…999999 10
Sets the decrease ramp rate for the setpoint, in engineering units per second. For example, if set to
2 and the SP is changed from 300 to 280 Amps, the SP in use will ramp from 300 down to 280 at 2
Amps-per-second. After 10 seconds, the SP will reach the value of 280.

80 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Table 52 - Parameter List 22: Capacity Secondary PID Loop (Continued)


No. Description Range Initial Value User-configured
Value
08 Proportional Tuning value (Gain). 0…100 1
Tuning value for the proportional action of the PID loop, in units of gain. Gain represents the
percent control value per percent-error. For example, to create a 2% change of output for each %-
error, set the gain to 2. This representation is the reciprocal of proportional band.
09 Proportional Action based on PV or Error. Choices: 0 or 1 1
0 = PV, Proportional action is based on changes in the process variable.
1 = Error, Proportional action is based on error
When based on error, the proportional action responds to changes in setpoint. When based on PV,
the proportional action responds to changes in PV only, and is not affected by setpoint changes.
10 Integral Tuning value (Repeats/minute) 0…100 2
11 Derivative Tuning value (seconds) 0…100 0
12 Interactive Tuning. Choices: 0 or 1 1
0 = Non-Interactive. The proportional gain value does not interact with the integral or derivative
contributions.
1 = Interactive. The proportional gain is used to calculate the integral and derivative contributions.
The setting of 1, “Interactive,” represents the traditional form of PID tuning behavior. In other
words increasing the gain also increases the integral and derivative contributions.
The setting of 0, “Non-Interactive,” calculates the integral and derivative contributions
independent of the proportional gain. The integral and derivative are calculated as if they have an
effective gain of 1.
13 PID Loop Control Action (a.k.a. Direction). Choices: 0 or 1 1
0 = Reverse Acting
1 = Direct Acting
This parameter determines the direction the output moves in consequence to the direction the PV
moves:
Direct - An increasing PV will cause the output to increase
Reverse - A increasing PV will cause the output to decrease
14 PID Control Value (CV) Maximum Limit (% Open). 0…100 100
The maximum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 100% open, but can be reduced if desired.
15 PID Control Value (CV) Minimum Limit (% Open). 0…100 0
The minimum limit imposed on the control value (output) calculated by the PID loop. Normally set
to 0% open, but can be increased if desired.
16 PID Deadband (EU). 0…999999 0
A deadband in PV engineering units above and below the loop setpoint. When the PV is within the
deadband, the output of the PID loop is held at its present value and not updated.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 81


Chapter 5 SSCC Configuration

23: Anti-Surge - Capacity Decoupling Configuration

List 23 defines the configuration settings used for decoupling the anti-surge and
capacity controls. The following decoupling features are available.

• Useful when anti-surge control and capacity control are configured in the
SSCC. If capacity control is not configured, these settings can be ignored.

• Management of the anti-surge and capacity controls so they do not “fight”


each other at operating points near the control limit line.

• At operating points between the specified initiate and release points, the
capacity control action is held, so the capacity controller does not drive the
compressor to surge.

• This decoupling method allows the anti-surge controller to stabilize flow


first, and then release the capacity control for further action when safe to
do so.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 53 - Parameter List 23: Anti-Surge – Capacity Decoupling Configuration
No. Description Range Initial Value User-configured
Value
01 Use Decoupling. Choices: 0 or 1 0
0 = No, do not use decoupling methods.
1 = Yes, use the decoupling methods
02 Decoupling Initiate Point, DP1. -100…0 -3
This value defines the distance below the control limit line where decoupling action is Initiated.
When the operating point moves below the control limit line by this distance, the capacity control
output will be held.
The value of DP1 should be further from 0 than DP2.
In other words, DP1 < DP2 < 0.0
03 Decoupling Release Point, DP2. -100…0 -1
This value defines the distance below the control limit line where decoupling action is released.
When the operating point moves within this distance of the control limit line, the decoupling
action is released, and the capacity control output is free to move normally.
The value of DP2 should be closer to 0 than DP1.
In other words, DP1 < DP2 < 0.0

82 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

24: AINs - Substitute PV

List 24 defines whether to allow or dis-allow the use of substitute PV for each
analog input channel. Substitute PV mode allows the user to override the actual
measured and scaled analog input value with a substitute process value entered by
the user.

The configuration setting for use of substitute PV mode is configured as one of


the following values.
0 = Allow Substitute PV mode to be used
1 = Dis-Allow Substitute PV mode

The following table identifies the configuration parameters, range limits, and
initial values.
Table 54 - Parameter List 24: AINs – Substitute PV
No. Description Range Initial Value User-configured
Value
01 Compressor Flow, Q (AIN channel 0) 0 or 1 0
02 Suction Pressure, Ps (AIN channel 1) 0 or 1 0
03 Discharge Pressure, Pd (AIN channel 2) 0 or 1 0
04 Auxiliary Control Signal, AuxCntrlSig (AIN channel 3) 0 or 1 0
05 Suction Temperature, Ts, (AIN channel 4) 0 or 1 0
06 Discharge Temperature, Td (AIN channel 5) 0 or 1 0
07 Multi-Use Signal A, (AIN channel 6) 0 or 1 0
08 Multi-Use Signal B, (AIN channel 7) 0 or 1 0

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 83


Chapter 5 SSCC Configuration

25: DINs - Substitute PV

List 24 defines whether to allow or dis-allow the use of substitute PV for each
digital input channel. Substitute PV mode allows the user to override the actual
measured digital input value with a substitute process value entered by the user.

The configuration setting for use of substitute PV mode is configured as: one of
the following values:

0 = Allow Substitute PV mode to be used

1 = Dis-Allow Substitute PV mode

The following table identifies the configuration parameters, range limits, and
initial values.
Table 55 - Parameter List 25: DINs – Substitute PV
No. Description Range Initial Value User-configured
Value
01 Compressor Run (DIN channel 0) 0 or 1 0
02 Reset Push Button (DIN channel 1) 0 or 1 0
03 Load Push Button (DIN channel 2) 0 or 1 0
04 Unload Push Button (DIN channel 3) 0 or 1 0
05 External Ready-to-Start 1 (DIN channel 8) 0 or 1 0
06 External Ready-to-Start 2 (DIN channel 9) 0 or 1 0
07 External Ready-to-Start 3 (DIN channel 10) 0 or 1 0
08 External Ready-to-Start 4 (DIN channel 11) 0 or 1 0
09 External Compressor Trip 1 (DIN channel 12) 0 or 1 0
10 External Compressor Trip 2 (DIN channel 13) 0 or 1 0
11 External Compressor Trip 3 (DIN channel 14) 0 or 1 0
12 External Compressor Trip 4 (DIN channel 15) 0 or 1 0

26: Reserved for Future Use


List 26 is not implemented on the HMI and is reserved for future use.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 56 - Parameter List 26: Reserved for Future Use
No. Description Range Initial Value User-configured
Value
NA This parameter list is not implemented on the HMI, and is reserved for future u.se NA NA

84 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

27: Interlock Bypassable Configuration

List 27 contains the bypassable configuration for each of the interlocks for the
compressor. When an interlock is configured as bypassable and bypasses are
enabled, the interlock is bypassed and will not initiate the compressor trip.

Normally, the Interlock Configuration pop-up screen is used to set the interlock
bypassable configuration. This parameter list is intended to allow this bypassable
configuration to be saved to the non-volatile file memory of the HMI.

For each interlock, the bypassable configuration choice is 0 or 1.

0 = Not Bypassable

1 = Bypassable.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 57 - Parameter List 27: Interlock Bypassable Configuration
No. Description Range Initial Value User-configured
Value
01 Multiple Surge Trip. 0 or 1 0
02 Operating Point Fault. 0 or 1 0
03 Spare Interlocks. Choices: 0 or 1 0
04 These six Interlock positions are not presently used in the SSCC application.
05
06
07
08
09 External Compressor Trip 1. 0 or 1 0
10 External Compressor Trip 2. 0 or 1 0
11 External Compressor Trip 3. 0 or 1 0
12 External Compressor Trip 4. 0 or 1 0
13 Spare Interlocks. 0 or 1 0
14 These four Interlock positions are not presently used in the SSCC application.
15
16

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 85


Chapter 5 SSCC Configuration

28: Permissive Bypassable Configuration

List 27 contains the bypassable configuration for each of the permissives for the
compressor. When a permissive is configured as bypassable and bypasses are
enabled, the permissive is bypassed and will not affect the ready-to-start
condition.

Normally, the Permissive Configuration pop-up screen is used to set the


permissive bypassable configuration. This parameter list is intended to allow this
Bypassable configuration to be saved to the non-volatile file memory of the HMI.

For each permissive, the bypassable configuration choice is 0 or 1:.

0 = Not Bypassable

1 = Bypassable.

The following table identifies the configuration parameters, range limits, and
initial values.
Table 58 - Parameter List 28: Permissive Bypassable Configuration
No. Description Range Initial Value User-configured
Value
01 Control Loops Ready. 0 or 1 0
02 Anti-Surge Valve Ready. 0 or 1 0
03 Capacity Valve/Inlet Guide Vane Ready. 0 or 1 0
04 Spare Permissive. 0 or 1 0
These four Interlock positions are not presently used in the SSCC application.
05 Digital Inputs OK. 0 or 1 0
06 Analog Inputs OK. 0 or 1 0
07 Digital Outputs OK. 0 or 1 0
08 Analog Outputs OK. 0 or 1 0
09 External Ready-to-Start 1. 0 or 1 0
10 External Ready-to-Start 2. 0 or 1 0
11 External Ready-to-Start 3. 0 or 1 0
12 External Ready-to-Start 4. 0 or 1 0
13 Spare Permissives. 0 or 1 0
14 These four permissive positions are not presently used in the SSCC application.
15
16

86 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

29: Modbus Serial Port Configuration

List 29 defines the settings used for the Modbus serial port configuration. These
parameters are used for the following settings.

• Set the slave ID and register scaling configuration

• Set the serial port baud rate and parity

• Read back the serial port baud rate and parity

The following table identifies the configuration parameters, range limits, and
initial values.
Table 59 - Parameter List 29: Modbus Serial Port Configuration
No. Description Range Initial Value User-configured
Value
01 Slave ID. 1…254 1
The slave ID number identifies the controller number on a Modbus multi-drop serial link. Each
controller on the multi-drop link has a unique slave ID.
02 Register Scaling Range. 1000…32767 32767
The internal engineering unit values in the controller are scaled to this integer range for sending
over the Modbus protocol. Refer to Modbus Holding Registers on page 160 for details on the
engineering unit ranges for Modbus variables.
03 Baud Rate Configuration. 110, 300, 600, 1200, 2400, 19200
Enter the desired baud rate for the Modbus serial port. Use parameter 7 of this list to trigger setting 4800, 9600, 19200, or 38400
the port to this baud rate.
04 Parity Configuration. 0 = No Parity
Enter the code to the right for the desired parity for the Modbus serial port. Use parameter 7 of this 1 = Odd Parity
list to trigger setting the port to this parity. 2 = Even Parity
05 Baud Rate Readback. 110, 300, 600, 1200, 2400, 0
Leave the value of this parameter set to 0 (read only parameter). 4800, 9600, 19200, or 38400
The CURR column reads back the actual baud rate in use on the controller.
06 Parity Readback. 0 = No Parity 0
Leave the value of this parameter set to 0 (read only parameter). 1 = Odd Parity
The CURR column reads back the actual parity in use on the controller. 2 = Even Parity
07 Set Port Configuration. 0 or 1 0
Set this value to 1 to trigger setting the serial port.
Note: The controller always clears this value after setting the port, so the CURR column will always
read back a 0 value.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 87


Chapter 5 SSCC Configuration

30: Application (HMI Configuration)

List 30 defines key properties for the HMI application. These parameters are
used for the following settings.

• The maximum number of pages to support on various HMI screens

• To permit or deny the use of interlock/permissive bypasses for the system

The following table identifies the configuration parameters, range limits, and
initial values.
Table 60 - Parameter List 30: Application (HMI-related Configuration)
No. Description Range Initial Value User-configured
Value
01 Maximum Operator Screens 0…8 6
Sets the number of pages for the Operator screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
02 Maximum Maintenance Screens 0…8 3
Sets the number of pages for the Maintenance screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
03 Maximum Warning Screens 0…8 2
Sets the number of pages for the Warnings screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
04 Maximum Interlocks Screens 0…8 2
Sets the number of pages for the Interlocks screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
05 Maximum Permissives Screens 0…8 2
Sets the number of pages for the Permissives screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
06 Maximum Help Screens 0…8 8
Sets the number of pages for the Operator screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
07 Maximum Status Screens 0…8 3
Sets the number of pages for the Hardware Status screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
08 Maximum IO Cards 0…8 4
Sets the number of IO modules presented in the IO module selector Hardware Status screen.
DO NOT CHANGE UNLESS ADVISED BY FACTORY.
09 Bypass Enable. Choices: 0 or 1 0
0 = Disable
1 = Enable
This parameter is presented in the list, so that the current status of bypass enable/disable can be
saved to the non-volatile file memory for archive.
To enable and disable the bypasses, parameter 10 must be set to 1, and then use the Enable and
Disable buttons on the Maintenance screen.
10 Has Bypass. Choices: 0 or 1 0
0 = No, Hide the Bypass Enable/Disable buttons on the HMI
1 = Yes, Present Bypass Enable/Disable buttons on the Maintenance screen of the HMI
If you want to configure and allow bypassing of interlocks and permissives on the HMI, then this
parameter must be set to 1.

88 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Parameter List Configuration Parameter lists are configured using the Parameter Configuration screen on the
HMI. Follow these steps to access the parameter lists on the Parameter
Configuration screen.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

3. Press to page forward, or to page backward, as required to


navigate to page one of the Maintenance screen (shown here).

4. Press to open the Parameter Configuration pop-up screen (shown


here).

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 89


Chapter 5 SSCC Configuration

Parameter Configuration Screen Overview


Table 61 - Parameter Configuration Screen
Display Features (see Figure 9 for the location of these features):
• Parameter list selector
• Parameter list action buttons
• Parameter details table
• Parameter list action status (For example: Restore successful)
Operational Features:
• Press to the right of the Select field to choose a parameter list.

• Press to update the parameter details table - security privilege required (O, S, M, E, or A).

• Press to upload values from the controller and store them in the HMI file memory – security privilege required (E, or A).

• Press to download values from HMI file memory to the controller – security privilege required (E, or A).

• Press to save parameter value changes entered from the HMI to the HMI file memory – security privilege required (E, or
A).

• Press or to the right of the parameter details table to choose a parameter.

• Press to the right of the parameter details table to edit the value for a selected parameter – security privilege required (E,
or A). This opens the on-screen keypad for data entry.

Figure 9 - Parameter Configuration Screen Components

Parameter List Action Status

Close Button

Parameter List Selector List Selector Buttons

Scroll Up Button
Parameter Details Table
Edit Parameter Button

Scroll Down Button

90 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Parameter List Actions

The functions performed when using the parameter list action buttons are
illustrated in Figure 10 and explained in detail in Table 62.

Figure 10 - Parameter List Action Details

Select List

Edit
Parameter

Save
Restore Restore HMI
Non-Volatile
Upload
Controller File Memory

Download

Table 62 - Parameter List Actions Details


Button Action Security Operation Performed on the Selected Parameter
Restore O, S, M, E, or A Updates the Parameter Details table screen values:
• Parameter names are read from the HMI file memory.
• CURR value is read from the controller (read once, not continuous).
• FILE value is read from the HMI file memory.
Upload E or A Reads values from the controller and stores them in the HMI file memory.
• Clicking Upload does not update screen values.
• After an upload, click Restore to view uploaded values on the screen.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 91


Chapter 5 SSCC Configuration

Table 62 - Parameter List Actions Details (Continued)


Button Action Security Operation Performed on the Selected Parameter
Download E or A Writes values from the HMI file memory to the controller.
• Clicking the Download button does not write values from the screen to the controller and does not read values from the
controller (doesn’t update CURR column).
• If you have modified values on the screen using Edit Parameter, then use Save before a download.
• After a download use Restore to update CURR values from the controller.
Save E or A Saves all the screen values for the current parameter list to the HMI file memory. This function is normally used after making
changes using Edit Parameter.
• Does not save CURR values (from the controller) to the HMI file memory.
• If you want to save controller values to the HMI file memory, use Upload.
Edit Parameter E or A Modifies the value presented on screen in the FILE column.
• Does not change the value in the Controller.
• Does not change the value in the HMI file memory.
• After making changes using Edit Parameter, use Save to write the changed parameter values to the HMI file memory.

When working with the parameter lists, you will typically complete a sequence of
actions to accomplish the desired task. Use the following table to identify the task
you want to complete and the recommended sequence of actions.

What Task Do You Want to Accomplish? Recommended Action Sequence


I want to view parameter configuration settings. 1. Select the desired parameter list.
2. Click Restore to update the parameter table.
3. Scroll as required to view parameter values.
I want to configure parameters for a new system. For each parameter list:
1. Select the desired parameter list.
2. Click Restore to update the parameter table on the screen.
3. For each parameter in the list, click Edit Parameter to set the desired value.
4. Click Save to save the configuration to the HMI file memory.
5. Click Download to download the configuration to the controller.
6. Click Restore to confirm the controller values.
I want to modify settings currently in use in the present Is your compressor running?
controller. • Yes: You cannot use the Parameter Configuration screen to make changes. Instead, you can use the device
faceplates on the HMI to change many configuration parameters.
• No: Perform the following steps:
1. Select a parameter list.
2. Click Restore to update the parameter table.
3. Review the table to determine if the parameter you want to change in this list. If so continue, if not
return to step 1.
4. Click Upload to read the controller values to the HMI file memory.
5. Click Restore to update the parameter table (FILE column is updated from the Upload).
6. Scroll to the parameter(s) you want to change, enter the desired value, and click Edit Parameter.
7. Click Save to save the changes to the HMI file memory.
8. Click Download to download the configuration to the controller.
9. Click Restore to confirm the controller parameter values.

