Ⅰ. Brief introduction
ETCR3200 Double Clamp Multi-function Grounding Resistance Tester specially design for the
measurement of earth resistance, soil resistivity, earth voltage, leakage current of grounding line, AC
current, DC resistance. Adopting the latest digital technology, precise 4-pole, 3-pole and simple 2-pole
method, selection method, double clamp method to measure grounding resistance, for earth
resistance measurement; large caliber clamp design, can use to measure the grounding system which
adopt large-scale down conductor; can flexibly and precisely measure the value of grounding resistance
in every complicated situation like single point grounding, grounding mesh; it is not need to disconnect
any parallel connection pole when measuring parallel-grounding, and massively improve the
convenience when measuring. Importing FFT and AFC technology, with a unique function of
anti-interference capability and the ability to adapt to the environment, consistency of repeat testing, to
ensure high precision, high stability and reliability for prolonged measure, which is widely used in electric
power, telecommunications, meteorology, oil field, construction, lightning protection, industrial electrical
equipment and other earth resistance, soil resistivity, earth voltage, AC voltage measurement.
ETCR3200 Double Clamp Multi-function Grounding Resistance Tester is composed of host machine,
monitoring software, testing wires, auxiliary ground pillars, communication wires and others. The large
LCD display of host machine is with blue backlight and bar graph indicating that can be seen clearly. At
the same time it can store 100 sets of data, fulfilling historical inquiry and online real-time monitoring
through monitoring software, dynamic display, and alarm indicator, auto-shut down and with the
functions like historical data access, reading, preservation, report forms, printing and so on.
Ⅱ. Technical specification
1.Base Conditions and Working Conditions
Influence Quantity Base Condition Working Conditions Remark
Ambient Temp 23℃±1℃ -10℃-40℃ ----
Ambient Humidity 40%-60% <80% ----
Working Voltage 9V±0.1V 9V±1.5V rC、rP
Auxiliary Earth Resistance <100Ω <30kΩ ----
Interference Voltage None <20V ----
Interference Current none <2A
Electrode Distance when measuring R a>5d a>5d ----
Electrode Distance when measuring ρ a>20h a>20h ----
2.General specification
Measure grounding resistance, soil resistivity; Measurement of earth voltage,
Function
AC voltage, leakage current of AC current
DC 9V(Zn-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300
Power Supply
hours )
Backlight Blue screen backlight, suitable for dim places
Precise 4-pole measurement, 3-pole measurement, simple 2-pole
Measuring Mode measurement, selection method, double clamp method measure grounding
resistance
2/3/4 pole method: change-pole method, measurement current 20mA Max
Selection method: change-pole method, measurement current 20mA Max
Double clamp method: disconnect mutual inductance method, measurement
Measuring current 1mA Max
Method Soil Resistivity: 4-pole measurement (Wenner method)
DC resistance: change-pole method
AC current: mutual inductance method
Earth Voltage: average rectification(between P(S)-ES)
Test Voltage
Sine wave
Wave
Test Frequency 128Hz/111Hz/105Hz/94Hz(AFC)
Short-circuit Test AC 20mA max
3
Current
Open-circuit Test
AC 40V max
Current
Electrode
Can be set 1m-100m
Distance Range
Display Mode 4-digital super-large LCD display, blue screen backlight
Measuring During measurement, LED flash indicator, LCD countdown display, progress
Indicator bar indicator
LCD Frame
128mm×75mm
Dimension
LCD Window
124mm×67mm
Dimension
Dimension L×W×H: 215mm×190mm×95mm
Size of clamp LxWxH:185mmX115mmX43mm
Standard Test
4 wires: each for red 20m, black 20m, yellow 10m, and green 10m
Wire
Simple Test Wire 2 wires: each for red 1.6m and black 1.6m
Auxiliary 4 wires: Φ10mm×150mm Over 5000 times (Short-circuit test, interval time
Grounding Rod should be at least 30 seconds)
Clamp 2pc :1 blue-black plug and 1 red-black.
Caliber of clamp Φ68mm
Turn Ratio 1000 :1
Lead line of
2m
clamp
AC current: about 2 times/second
Measuring Rate Voltage to ground: about 2 times/second
Earth resistance, soil resistivity: about 7 seconds/time
Measuring Times Over 5000 times (Short-circuit test, interval time should be at least 30
Voltage of circuit AC 600V
RS232 interface, software supervision, storage data can be uploaded to
RS232 Interface
computer, saved or printed.
