201A Series: Protection Relays

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Protection Relays

Voltage Monitoring Relays

201A SERIES
3-Phase Voltage/Phase Monitor

Description
The 201A is a 3-phase, auto-ranging, dual-range voltage monitor
that protects 190-480 V ac, 50/60 Hz motors regardless of size.
The product provides a user selectable nominal voltage setpoint
and the voltage monitor automatically selects between the
200 V and 400 V range. The 201A includes advanced single LED
diagnostics, where color and light patterns distinguish between
faults and normal conditions.
This unique microcontroller-based voltage and phase-sensing
device constantly monitors the 3-phase voltages to detect
harmful power line conditions. When a harmful condition is
detected, the 201A’s output relay is deactivated after a specified
trip delay. The output relay reactivates after power line conditions
return to acceptable levels for a specified restart delay time.

Features & Benefits


FEATURES BENEFITS
Wiring Diagram Proprietary Constant monitoring of single-phase, low voltage,
201A WITH MOTOR CONTROL microcontroller voltage unbalance, phase reversal, harmful power
based circuitry line conditions. High voltage monitoring optional.
Compact design for 8-pin; Allows flexiblility in panel installation
DIN rail or surface mount
Auto-sensing wide Automatically senses system voltage between
voltage range 190 - 480 V ac. Saves setup time.
Quick visual indicator for cause of trip. LED
Advanced LED indications include: normal operation, power-up
diagnostics restart delay, reverse-phase trip, unbalance/
single-phase trip, high/low voltage trip

Accessories
OT08PC Octal 8-pin Socket
8-pin 35 mm DIN rail or surface mount. Rated at
10 A @ 600 V ac. Surface mounted with two #6
screws or snaps onto a 35 mm DIN rail.
201A WITH ALARM CONTROL

Ordering Information
MODEL LINE VOLTAGE DESCRIPTION

201A 190–480VAC DIN rail or surface mountable


Includes high voltage detection. DIN rail or
201A-9 190–480VAC
surface mountable

© 2020 Littelfuse, Inc. Rev: 2-A-061220


1-A-062716
www.littelfuse.com/
www.littelfuse.com/201a
Protection Relays
Voltage Monitoring Relays

201A SERIES

Specifications Standards Passed


Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Frequency 50/60 Hz
Radio Frequency Immunity
Functional Characteristics
(RFI), Radiated 150MHz, 10 V/m
Low Voltage (% of setpoint)
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power
Trip 90 % ±1 %
& controls
Reset 93 % ±1 %
Surge
Voltage Unbalance (NEMA)
Immunity IEC IEC 61000-4-5, Level 3, 4 kV line-to-line;
Trip 6%
Level 4, 4 kV line-to-ground
Reset 4.5 %
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to
Optional High Voltage
a level of 6 kV line-to-line
(% of setpoint)
Hi-potential Test Meets UL508 (2 x rated V + 1000V for 1 min.)
Trip 110 % ±1 %
Safety Marks
Reset 107 % ±1 %
UL (OT08PC octal
Trip Delay Time
socket required) UL 508 (File #E68520)
High/Low Voltage Fault 4 seconds
Dimensions H 44.45 mm (1.75”); W 60.33 mm (2.38”);
Unbalance & Phasing Faults 2 seconds
D (with socket) 104.78 mm (4.13”)
Restart Delay Time
Weight 0.7 lbs. (11.2 oz., 317.51 g)
After a Fault 2 seconds
Mounting Method DIN rail or surface mount
After a Complete Power Loss 2 seconds
(plug in to OT08PC socket)
Output Characteristics
Socket Available Model OT08PC (UL Rating 600 V)
Output Contact Rating (SPDT)
Pilot Duty 480 VA @ 240 V ac
The 600 V socket can be surface mounted or installed on DIN Rail.
General Purpose 10 A @ 240 V ac
Note: Manufacturer’s recommended screw terminal torque for the OT Series Octal Sockets is
General Characteristics
12 in.-lbs.
Temperature Range -20° to 70°C (-4° to 158°F)
Must use Model OT08PC socket for UL Rating!
Trip & Reset Accuracy ±1%
Maximum Input Power 5W
Relative Humidity 10–95%, non-condensing per IEC 68-2-3
Terminal Torque 12 in.-lbs. (for OT08-PC socket)
Wire Gauge 12-22 AWG solid or stranded
Transient Protection
(Internal) 2500 V for 10 ms

© 2020 Littelfuse, Inc. Rev: 2-A-061220


1-A-062716
www.littelfuse.com/
www.littelfuse.com/201a

You might also like