92 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

What Task Do You Want to Accomplish? Recommended Action Sequence


I have changed settings in the controller using device faceplates Is your compressor running?
on the HMI. Now I want to save the controller values to the HMI • Yes: Wait until the compressor stops.
file memory.
• No: Complete the following steps:
For each parameter list:
1. Select the desired parameter list.
2. Click Upload to upload the controller values to the HMI file memory.
3. Optional: Click Restore to update the parameter table values on the HMI screen. You can verify that
the CURR and FILE values now match.
I have replaced my controller, and it is loaded with the default If you have replaced the controller, you may need to re-activate the HMI. Refer to Activate the HMI on page 25.
SSCC Logix application and settings.
If your HMI is successfully activated, follow these steps for each parameter list:
All my configured settings are saved in the HMI file memory. 1. Select the desired parameter list.
2. Click Restore to display the contents of the list on the HMI screen.
I want to apply all my settings in the HMI to the controller.
3. Review the list, checking that the FILE column has the intended values.
4. Click Download to download the values to the controller.
5. Click Restore to refresh the list on the screen.
6. Review and confirm that the CURR values (from the controller) now match the FILE values (from the HMI file
memory).
All my settings are saved in the HMI file memory. I want to make In order to make an archive copy to a compact flash memory card, the normal HMI color graphics must be shut
an archive copy to a compact flash memory card. down to allow access the PanelView Plus file utilities. During this time, the HMI will be unavailable for compressor
operation.

Follow these steps to shut down the HMI graphics – security privilege will be required.
1. Navigate to page 1 of the Maintenance screen.

2. Press to display the Hardware Status screen.

3. Scroll to page 3 f the Hardware Status screen for PanelView maintenance.

4. Press to shutdown the HMI graphics.

Consult the PanelView Plus user manual for details on accessing the file utilities to copy the HMI application file to
your compact flash card.

Interlock and Permissive The SSCC system has pre-allocated input signals for use as interlocks and
permissives for the compressor. These signals appear in the Interlocks and
Customization Permissive screens with initial names which may be customized. Interlock
Configuration and Permissive Configuration screens allow for customizing these
signals.

Follow these steps to navigate to the Maintenance screen, and open the Interlocks
Configuration or Permissives Configuration screen.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 93


Chapter 5 SSCC Configuration

3. Press to page forward, or to page backward, as required to


navigate to page one of the Maintenance screen (shown here).

4. Press or to open the desired Configuration pop-up screen


(example Permissive Configuration screen shown here).

Note: The Configuration buttons always contain a lock symbol, as some of their
configuration features (invert and latched) are set in the system design and
cannot be changed.

Interlock Configuration Screen

The Interlock Configuration screen has two pages. Page 1 contains interlocks
internal to the SSCC controller; page 2 contains interlocks external to the
controller. Use the screen navigation arrow keys at the bottom to navigate
between the two pages.

Figure 11 - Interlock Configuration Screens with Default Settings

94 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Configuration Chapter 5

Customizing Interlocks

From the configuration screen, you can edit the interlock description. These
represent string tags in the HMI (not the controller). These tags are retentive and
saved in the HMI memory.

You are encouraged to customize the external interlock descriptions on page 2, to


provide a more functional description. For example, you may connect a lube oil
low pressure switch interlock, and therefore change the associated interlock
description (e.g. “Low Lube Oil Press”). Editing the description requires security
privileges (Engineer or Administrator). The description string tag limit is 20
characters.

Configuring Interlock Bypasses

Each interlock has a configuration option for “Bypassable.”The bypassable setting


on this screen is the same as that configured in parameter List 27: Interlock
Bypassable Configuration. Changing the bypassable setting requires security
privileges (Engineer or Administrator).

An interlock is bypassed when:

1. The interlock is configured as “Bypassable,” and


2. Bypass is enabled on the Maintenance screen.

Permissive Configuration Screen

The Permissive Configuration screen has two pages. Page 1 contains permissives
internal to the SSCC controller; page 2 contains permissives external to the
controller. Use the screen navigation arrow keys at the bottom to navigate
between the two pages.

Figure 12 - Persmissive Configuration Screens with Default Settings

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 95


Chapter 5 SSCC Configuration

Customizing Permissives

From the configuration screen, you may edit the permissive descriptions. These
represent string Tags in the HMI (not the controller). These tags are retentive
and saved in the HMI memory.

You are encouraged to customize the external permissive descriptions on page 2,


to provide a more functional description. For example, you may connect a Lube
Oil Auxiliary Pump Running permissive, and therefore change the associated
permissive description (e.g. “Aux Lube Pump Run”). Editing the description
requires security privileges (Engineer or Administrator). The description string
tag limit is 20 characters.

Configuring Permissive Bypasses

Each permissive has a configuration option for “Bypassable.” The bypassable


setting on this screen is the same as that configured in parameter list 28:
Permissives Bypassable Configuration. Changing the bypassable setting requires
security privileges (Engineer or Administrator).

A permissive is bypassed when:

1. The permissive is configured as “Bypassable,” and


2. Bypass is enabled on the Maintenance screen.

96 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 6

SSCC Operation

This section provides details for the main Operation screens and guides you
through the process of putting the SSCC in operation.

Operation Screen Details The main Operator screen has many visualization features that are based on
choices made during configuration. This section provides details about these
features.

Compressor Overview
The Compressor Overview is page 2 of the Operator screen. This screen provides
a process diagram overview of the compressor and the configured
instrumentation. Key features for anti-surge control are represented in the
following illustration.

Figure 13 - Compressor Overview Page

Discharge Transmitters
• Pressure, Pd
Suction Transmitters • Temperature, Td
• Pressure, Ps • Flow, Qd, Qdd, Qalt
• Temperature, Ts (based on configuration)
• Flow, Qs
(based on configuration) Unit Status Indications

Load / Unload Buttons


Anti-surge Control
Distance Between OP and CLL Optional Signals
• Dist < 0.0 ASC Valve Opening • Auxiliary Control PV
• Dist ~ 0.0 ASC on Control Limit Line • Incipient Surge Signal
• Dist > 0.0 ASC Valve Closing (based on configuration)

Anti-surge Control Valve


• Recycle
• Blow-off
(based on configuration)

CV: Control Valve


Pos: Position Feedback (if configured)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 97


Chapter 6 SSCC Operation

The suction and discharge transmitters presented on the screen are based on the
individual analog input channel configuration options. The units displayed for
each transmitter (default “EU” shown) follow the unit string customization
available on the analog input device faceplates.

The algorithm for anti-surge control calculates the operating point (OP). The
instrumentation requirements are based on the type of flow measurement
configured. These requirements are reflected in the following table.
Flow Configuration Suction Transmitters Discharge Transmitters
Pressure, Ps Temperature, Ts Pressure, Pd Temperature, Td

Flow in Suction Required Optional Required Optional

Flow in Discharge, Required Optional Required Optional


no coolers

Flow in Discharge, Required Required Required Required


downstream of coolers

Alternate measurement Required Optional Required Optional

Unit Status Indicators

The unit status indicators along the right side of the page reflect key operational
controls/indications and correspond to the unit’s digital outputs. The indications
presented on the screen are detailed in Table 63.
Table 63 - Unit Status Indicator Descriptions
Status Digital Output Status Indicator and Description
Ready Ready to Start, DO channel 3 Not Ready-to-Start, check permissives
Ready-to-Start, all permissives OK
Trip Comp Trip Interlock, DO channel 0 Not Tripped, all interlocks OK
Compressor Trip, check interlocks
Surge Surge Alarm, DO channel 1 Normal, no surge alarm
Surge alarm activated
Run Compressor Running, DO channel 4 Not Running, no Run condition detected
Confirmed Run determination
Load Compressor Loaded, DO channel 5 Unloaded, valves at override CV value
Loaded, valves released for control
Trouble System Trouble Alarm, DO channel 2 Normal
System trouble, hardware or device fault

98 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Load / Unload Control Buttons

The Load and Unload buttons provide both control and indication of the control
mode for the compressor. When unloaded, the SSCC drives the control valves to
their configured override position. When loaded, the SSCC is allowed to control
the valves based on the configured PID regulatory controls. The load/unload
modes and indications are detailed in Table 64.
Table 64 - Load / Unload Control Button Descriptions and Operations
Buttons Indication Description Button Operation Available
Unload mode – Valve control set to None, security privilege required (O, S, M or E).
override CV value
Load mode – Valve control released for None, security privilege required (O, S, M or E).
regulatory control
Unload mode – Valve control set to Press to switch to Load mode.
override CV value
Load mode – Valve control released for Press to switch to Unload mode.
regulatory control

Capacity Control Visualization

When capacity control is configured, the capacity control type is visualized on


the Compressor Overview page. The various capacity configuration options and
visualization arrangements are detailed in the following illustrations.

Figure 14 - Capacity Control Type: Suction Throttling Example

CV: Control Valve, % Open


Pos: Position Fdbk (if configured)

Figure 15 - Capacity Control Type: Inlet Guide Vanes Example

CV: Control Valve, % Open


Pos: Position Fdbk (if configured)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 99


Chapter 6 SSCC Operation

Figure 16 - Capacity Control Type: Discharge Throttling Example

CV: Control Valve, % Open


Pos: Position Fdbk (if configured)

Figure 17 - Capacity Control Type: Speed Setpoint to Speed Controller Example

CV: Speed Setpoint, where:


0% = Minimum Governor
100% = Maximum Governor

100 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Compressor Map

The Compressor Map is page 3 of the Operator screen. It provides a dynamic X-Y
plot for the compressor map, key anti-surge calculated values (head, OP, SLL,
CLL, SCL, and margin) and summary status for the anti-surge and capacity
control signals. Key features of the Compressor Map page are represented in the
following illustration.

Figure 18 - Compressor Map Page Example

Dynamic Compressor Map


Y-Axis: Compressor Head
Anti-surge
X-Axis: Normalized Flow, %(Q/QMAX)2 Control
SLL: Surge Limit Line (red)
Summary
CLL: Control Limit Line (green)
SCL: Surge Control Line (blue)
OP: Operating Point (yellow point) Capacity
Control
Anti-Surge Control Summary
Distance between OP and CLL
Dist < 0.0 ASC Valve Opening
Dist ~ 0.0 ASC on Control Limit Line
Dist > 0.0 ASC Valve Closing

Anti-surge Controls
CV to Anti-surge Valve
Primary PID (Control vs. Tracking)
PID Loop Output Control Value
Secondary PID (Control vs. Tracking)
PID Loop Output Control Value
(visible when loop(s) are configured)

Capacity Controls
CV to Capacity Valve/Device
Primary PID (Control vs. Tracking)
PID Loop Output Control Value
Secondary PID (Control vs. Tracking)
PID Loop Output Control Value
(visible when loop(s) are configured)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 101


Chapter 6 SSCC Operation

Dynamic Compressor Map

The dynamic compressor map provides real-time presentation of the surge limit
line, control limit line, surge control limit line (OP tracking), and the live
operating point. This visualization provides a clear view of where the compressor
is operating relative to surge and control limits, and how much margin is in use.

Further details of the compressor map are shown in the following illustration.

Figure 19 - Dynamic Compressor Map Example

Y-Axis: Compressor Head Surge Limit Line (SLL)


Scale is configured Red line, 10-segment,
automatically based on values plotted from the configured
for Surge Line. Surge Line values.

X-Axis: Normalized Flow Control Limit Line (CLL)


Scale is fixed at 0...100% Green line, shaped the
(Q/QMAX)2 same as the SLL and
shifted to the right by the
Total Margin in use.

Margin

Compressor Running Operating Point (OP)


Anti-surge control along the Yellow point, plotted at:
control line limit X = OP value
Y = Head value

Head

OP
Compressor Running Surge Control Line (SCL)
Anti-surge valve closed, Blue line, shaped the same
OP tracking safely to the right as the SLL, tracks the OP by
of the control limit line. the OP track margin.

Head

SLL value
CLL value

SCL value
OP value
OP Track Margin

102 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Margin Control

For the primary anti-surge PID, the setpoint is dynamic based on operating
conditions and is automatically generated by the functional components of the
algorithm. The operator does not directly enter the setpoint. However, the
operator can influence the setpoint through adjustment of the margin. Margin
adjustments are managed on the Margin Control page four of the Operator
screen.

Key features of the Margin Control page are represented in the following
illustration.

Figure 20 - Compressor Map Page Example


Base Margins
• The minimum limit for
the In Use values Margin Increment /
Decrement buttons
Maximum Margin • Adjusts the In Use values
• Maximum limit for In
Use, and Total Margin Adjustment amount for
increment/decrement
In Use Margins
• Values in use, after Adjustment type
increment/decrement
determines which margin
Total Margin Results component(s) to adjust:
• Contributions for offset 1 = Offset Margin only
and percent 2 = Percent Margin only
3 = Both Offset and
Percent Margin

Surge Limit Line Surge Limit Line Surge Limit Line


Control Limit Line Control Limit Line Control Limit Line

Offset Margin Only + Percent Margin Only = Offset and Percent Margin
Same margin for all Margin varies: Total Margin varies:
operating conditions. 0 at minimum conditions. Offset value at minimum
Increases with SLL. conditions. Increases with SLL as
operating conditions increase.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 103


Chapter 6 SSCC Operation

Margin Configuration
The Margin Control page provides access to certain margin configuration
properties from the configuration parameter list 13: Surge and Margin
Configuration. A cross reference between the operator page and the parameter
list is included here.
Screen Configuration Item Security Parameter List Cross Reference
List 13: Surge and Margin Configuration
Offset Margin M, E or A 01: Base Offset Margin (%)
Percent Margin M, E or A 02: Base Percent Margin (%)
Maximum Margin M, E or A 03: Max Margin Limit (%)
Adjust Amount M, E or A 04: Margin Adj Amount (%)
Adjust Type M, E or A 05: Adj (1=Ofst, 2=Pct, 3=Both)

Margin Increment / Decrement

The anti-surge algorithm automatically increments the margin “in use” values
whenever a surge is detected. The margin “in use” values may also be manually
adjusted using and on the screen – security privilege required (O,
S. M, E, or A). The adjustment amount and type are applied to these increments
and decrements. The margins cannot be decremented less than the configured
base margins, and cannot be incremented larger than the maximum margin limit.

Anti-Surge Control PID Loops Overview

Anti-surge control is provided through a primary PID loop configured to control


the operating point relative to the surge control line. In addition, a secondary
PID loop can be optionally configured, often based on suction pressure or
discharge pressure.

Page 5 of the Operator screen provides an overview of these two anti-surge


control PID loops.

Figure 21 - Operator Screen Page 5 Example

Configurable Secondary PID Loop


Primary Loop Pre-configured • Faceplate (configured)
• OP is the PV, SCL is the SP • Blank Panel (not configured)
• PV signal type

Common Faceplate Features:


• PV value, units, and bar graph
• SP value and slider indication
• CV value and bar graph

• Control / Track indication

• PID button to access Loop


Faceplate detail

104 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

There are no direct operation features on this page. To operate or tune the loops,
press to open the individual PID loop faceplate. More details on the PID
faceplate are provided later in this chapter.

These two PID loop are managed together through a min/max selector, control
override selector, and a control limiter to create a final control value for the anti-
surge control valve. These control features are illustrated in the following
function diagram.
Tripped
Running AND
Load

ASC Primary
PID Loop Control AO Control
Limiter
OP PV Min/Max Override
Selector Selector
Slew Rates AO To Valve
SCL SP Select
Fdbk CV CV1 CVmin From
Override
False CVmax HMI Oper CV
CV
CV2 2 CV True CV CV Prog CV
ASC Secondary
Configurable:
PID Loop Control/Track
Q, Ps, Pd, or
AuxCtrlPV PV Feedback
CV
From HMI SP CV1 Fdbk1
Fdbk CV CV2 Fdbk2

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 105


Chapter 6 SSCC Operation

Capacity Control PID Loops Overview

Capacity control is provided through two optional PID loops, each configurable
for the choice of process variable to control. Typically one PV would be the
primary control measure, and a secondary control measure might be considered
for an override controller. For instance, the primary capacity control measure may
be discharge pressure (for example, Pd on AIN channel 2). A secondary override
control may be required to limit power or amps on an electric motor driving the
compressor. The auxiliary control PV input (AIN channel 3) would be
connected to this measurement.

Page 6 of the Operator screen provides an overview of these two capacity control
PID loops.

Figure 22 - Operator Screen Page 6 Example

Configurable Primary and Secondary


PID Loops
• Faceplates (configured)
Common Faceplate features:
• PV value, units, and bar graph • Blank Panels (not configured)
• SP value and slider indication • PV signal type
• CV value and bar graph

• Control / Track indication

• PID button to access loop


faceplate detail

There are no direct operation features on this page. To operate or tune the loops,
use the PID button to open the individual PID loop faceplate. More details
on the PID faceplate are provided later in this chapter.

These two PID loop are managed together through a min/max selector,
decoupler, control override selector, and a control limiter to create a final control
value for the capacity control valve/device. These control features are illustrated
in the following function diagram.

