C1.5 11ekw 50Hz Spec Sheet HEX Open

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CAT C1.5 generator set.

Image may not reflect actual generator set offered.

Technical specification for C1.5 Heat Exchanger cooled open


generator set with rating 11ekW @ 1500rpm 50Hz
GENSET SPECIFICATIONS Project no
CAT C1.5 11ekW Yard no
CAT GENERATOR 11ekW 50Hz Date

Caterpillar diesel engine, type C1.5, a 4-stroke, 3-cylinder indirect injection Inline-engine, naturally
aspirated

1.0 Basic model


1.1 Caterpillar model C1.5 DINA
1.2 Rating 11 ekW ±3%1) at 1500 rpm
1.3 Specification 4-stroke, electronically indirect injection Inline-engine naturally
aspirated
1.4 Rotation SAE standard, CCW viewed towards flywheel
1.5 Dimensions Displacement: 1,5 liters
Bore: 84 mm
Stroke: 90 mm
1.6 Dry weight 332 kg WO Sound Enclosure
1.7 Voltage Voltage for all pumps and starters, unless otherwise stated in spec:
3 x 220/380V 50Hz
Note1)
Engine performance is corrected to inlet air standard conditions of 99kPa and 25 oC. These values
correspond to the standard atmospheric pressure and temperature in accordance with SAE J1995. Also
included is a correction to standard fuel gravity and 35 degrees API having a lower heating value of
42,780kJ/kg when used at 29 oC where the density is 838,9 g/l.

2.0 Generator
2.1 Generator CAT
2.2 Generator IP 23
specifications 220/380V 50Hz
14 KVA
PF: 0,8
Max ambient temp 45 deg C
2.3 Cooling IP23 air cooled
2.4 Bearings Roller bearing NDE
2.5 AVR Solid state analogue voltage regulator

3.0 Cooling system


3.1 Cooling system Heat exchanger cooled
3.2 HT Cooling system Belt driven HT pump, centrifugal type
Gear driven SW pump
Integrated tube and shell heat exchanger
Expansion tank
3.3 Yard Supplied Cooling Water Equipment:
SW supply
All external piping and valves
GENSET SPECIFICATIONS Project no
CAT C1.5 11ekW Yard no
CAT GENERATOR 11ekW 50Hz Date

4.0 Exhaust system


4.1 Exhaust Maximum design backpressure 4,5kPa.
specifications Dry exhaust system
4.2 Exhaust manifold Weld flange and gasket
4.3 Optional Dry exhaust silencers available on request
Ask for quote.

5.0 Air Inlet system


5.1 Air Inlet Max air inlet temp 45 deg C
specifications
5.2 Air Cleaners Dry type air cleaners included

6.0 Fuel system


6.1 Fuel system Mechanical engine pump with fuel injectors and glow plugs
6.2 Fuel specifications Fuel type according to ISO8217, DMA/DMB/DMC (MGO/MDO)
6.3 Fuel lines Double wall fuel lines With mounted alarm reservoir. Provides
installed alarm reservoir.
6.4 Fuel Filters Simplex engine filters with manual priming pump.
6.5 Shipped loose Primary fuel FLTR/Water separator with NPT and BSP connections

7.0 Lube oil system


7.1 Lube oil system Closed system and closed crankcase ventilation. Oil filler and dipstick
7.2 Lube specifications According to Cat specifications
7.3 Lube oil Filters Engine oil filters
7.4 Shipped loose Oil Pan Drain Pump - Brass with 3/8" BSP male connection

8.0 Starting system


8.1 Starting system Electric Starting motor
8.2 Starting motor 24V Starting motor
specifications Negative isolated ground electric system
8.3 Yard Supply Starting equipment:
Set of batteries
Battery charger

9.0 Engine control


system
9.1 Engine control Electronic governor
system
GENSET SPECIFICATIONS Project no
CAT C1.5 11ekW Yard no
CAT GENERATOR 11ekW 50Hz Date

10.0 Instrumentation
10.1 Control system CAT Deluxe Instrument Panel 24V
Local start/stop and alarms
10.2 Shipped loose Harness from engine to remote mounted CAT Deluxe instrument
panel. 6 m
10.3 Yard supply 24V DC 10A power supply

11.0 Mounting
system
11.1 Mounting system Engine and generator resiliently mounted to a common baseframe
for fixed assembly towards ship structure.
11.2 Coupling Coupling plate
specifications

12.0 Paint
12.1 Engine paint Caterpillar matterhorn white

13.0 Tests
13.1 Engine tests Engine Test at 100 and 10% Overload including Start Stop
Retrospective Engine Certification is not possible.

14.0 Society
Approval
14.1 Certificates NA
Type Approval not required below 37kW. PC not available
14.2 Environmental NA
certificates No EIAPP needed below 130kW