Communication
One piece of RS232 communication wire, with length 1.5m
Wire
Data Hold Data hold function: “HOLD” icon display
Data Storage 2000 sets, “MEM” storage indicator, flash display “FULL” icon to indicate
Data Read Data read function: “READ” icon display
Overflow Display Exceeding measuring range overflow function: “OL” icon display
Low current When use select method or double clamp to measure, and the current signal
direction of CT2 receive is lower than 0.5mA,and” ” display, then would check the
clamp direction of CT2 clamp into
Recognize interference signal automatically, “NOISE” icon display when
Interference Test
interference voltage exceed 5V
Auxiliary Can measure auxiliary earth resistance, 0.00KΩ-30kΩ(100R+rC<50kΩ,
Grounding Test 100R+rP<50kΩ)
When measuring value exceeds alarm setting value, there is “Toot-toot-toot”
Alarm Function
alarm hint
When battery voltage decreases to about 7.5V, battery voltage low icon
Battery Voltage
will display, reminding to replace battery.
Auto-shut off Automaticlly shut down 15minutes after booting
Standby: about 25mA Max(Backlight shut off)
Power
Boot 25mA Max(without backlight)
Consumption
Measurement: about 150mA Max(Backlight shut off)
Total weight: 8.05kg (including package)
Tester: 1653g (including battery)
Weight
Testing wires: 1560g
Auxiliary grounding rods: 935g (4pcs)
Working -10℃-40℃, below 80%rh
4
Temperature &
Humidity
Storage
temperature & -20℃-60℃, below 70%rh
humidity
Overload Earth resistance: between each interfaces of C(H)-E、P(S)-ES, AC 280V/3
Protection seconds
Insulation
Over 20MΩ (between circuit and enclosure it is 500V)
Resistance
Withstanding
AC 3700V/rms. (Between circuit and enclosure)
Voltage
Electromagnetic
IEC61326(EMC)
Features
IEC61010-1 (CAT Ⅲ 300V、CAT IV 150V、Pollution 2), IEC61010-031;
IEC61557-1 (Earth resistance);
Protection Type IEC61557-5 (Soil resistivity);
JJG 366-2004(Grounding resistance meter)
JJG 1054-2009(Clamp grounding resistance meter)
5
Ⅲ. Structure of tester
Ⅳ. LCD display
6
1. Bar graph of testing process(dynamically display the process of measurement,)
2. Alarm direction symbol (the icon will display when the alarm function has been boot, and it will
flash display when the value is over the alarm value)
3. The direction of overvoltage(it will display when the voltage to be measure is over 30V, safety
warning )
4. AC direction
5. Data hold direction(it will display when press MEM to keep the data)
6. Data read direction(it will display when press MEM for 3 second to read the data)
7. Data storage direction(it will display when press MEM to hold the data and store the data at the
same time)
8. Signal interference direction(it will display when the interference voltage is over 5V)
9. Low voltage direction(it will display when the voltage of battery is below 7.5V )
10. Direction of the number of sets of data has been stored
11. Direction of the current signal of current clamp CT2 is too low(it will display when the current
signal CT2 has received is lower than 0.5mA, it may because CT2 clamp into the opposite
direction)
12. Interference pole direction(it will display when the pole has been interfered)
13. Data display
14. Unit symbol of voltage
15. Unit symbol of resistance, soil resistivity, current, length
Ⅴ. Principle of measurement
1. 3 wires and 4 wires method to measure grounding resistance adopt rate current pole changing
method (suit for accurately measure the single point grounding system), it means to measure the AC
rate current I between grounding electrode object E and current electrode C(H),calculating the
potential difference between grounding electrode E and voltage electrode P(s),base on the formula
R=V/I to calculate the grounding resistance R. To ensure the accuracy of measurement, we adopt 4
wires method, add ES auxiliary grounding electrode, ES and E clip at the same point of the
grounding body when testing.
2. Selection method to measure grounding resistance adopt current change-pole method (suit for
measuring one of earth screen grounding resistance of parallel connection grounding system without
grounding wire disconnect.), add AC current I between Re1 Re2 Re3 grounding electrode and C(H)
7
electrode, measure I3 which flow through Re3 by CT2, measure the potential difference V between
Re3 grounding electrode and P(s) electrode, calculate the grounding resistance Re3 base on
formula Re3=v/I3. To ensure the accuracy of measurement, adopt 4 wires method, add ES auxiliary
electrode, ES and E clip at the same point of the grounding body when testing.
3. Double clamp method to measure grounding resistance (suit for measurement of multiple
independent point parallel connecting grounding system without auxiliary rod), generate an AC
electromotive force V by excitation clamp CT1; under the effect of AC electromotive force V,
generate a current I in the circuit, and get its value by CT2; base on formula R=V/I, calculate the
value of resistance. In the graph below, R=Re+R1//R2//R3// · · · Rn-1//Rn, if
Re+R1//R2//R3//· ··Rn-1//Rn (resistance of multiple grounding point parallel connect) is much less
than Re, then R≈Re.