106 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Tripped
Running AND
Load
Capacity
Primary PID
Configurable: Control AO Control
Loop
Q, Ps, Pd, or Limiter
AuxCtrlPV PV Min / Max Override
Selector Selector
Slew Rates AO To Device
From HMI SP Select
Override From
Fdbk CV CV1 False CVmin
CV HMI
CVmax Oper CV
Capacity CV2 CV Decouple True CV CV Prog CV
Configurable: Secondary PID
Loop OP
Q, Ps, Pd, or Control / Track
AuxCtrlPV PV CLL Feedback
CV
From HMI SP CV1 Fdbk1
Fdbk CV CV2 Fdbk2

Checking Interlocks, Interlocks and permissives should be cleared prior to a compressor startup. An
interlock is a condition that needs to be normal or healthy in order to operate;
Permissives, and Warnings while a permissive is a condition that needs to be healthy for the Ready-to-Start
condition, but once the compressor is running the healthy condition can be lost
without affecting the system.

A warning brings attention to an item that may prevent operation or reflect


disabled/bypassed functionality of the unit.

Before attempting to start the compressor, the operator should check and
understand all interlock, permissive and warnings present for the unit.

Interlocks

The overall unit interlock status is presented on the Interlock icon (third from
the right) displayed on the navigation toolbar of any main screen.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 107


Chapter 6 SSCC Operation

The five icon status indications for interlocks are described in this table.

Interlock Icon Interlock Status Compressor Trip Output State


All interlocks are healthy. Normal – Healthy
Bypass is not enabled (no yellow caution symbol)

Interlocks status is unhealthy. Tripped


Bypass is not enabled (no yellow caution symbol)

All interlocks are healthy. Normal – Healthy


Bypass is enabled (yellow caution symbol)

All non-bypassed interlocks are healthy Normal – Healthy


One or more bypassed interlocks are unhealthy
Bypass is enabled (yellow caution symbol)
Interlock status is unhealthy Tripped
Bypass is enabled (yellow caution symbol)

To check the status of the individual interlocks, press on the toolbar to open
the Interlock screen.

Figure 23 - Interlock Screen, Both Pages – All Healthy

The Interlock screen has two pages. Use the screen navigation arrow keys at the
bottom to navigate between the two pages.

108 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

On the Interlock screen, each interlock has a visual status indication to identify
whether the interlock is Normal/Tripped, Bypassed, or First-Out. This table
explains these visual indications.

Visual Indication Example Explanation


The green check mark indicates the interlock status is normal-healthy.

The red “X” indicates the interlock has tripped and latched.
The interlock was not the first-out interlock.
Once tripped, this indication remains until an interlock reset.
The red “X” indicates the interlock has tripped and latched.
The yellow highlight indicates the interlock is the first-out.
Once tripped, this indication remains until an interlock reset.
The yellow highlight indicates the interlock was first-out.
The check mark indicates the interlock status is normal after the interlock
reset was performed.
The yellow highlight remains until all interlocks are normal and reset.
The grey appearance indicates the interlock is bypassed.
The check mark indicates the interlock status is normal.
The grey appearance indicates the interlock is bypassed.
The “X” indicates the interlock status is tripped.

Table 65 provides an explanation of each interlock.


Table 65 - Description of Interlocks
Interlock Explanation
Multiple Surge Trip A number of surges have occurred within a defined period of time.
It would be unsafe to continue operation of the compressor.
The reason for the surges should be investigated.
Operating Point Fault The calculation for the compressor operating point (OP) has faulted.
This may be due to invalid configuration, or failed transmitters that are
necessary to determine the operating point.
External Comp Trip 1 The external compressor trip signal on the associated DIN channel has tripped.
External Comp Trip 2 The external compressor trip signal on the associated DIN channel has tripped.
External Comp Trip 3 The external compressor trip signal on the associated DIN channel has tripped.
External Comp Trip 4 The external compressor trip signal on the associated DIN channel has tripped.

Note: The name presented on the screen for each interlock is configurable. The
default names are presented in the above table. You are encouraged to customize
the names for the external interlocks to provide a more meaningful name
presented for the interlock signal.

Latching Interlocks and Interlock Reset

The status indications for interlocks are latching. This traps any transitory
interlocks that occurred on the system so they can be presented on the Interlocks
screen.

When a tripped interlock has returned to normal it must be reset by pressing the
interlock reset button on either page of the Interlock screen.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 109


Chapter 6 SSCC Operation

The availability to perform the interlock reset is represented by its appearance on


the screen.

Button Interlock Reset Availability


Appearance
Interlock reset action not available due to:
• There are no tripped interlocks
• All tripped interlock indications remain tripped (not returned to normal yet).
• Security privilege is required.
Interlock reset action is available:
• Security privilege has been met (operator, supervisor, maintenance, engineer, or administrator).
• One or more tripped interlocks has returned to normal.

Check and Reset an Interlock Example

The following sequence provides an example of how to check and reset


interlocks.

Interlock Status Indications Observations and Actions


The Interlock icon status indicates tripped interlocks.
Press the Interlock icon to open the Interlocks screen.

On page 2 of the Interlocks screen, two of the external


interlocks are shown tripped.
• External Comp Trip 4 was first-out
• External Comp Trip 1 also tripped.
The appearance of the interlock Reset button indicates
that reset is not available.
• Assume that the operator is logged in.
• The interlocks are still tripped.

A while later, the interlock reset button is available,


indicating one or more of the tripped interlocks can be
reset.
Press the interlock Reset button.

110 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Interlock Status Indications Observations and Actions


After the interlock has been reset:
• External Comp Trip 4 is normal (check mark). Yellow
highlight still informs user that it was the first-out.
• External Comp Trip 1 remains tripped (red X).
The interlock Reset button is unavailable (waiting for
External Comp Trip 1 to return to normal).

A while later, the interlock Reset button is available,


indicating that the remaining tripped interlock can be
reset.
Press the interlock Reset button.

All interlocks are normal.


The unit level interlock status indication on the toolbar
is normal.
The interlock Reset button is dimmed (there are no
tripped interlocks remaining).

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 111


Chapter 6 SSCC Operation

Permissives

The overall unit permissive status is presented on the Permissives icon (second
from the right) displayed on the navigation toolbar of any main screen.

The five icon status indications for permissives are described in this table.

Permissive Explanation of Interlock Status Compressor Ready-To-


Icon Start Output
All permissives healthy. Ready
Bypass is not enabled (no yellow caution symbol)

Permissives status is unhealthy. Not Ready


Bypass is not enabled (no yellow caution symbol)

All permissives are healthy. Ready


Bypass is enabled (yellow caution symbol)

All non-bypassed permissives are healthy Ready


One or more bypassed permissives are unhealthy
Bypass is enabled (yellow caution symbol)
Permissives status is unhealthy Not Ready
Bypass is enabled (yellow caution symbol)

To check the status of the individual permissives, press the Permissive icon on the
navigation toolbar to open the Permissive screen.

Figure 24 - Permissive Screen, Pages 1 and 2 – All Healthy

The Permissives screen has two pages. Use the screen navigation arrow keys at the
bottom to navigate between the two pages.

112 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

On the Permissives screen, each permissive has a visual status indication to


identify whether the permissive is Ready/Not-Ready, Bypassed, or First-Out.
This table explains these visual indications.

Visual Indication Example Explanation


The green check mark indicates that the permissive status is Ready.

The red “X” indicates the permissive is Not Ready.


The permissive was not the First-Out permissive.
The red “X” indicates the permissive is Not Ready.
The yellow highlight indicates the permissive is the First-Out.
The yellow highlight indicates the permissive was First-Out.
The check mark indicates the permissive status has returned to Ready.
The yellow highlight remains until all permissives have returned to Ready.
The grey appearance indicates the permissive is Bypassed.
The check mark indicates the permissive status is Ready.
The grey appearance indicates the permissive is Bypassed.
The “X” indicates the permissive status is Not Ready.

Table 66 provides an explanation of each permissive.


Table 66 - Description of Permissives
Permissive Explanation
Control Loops Ready Ready when all the PID loops configured for use are in the Auto mode.
AntiSurge Vlv Ready Ready when the anti-surge control value and position feedback signals are
within position deviation limits.
If anti-surge position feedback signal is not configured, this permissive is always
Ready.
Capacity/IGV Ready Ready when the capacity control value and position feedback signals are within
position deviation limits.
If capacity control feedback signal is not configured, this permissive is always
Ready.
Digital Inputs OK Ready when the digital input module slot is healthy.
Analog Inputs OK Ready when analog input module slot is healthy and all configured AIN channels
are within range limits (no under-range or over-range conditions).
Digital Outputs OK Ready when all digital output channels are in Program mode and the digital
output module slot is healthy.
Analog Outputs OK Ready when all analog output channels are in Program mode and the analog
output module slot is healthy.
External Ready To Start 1 Ready when the associated external DIN signal is in the Ready state.
If the DIN is not configured for use, the status is always Ready.
External Ready To Start 2 Ready when the associated external DIN signal is in the Ready state.
If the DIN is not configured for use, the status is always Ready.
External Ready To Start 3 Ready when the associated external DIN signal is in the Ready state.
If the DIN is not configured for use, the status is always Ready.
External Ready To Start 4 Ready when the associated external DIN signal is in the Ready state.
If the DIN is not configured for use, the status is always Ready.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 113


Chapter 6 SSCC Operation

Note: The name presented on the screen for each permissive is configurable. The
default names are presented in the above table. You are encouraged to customize
the names for the external Ready-To-Start permissives to provide a more
meaningful name presented for the permissive signal.

Permissive Reset

The status indications for permissive are non-latching. The Ready status (green
check-mark) and Not-Ready status (red X) automatically update to show the
present condition of the permissive.

Since the permissives do not latch, it is not necessary to use the permissive Reset
button on the Permissive screen.

Check and Reset a Permissive Example

The following sequence provides an example of checking permissive indications.

Permissive status Indications Observations and Actions


The unit permissive status on the navigation toolbar
informs the user that:
• Permissives are not-ready (red diamond)
• Bypass is enabled (yellow caution triangle)
Press the Permissive Icon to open the Permissives
screen.
On page 1 of the Permissives screen:
Digital outputs OK is not ready. This could be because:
• A digital output is not in Program mode
• The digital output module slot is not healthy

Investigating the digital outputs revealed a digital


output channel was in Operator mode. The channel
was returned to Program mode.
As a result, the unit permissive status on the
navigation toolbar now indicates:
• All non-bypassed permissives OK (yellow square).

114 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Permissive status Indications Observations and Actions


Re-examining the permissives status:
On page 1, all permissives are ready.

On page 2, the external ready to start 2 permissive is


not ready, but the dimmed appearance indicates the
signal is bypassed.
Because it is bypassed, this permissive is not required
to be ready.
The compressor ready-to-start output signal is ready.

Warnings

The overall unit warnings status is presented on the Warnings button (fourth
from the left) displayed on the navigation toolbar of any main screen.

The three icon status indications for warnings are described in this table.

Warnings Icon Explanation of Warning status Recommended Action


No warnings present None Required

Level 1: Preventing operation Check Warning screen, page 1

Level 2: Function disabled or bypassed Check Warning screen, page 2

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 115


Chapter 6 SSCC Operation

To check the status of the individual warnings, press the Warnings button on the
navigation toolbar to open the Warnings screen.

Figure 25 - Warnings Screens – Examples

The Warnings screen has two pages. Use the screen navigation arrow keys at the
bottom to navigate between the two pages.

On the Warnings screen, each warning has a visual status indication. This table
explains these visual indications.

Warning – Visual Indication Example Explanation


Normal, no warning condition (no color indication)

Level 1 warning condition exists (orange color)

Level 2 warning condition exists (yellow color)

Table 67 provides an explanation of each warning.


Table 67 - Descriptions of Warnings
Warning Explanation
Not Logged In Default user - No security privileges.
Log into HMI to obtain desired level of access.
Head Calc Config Error Configuration parameters required for compressor head calculation are
invalid.
Check relevant configuration settings and correct as required.
OP Calc Config Error Configuration parameters required for compressor operating point
calculation are invalid.
Check relevant configuration settings and correct as required.
Surge Map Config Error Configuration parameters required for compressor surge map are
invalid.
Check relevant configuration settings and correct as required.
Interlock and Permissive Bypassed Bypasses are enabled for interlocks and permissives.
Check interlocks and permissives to familiarize which functions may be
bypassed.
Digital Input in Substitute PV mode One or more digital input channels in substitute PV mode.
System will not respond to the relevant field input device(s).

116 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 67 - Descriptions of Warnings (Continued)


Warning Explanation
Analog Input in Substitute PV mode One or more analog input channels in substitute PV mode.
System will not respond to actual field transmitter signal(s).
Fallback to fixed polytropic exponent A failed transmitter exists which prevents the system from calculating a
polytropic exponent from actual pressure and temperature
measurements.
A fixed polytropic exponent calculation is used f(k, Peff). This may
affect the accuracy of the head calculation.
Surge Test: ASC mode protection bypassed Surge test is enabled, bypassing the normal protection limits for
Manual mode operation of the anti-surge primary PID loop.
In this condition, it is possible to drive the compressor into surge by
operating the ASC primary PID loop in Manual mode.

Check and Reset a Warning Example

The following sequence provides an example of checking warning indications.

Screen Indications Observations and Actions


The unit warning status on the navigation toolbar
informs the user that:
- Warnings are present (yellow)
Press the Warnings icon to open the Warnings screen.
Page 1: Preventing Operation - No warnings

Page 2: Function Disabled/ Bypassed - warning


Analog input in Substitute mode indicates that one or
more of the configured analog input channels is using a
substitute PV, bypassing the actual input PV from the
transmitter.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 117


Chapter 6 SSCC Operation

Screen Indications Observations and Actions


Navigation to the Maintenance/Configuration Screen
Using the Device Operation & Settings selector field to
browse the analog input devices:
Compressor Flow
Suction Pressure
Discharge Pressure
Auxiliary Control Signal
Suction Temperature
Discharge Temperature
Multi-Use Signal A
MultiUse Signal B

Through browsing the analog input devices, it is


observed that the suction pressure input is in Substitute
PV mode.
Check with operations and maintenance to identify if it
is safe to operate the unit in this condition.

Compressor Start and Stop The SSCC is primarily responsible for anti-surge and capacity control for the
compressor. Typically another controller or interlock system is used to start and
stop the drive (motor, turbine, etc.) that turns the compressor.

The SSCC provides interface I/O to coordinate the following signals with the
drive controller.

• Ready-to-start digital output signal to the drive controller. This signal is


controlled based on the unit permissive status.

• Compressor trip digital output signal to the drive controller. This signal is
controlled based on the unit interlock status.

• Compressor running digital input signal from the drive controller.

The compressor state of operation is influenced by the interlocks (trip),


permissives (ready-to-start), running determination, and load/unload requests.

It is highly recommended that alarms or warnings be cleared before starting the


compressor. The toolbar icons for alarm and warning should be white indicating
that none of these categories has active items.

118 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

ATTENTION: Do not attempt to start the compressor if the unit’s configuration


has not been completed. All relevant configuration parameters discussed in this
chapter must be properly configured. Failure to do so may cause equipment
damage or personal injury.

ATTENTION: Visual confirmation of the anti-surge valve position and capacity


valve position is recommended before starting the compressor. Failure to do so
may cause equipment damage or personal injury.

When the compressor is ready to start, the Compressor Overview screen should
appear as shown in Figure 26.

Figure 26 - Compressor Overview – Ready to Start

The following key indications are present when the compressor is ready to start.
Indication Description
Alarm Status Alarms clear
If alarms are present, they have been checked, understood, and operations
ready to proceed.
Warning Status No warnings
If warnings are present, they have been checked, understood, and operations
ready to proceed.
Interlock Status Interlocks OK, or all non-bypassed OK.

Compressor trip output, Not-Tripped


Permissive Status Permissives – Ready, or all non-bypassed – Ready

Ready-to-Start output, Ready


ASC Valve Anti-surge valve CV at pre-start override value.
Capacity Valve/Device Capacity valve/device CV at pre-start override value.
(if configured)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 119


Chapter 6 SSCC Operation

Compressor Running Compressor running condition is determined by one or more of the following
conditions.
Determination
• Compressor running digital input status

• Compressor head calculation > threshold

• Auxiliary control signal > threshold

When one of the above conditions is met for the configured on-delay time, then a
confirmed compressor running status is determined.

These specific running determination methods are configured in 14: Run and
Load Configuration on page 68.

The confirmed compressor running status is annunciated on the Compressor


Overview - Operator (page 2) screen. In addition to this HMI annunciation, the
compressor running digital output (DOUT channel 4) is energized for external
indication/usage.

Figure 27 - Compressor Overview – Running Status

Once reaching the running state the compressor is ready for loading.

120 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Compressor Load/Unload After the compressor running condition is established and there are no
compressor trip conditions, the compressor is available to load. Loading the
compressor can be accomplished in one of the following ways, based on
configured options.

• Auto-load on confirmed run - Load is automatically triggered after the


confirmed running condition described previously.

• Load push-button - Digital input channel 2 may be wired to an external


push button to manually request compressor load.

• Load button on HMI - Load button on Compressor Overview - Operator


screen is pressed to manually request compressor load.

The confirmed compressor load status is annunciated on the Compressor


Overview - Operator screen (page 2). In addition to this HMI annunciation, the
compressor loaded digital output (DOUT channel 5) is energized for external
indication/usage.

Once the compressor is set to load, the anti-surge and capacity valve/devices are
released from their respective override values, and available for regulatory control
by the configured anti-surge and capacity control PID functions.

Figure 28 - Compressor Overview – Compressor Loaded Status

The Operator screens and PID faceplates can now be used to control and adjust
the operating behavior of the compressor.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 121


Chapter 6 SSCC Operation

Device Faceplates The HMI provides several device faceplates to operate and configure devices.
The following tables provide an overview of these device faceplates and their
features.
Table 68 - Analog Input Device Faceplate
Tab Sample Screen Description
Analog Input Device Faceplate – Operator tab
Display Features:
• Banner with device name
• Bar graph display of PV value in use
• High and low alarm value setpoint values, and level
indicators on bar graph
• Indicators for Over-range, Under-range, IO Fault, and
Channel Not Configured For Use when conditions are
present
• Visual indication of Input PV or Substitute PV modes
Input PV Mode
Operational Features:
• Use Mode select buttons to choose between PV
from input, or Substitute PV mode - security privilege
required (M, E, or A).
• In Substitute PV mode, enter the substitute PV value -
security privilege required (M, E, or A).

