7UT CT-Requirements en
7UT CT-Requirements en
7UT CT-Requirements en
§ Basics
§ Magnitude and angle errors of current transformers
§ Transients
§ Design
§ Summary of current transformers
Current transformers
insulator-type transformer
slip-over transformer
N
I‘p = Ip. 1
N2
Equivalent circuit:
Ip I‘p Rct e
Is Magnitude
error
N1 N2 I0 Is
L0 E U2 Rba
Note:
The secondary current is leading
(positive angle error) I0
© Siemens AG 2015. All rights reserved.
Page 4 30.06.2015 Energy Automation Division Energy Management
Basics
Defined errors at the P class
Definition:
5 P 20 30 VA
Rated burden
Rated accuracy limiting factor (ALFN old n)
accuracy in % at ALFN · IN
% minute centigrade %
5P ±1 ±60 ±1,8 5
10P* ±3 ¾ ¾ 10
All values are valid for steady state conditions (symmetrical currents)
* fault angle is not specified in IEC 61869-2, therefore, the Class 10P for the differential protection is not recommended.
© Siemens AG 2015. All rights reserved.
Page 5 30.06.2015 Energy Automation Division Energy Management
Basics
Influence of the burden on the errors
Improvement
Under of the saturation
burden degree
10 burden = 15 VA
Fi = 10%
Note:
burden > 15 VA The burden is mainly
determined by the instrument
5
leads.
10P10, 15 VA Over
burden
0 5 10 15 Iprimary/In
E = Is·(Rct + Rba)
I0
© Siemens AG 2015. All rights reserved.
Page 8 30.06.2015 Energy Automation Division Energy Management
Basics
Special features of class P CTs
Problem:
Remanence § Current transformer is magnetized e.g. via
switching off of a transient current with a large
Hysterese
DC time constant. He remains in the resulting
Initial
remanence point.
magnetizing
curve
§ An new fault current can immediately lead to a
saturation. Reason: The process starts from the
remanence point (worst case: 80%)
§ The actual value of remanence is unknown (e.g.
the fault current can also start in the opposite
direction). This leads to a reduction of
remanence)
Primary- and
I‘p [A]
secondary IS [A]
current
CT goes into
saturation
Magnetizing I0 [A]
current
Trip
45°
Block
69 kV Industrial infeed
30 km
12 MVA
6,9 kV
G1 G2
5,6 MVA G G
© Siemens AG 2015. All rights reserved.
Page 12 30.06.2015 Energy Automation Division Energy Management
Current differential protection
Switching on of external loads can lead to problems 2/3
Different DC transient
transmission leads to a
small increased differential
current with a low
0,15 stabilizing current
0,18 Countermeasure:
Increasing of the
inclination of slope 1 from
0,15 to 0,25 (factory
setting)
ALF = K td × K SSC
R BC + R Ct
ALF' = ALF
R BN + R Ct
ALF'
Recommendation:
As remanence leads to earlier saturation which, in general, is critical for the differential protection. For new
systems, Siemens recommends anti-remanence cores in the classes 5PR, PXR and TPY. In case of the high
direct-current components to be expected, Siemens recommends the class TPZ, so that an overfunction with
external faults is avoided. © Siemens AG 2015. All rights reserved.
Page 17 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
CT verification 1/5
l= 60m
110 kV, 50Hz A= 4mm2
7UT85
-T (T HV) -T1
1250/1A 200MVA
5P30 110/30 kV
5 VA 50 Hz
Rct = 18Ω uk = 14%
a.)IEC class 5P
31500 A
1. Internal fault : ALF' = 0.5 × = 12.6
1250 A
7498 A
2. External fault : ALF' = 2 × = 12 " but minimum 25"
1250 A
Result :
Operating accuracy limiting factor of ³ 25, for example : 5P30, R b = Sr /I sr ³ connected burden
R ba for example : Sr = 2.5 VA or 5 VA - > 5P30 5VA
S n 5 VA
Rb = 2
= = 5Ω
I sn 1A 2
2×ρ ×l
R ba = R Cable + R Relay = + 0.1 Ω
A
Ω mm 2
2 × 0.0175 × 60 m
= m + 0.1 Ω = 0.625 Ω
4 mm 2 ALF required = 25
ALF CT = 37.05
CT: 25 < 37.05
R Ct + R BN 18 Ω + 5 Ω
ALF = ALF N × = 30 × = 37.05 à CT Dimensioning is okay
R Ct + R BC 18 Ω + 0.625 Ω
Present practice:
Current applications live the risk of remanence (low probability assumed) and
trust the saturation detection in the relays