4. The measurement of Soil resistivity (ρ) adopt 4-pole method (wenner): There is a AC current I
between E grounding electrode and C(H) current electrode, find the potential difference V between
P(S) voltage electrode and ES auxiliary grounding electrode, the potential difference V divided by AC
current I is earth resistance R, electrode distance is a(m), then soil resistivity can be got according to
formula ρ=2πaR(Ωm). If the electrode distance of C(H)-P(S) is equal to P(S)-ES (both is a) that is
for wenner method. In order to simple the calculation, please make electrode distance a far more
than embedding depth h, generally should meet a>20h, as shown below.
8
5. 2/3/4 wires DC resistance measurement adopt rated current change-pole method(suit for
equipotential bonding resistance measurement test),it means to measure the direct rated current I
flow through measurement target R, find the potential difference V of both ends of R, calculate the
resistance value of R base on formula R=V/I. To insure the accuracy of measurement, adopt 4 wires
method, and add ES auxiliary rod, ES and E clip at the same point of the grounding body when
testing.
6. Operating error (B) of the method mention above is under the nominal working conditions, it can be
found by the inherent error (A) and variable error (Ei).
Ⅵ. Operation Methods
1.Switch On/Off
Rotate FUNCTION rotary switch to fulfill switch on and off. When rotary switch button displays “OFF”
for shut-off. The tester has no auto shut-off function, so please shut it off after usage in case of battery
consumption saving.
9
3.4 wires Precise Earth Resistance Measurement
In the testing of earth resistance, should firstly confirm the earth voltage of grounding
wire, the voltage between C(H) and E or P(s) and ES must under 20V, the meter
showing NOISE symbols when the earth voltage exceed 5V, and the measured value of
earth resistance may produce error. At this time, firstly interrupt power supply to
grounding equipment, make sure the earth voltage decrease, and then test earth
resistance again.
4-wires measurement: The 4-wires method can eliminate influence of contact resistance (usually
result from dirty or rusty) between measured grounding body, auxiliary grounding rods, test clips,
meter’s input interface. The 4-wires method can also eliminate influence of line resistance. So it is
better than 3-wires measurement.
As shown below: Start from the measured body, interval 5m-20m, respectively insert P(S), C(H)
auxiliary grounding rods deep into the earth in a straight line, and then connect testing wires (black,
green, yellow, red) from E, ES, P(S), C(H) interfaces corresponding to measured earth electrode E,
auxiliary voltage electrode P(S), auxiliary current electrode C(H).
The distance from measured grounding body to current electrode C(H), should at least
five times deeper than the embedded depth of measured grounding body, or the
embedded electrode depth (d).
When measuring the total earth resistance of complex grounding system, d is the length
of the biggest diagonal line of this grounding system.
Testing wires can’t be winded together, or may affect the measuring accuracy.
For multi independent grounding system or larger earth net, 50m or longer testing wire is optional,
as shown below:
After finishing wires connection, firstly rotate FUNCTION rotary switch to “ ”, press “START”
button to resistance testing mode. During testing, display countdown and process bar indicator.
Stable earth resistance value is shown when finish testing.
For multi independent grounding system or larger earth net, 50m or longer testing wire is optional, as
shown below: the result is grounding resistance of Re has nothing to do with r1,r2,r3,r4,r5···
13
As shown below: use 4 wires selection method can precisely measure the grounding resistance Re of
the tower under the condition of the grounding line is connected; the value of grounding resistance is the
result of Re parallel connect with R1, R2, R3 if use traditional way like 3 wires 4 wires method under the
condition of the grounding line is connected; if there is a fault with Re, at the same time, the value after
R1, R2, R3 parallel connect is small, in this situation, traditional 3 wires 4 wires method is hard to find the
fault point, and it is easy to be ignored.
14
When testing the grounding resistance, firstly confirm the value of leakage of the
grounding line, and the current of the grounding line should below 2A; current of
grounding line over 100mA, there would be error with the value of grounding
resistance, At this time, firstly interrupt power supply to grounding equipment, make
sure the earth voltage decrease, and then test earth resistance again. At the same
time have to ensure the current flow from front of the clamp; otherwise, the grounding
resistance can’t be test in normal way. When “ ” display in the screen, it means
current signal CT2 received is too low, then should check whether CT2 has clamped
the wires in a right way, the direction of CT2 is right, the resistance of the circuit is too
big or doesn’t form a loop. The two clamps has to keep a distance above 30cm,
otherwise, there is an error exist.