Substitute PV Mode
Analog Input Device Faceplate – Configuration tab
Display Features:
• Configuration parameter values viewable regardless of
security privilege

Configuration Features:
• Customize the device name, and unit of measure strings -
security privilege required (E or A).
• Configure engineering unit scaling - security privilege
required (E or A).
• Configure alarm settings - security privilege required (E or
A)

122 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 69 - Analog Output Device Faceplate


Tab Sample Screen Description
Analog Output Device Faceplate – Operator tab
Display Features:
• Banner with device name
• Bar graph display of CV value in use
• Valve position feedback value (when configured)
• Indicator for IO Fault when condition present
• Visual indication of Program or Operator modes

Operational Features:
Program Mode
• Use and to choose between Program and
Operator mode - security privilege required (O, S, M, or E).
• In Operator mode, enter the manual CV value - security
privilege required (O, S, M, or E).

Operator Mode
Analog Output Device Faceplate – Configuration tab
Display Features:
• Configuration parameter values viewable regardless of
security privilege
Configuration Features:

• Customize the device name, and unit of measure strings -


security privilege required (E or A).
• Other configurable properties for reference only. Some
available from compressor details device faceplate.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 123


Chapter 6 SSCC Operation

Table 70 - Digital Input Device Faceplate


Tab Sample Screen Description
Digital Input Device Faceplate – Operator tab
Display Features:
• Banner with device name
• Device state represented with descriptive word
• Indicators for IO Fault, and Channel Not Configured For
Use when conditions present
• Visual indication of Input PV or Substitute PV modes

Operational Features:
Input PV Mode • Use to choose between PV from Input, or
Substitute PV mode - security privilege required (M, E, or
A).
• In Substitute PV mode, use state buttons to set substitute
PV state - security privilege required (M, E, or A).

Substitute PV Mode
Digital Input Device Faceplate – Configuration tab
Display Features:
• Configuration parameter values viewable regardless of
security privilege

Configuration Features:
• Customize the device name - security privilege required (E
or A).
• Configure channel usage, active state, and use of
Substitute PV mode - security privilege required (E or A).

124 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 71 - Digital Output Device Faceplate


Tab Sample Screen Description
Digital Output Device Faceplate – Operator tab
Display Features:
• Banner with device name
• Indication of device state; Activated or Deactivated
• Indicator for IO Fault when condition present
• Visual indication of Program or Operator modes

Operational Features:

• Use and to choose between Program and


Program Mode Operator mode - security privilege required (O, S, M or E).

• In Operator mode, use and to set output


value - security privilege required (O, S, M or E).

Operator Mode
Digital Output Device Faceplate – Configuration tab
Display Features:
• Configuration parameter values viewable regardless of
security privilege

Configuration Features:
• Customize the device name - security privilege required (E
or A).
• Configure device operation/fail state.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 125


Chapter 6 SSCC Operation

Table 72 - PID Loop Faceplate


Tab Sample Screen Description
PID Loop Faceplate – Operator tab
Display Features:
• Banner with loop name
• Indication of Loop mode
• Values for SP, PV, CV
• Vertical bar graph of PV with setpoint slider
• Horizontal bar graph of CV
• Visual indication of Program or Operator modes

Auto Mode Operational Features:


• Use to choose between Auto and Manual mode - security
privilege required (O, S, M, or E).
• In Auto mode, use SP value entry - security privilege
required (O, S, M, or E).
• In Manual mode, use CV value entry - security privilege
required (O, S, M, or E).

Manual Mode
PID Loop Faceplate – Configuration/Tuning tab
Display Features:
• Configuration parameter values viewable regardless of
security privilege

Configuration Features:
• Customize the loop name and units for PV and CV -
security privilege required (E or A).
• Adaptive tuning parameters (ASC primary PID loop)
• Standard tuning parameters (other PID loops)
Anti-Surge Primary PID Loop • Setpoint configuration parameters (other PID loops)

Other PID Loops

126 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 73 - Compressor Details Faceplate


Tab Sample Screen Description
Compressor Details Faceplate – Head tab
Configuration Features:
• Head calculation properties - security privilege required
(E or A).
• Pressures and temperatures in absolute units.
• Head calculation values .
• Head calc configuration error indications if present.

Compressor Details Faceplate – Base Conditions tab


Configuration Features:
• Flow element location type.
• Flow element configuration (base press and temp, max
flow for normalization) - security privilege required (E or
A).
• Compressor base configuration (base press and temp, gas
properties) - security privilege required (E or A).
• IGV method configuration - security privilege required (E
or A).
• OP calc configuration error indications if present.
Compressor Details Faceplate – Map tab
Configuration Features:
• Compressor map surge limit line configuration - security
privilege required (E or A).
• Map configuration error indications if present.

Compressor Details Faceplate – OP Tracking / Decoupling tab


Configuration Features:
• OP tracking tuning properties - security privilege required
(M, E, or A).
• Decoupling tuning properties - security privilege required
(M, E, or A).
• Use decoupling configuration property - security privilege
required (E or A).
• Decoupling status.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 127


Chapter 6 SSCC Operation

Table 73 - Compressor Details Faceplate (Continued)


Tab Sample Screen Description
Compressor Details Faceplate – Anti-Surge / Capacity Valve
tab
Configuration Features:
• Anti-surge valve configuration properties (slew rates,
control limits, position deviation alarm settings) - security
privilege required (M, E, or A).
• Capacity calve / IGV configuration properties (slew rates,
control limits, position deviation alarm settings) - security
privilege required (M, E, or A).

Compressor Details Faceplate – Surge Configuration tab


Configuration Features:
• Multi-surge trip configuration properties - security
privilege required (E or A).
• Rate-of-change and positional surge properties - security
privilege required (M, E, or A).

Operational Features:
• Press the reset button to reset the compressor surge
counter - security privilege required (E, or A).
Compressor Details Faceplate – Surge Test tab
Display Features:
• Surge testing status and configuration.
• Live/Trapped operational data from surge test.

Operational Features:

• Activate and Deactivate surge test buttons -


security privilege required (E, or A).
• Choose from positional, rate-of-change, and incipient
surge methods for surge test capture - security privilege
required (E or A).

• Press to reset surge test data - security privilege


required (E or A).

Accessing Device Faceplates

The device faceplates provide graphical detail of both operational and


configurable features for a particular I/O device, PID loop, or the compressor
details.

To access the faceplates within the HMI, follow these steps to navigate to the
Maintenance screen, and successfully open the faceplate of choice.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

128 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

3. Press to page forward, or to page backward, as required to


navigate to page one of the Maintenance screen (shown here).

4. Press to select the device you want to access in the Device


Operation & Settings selector list at the bottom of the screen.

5. Press to open the selected device faceplate.

Accessing the PID Faceplates from the Operator Screen

For convenience, the PID faceplates and the compressor details faceplate can be
accessed from certain Operator screens. Follow these steps to access the PID
faceplates.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the main navigation toolbar to navigate to the Operator


screen.

3. Press to page forward, or to page backward, as required to


navigate to the Operator screen, Anti-Surge PID Overview (page 5), or the
Capacity PID Overview screen (page 6), shown here.

Note, only those PID loops that are configured will be shown on these
screens.

4. Press to open the desired PID faceplate.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 129


Chapter 6 SSCC Operation

Accessing the Compressor Details Faceplates from the Operator Screen

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the main navigation toolbar to navigate to the Operator


screen.

3. Press to page forward, or to page backward, as required to


navigate to the Operator screen - Compressor Map Overview (page 3),
shown here.

4. Press to open the Compressor Details faceplate.

Device Names and Device Selector

The Device Operation & Settings (device) selector on the Maintenance screen
presents the devices by the device name. From the device faceplates the names can
be customized, and even made blank. If after customization the device names are
changed and it becomes difficult to identify the devices presented in the device
selector, the following list can be helpful to re-orient and identify the devices.

The device selector presents the devices in a pre-determined order. The order and
default names for each device are shown in Table 74 on page 131.

Each time you navigate to the Maintenance screen from another main screen, the
device order resets to the start of the list at the device allocated for compressor
flow.

130 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 74 - Order of Devices on the Device Selector


Order Device Name (default) Description of Device
1 Compressor Flow AIN channel 0, allocated for Compressor Flow
2 Suction Pressure AIN channel 1, allocated for Suction Pressure
3 Discharge Pressure AIN channel 2, allocated for Discharge Pressure
4 Auxiliary Control PV Signal AIN channel 3, allocated for an additional process transmitter which can be
used as a PV for control loops.
5 Suction Temperature AIN channel 4, allocated for Suction Temperature
6 Discharge Temperature AIN channel 5, allocated for Discharge Temperature
7 Multi-Signal A AIN channel 6, configurable usage
8 Multi-Signal B AIN channel 7, configurable usage
9 Antisurge Control valve AOUT channel 0, allocated for Anti-Surge Valve
10 Capacity Control valve AOUT channel 1, allocated for Capacity control device
11 Compressor Run DI DIN channel 0, allocated for Compressor Run input from the drive system
12 Reset Push Button DIN channel 1, allocated for external Reset P.B.
13 Load Request Push Button DIN channel 2, allocated for external Load P.B.
14 Unload Request Push Button DIN channel 3, allocated for external Unload P.B.
15 External Ready To Start 1 DIN channel 8, allocated for Ready To Start 1, a Permissive
16 External Ready To Start 2 DIN channel 9, allocated for Ready To Start 2, a Permissive
17 External Ready To Start 3 DIN channel 10, allocated for Ready To Start 3, a Permissive
18 External Ready To Start 4 DIN channel 11, allocated for Ready To Start 4, a Permissive
19 External Compressor Trip 1 DIN channel 12, allocated for Compressor Trip 1, an Interlock
20 External Compressor Trip 2 DIN channel 13, allocated for Compressor Trip 2, an Interlock
21 External Compressor Trip 3 DIN channel 14, allocated for Compressor Trip 3, an Interlock
22 External Compressor Trip 4 DIN channel 15, allocated for Compressor Trip 4, an Interlock
23 Compressor Trip DO DOUT channel 0, allocated for Compressor Trip Interlock signal to the drive
controller.
24 Surge Alarm DOUT channel 1, allocated for optional Surge Alarm status indication
25 System Trouble DOUT channel 2, allocated for optional System Trouble status indication
26 Ready To Start DO DOUT channel 3, allocated for Ready To Start Permissive signal to the drive
controller
27 Compressor Running DO DOUT channel 4, allocated for optional Compressor Running status indication
28 Compressor Loaded DOUT channel 5, allocated for optional Compressor Loaded status indication
29 AntiSurge Primary Loop Anti-Surge Primary PID Loop, allocated to pre-configured algorithm to
control Operating Point (OP) as PV relative to Surge Control Line (SCL) as the
SP. Controls the Anti-Surge valve.
30 AntiSurge Secondary Loop Optional Anti-Surge Secondary PID Loop. Configurable PV choice. Used as
over-ride PID in a Max select arrangement with the Anti-Surge Primary PID
Loop.
31 Capacity Primary Loop Optional Capacity Primary PID Loop. Configurable PV choice. Controls the
Capacity control valve / IGV.
32 Capacity Secondary Loop Optional Capacity Secondary PID Loop. Configurable PV choice. Use as over-
ride PID in a Min/Max select arrangement with the Capacity Primary PID
Loop.
33 Compressor Details Compressor configuration and information details popup.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 131


Chapter 6 SSCC Operation

Analog Input Device Faceplate

The Analog Input Device faceplate provides a graphical interface to the


operational and configurable behaviors of the analog input channels.

Analog Input Device Operation

Press to display the Operations page. The following illustration details the
features of the Device Operation page.

Figure 29 - Analog Input Faceplate – Operations Page

Channel Not Configured Indicator Close Screen

Device Name
Over-range indicator Hi Alarm Limit
PV Value in Use
Channel Fault indicator Unit of Measure

Under-range indicator Lo Alarm Limit

Mode Operation

Engineering Unit Scale Substitute PV value


Input Signal raw count (0…10000)

The analog input device supports two modes of operation: 1) PV from Input,
and 2) Substitute PV.

Under normal operations, the mode should be PV from Input. This mode uses
the measured input signal raw count (0…10000), and converts it to engineering
units according to the configured scaling settings. The scaled value is presented as
the process value (PV) in use.

Substitute PV mode lets you to override the measured value, and substitute in its
place, a desired engineering unit value. This mode may be useful should a
transmitter fail, require maintenance, or calibration. Use of Substitute PV mode
produces a warning.

Through configuration (refer to parameter list 24: AINs - Substitute PV) the use
of Substitute PV mode can be disallowed. When disallowed, the Substitute PV
features are absent from the device operation graphic and the device mode will be
PV from Input.

The mode operation buttons and Substitute PV value entry require security
privileges (maintenance, engineer, or administrator).

132 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

When the device is in PV from Input mode, the Substitute PV value


automatically tracks the scaled PV value. This makes the transition to Substitute
PV mode bumpless.

Analog Input Device Configuration

Press to display the Configuration page. Many of the analog input channel
configuration parameters may be adjusted on this page.

Figure 30 - Analog Input Faceplate – Configuration Page

Close Screen

Edit Device Name

Scaling Configuration

Edit Units of Measure

Alarm Configuration

Table 75 lists the configuration items displayed on the Analog Input Faceplate -
Configuration page and the corresponding parameter used for configuration.
The parameters listed in the table are contained in the 01: AIN - Compressor
Flow parameter list.
Table 75 - Analog Input Faceplate to Parameter Cross Reference
Faceplate Configuration Item Configuration Parameter
Scaled EU - Maximum 02: Eng Unit Scale Max (EU)
Scaled EU - Minimum 03: Eng Unit Scale Min (EU)
Has Extend Scaling (check box) 05: Extrap Scaling (1=Yes)
Square Root Extract (check box) 04: Scaling (0=Linear, 1=Sqrt)
Has Hi Alarm (check box) 07: Has Alarm High (1=Yes)
Has Lo Alarm (check box) 08: Has Alarm Low (1=Yes)
Hi Alarm Limit (value) 09: High Alarm Limit (EU)
Lo Alarm Limit (value) 10: Low Alarm Limit (EU)
Alarm DB 11: Alarm Deadband (EU)

Customize the Channel

From the device configuration, you may edit the description, and the units of
measure. These represent string tags in the HMI (not the controller). These tags
are retentive and saved in the HMI memory. For example, you may want to
include the device tag number in the description (for example: “FT-1007
Compressor Flow”), and set the units of measure (for example: “acfm”).

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 133


Chapter 6 SSCC Operation

String Tag limits are:


Description: 34 characters
Unit of Measure: 6 characters

Analog Output Device Faceplate

The Analog Output Device faceplate provides a graphical interface to the


operational and configurable behaviors of the analog output channels.

Analog Output Device Operation

Press to display the Operations page. The following illustration details the
features of the Device Operation page.

Figure 31 - Analog Output Faceplate – Operations Page

Close Screen

Device Name
Mode control button
Channel Fault
Mode status indication indicator

Position Feedback CV In Use & Units


(if configured)

Operator CV value

The analog output device supports two modes of operation: 1) Program, and 2)
Operator.

Under normal operations, the mode should be Program. In Program mode the
application program and interlocks determine the control value (CV) in use.
When the device is in Program mode, the operator CV value automatically tracks
the CV value in use. This makes the transition to Operator mode bumpless.

Operator mode is intended only for device maintenance and testing when the
compressor is not running. When in Operator mode, the operator CV value can
be entered from the screen. Use of Operator mode sets the permissive, analog
outputs OK, to Not-Ready.

When the compressor is running, the device mode is automatically set to


Program mode, and the Mode control button is not available. When the
compressor is not running, the mode control button is presented on the screen.

134 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Current Mode Mode Button Button Action


Program None The compressor is running, mode change not available.
Program Pressing the button switches the mode to Operator.

Operator Pressing the button switches the mode to Program.

The mode operation buttons and operator CV value entry require security
privileges (operator, supervisor, maintenance, or engineer).

Analog Output Device Configuration

Press to display the Configuration page. Configuration parameters relating


to the valve devices can be observed on this page. Note, these configuration
parameters are not changed on this page. See Table 76.

Figure 32 - Analog Output Faceplate – Configuration Page

Close Screen

Edit Device Name

Control Valve
Configuration
Properties
Edit Units

Position Alarm
Configuration
Properties

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 135


Chapter 6 SSCC Operation

Table 76 lists the configuration items displayed on the Analog Output Faceplate -
Configuration page and the corresponding parameter lists and parameter
numbers used for configuration.
Table 76 - Analog Output Faceplate Configuration Parameter List Cross Reference
Faceplate Configuration Item Parameter List / Parameter
CV Range – Maximum None, set in logic, 100.0% Open
CV Range – Minimum None, set in logic, 0.0% Open
Fail Open (check box) Anti-Surge Valve Capacity Valve / IGV
List: 15, Parameter: 10 List: 20, Parameter: 09
Valve Fail: (0=Clsd,1-Opn) Valve Fail: (0=Clsd,1-Opn)
Has Low Res AO (check box) None, not used
Has Position Feedback (check box) None, set in logic based on Multi-Sig AIN usage for position feedback
signals.
Position Deviation DB Anti-Surge Valve Capacity Valve / IGV
List: 15, Parameter: 11 List: 20, Parameter: 10
Pos Dev Alm DB (%) Pos Dev Alm DB (%)
Deviation Minimum Duration (Sec) Anti-Surge Valve Capacity Valve / IGV
List: 15, Parameter: 12 List: 20, Parameter: 11
Pos Dev Alm Time (sec) Pos Dev Alm Time (sec)

Customize the Channel


From the device configuration, you may edit the description, and the units of
measure. These represent string tags in the HMI (not the controller). These tags
are retentive and saved in the HMI memory. For example, you may want to
include the device tag number in the description (for example: “FCV-1007
AntiSurge Valve”), and set the units of measure (for example: “% Open”).
String Tag limits are:
Description: 34 characters
Unit of Measure: 6 characters

136 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Digital Input Device Faceplate

The Digital Input Device faceplate provides a graphical interface to the


operational and configurable behaviors of the digital input channels.

Digital Input Device Operation

Press to display the Operations page. The following illustration details the
features of the Device Operation page.

Figure 33 - Digital Input Faceplate – Operations Page

Channel Not Configured Indicator Close Screen

Device Name

Channel Fault Indicator PV Value in Use

Input Signal State Mode Operation

Substitute PV Control

The digital input device supports two modes of operation: 1) PV from Input, and
2) Substitute PV.

Under normal operations, the mode should be PV from Input. This mode uses
the actual input signal applying the configured input state. The value is presented
as the process value (PV) in use.

Substitute PV mode allows the user to override the input value, and substitute in
its place, the desired value. This mode may be useful should a device fail, require
maintenance, or troubleshooting. Use of Substitute PV mode produces a
warning.

Through configuration (refer to parameter list 25: DINs - Substitute PV) the use
of Substitute PV mode can be disallowed. When disallowed, the substitute PV
features are absent from the device operation graphic and the device mode will be
PV from Input.

The mode operation buttons and substitute PV value buttons require security
privileges (maintenance, engineer, or administrator).

When the device is in PV from Input mode, the substitute PV value


automatically tracks the scaled PV value. This makes the transition to Substitute
PV mode bumpless.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 137


Chapter 6 SSCC Operation

Digital Input Device Configuration

Press to display the Configuration page. Many of the digital input channel
configuration parameters may be adjusted on this page.

Figure 34 - Digital Input Faceplate – Configuration Page

Close Screen

Edit Device Name


Disallow
Channel Configuration Substitute PV
mode

Table 77 lists the configuration items displayed on the Digital Input Faceplate -
Configuration page and the corresponding parameter lists and parameter
numbers used for configuration.
Table 77 - Digital Input Faceplate Configuration Parameter List Cross Reference
Faceplate Configuration Item Parameter List / Parameter
Disallow Substitute PV List: 25: DINs, subst PV (0=Allow, 1=DisAllow)
Parameter: various, individual per channel
DI = 1 = Active Status List: 09: Digital Input Channel Configuration
Parameter: various, individual per channel
Use This Signal List: 09: Digital Input Channel Configuration
Parameter: various, individual per channel

Customize the Channel

From the device configuration, you may edit the description. This represents a
string tag in the HMI (not the controller). This tag is retentive and saved in the
HMI memory. For example, you may want to include the device tag number in
the description and identify the signal more clearly (for example: “PSL-1014 Low
Lube Oil Pressure”).

String Tag limits are:

Description: 34 characters

138 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Digital Output Device Faceplate

The Digital Output Device faceplate provides a graphical interface to the


operational and configurable behaviors of the digital output channels.

Digital Output Device Operation

Press to display the Operations page. The following illustration details the
features of the Device Operation page.

Figure 35 - Digital Output Faceplate – Operations Page

Close Screen

Device Name
Mode Control Button

Mode Status Indication Channel Fault


Indicator
Control Value in Use

Operator Control Buttons

The digital output device supports two modes of operation: 1) Program, and 2)
Operator.

Under normal operations, the mode should be Program. In Program mode the
application program and interlocks determine the control value (CV) in use.
When the device is in Program mode, the operator CV value automatically tracks
the CV value in use. This makes the transition to Operator mode bumpless.

Operator mode is intended only for device maintenance and testing when the
compressor is not running. When in Operator mode, the operator control
buttons can be used to set the control value. Use of Operator mode sets the
permissive, digital outputs OK, to not-ready.

When the compressor is running, the device mode is automatically set to


Program mode, and the mode control button is not available. When the
compressor is not running, the mode control button is presented on the screen.

Current Mode Mode Button Button Action


Program None The compressor is running, mode change not available.
Program Pressing the button switches the mode to Operator.

Operator Pressing the button switches the mode to Program.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 139


Chapter 6 SSCC Operation

The mode buttons and operator control buttons require security privileges
(operator, supervisor, maintenance, or engineer).

Digital Output Device Configuration

Press to display the Configuration page. Many of the digital output channel
configuration parameters may be adjusted on this page.

Figure 36 - Digital Output Faceplate – Configuration Page

Close Screen

Control Value
Configuration Edit Device Name
properties

Table 78 lists the configuration items displayed on the Digital Output Faceplate -
Configuration page and the corresponding parameter lists and parameter
numbers used for configuration.
Table 78 - Digital Output Device Configuration Parameter List Cross Reference
Faceplate Configuration Item Parameter List / Parameter Number
Fail On List: 10: Digital Output Channel Configuration
Parameter: various, individual per channel

Customize the Channel

From the device configuration, you may edit the description. This represents a
string tag in the HMI (not the controller). This tag is retentive and saved in the
HMI memory. For example, you may want to include the device tag number in
the description and identify the signal more clearly (for example: “XA-1004
Surge Alarm”).

String tag limits are:

Description: 34 characters

140 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

PID Loop Faceplate

The PID Loop faceplate provides a graphical interface to the anti-surge and
capacity control PID loops. The PID faceplate has an Operations page and a
Configuration page.

PID Loop Device Operation

Press to display the Operations page. The following illustration details the
features of the PID loop Operation page.

Figure 37 - PID Faceplate – Operations Page

Close Screen

Device Name
Setpoint In Use
Process Variable &
Units
Mode Control Button
Control Value in Use

Setpoint Entry (Auto Mode) Control Value Entry (Manual Mode)

The PID loop is a Proportional - Integral - Derivative controller used for


regulatory control applications. The PID loop is used for both anti-surge and
capacity control within the SSCC system.

Loop Mode

The mode buttons provide both control and indication of the Loop mode.

Mode Buttons Indication Description Operation available


Loop is in Manual None, security privilege required (O, S, M or E)

Loop is in Auto None, security privilege required (O, S, M or E)

Loop is in Manual Press to switch to Auto Mode

Loop is in Auto Press to switch to Manual Mode

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 141


Chapter 6 SSCC Operation

For the anti-surge primary PID loop, the application provides a mode protection
feature to switch the loop from Manual back to Auto mode when the operating
point is within a certain distance of the surge limit line. This prevents the
operator from driving the compressor into surge. This protection feature is
bypassed when surge testing is enabled. The anti-surge secondary PID loop and
the capacity PID loops do not incorporate this mode protection.

When all configured loops are in Auto mode, the control loops ready permissive
is generated. If operational procedures for the compressor require one or more of
the configured loops to be in Manual mode at startup, then this permissive may
need to be configured for bypass.

Loop Setpoint

When the PID loop is in Auto mode, the setpoint of the loop may be adjusted
(security privilege required: O, S, M or E). Setpoint entry is limited by the
configured SP Minimum and SP Maximum values. When a new setpoint is
entered, the setpoint in use will adjust to the new target value at the configured
SP Increase and Decrease limits.

For the anti-surge primary PID loop, the loop setpoint is determined by the
application logic (SCL value from the OP tracking function). While the faceplate
provides SP entry, the application will over write any entered value from the
HMI.

Manual Control Value

When the loop is in Manual mode, the manual control value can be adjusted
(security privilege required: O, S, M or E). Control value entry is limited by the
configured CV Minimum and CV Maximum values.

PID Loop Device Configuration

Press to display the Configuration page. There are two types of


Configuration pages for the PID loop: 1) Standard Tuning, 2) Adaptive Tuning.
The anti-surge primary PID loop uses the Adaptive Tuning configuration page,
and the other PID loops use the Standard Tuning configuration page.

Configuration Page – Adaptive Tuning

The following illustration details the features of the PID Adaptive Tuning
Configuration page used for the anti-surge primary PID loop.

142 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Figure 38 - PID Faceplate – Adaptive Tuning Configuration Page

Close Screen

Edit Device Name

Edit Units of Measure

Values influencing
Adaptive Tuning
calculation

Base Tuning Values

Adaptive Tuning values

Adaptive tuning is used to automatically adjust the proportional and integral


tuning values based on operating conditions. The adaptive tuning adjustment
principles are illustrated in the following figure.

Figure 39 - Adaptive Tuning Principles

Maximum Limit, Kmax

Slope 1, S1

Base value, Kbase

Slope 2, S2

Minimum Limit, Kmin

(-) BP1, 0 BP2, (+ )


Breakpoint 1 Breakpoint 2

The controller calculates the difference between the operating point and the
surge control line = (OP – SCL). These values are shown on the Configuration
page. When difference between the operating point and the surge control line
(Diff ) is between the breakpoints, the base tuning value is used. When the Diff is

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 143


Chapter 6 SSCC Operation

outside the breakpoints, the tuning value is calculated based on the slopes S1 or
S2. A positive value for slope increases the tuning value (slope 1 in the
illustration). A negative value for slope decreases the tuning value (slope 2 in the
illustration). The calculated adaptive tuning value is shown as Kcalc on the
Configuration page. The calculated value is clamped at the configured minimum
and maximum limits.

Table 79 lists the configuration items displayed on the PID Loop Faceplate -
Adaptive Tuning Configuration page and the corresponding parameter lists and
parameter numbers used for configuration.
Table 79 - PID Loop - Adaptive Tuning Configuration Parameter List Cross Reference
Faceplate Configuration Item Security Parameter List / Parameter
Proportional – BP1 E or A List 18, Param 04: BreakPoint 1 (%)
Proportional – S1 E or A List 18, Param 06: Slope 1 (Gain / %)
Proportional – BP2 E or A List 18, Param 05: BreakPoint 2 (%)
Proportional – S2 E or A List 18, Param 07: Slope 2 (Gain / %)
Proportional – Max E or A List 18, Param 02: Max Proportional (Gain)
Proportional – Min E or A List 18, Param 03: Min Proportional (Gain)
Proportional - Base M, E or A List 18, Param 01: Base Proportional (Gain)
Integral – BP1 E or A List 17, Param 04: BreakPoint 1 (%)
Integral – S1 E or A List 17, Param 06: Slope 1 (Rpt/min / %)
Integral – BP2 E or A List 17, Param 05: BreakPoint 2 (%)
Integral – S2 E or A List 17, Param 07: Slope 2 (Rpt/min / %)
Integral – Max E or A List 17, Param 02: Max Integral (Rpt/min)
Integral – Min E or A List 17, Param 03: Min Integral (Rpt/Min)
Integral – Base M, E or A List 17, Param 01: Base Integral (Rpt/min)

Customize the Loop

From the device configuration, you may edit the description, and the units of
measure. These represent string tags in the HMI (not the controller). These tags
are retentive and saved in the HMI memory. For example, you may want to
include the device tag number in the description (for example: “UIC-1007
AntiSurge Control”). You may also set the units of measure if desired. Note that
for the anti-surge primary PID loop, the PV is always the calculated operating
point, which is normalized 0…100% value. The control value of the PID loop is
intended to represent a control signal as 0…100% open.

String Tag limits are:


Description: 34 characters
Unit of Measure: 6 characters

144 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Configuration Page – Standard Tuning

The following illustration details the features of the PID Standard Tuning
Configuration page used with the anti-surge secondary PID loop and both
capacity PID loops.

Figure 40 - PID Faceplate – Standard Tuning Configuration Page

Close Screen

Edit Device Name

Edit Units of Measure

Setpoint Parameters Tuning Parameters

Table 80 lists the configuration items displayed on the PID Loop Faceplate -
Standard Tuning Configuration page and the corresponding parameter lists and
parameter numbers used for configuration.
Table 80 - PID Loop - Standard Tuning Configuration Parameter List Cross Reference
Faceplate Configuration Item Security Parameter List Cross Reference
List 19: Anti-Surge Secondary PID Loop
List 21: Capacity Primary PID Loop
List 22: Capacity Secondary PID Loop
SP Max Limit M, E or A Param 04: SP Max Limit (EU)
SP Min Limit M, E or A Param 05: SP Min Limit (EU)
SP Inc Rate M, E or A Param 06: SP Inc Limit (EU/sec)
SP Dec Rate M, E or A Param 07: SP Dec Limit (EU/sec)
Track PV in Manual (check box) E or A Param 03: SP Track PV in Man(1=Y)
Proportional M, E or A Param 08: Proportional (Gain)
Integral M, E or A Param 10: Integral (Rpt/min)
Derivative M, E or A Param 11: Derivative (sec)
Interactive Gain (check box) E or A Param 12: Interactive Tuning (1=Y)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 145


Chapter 6 SSCC Operation

Customize the Loop

From the configuration page, you may edit the description, and the units of
measure. These represent string tags in the HMI (not the controller). These tags
are retentive and saved in the HMI memory. For example, you may want to name
the loop based on tag number and function (for example: “PIC-1012 Discharge
Press Control”). You may also set the units of measure if desired. For example, set
the units for PV (also used for SP) to “psia”. The control value of the PID loop is
intended to represent a control signal as 0…100% open.

String tag limits are:

Description: 34 characters

Unit of Measure: 6 characters

Compressor Details Faceplate

The Compressor Details faceplate provides an interface to the many of the


operational and configuration details associated with the compressor. These
details are organized into seven groups represented by tabs along the top of the
faceplate.

Compressor Details - Head Page

Press to display the Compressor Details - Head page. The following


illustration details the features of the page.

Figure 41 - Compressor Details – Head Page

Page Navigation Close Screen

Pressures and
Temperatures
Head Calculation Corrected to
Configuration Absolute Units
Parameters
Three forms of
calculated Head
presented.

This page provides access to configuration details and calculated values


pertaining to the compressor head calculation.

146 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 81 lists the configuration items displayed on the Compressor Details -


Head page and the corresponding parameter lists and parameter numbers used
for configuration.
Table 81 - Compressor Details - Head Faceplate Information Parameter List Cross Reference
Faceplate Configuration Item Security Parameter List / Parameter
Head Type 0=HpSim, 1=Pratio (read only) E or A List 11, Param 08: Head(0=HpSim,1=Pratio)
k, (Cp/Cv) E or A List 11, Param 03: Ratio of Specific Heats
Efficiency E or A List 11, Param 04: Polytropic Efficiency(0 - 1)
PolyExp Type (0=Fixed, 1=Variable) E or A List 11, Param 09: PolyExp(0=Const,1=Var)
PolyExp Max E or A List 11, Param 10: Var Poly Exp Max (EU)
PolyExp Min E or A List 11, Param 11: Var Poly Exp Min (EU)

Compressor Details - Base Condition Page

Press to display the Compressor Details - Base Conditions page. The


following illustration details the features of the page.

Figure 42 - Compressor Details – Base Conditions Page

Page Navigation Close Screen

Flow Element
Base conditions Compressor Base
Conditions of the Surge
Max Flow for OP Map. Also Gas
calc normalization Properties for reference.
Flow Location
Optional Map Methods
determines form of
for Inlet Guide Vane
OP calculation
applications

This page provides access to configuration details pertaining to the operating


point calculation and inlet guide vane methods for the surge map.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 147


Chapter 6 SSCC Operation

Table 82 lists the configuration items displayed on the Compressor Details - Base
Conditions page and the corresponding parameter lists and parameter numbers
used for configuration.
Table 82 - Compressor Details - Base Conditions Faceplate Information Parameter List Cross
Reference
Faceplate Configuration Item Security Parameter List / Parameter
Flow Element Base – Press (Abs) E or A List 11, Param 06: Orifice Base Press (Abs)
Flow Element Base – Temp (Abs) E or A List 11, Param 05: Orifice Base Temp (Abs)
Qmax for %Q2 E or A List 11, Param 07: Max Flow, Qmax (EU)
Flow Location (read only) E or A List 01, Param 01: Qs=1,Qd=2,Qdd=3,Alt=4
Compressor Base – Press (Abs) E or A List 11, Param 02: Comp Base Press (Abs)
Compressor Base – Temp (Abs) E or A List 11, Param 01: Comp Base Temp (Abs)
Compressor Base – Gas MW E or A List 11, Param 14: Gas Molecular Weight
Compressor Base – Gas Z E or A List 11, Param 15: Gas Compressibility
IGV Methods – Map Uses IGV (0=No, 1=Yes) E or A List 11, Param 12: Map using IGV (1=Yes)
IGV Methods – Min Limit E or A List 11, Param 13: IGV Min Limit (0 - 100)

Compressor Details - Surge Map Page

Press to display the Compressor Details - Surge Map page. The following
illustration details the features of the page.

Figure 43 - Compressor Details – Surge Map Page


Page Navigation Close Screen

Compressor Surge Map: Optional, for Inlet


X-axis: Normalized %Q2 Guide Vane
Y-axis: Head units (HpSim or Pratio) applications

This page provides access to configuration values that define the Compressor
Details - Surge Map.

148 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 83 lists the configuration items displayed on the Compressor Details -


Surge Map page and the corresponding parameter lists and parameter numbers
used for configuration.
Table 83 - Compressor Details - Surge Map Faceplate Information Parameter List Cross Reference
Faceplate Configuration Item Security Parameter List / Parameter
2
X-axis, %Q , Points 0 to 10 E or A List 12, Param 01: %Q2, Pt 0
through
List 12, Param 11: %Q2, Pt 10
Y-axis, Head, Points 0 to 10 E or A List 12, Param 12: Comp Head, Pt 0
through
List 12, Param 22: Comp Head, Pt 10
IGV, Points 0 to 10 E or A List 12, Param 23: Inlet Guide Vane, Pt 0
through
List 12, Param 33: Inlet Guide Vane, Pt 10

Compressor Details - OP Tracking and Decoupling Page

Press to display the Compressor Details - OP Tracking and Decoupling


page. The following illustration details the features of the page.