After finishing wires connection, firstly rotate FUNCTION rotary switch to” ”, press “START”
button to resistance testing mode. During testing, display countdown and process bar indicator. Stable
earth resistance value is shown when finish testing and that is the resistance of grounding body:
R=Re+R1//R2//R3, if Re+R1//R2//R3<<Re, R can be regarding as Re: R≈Re
15
The value of soil resistance confirm by wenner method is approximate the soil resistance of two rods
which has a distance a between them.
Setting distance between auxiliary grounding rods: After finishing wires connection, firstly rotate
FUNCTION rotary switch to “ρEARTH”, long press “SET” button (about 3 seconds) to enter setting,
short press “SET” button to move the cursor, press “ ”or “ ” button to change current data
value (a range: 1m-100m), then long press “SET” button to save the set a value, and return soil
resistivity testing mode.
After setting a value, in soil resistivity testing mode, press the “START” button to start testing, and
countdown display testing process, stable soil resistivity value is shown when finish testing.
As shown below, the measured soil resistivity is 53.38Ωm, already stored 157 sets of data. Press
“SET” button, the earth resistance rC of auxiliary current electrode C(H) and earth resistance rP of
auxiliary voltage electrode P(S) will be displayed, and then automatically return display of measured
soil resistivity ρ.
16
When connection is done, rotate” FUNCTION“ switch to” ”, and press” START” button to enter
resistance testing mode. During testing, display countdown and process bar indicator. Stable values
shown on the screen is equipotential connection resistance R between equipment and grounding
body when finish testing.
17
When the connection of current clamp is done, rotate FUNCTION switch to “Iclamp”, enter current
measurement mode, LCD display effective value directly, and bar chart indicate the change of
amplitude
14.Alarm Settings
After startup, rotate FUNCTION rotary switch to select function, press “ AL” button for a brief time to
open or shut off alarm function, press“ AL” button for a long time (about 3 seconds) to enter alarm
critical value settings, press “ ”or“ ” to change current digital, press “ AL” button to move
cursor and then press “ AL” button to store and exit. When measurement value is larger than alarm
critical settings value and it has opened alarm function, the tester will flash and display icon and
give out “toot-toot-toot--”alarming sound.
15.Data Lock/Storage
In test mode, press “MEM” button for a brief time to lock current displayed data, showing “HOLD”,
“MEM” icon and automatically store with serial numbers. If storage is full, the tester will display
“FULL” icon, and then press button to remove lock.
As shown in the left figure below: the lock measurement data of soil resistivity is 53.38Ωm, as the
18
28th group of data storage.
16.Data Reading/Deletion
In test mode, press “MEM” button for a longer time (over 3 seconds) to enter data reading, press
“ ”or“ ” button to select reading data group number by step value 1, press“ ”or“ ”button
constantly to select reading data group number by step value 10. When the current data is earth
resistance or soil resistivity, press “SET” button to read data value of rC, rP and a, then press “MEM”
button to exit from reading.
On reading if there is no storage data, LCD will display “- - - -”, see the above right figure.
Under data reading status, press “CLR” button to enter data deletion, press “ ”or“ ” to
select “no” or “yES”, selecting “no” and then pressing “CLR” button for not deleting and return data
reading status, selecting “yES” and then pressing “CLR” button for deleting stored data and it will
show as above right figure after deletion.
Notice: Operating data deletion will delete all the stored data one-time, and unable to be restored.
Please careful operation.
17.Data Upload
It is forbidden to connect to computer during testing; otherwise, earth voltage would destroy
computer or the instrument.
The stored data can be uploaded to computer. Make good connection of computer with RS232
communication wire of the tester, switch on the tester and run monitoring software, and if the
software displays that interface is open and the connection is successful, then it can read the stored
historical data, upload to company and preserve.
Monitoring software has the function of online real-time monitoring and historical inquiry, dynamic
display, with alarm value settings and alarm indicator, and the function of historical data access,
reading, preserve, print and other functions.
19
Ⅷ. ACCESSORIES
Tester 1 PC
Tester Bag 1 PC
Auxiliary Grounding Rod 4 PCS
Standard testing Wire 4 wires: each for red 20m, black 20m, yellow 10m, and green 10m
Simple testing Wire 2 wires: each for red 1.6m and black 1.6m
Current clamp 2PC
Zinc-manganese Dry Battery 6 PCS(R14S 1.5V)
Monitoring Software Disk 1 Copy
RS232 Communication Cable 1 PC
Manual/Warranty
1 Copy
Card/Qualification Certificate