Figure 44 - Compressor Details – OP Tracking / Decoupling Page

Page Navigation Close Screen

OP Tracking When set for Use, Decoupling


Determines Trigger and Release points Hold
the Surge the Capacity controls, prioritizing
Control Line the Anti-Surge controller response
(CSCL) Value
Active when Decouple Triggered:
(OP – CLL) < Trigger Pt
Inactive when Decouple Released:
(OP – CLL) > Release Pt

This page provides access to configuration values that define the OP tracking
behavior and the anti-surge/capacity control decoupling behavior of the system.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 149


Chapter 6 SSCC Operation

Table 84 lists the configuration items displayed on the Compressor Details - OP


Tracking and Decoupling page and the corresponding parameter lists and
parameter numbers used for configuration.
Table 84 - Compressor Details - OP Tracking/Decoupling Faceplate Information Parameter List
Cross Reference
Faceplate Configuration Item Security Parameter List / Parameter
OP Tracking – Max Limit, % M, E or A List 13, Param 16: OP Track Max SP (%)
OP Tracking – Margin, % M, E or A List 13, Param 14: OP Track Margin (%)
OP Tracking – Rate, %/sec M, E or A List 13, Param 15: OP Track Rate (%/sec)
Decoupling – Trigger Pt, % M, E or A List 23, Param 02: DP1, Initiate Pt (ASC EU)
Decoupling – Release Pt, % M, E or A List 23, Param 03: DP2, Release Pt (ASC EU)
Decoupling – Use Decoupling (check box) E or A List 23, Param 01: Use Decoupling (1=Yes)

Compressor Details - Anti-Surge and Capacity Valve Page

Press to display the Compressor Details - Anti-Surge and Capacity Valve


page. The following illustration details the features of the page.

Figure 45 - Compressor Details – Anti-Surge and Capacity Valve Page

Page Navigation Close Screen

Defines the
Opening and
Closing rate limits
Control output limited
Override CV applied by these Min and Max
when compressor is: values (% Open)
• - Not Running,
• - Unloaded, or Position Deviation
• - Comp Trip Interlock Alarm Configuration
parameters

This page provides access to configuration of control behaviors (control rates,


control limits, and position alarms) associated with the anti-surge valve and the
capacity control device (valve, IGV, etc.).

150 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Table 85 lists the configuration items displayed on the Compressor Details -


Anti-Surge and Capacity Valve page and the corresponding parameter lists and
parameter numbers used for configuration.
Table 85 - Compressor Details – Anti-Surge and Capacity Valve Faceplate Information Parameter List
Cross Reference
Faceplate Configuration Item Security Parameter List / Parameter
List 15, AntiSurge List 20, Capacity Function
Valve Slew Rate – Open, %/sec M, E or A Param 05: Param 05: OpenSlewRate (%/sec)
Valve Slew Rate – Close, %/sec M, E or A Param 06: Param 06: CloseSlewRate (%/sec)
Control Limit – CV Max, % M, E or A Param 07: Param 07: CV Max (%)
Control Limit – CV Min, % M, E or A Param 08: Param 08: CV Min (%)
Override CV (NotRun, Unload, Trip) % M, E or A Param 02: Param 02: Not Running CV (%)
Position Deviation – Pos Dev, % M, E or A Param 11: Param 10: Pos Dev Alm DB (%)
Position Deviation – Dev Time, sec M, E or A Param 12: Param 11: Pos Dev Alm Time (sec)

Compressor Details - Surge Configuration Page

Press to display the Compressor Details - Surge Configuration page. The


following illustration details the features of the page.

Figure 46 - Compressor Details – Surge Configuration Page

Page Navigation Close Screen

Multi-Surge Trip is Rate-of-Change Surge


triggered when a configuration parameters
Quantity of Surges based on a Rate averaged
occur in the Time over specified Time duration
configured
Live Rate-of-Change Value
Total Surge Count
and Counter Positional Surge
Reset button configuration threshold and
present distance from Surge
(OP – SLL)

This page provides access to configuration values pertaining to surge detection


methods (rate-of-change, and positional), multi-surge trip, and surge counters for
the compressor.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 151


Chapter 6 SSCC Operation

Table 86 lists the configuration items displayed on the Compressor Details -


Surge Configuration page and the corresponding parameter lists and parameter
numbers used for configuration.
Table 86 - Compressor Details – Surge Configuration Faceplate Information Parameter List Cross
Reference
Faceplate Configuration Item Security Parameter List / Parameter
Multi-Surge Trip – Quantity E or A List: 13, Param 08: Surge Trip Qty
Multi-Surge Trip – Time, sec E or A List: 13, Param 09: Surge Trip Time (sec)
Rate-of-Change Surge – Rate, -%.sec M, E or A List: 13, Param 10: Surge RoC Low (-%/sec)
Rate-of-Change Surge – DB, %,sec M, E or A List: 13, Param 11: Surge RoC DB (%/sec)
Rate-of-Change Surge – Time, msec M, E or A 12: Surge RoC Time (msec)
Positional Surge – Threshold M, E or A 13: Positional Srg Margin (%)

Compressor Details - Surge Test Page

Press to display the Compressor Details - Surge Test page. The following
illustration details the features of the page.

Figure 47 - Compressor Details – Surge Test Page


Page Navigation Close Screen

Surge Test Activation


controls and status. Compressor Data to be
Automatically captured when Surge is
deactivates on Surge Detected. OP and Head
values plotted on the
Choose which Compressor Map
methods are used to
End Surge Test and
Reset Trapped Data
Trap Surge Data
Indicates if Data is Live or Trapped

This page is used during surge testing the compressor. Use this page to do the
following tasks.
• Activate/deactivate surge testing
• Choose the surge methods used to end the test and trap data
• Examine trapped surge data
• Reset trapped data

The above operations require security privilege engineer or administrator.

152 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Trends The SSCC HMI includes several trend displays which graph key control and
operating data on convenient time plots.

Follow these steps to navigate and select a particular trend display.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Trend Select screen appears as shown here.

3. Press or to select the trend in the list that you want to view.

4. Press to open the selected Trend Detail screen.

There are eight pre-configured Trend Detail screens. The following table
contains an example and description of the variables available on each Trend
Detail screen.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 153


Chapter 6 SSCC Operation

Trend Detail Description / Variables Example Screen


ASC01 Control Anti-Surge Primary PID Loop variables:

Loop PV: the calculated Operating Point value, OP


Loop SP: the Surge Control Line value, SCL
Loop CV: the PID output Control Value
CLL value: Control Limit Line value, represents the minimum SP for the loop

ASC02 Control Anti-Surge Secondary PID Loop variables (if configured)

Loop PV: Process Variable, as configured


Loop SP: Setpoint
Loop CV: The PID output Control Value

Cap01 Control Capacity Primary PID Loop variables (if configured)

Loop PV: Process Variable, as configured


Loop SP: Setpoint
Loop CV: The PID output Control Value

154 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Trend Detail Description / Variables Example Screen


Cap02 Control Capacity Secondary PID Loop variables (if configured)

Loop PV: Process Variable, as configured


Loop SP: Setpoint
Loop CV: The PID output Control Value

Analog Inputs Pressure and Temperature signals

Discharge Pressure, Pd
Suction Pressure, Ps
Discharge Temperature, Td
Suction Temperature, Ts

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 155


Chapter 6 SSCC Operation

Trend Detail Description / Variables Example Screen


Valve Control Anti-Surge and Capacity Valve signals

ASC Valve Control Output


ASC Valve Position signal input
Capacity Valve/Device Control Output
Capacity Valve/Device Position signal input

Compressor Compressor values of interest

Compressor Head value


Surge Limit Line value, SLL
Control Limit Line value, CLL
Incipient Surge input signal (if configured)

Aux / Flow PV Auxiliary Control Signal and Compressor Flow

Auxiliary Control PV input signal (if configured)


Compressor Flow input signal (as configured: Qs, Qd, Qdd, or Qalt)

156 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


SSCC Operation Chapter 6

Using the Trend Detail Screen

Features common to all of the Trend Detail screens are illustrated in Figure 48.

Figure 48 - Trend Details Screen


Trend Detail Screen Name Current Day, Date

Trend Plot Area

Y-Axis Scale: Trend Legend:


• Based on Pen EU scale • From 1 to 4 Pens
• Use “Next Pen” to • Pen colors
cycle through Pens • Pen values
• Color matches Pen

X-Axis, time scale Cycles the Y-Axis display


scale for each Pen

Trend Plot control buttons Pen Indicators

The trend plot area is configured to display four minutes of trend data. Trend
data scrolls from right to left. For each pen, the trend legend identifies the
variable, the pen color, and the current value. Each pen indicator’s vertical
position along the right edge of the plot area follows the current value of the pen.
The Y-axis scale only presents one pen scale at a time. To switch the Y-axis scale,
use the next pen button to cycle through the available pens. The color of the Y-
axis values follows the pen color.

The trend plot control buttons allow the user to scroll through trend data
buffered by the display. The functions for each button are described here.

Button Name Function


Home Scroll trend plot back to earliest trend data in display buffer and Pause

Scroll Left Scroll trend plot back 2-minutes and Pause

Pause / Resume If trend plot is Live, then Pause


If trend plot is Paused, then resume Live updates
Scroll Right Scroll trend plot forward 2-minutes and Pause

End Scroll trend plot forward to most recent trend data and Resume Live update

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 157


Chapter 6 SSCC Operation

Trend Technical Specifications

Trend Plot area:


X-Axis, Time scale 4-minutes (fixed)
Y-Axis Pre-configured to EU range of Pen(s)
Trend Sampling 1-second
Trend History
Trend Log 240 samples (4-minutes) available on Trend Open
Display Buffer 4800 samples (80-minutes) while screen open.
Clears when screen closed.

158 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 7

Modbus Interface

The SSCC has a RS-232 serial port for Modbus communication. The port is
located on the front of the controller. The protocol supported is RTU in slave
mode.

Serial Port Configuration The following table shows the parameters related to Modbus communication.
Table 87 - Modbus Communication Parameters
Parameter Description Range
1 Slave ID 1…254
2 Register Scaling Range 0…32767
3 Baud Rate Configuration 0…38400
4 Parity Configuration (0=None, 1=Odd, 2=Even) 0…2
5 Baud Rate Read back 0…38400
6 Parity Read back 0…2
7 Set Port Config (1=Set Port Config) 0…1

Configuration of the Modbus interface is performed through the HMI. Refer to


configuration details for parameter list 29: Modbus Serial Port Configuration on
page 87.

Figure 49 - Modbus Serial Port Configuration Screen

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 159


Chapter 7 Modbus Interface

Modbus Holding Registers Modbus data access to the SSCC utilizes only Modbus holding registers. Modbus
function code 3 can be used to read these registers.

The map of Modbus registers is presented in the following table. Where


indicated, the SSCC EU (engineering unit) value range is converted to the
Modbus register range configured in parameter 2.
Table 88 - Modbus Holding Register Assignments
Address Data Type EU Range Service
40001 INT 0.0 to 100.0 ASC Primary PID Loop – Process Value (Operating Point, OP)
40002 INT 0.0 to 100.0 ASC Primary PID Loop – Setpoint in Use
40003 INT 0.0 to 100.0 ASC Primary PID Loop – Control Value
40004 INT EU Min to EU Max Compressor Flow input signal
40005 INT EU Min to EU Max Suction Pressure input signal
40006 INT EU Min to EU Max Suction Temperature input signal
40007 INT EU Min to EU Max Discharge Pressure input signal
40008 INT EU Min to EU Max Discharge Temperature input signal
40009 INT 0.0 to 100.0 Incipient Surge input signal
40010 INT 0.0 to 100.0 ASC Valve Position input signal
40011 INT 0.0 to 100.0 CAP Valve/IGV Position input signal
40012 INT 0.0 to 10.0 Compressor Head (HpSim or Pratio)
40013 INT 0.0 to 100.0 Surge Limit Line, SLL
40014 INT 0.0 to 100.0 Control Limit Line, CLL
40015 INT 0.0 to 100.0 Surge Control Line, SCL
ASC Primary PID Loop - Setpoint
40016 INT 0.0 to 100.0 Surge Map X-Axis, Pt-0
40017 INT 0.0 to 100.0 Surge Map X-Axis, Pt-1
40018 INT 0.0 to 100.0 Surge Map X-Axis, Pt-2
40019 INT 0.0 to 100.0 Surge Map X-Axis, Pt-3
40020 INT 0.0 to 100.0 Surge Map X-Axis, Pt-4
40021 INT 0.0 to 100.0 Surge Map X-Axis, Pt-5
40022 INT 0.0 to 100.0 Surge Map X-Axis, Pt-6
40023 INT 0.0 to 100.0 Surge Map X-Axis, Pt-7
40024 INT 0.0 to 100.0 Surge Map X-Axis, Pt-8
40025 INT 0.0 to 100.0 Surge Map X-Axis, Pt-9
40026 INT 0.0 to 100.0 Surge Map X-Axis, Pt-10
40027 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-0
40028 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-1
40029 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-2
40030 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-3
40031 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-4
40032 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-5
40033 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-6

160 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Modbus Interface Chapter 7

Table 88 - Modbus Holding Register Assignments (Continued)


Address Data Type EU Range Service
40034 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-7
40035 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-8
40036 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-9
40037 INT 0.0 to 10.0 Surge Map Y-Axis, Pt-10
40038 INT EU Min to EU Max ASC Secondary PID Loop – Process Value
40039 INT EU Min to EU Max ASC Secondary PID Loop – Setpoint Target
40040 INT EU Min to EU Max ASC Secondary PID Loop – Setpoint in Use
40041 INT 0.0 to 100.0 ASC Secondary PID Loop – Control Value
40042 INT EU Min to EU Max Capacity Primary PID Loop – Process Value
40043 INT EU Min to EU Max Capacity Primary PID Loop – Setpoint Target
40044 INT EU Min to EU Max Capacity Primary PID Loop – Setpoint in Use
40045 INT 0.0 to 100.0 Capacity Primary PID Loop – Control Value
40046 INT EU Min to EU Max Capacity Secondary PID Loop – Process Value
40047 INT EU Min to EU Max Capacity Secondary PID Loop – Setpoint Target
40048 INT EU Min to EU Max Capacity Secondary PID Loop – Setpoint in Use
40049 INT 0.0 to 100.0 Capacity Secondary PID Loop – Control Value
40050 INT 0.0 to 100.0 Capacity Valve/IGV Control Output
40051 INT 0.0 to 100.0 Total Margin in Use
40052 INT No scaling Surge Counter
40053 INT 0.0 to 100.0 Reserved for future use
40054 INT 0.0 to 100.0 Reserved for future use
40055 INT 0.0 to 100.0 Reserved for future use
40056 INT 0.0 to 100.0 Reserved for future use
40057 INT 0.0 to 100.0 Reserved for future use
40059 INT 0.0 to 100.0 Reserved for future use
40060 INT 0.0 to 100.0 Reserved for future use

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 161


Chapter 7 Modbus Interface

Notes:

162 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Chapter 8

Troubleshooting

This section covers topics to help troubleshooting the SSCC during


commissioning or during its normal lifecycle.

System Power The SSCC field signals should be connected to the marshaling terminals
indicated on Chapter 3 of this manual. All internal wiring is completed at the
factory; therefore signal troubleshooting is limited to checking the functioning of
the power supplies, circuit breakers and fuses. This guide is not intended for
troubleshooting field signals. All field signals should be tested using the field loop
drawings.

Make sure you have a set of system drawings before starting to troubleshoot.
Table 89 - Troubleshooting Matrix
Symptom Suggestions
General power related symptoms If the system is powered from an AC source:
• Make sure 120 VAC is available at CB1.
• Make sure CB1 is in the “On” position.
If the system is powered from a DC source:
• Check voltage on 24VDC input power terminals
24V-1 (+)
24V-2 (-)
Controller fails to power up Check the suggestions for “General power related symptoms” above
Check the voltage on terminals TS3-1 and TS3-2 (24VDC)
Check the fuse (2A) on TS3-1
PanelView fails to power up Check the suggestions for “General power related symptoms” above
Check the voltage on terminals TS3-15 and TS3-16 (24VDC)
Check the fuse (1A) on TS3-15
Digital Inputs not working Check the suggestions for “General power related symptoms” above
Check the voltage on terminals TS3-5 and TS3-6 (24 VDC)
Check the fuse (1A) on TS3-5 (common power to all DIN channels)
Check the individual channel fuses (0.25A) on TS1
Digital Outputs not working Check the suggestions for “General power related symptoms” above
Check the voltage on terminals TS3-7 and TS3-8 (24 VDC)
Check the f use (5A) on TS3-7 (common power to all DOUT channels)
Check the individual channel fuses (0.5A) on TS2
Analog Inputs not working Check the suggestions for “General power related symptoms” above
Check the voltage on terminals TS3-3 and TS3-4 (24 VDC)
Check the fuse (1A) on TS3-3 (common power to all AIN channels)
Check the individual channel fuses (0.25A) on TS1
Analog Output not working Check the suggestions for “General power related symptoms” above
Note: 24V DC power for AO channels are sourced from the controller power
supply.
Check the individual channel fuses (0.25A) on TS1

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 163


Chapter 8 Troubleshooting

Hardware Status The Hardware screen on the HMI provides detailed status of the controller, I/O
modules, I/O channels, and access to the HMI configuration (exit graphics).

The Hardware screen has three pages to support troubleshooting/maintenance


activities the SSCC hardware. When the Hardware screen opens, the last viewed
page is presented to the user.
Table 90 - Hardware Screen Pages
Page Screen Examples Description
1 Hardware Screen – Controller Status
Display Features:
• Controller status indications: Mode, Controller, Battery, I/O System, Minor Faults, Major Faults and
Ethernet.
• Memory usage statistics.
Operational Features:

• Use or to check the status of the individual modules.

• Press to open a Module Detail popup for the chosen I/O module.

2 Hardware Screen – Major / Minor Faults


Display Features:
• Detailed major fault and minor fault status.
Operational Features:

• Press to reset major and minor faults - security privilege required (O, S, M, E, or A).

3 Hardware Screen – PanelView Plus Maintenance


Operational Features:

Press to exit the HMI graphics and access the PanelView Plus device configuration - security privilege
required (E, or A).

Press to set the controller clock time to the PanelView clock time - security privilege required (E, or
A).

164 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Follow these steps to access the Hardware screen.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

3. Press to page forward, or to page backward, as required to


navigate to page one of the Maintenance screen, page 1, Configuration and
Settings (shown here).

4. Press to open the Hardware screen - Controller Status (page 1).

Controller Status

The Controller Status page provides details on the controller and a selector to
access individual I/O module details.

Figure 50 - Hardware Screen, Page 1 - Controller Status

A variety of status information is presented adjacent to the controller graphic


image on the Controller Status page. These indications are detailed in the
following tables.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 165


Chapter 8 Troubleshooting

Table 91 - Application Mode Status


Indication Description
The application is in Run mode.
This is the normal operating mode for the system.
The application is in Program mode.
Use the key on the front of the controller to switch to Run mode.
The application is in Test mode.
Use the key on the front of the controller to switch to Run mode.

Table 92 - Controller Status


Indication Description
The controller is healthy.
This is the normal operating mode for the system.
The controller status is faulted.
A critical fault has occurred on the controller and it is not in operation.
Search for additional details under the major faults.

Table 93 - Battery Status


Indication Description
The controller battery is OK.
This is the normal indication for the system.
The controller batter is low and should be replaced.

Table 94 - I/O System Status


Indication Description
All the I/O modules are running.
This is the normal indication for the system
At least one I/O module is not running.
Check individual module status on the I/O Module Selector to identify a particular
module. Search additional details for individual I/O modules.
(flashing green)
None of the I/O modules are running.
Check the levers on the top of each Compact I/O module and I/O end cap. They should
all be properly positioned to left, to engage the connection to each other and the
(flashing red) controller.
Restart the system. If the problem persists contact Rockwell Automation for
assistance.
There are no I/O modules configured in the system.
This indication is not expected to appear, as the system is pre-configured for I/O
connections. Contact Rockwell Automation for assistance.

166 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Table 95 - Minor Fault Status


Indication Description
There are no minor faults reported for the controller.
This is the normal indication for the system.
There is at least one minor fault reported for the controller.
Navigate to Hardware Status page 2 for further details on minor faults.
Minor faults are recoverable, and can be reset on page 2. If the fault persists contact
Rockwell Automation for assistance.

Table 96 - Major Fault Status


Indication Description
There are no major faults reported for the controller.
This is the normal indication for the system.
There has been a major fault reported for the controller, and the controller has been
stopped.
Some major faults are recoverable. You can restart the system and observe if the fault
is cleared or persists. If the fault persists contact Rockwell Automation for assistance.

Table 97 - Ethernet Status


Indication Description
The onboard Ethernet interface is operating normally.
This is the normal indication for the system.
A fault is reported for the onboard Ethernet interface.
Restart the system. If the problem persists contact Rockwell Automation for
assistance.

Controller Major and Minor Fault Status

Additional details about major and minor fault status for the controller is
available on page 2 of the Hardware Status screen.

Figure 51 - Hardware Screen, Page 2 - Major and Minor Faults

The reset button on this screen can be used to reset controller faults. This will
normally pertain to minor faults. In case of major faults, it is often necessary to
restart the controller.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 167


Chapter 8 Troubleshooting

The Reset button requires security privileges (operator, supervisor, maintenance,


engineer, or administrator).

PanelView Maintenance

The PanelView Plus Maintenance page is shown in Figure 52.

Figure 52 - Hardware Screen, Page 3 - PanelView Plus Maintenance

This page contains the following icons.


Icon Action
Exits the HMI graphics, and accesses the PanelView Plus configuration and maintenance features
(network settings, file management, screen saver, and PanelView date/time).
Consult the PanelView Plus product documentation for details.

Sets the clock in the controller using the present clock settings on the PanelView.

I/O Modules I/O Module Detail screens facilitate installation and commissioning activities,
and system troubleshooting. Follow these steps to access the desired I/O Module
Detail screen.

1. Press to close any open pop-up screens and return to a main screen
showing the navigation toolbar.

2. Press on the navigation toolbar.

The Maintenance screen appears.

168 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

3. Press to page forward, or to page backward, as required to


navigate to page one of the Maintenance screen, page 1, Configuration and
Settings (shown here).

4. Press to open the Hardware screen - Controller Status (page 1).

5. Press to page forward, or to page backward, as required to


navigate to page one of the Hardware screen, page-1 – Controller Status
(shown here).

6. Press to select the desired module from the I/O Module selector
list at the bottom of the screen. The following I/O modules are available.
• For Digital Inputs: Slot 1: 1769-IQ16
• For Digital Outputs: Slot 2: 1769-OB16
• For Analog Inputs: Slot 3: 1769-IF8
• For Analog Outputs: Slot 4: 1769-OF4

7. Press to open the IO Module Detail page (for example: Analog


Inputs).

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 169


Chapter 8 Troubleshooting

Digital Input Module Detail

The Digital Input Module Detail screen is shown in Figure 53.

Figure 53 - Digital Input Module Detail

For each input channel, the channel number and description are presented. The
channel descriptions on this screen are fixed and cannot be customized. They
reflect the allocated function for each channel. The channel number is used as a
status indicator for the individual channel.
Visual Indication Example Explanation
The green color indicates the input is energized, logic 1.

The grey color indicates the input is de-energized, logic 0.

The red color indicates a fault is reported.

Digital Output Module Detail

The Digital Output Module Detail screen is shown in Figure 54.

Figure 54 - Digital Output Module Detail

For each output channel, the channel number and description are presented. The
channel descriptions on this screen are fixed and cannot be customized. They

170 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

reflect the allocated function for each channel. The channel number is used as a
status indicator for the individual channel.
Visual Indication Example Explanation
The green color indicates the output command is logic 1, to energize the
connected device.
The grey color indicates the output command is logic 0, to de-energize the
connected device.
The red color indicates a fault is reported.

Analog Input Module Detail

The Analog Input Module Detail screen is shown in Figure 55.

Figure 55 - Analog Input Module Detail

For each input channel, the channel number, input raw count, and description are
presented. The channel descriptions on this screen are fixed and cannot be
customized. They reflect the allocated function for each channel. The channel
number and value are used as a status indicator for the individual channel.
Visual Indication Example Explanation
The grey color indicates the input is normal.

The red color indicates a fault is reported.

The analog input channels are configured for input range of 4…20 mA, with data
format percent range. This configuration reports a raw count of 0 at 4 mA, to
10000 at 20 mA. The percent range configuration makes reading the input as a
percent of transmitter span quite simple. For example, a reading of 2500 is
25.00% of the transmitter span, or 8.0 mA. The absolute measurement/reported
range is -500 (3.2 mA) to 10625 (21.0 mA).

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 171


Chapter 8 Troubleshooting

Analog Output Module Detail

The Analog Output Module Detail screen is shown in Figure 56.

Figure 56 - Analog Output Module Detail

For each output channel, the channel number, output command value, and
description are presented. The channel descriptions on this screen are fixed and
cannot be customized. They reflect the allocated function for each channel. The
channel number and value are used as a status indicator for the individual
channel.
Visual Indication Example Explanation
The grey color indicates the output is normal.

The red color indicates a fault is reported.

The analog output channels are configured for output range of 4…20 mA, with
data format percent range. This configuration generates the 4…20 mA output
from a command range of 0 to 10000 counts. The percent range configuration
makes reading the output command as a percentage, e.g. a command of 7500 is
75.00% to the control device, or 16.0 mA.

Alarms The overall unit Alarm status is presented on the Alarms button (third from the
left) displayed on the Navigation Toolbar of any main screen.

The alarm status is represented by the bell color and its steady or flashing status as
explained in Table 98 on page 173.

172 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Table 98 - Unit Alarm Summary Icon Indications


Alarm Alarm Severity Bell Color - Status Explanation
Icon
4: Fault Pink - steady Active alarm present, check Alarm screen for
Hardware faults, Xmtr faults details
Pink - flashing Alarm cleared, reset alarm on Alarm screen
3: Exception Red - steady Active alarm present, check Alarm screen for
Compressor Trip conditions details
Red - flashing Alarm cleared, reset alarm on Alarm screen
2: Alert Yellow - steady Active alarm present, check Alarm screen for
Hi / Lo Alarms, details
Control Fallback Strategies
Yellow - flashing Alarm cleared, reset alarm on Alarm screen
1: Information Blue - steady Active alarm present, check Alarm screen for
Surge Testing details
Blue - flashing Alarm cleared, reset alarm on Alarm screen
None White - solid No active alarms, no alarms require reset

To check the status of the Alarms, press the Alarms button on the toolbar to open
the Alarms screen.

Managing Alarms
The SSCC alarms are managed from a single Alarm screen. The features of the
Alarm screen are shown in the following figure.

Figure 57 - Alarm Screen Components

Alarm Select Indicator

Alarm List

Move Alarm Selector:


Page Up Alarm Reset
Scroll Up Acknowledge All Alarms
Scroll Down Acknowledge Selected Alarm
Page Down

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 173


Chapter 8 Troubleshooting

Within the alarm list, the individual alarm message status is graphically
represented based on the alarm state (active or inactive) and acknowledgement
(Ack’d or not-Ack’d).
Alarm State Acknowledgement Alarm Message Representation
Active Not Acknowledged Severity Color – Flashing
Active Acknowledged Severity Color – Steady
Inactive Not Acknowledged Dark Grey – Flashing
Inactive Acknowledged Light Grey – Steady (historical)

All the alarms defined in the SSCC are listed in the next table. The table is sorted
alphabetically by alarm message.
Table 99 - Alarm Messages
Alarm Message Severity Explanation of Condition
Analog Input Module Failure Fault (4) Fault reported for analog input module in Slot 3
Analog Output Module Failure Fault (4) Fault reported for analog output module in Slot 4
AntiSurge Valve Position Error Alert (2) Deviation between control signal and position feedback >
deviation limit and duration.
Aux Control Signal Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Aux Control Signal Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Auxiliary Control Signal High Alert (2) Auxiliary control signal > high alarm limit
Auxiliary Control Signal Low Alert (2) Auxiliary control signal < low alarm limit
Capacity Valve Position Error Alert (2) Deviation between control signal and position feedback >
deviation limit and duration
Comm Interface Failure Fault (4) Fault reported for the Ethernet communication interface
Compressor Flow High Alert (2) Compressor flow > high alarm limit
Compressor Flow Low Alert (2) Compressor flow < low alarm limit
Compressor Flow Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Compressor Flow Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Compressor Head Fault Alert (2) Conditions exist (i.e. transmitter faults) that prevent calculation of
compressor head. As a result:
Head values are set to default values (HpSim = 0.0, Pratio = 1.0,
Prise = 0.0).
This condition will trigger the minimum flow fallback.
Compressor Surge Detected Alert (2) Compressor surge detected by either:
Positional surge: Operating point (OP) is below the surge limit line
(SLL) value by more than the positional surge margin.

Rate-of-change: The operating point decreased at a rate exceeding


the configured rate-of-change limits.

As a result, the offset and/or percent margin in use are


automatically increased.
Controller Failure Fault (4) Fault reported for the controller
Digital Input Module Failure Fault (4) Fault reported for digital input module in Slot 1

174 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Table 99 - Alarm Messages (Continued)


Alarm Message Severity Explanation of Condition
Digital Output Module Failure Fault (4) Fault reported for digital output module in Slot 2
Discharge Press Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Discharge Press Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Discharge Pressure High Alert (2) Discharge pressure > high alarm limit
Discharge Pressure Low Alert (2) Discharge pressure < low alarm limit
Discharge Temp Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Discharge Temp Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Discharge Temperature High Alert (2) Discharge temperature > high alarm limit
Discharge Temperature Low Alert (2) Discharge temperature < low alarm limit
External Trip 1 Exception The external compressor trip signal connected to DIN channel 12 is
(3) in the “Tripped” condition.

As a result, a compressor trip is generated.


External Trip 2 Exception The external compressor trip signal connected to DIN channel 13 is
(3) in the “Tripped” condition.

As a result, a compressor trip is generated.


External Trip 3 Exception The external compressor trip signal connected to DIN channel 14 is
(3) in the “Tripped” condition.

As a result, a compressor trip is generated.


External Trip 4 Exception The external compressor trip signal connected to DIN channel 15 is
(3) in the “Tripped” condition.

As a result, a compressor trip is generated.


Incipient Surge Alert (2) Incipient surge signal > high alarm limit
Minimum Flow Fallback Alert (2) Triggered by Compressor Head Fault.

Without a calculated head, the surge limit line (SLL) value cannot
be determined by normal lookup table.

In this condition, the SLL value is set to the largest OP value defined
for the surge map, to assure a minimum safe flow through the
compressor.
Minimum IGV Fallback Alert (2) Triggered by an inlet guide vane (IGV) position signal failure.

As a result, IGV methods for the surge limit line fallback to using
the most conservative IGV position - full open.
Multi-Use Signal A Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Multi-Use Signal A Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Multi-Use Signal B Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Multi-Use Signal B Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 175


Chapter 8 Troubleshooting

Table 99 - Alarm Messages (Continued)


Alarm Message Severity Explanation of Condition
Multiple Surge Trip Exception Multiple surges have occurred within a configured time period.
(3) As a result, a compressor trip is generated.
Operating Point (OP) Fault Exception Conditions exist (i.e. transmitter fault or configuration errors) that
(3) prevent calculation of the operating point.
As a result, a compressor trip is generated.
Suction Press Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Suction Press Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Suction Pressure High Alert (2) Suction pressure > high alarm limit
Suction Pressure Low Alert (2) Suction pressure < low alarm limit
Suction Temp Overrange Fault (4) Transmitter signal > 20.4 mA
(Analog input raw count > 10250)
Suction Temp Underrange Fault (4) Transmitter signal < 3.6 mA
(Analog input raw count < -250)
Suction Temperature High Alert (2) Suction temperature > high alarm limit
Suction Temperature Low Alert (2) Suction temperature < low alarm limit
Surge Test Enabled Information Surge test is enabled, which bypasses the Manual mode protection
(1) for the anti-surge primary PID loop.

176 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Alarm Example

The following sequence provides an example of checking and resetting alarms.

Alarm status Indications Observations and Actions


The color of the Alarm button indicates the alarm condition:
• Color is pink - steady: alarm severity is Fault (4).

• Press to open the Alarm screen.

On the Alarm screen, there are three alarms shown. Each alarm has a
flashing color indication.
The alarm with the alarm severity, fault (pink) is represented by the
“Discharge Press Underrange” alarm.
In this case, a bad discharge pressure signal causes the “Compressor Head
Fault,” which triggers the “Minimum Flow Fallback” control strategy.

Press to acknowledge all of the alarm indications.

All three alarms become steady color after acknowledgement.

Investigation of the discharge pressure analog input signal confirms that the
transmitter signal is below the threshold for underrange.
This example shows the Analog Input Module Detail screen and AI channel 2
percent range value is less than the underrange threshold of “-250.”
Maintenance is tasked with field troubleshooting and repairing of the
transmitter signal.

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 177


Chapter 8 Troubleshooting

Alarm status Indications Observations and Actions


Maintenance determines the field transmitter is bad and replaces it. The
analog input signal is back in normal range.

Returning to the Alarm screen, two of the alarms have cleared:


• The underrange cleared with the successful transmitter replacement.
With the discharge pressure signal healthy, the compressor head
calculation fault has also cleared.
• The “Minimum Flow Fallback” is still presented as an active alarm, as the
system is still using this fallback strategy.
The Alarm button is flashing pink, indicating the alarm severity (Fault-4) is
cleared and can be reset.

Press . This resets the alarm status, and also resets the “Minimum

Flow Fallback” condition, returning the anti-surge control strategy to


normal.
All the alarm conditions are clear on the alarm list.
The Alarm button color is white (no alarms).

178 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Troubleshooting Chapter 8

Configuration Errors The SSCC has built in a basic configuration error routine. When a configuration
error is detected, a warning is generated. Configuration errors should be cleared
before running the compressor.
Table 100 - Configuration Errors
Configuration Error Check the following
Head Calc Config Error One or more of the following configuration properties must be corrected:
Suction Pressure AIN configured for Use, Ref List-2, Param-1
Discharge Pressure AIN configured for Use, Ref: List-3, Param-1
Gas ratio of Specific Heats (1.0 < value < 2.0), Ref List-11, Param-3
Polytropic Efficiency (0.0 < value < 1.0), Ref List-11, Param-4
If Variable Polytropic exponent is configured (Ref: List-11, Param-9) then:
Suction Temperature AIN configured for Use, Ref: List-5, Param-1
Discharge Temperature AIN configured for Use, Ref: List-6, Param-1
OP Calc Config Error One or more of the following configuration properties must be corrected:
Flow AIN configured for Use (value = 1, 2, 3, or 4), Ref: List-1, Param-1
Maximum Flow range normalization (Qmax > 0.0), Ref: List-11, Param-7
Base Pressure of Compressor (Pbc > 0.0), Ref: List-11, Param-2
Base Temp of Compressor (Tbc > 0.0), Ref: List-11, Param-1
Base Pressure of Flow Measurement (Pbo > 0.0), Ref List-11, Param-6
Base Temp of Flow Measurement (Tbo > 0.0), Ref List-11, Param-5
Surge Map Config Error One or more of the following configuration properties must be corrected:
Surge Map X-axis Normalized Flow values, %Q2 must be ascending:
Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
Ref: List-12, Param-1 to 11
Surge Map Y-axis Compressor Head values must be ascending:
Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
Ref: List-12, Param-12 to 22
If Inlet Guide Vane Method is configured (Ref: List-11, Param-12) then:
Surge Map IGV values must be ascending:
Pt-0 <= Pt-1, Pt-1 <= Pt-2,…Pt-8 <= Pt-9, Pt-9 < Pt-10
Ref: List-12, Param-23 to 33

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 179


Chapter 8 Troubleshooting

Startup or Operating Issues This section covers some of the issues that can be found during the compressor
startup or operation process and the suggested actions for correcting the issue.
Table 101 - Compressor Startup/Operation Symptoms and Suggested Action(s)
Symptom Suggested Action(s)
Compressor will not start Check the interlocks used to generate the compressor trip output signal.
Investigate any “Trip” conditions, they must be cleared or bypassed to start.
Reset the latched Interlocks using “Interlock reset”.
Check the Compressor Trip Digital Output Device faceplate - should be in
Program mode.
Check the permissives used to generate a “Ready to Start” output signal.
Investigate any “Not Ready” conditions - they must be ready or bypassed to
start.
Check the Ready To Start Digital Output Device faceplate - should be in
Program mode.
Compressor is running, but run is not Check methods for run determination:
indicated on the Compressor Compressor Run Digital Input:
Overview screen • Check the input signal on DIN channel-0.
• Check the channel fuse.
• Check that the digital input channel is configured for use.
• Check the device faceplate if the input is in Substitute PV mode.

Compressor head used for run determination:


• Check for: Compressor Head > Head Run Threshold
• Check for a “Compressor Head Calc” fault .

Auxiliary control PV used for run determination (i.e. Amps):


• Check for: Aux Control PV > Aux Run Threshold
• Check if the Aux Control Device faceplate if input is in Substitute PV mode.

Check the on-delay timer preset for run determination.


Compressor will not load Check method for load request.

External load push button:


• Check the input signal on DIN channel-2.
• Check the channel fuse.

The Load button is located on the HMI Operator screen - security privilege is
required.
Digital input signal is wired to Check the wiring for the input on TS1.
controller, but functionality does not Check the fuse for the input on TS1.
work Check that the DI status reports correctly on the IO screen for the digital input
module.
Check that the DI channel is configured for use.
Check that the input state for the channel is configured correctly.
Open the device faceplate, check if device in Substitute PV mode.
Analog input signal is wired to Check the wiring for the input on TS1. Verify that the polarity is correct.
controller, but functionality does not Check the fuse for the input on TS1.
work Check the analog input reading on the IO screen for the analog input module.
Raw counts read 0 at 4 mA, and 10000 at 20 mA.
Check that the AI channel is configured for use.
Check that the engineering unit range and scaling is configured correctly.
Open the device faceplate, check if device in Substitute PV mode.

180 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Index

A suction pressure high 176


suction pressure low 176
AC safety ground 16 suction temp overrange 176
access suction temp underrange 176
Device faceplate 128 suction temperature high 176
Hardware screen 165 suction temperature low 176
I/O Module Detail screen 168 surge test enabled 176
Interlocks Configuration screen 93 Alarm screen
Parameter Configuration screen 89 description 33
parameter list 89 security privileges 43
Permissives Configuration screen 93 alarms
Trend displays 153 manage 173
activate reset 177
human machine interface 25 view 177
activation key ID 25 analog input
adaptive tuning channel assignment 22
definition 143 channel status 171
features 11 configure 133
Adaptive Tuning Configuration page 142 operation 132
alarm icon processing 10
PV from input mode 132
status indications 173 substitute PV mode 132
alarm message 176
Analog Input Device faceplate 132
analog input module failure 174
analog output module failure 174 Analog Input Device screen
antisurge valve position error 174 security privileges 45
aux control signal overrange 174 analog input in substitute PV mode
aux control signal underrange 174 warning 117
auxiliary control signal high 174 Analog Input Module Detail screen 171
auxiliary control signal low 174 analog input module failure
capacity valve position error 174 alarm message 174
comm interface failure 174 analog input signal is wired to controller, but
compressor flow high 174
compressor flow low 174 functionality does not work 180
compressor flow overrange 174 analog inputs not working
compressor flow underrange 174 troubleshoot 163
compressor head fault 174 analog inputs ok
compressor surge detected 174 permissive 113
controller failure 174 analog output
digital input module failure 174 channel assignment 23
digital output module failure 175 channel status 172
discharge press overrange 175 configure 135
discharge press underrange 175 operation 134
discharge pressure high 175 processing 11
discharge pressure low 175 Analog Output Device faceplate 134
discharge temp overrange 175
discharge temp underrange 175 Analog Output Device screen
discharge temperature high 175 security privileges 45
discharge temperature low 175 Analog Output Module Detail screen 172
external trip 1 175 analog output module failure
external trip 2 175 alarm message 174
external trip 3 175 analog output not working
external trip 4 175 troubleshoot 163
incipient surge 175 analog outputs ok
minimum flow fallback 175
minimum IGV fallback 175 permissive 113
anti-surge control
multiple surge trip 176
multi-use signal A overrange 175 block diagram 10
multi-use signal A underrange 175 calculated values 101
multi-use signal B overrange 175 Compressor Overview page 97
multi-use signal B underrange 175 features 11
operating point (OP) fault 176 PID loop 141
suction press overrange 176 signal status 101
suction press underrange 176 view PID loops 104
anti-surge mode protection 142

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 181


Index

antisurge valve position error Compressor Details screen


alarm message 174 security privileges 47
antisurge vlv ready compressor flow low
permissive 113 alarm message 174
application mode status 166 compressor flow overrange
aux control signal overrange alarm message 174
alarm message 174 compressor flow underrange
aux control signal underrange alarm message 174
alarm message 174 compressor head
auxiliary control signal high features 11
alarm message 174 compressor head fault
auxiliary control signal low alarm message 174
alarm message 174 compressor is running, but run is not
indicated on the compressor
overview screen 180
B compressor map
battery status x-y plot 101
controller 166 Compressor Map page 101
buttons Compressor Overview page 97
toolbar 29 compressor ready-to-start
indications 119
compressor surge detected
C alarm message 174
capacity control compressor will not load 180
discharge throttling 100 compressor will not start 180
inlet guide vanes 99 configure
PID loop 106, 141
signal status 101 analog input 133
speed setpoint to speed controller 100 analog output 135
suction throttling 99 digital input 138
capacity decoupling digital output 140
interlock bypass 95
features 11 parameters 92
capacity valve position error permissive bypass 96
alarm message 174 PID loop 142
capacity/IGV ready control loops ready
permissive 113 permissive 113
change control margin
password 41 features 11
clock control slew rate
set (HMI) 168 features 11
comm interface failure control/track management
alarm message 174 features 11
communications interface controller
Modbus 159 download settings from HMI memory 93
compact flash card 93 features 19
compressor modify settings 92
control diagram 9 save values to memory 93
control mode 99 controller fails to power up
load 121 troubleshoot 163
process diagram 97 controller failure
running status conditions 120 alarm message 174
Compressor Details controller status 166
Anti-Surge and Capacity Valve page 150 application mode 166
Base Condition page 147 battery status 166
faceplate 146 Ethernet status 167
Head page 146 I/O system status 166
OP Tracking and Decoupling page 149 major fault status 167
Surge Configuration page 151 minor fault status 167
Surge Map page 148
Surge Test page 152

182 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Index

D discharge temperature low


data alarm message 175
discharge throttling
trend 157
default user capacity control 100
discharge transmitter
security 39
Compressor Overview page 98
Device faceplate
display buffer samples
access 128
overview 122 trend 158
download
device name
HMI settings to controller 93
default 130 parameters 92
digital input
drive controller
channel assignment 20
channel status 170 SSCC interface 118
dynamic compressor map
configure 138
operation 137 control limit line 102
processing 10 surge control limit line 102
Digital Input Device faceplate 137 surge limit line 102
Digital Input Device screen
security privileges 44 E
digital input in substitute PV mode
edit
warning 116
Digital Input Module Detail screen 170 interlock description 95
parameters 92
digital input module failure
permissive description 96
alarm message 174 electrostatic discharge
digital input signal is wired to controller, but
precautions 14
functionality does not work 180 enclosure (SSCC)
digital inputs not working mount 15
troubleshoot 163 environment
digital inputs ok requirements 15
permissive 113 Ethernet status 167
digital output external comp trip 1
channel assignment 21 interlock 109
channel status 171 external comp trip 2
configure 140
operation 139 interlock 109
external comp trip 3
processing 10
Digital Output Device faceplate 139 interlock 109
external comp trip 4
Digital Output Device screen
interlock 109
security privileges 45 external ready to start 1
Digital Output Module Detail screen 170
permissive 113
digital output module failure external ready to start 2
alarm message 175 permissive 113
digital outputs not working
external ready to start 3
troubleshoot 163
digital outputs ok permissive 113
external ready to start 4
permissive 113
permissive 113
discharge press overrange
external trip 1
alarm message 175
discharge press underrange alarm message 175
external trip 2
alarm message 175
discharge pressure high alarm message 175
external trip 3
alarm message 175
alarm message 175
discharge pressure low
external trip 4
alarm message 175
discharge temp overrange alarm message 175
alarm message 175
discharge temp underrange
alarm message 175
discharge temperature high
alarm message 175

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 183


Index

F interlock
check and reset 110
fallback to fixed polytropic exponent
configure bypass 95
warning 117 definition 107
flow measurement instrument requirements descriptions 109
98 management features 12
reset 110
status indications 109
G toolbar icon status indications 108
interlock and permissive bypassed
ground
warning 116
connections 16 interlock description
wire size 16
edit 95
Interlocks Configuration screen
H access 93
security privileges 44
Hardware screen Interlocks screen
access 165 description 35
Controller Status page 165
security privileges 43
Major/Minor Faults page 167
PanelView Plus Maintenance page 168
Hardware Status screen K
security privileges 44
head calc config error 179 key ID
warning 116 activation 25
Help screen
description 37 L
HMI. See human machine interface
holding registers legend
Modbus 160 trend 157
human machine interface load
activate 25 compressor control mode 99
exit graphics 168 log samples
login 39 trend 158
logout 41 login
memory 93 human machine interface 39
navigate 27 logout
security 38 human machine interface 41
set clock 168 loop mode
toolbar 29
PID control 141
loop setpoint
I PID control 142
I/O Module Detail screen
access 168 M
I/O modules 19
Maintenance screen
I/O system status 166 description 32
icons login 39
toolbar 29 security privileges 43
incipient surge major fault status 167
alarm message 175 manage
inlet guide vanes alarms 173
capacity control 99 manual control value
inspect PID control 142
SSCC 14 margin
installation adjustments 103
location requirements 15 configuration 104
SSCC enclosure 15 in use values 104
tools 15 parameters 104
instrument ground 16 Margin Control page 103
min/max selector
features 11

184 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Index

minimum flow fallback P


alarm message 175 PanelView
minimum IGV fallback
activate 25
alarm message 175 description 24
minor fault status 167
exit graphics 168
Modbus login 39
holding registers 160 logout 41
interface 159 memory 93
parameters 159 navigate 27
modify security 38
controller settings 92 set clock 168
mount toolbar 29
SSCC enclosure 15 PanelView fails to power up
multiple surge trip troubleshoot 163
alarm message 176 Parameter Configuration screen
interlock 109 access 89
multi-use signal A overrange description 90
alarm message 175 security privileges 44
multi-use signal A underrange parameter list
alarm message 175 01 AIN – Compressor Flow 53
multi-use signal B overrange 02 AIN – Suction Pressure 54
03 AIN – Discharge Pressure 55
alarm message 175
04 AIN – Auxiliary Control Signal 56
multi-use signal B underrange
05 AIN - Suction Temperature 57
alarm message 175 06 AIN – Discharge Temperature 58
07 AIN – Multi-use Signal A 59
08 AIN – Multi-use Signal B 60
N 09 Digital Input Channel Configuration 61
navigate 10 Digital Output Channel Configuration 63
HMI 27 11 Compressor Configuration Information 64
not logged in 12 Surge Map Definition 65
13 Surge and Margin Configuration 66
warning 116 14 Run and Load Configuration 68
15 Anti-Surge Control General Configuration
O 69
16 ASC Primary PID Loop 71
OP calc config error 179 17 ASC Primary PID Loop – Adaptive Integral
warning 116 72
operating point 18 ASC Primary PID Loop – Adaptive
features 11 Proportional 73
operating point (OP) fault 19 ASC Secondary PID Loop 74
20 Capacity Control General Configuration 76
alarm message 176 21 Capacity Primary PID Loop 78
operating point fault
22 Capacity Secondary PID Loop 80
interlock 109 23 Anti-Surge – Capacity Decoupling
operating point tracking Configuration 82
features 11 24 AINs – Substitute PV 83
operation 25 DINs – Substitute PV 84
analog input 132 26 Reserved for Future Use 84
digital input 137 27 Interlock Bypassable Configuration 85
digital output 139 28 Permissive Bypassable Configuration 86
PID loop 141 29 Modbus Serial Port Configuration 87
operator screen 30 Application (HMI-related Configuration)
descriptions 30 88
login 39 access 89
security privileges 43 action buttons 91
override limits
features 11

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 185


Index

parameters R
configure 92 ready-to-start
download 92
edit 92 compressor indications 119
Modbus 159 reset
restore 91 alarms 177
save 92 interlock 110
upload 91 permissive 114
view 92 restore
password parameters 91
change 41
initial 38
requirements 38, 39 S
permissive sampling rate
check and reset 114 trend 158
configure bypass 96 save
definition 107
descriptions 113 controller values to memory 93
HMI memory 93
management features 12
parameters 92
reset 114
security 38
status indications 113
toolbar icon status indications 112 default user 39
permissive description HMI 38
initial password 38
edit 96 password 38, 39
Permissives Configuration screen
user name 38
access 93 user roles 38
security privileges 44 security privileges
Permissives screen
Alarm screen 43
description 36 Analog Input Device screen 45
security privileges 43 Analog Output Device screen 45
PID control Compressor Details screen 47
features 11 Digital Input Device screen 44
loop mode 141 Digital Output Device screen 45
loop setpoint 142 Hardware Status screen 44
manual control value 142 Interlocks Configuration screen 44
PID loop Interlocks screen 43
anti-surge control 141 Maintenance screen 43
capacity control 106, 141 operator screen 43
configure 142 Parameter Configuration screen 44
operation 141 Permissives Configuration screen 44
PID Loop Device screen Permissives screen 43
security privileges 46 PID Loop Device screen 46
PID Loop faceplate 141 user roles 43
set clock
plot area
HMI 168
trend 157
single stage compressor controller
plot control buttons
components 13
trend 157 install 13
power distribution 16
interface to drive controller 118
power related symptoms power up 17
troubleshoot 163 specifications
power up trend 158
SSCC 17 speed setpoint to speed controller
processing capacity control 100
analog input 10 SSCC. See single stage compressor controller
analog output 11 Standard Tuning Configuration page 145
digital input 10
digital output 10 status
product ID number permissives 113
substitute PV mode
activation 25
PV from input mode analog input 132
suction press overrange
analog input 132
alarm message 176

186 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Index

suction press underrange Trend displays


alarm message 176 access 153
suction pressure high Trend Select screen
alarm message 176 description 34
suction pressure low troubleshoot
alarm message 176 analog inputs not working 163
suction temp overrange analog output not working 163
alarm message 176 controller fails to power up 163
suction temp underrange digital inputs not working 163
alarm message 176 digital outputs not working 163
suction temperature high PanelView fails to power up 163
power related symptoms 163
alarm message 176
suction temperature low
alarm message 176 U
suction throttling
unit status indicator
capacity control 99
suction transmitter description 98
unload
compressor overview page 98
surge compressor control mode 99
unpack
control algorithm 9
surge detection SSCC 14
upload
features 11
surge map parameters 91
user name
features 11
surge map config error 179 requirements 38
security 38
warning 116 user roles
surge test
security 38
ASC mode protection bypassed security privileges 43
warning 117
surge test and capture
features 12 V
surge test enabled 176
view
system serial number
alarms 177
activation 25 anti-surge control PID loops 104
parameters 92
T
toolbar W
HMI 29 warning
touchscreen 24 check and reset 117
trend definition 107
data 157 descriptions 116
display buffer samples 158 status indications 116
legend 157 toolbar icon status indications 115
log samples 158 Warnings screen
plot area 157 decription 34
plot control buttons 157 wire size
sampling rate 158 ground 16
specifications 158
x-axis 158
y-axis 158 X
Trend Detail
Analog Inputs screen 155 x-axis
ASC01 Control screen 154 trend 158
ASC02 Control screen 154 x-y plot
Aux / Flow PV screen 156 compressor map 101
Cap01 Control screen 154
Cap02 Control screen 155
Compressor screen 156 Y
Valve Control screen 156 y-axis
trend 158

Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 187


Index

188 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012


Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample
code and links to software service packs, and a MySupport feature that you can customize to make the best use of these
tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical
information, support chat and forums, software updates, and to sign up for product notification updates.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Publication 1711-UM002A-EN-P - September 2012


Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like