1MRK504118-BEN B en Product Guide RET670 1.2 Pre-Configured
1MRK504118-BEN B en Product Guide RET670 1.2 Pre-Configured
1MRK504118-BEN B en Product Guide RET670 1.2 Pre-Configured
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes
no responsibility for any errors that may appear in this document.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Revision: B
ABB 3
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Serial data communication is via optical Optional functions are not configured but a
connections to ensure immunity against maximum configuration with all optional
disturbances. functions are available as template in the
graphical configuration tool. An alternative
The wide application flexibility makes this
for Autotransformers is also available as a
product an excellent choice for both new
configuration template. Analog and tripping
installations and the refurbishment of existing
IO has been pre-defined for basic use on the,
installations.
as standard supplied one binary input
Six packages have been defined for the module and one binary output module. Add
following applications: binary I/O as required for your application at
• Transformer back-up protection (A10) ordering. Other signals need to be applied as
• Voltage control (A25) required for each application.
• Two-winding transformer in single For details on included basic functions, refer
breaker arrangements (A30) to chapter "Basic IED functions"
• Two-winding transformer in multi
The applications are shown in figures 1, 2,
breaker arrangements (B30)
3and 4 for single resp. multi-breaker
• Three-winding transformer in single
arrangement.
breaker arrangements (A40)
• Three-winding transformer in multi
breaker arrangements (B40)
4 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
TRIP BUSBAR
50BF
3I>
51/67
3I>
94/86 CB1
4
TRIP CB1 I->O 4
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
94/86 4
TRIP CB2 50BF
I->O
3I>
25
59 SC/VC
CB2
3U>
2
TRIP BUSBAR
2
27
3U<
2
2
en05000272.vsd
IEC05000272 V1 EN
Figure 1. A typical protection application for a two winding transformer in single breaker
arrangements is shown on the figure. The system earthing principle and connection
group will vary which gives different detailed arrangements for each application.
ABB 5
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
TRIP BUSBAR&CB2
TRIP CB1/3
CB1
50BF
51/67 3I>
3I> S 50BF
94/86
4 3I>
TRIP CB1
I->O 4
51N/67N
94/86 IN>
TRIP CB2 4 CB2
I->O
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
94/86 4
TRIP CB3 50BF
I->O
3I>
25
59 SC/VC
3U> CB3
2
TRIP BUSBAR
2
&CB1/2
27
3U<
2
2
en05000273.vsd
IEC05000273 V1 EN
Figure 2. A typical protection application for a two winding transformer in multi breaker
arrangements is shown on the figure. The system earthing principle and connection
group will vary which gives different detailed arrangements for each application.
Breaker failure function is here provided for each breaker.
6 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
TRIP BUSBAR
50BF
3I>
51/67
94/86 3I>
4 CB1
TRIP CB1
I->O 4
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I> 50BF
TRIP BUSBAR
&CB1/2 3I>
51N/67N
IN>
4 3I>
4 4
51/67 4
3I>
4 94/86
94/86 4 TRIP
I->O CB3
TRIP CB2 50BF
I->O
3I>
25
SC/
59
VC CB2
3U>
2 59N
TRIP BUSBAR 2 UN>
&CB1/2/3
27 t2 2
2
3U<
2
2
en05000274.vsd
IEC05000274 V1 EN
Figure 3. A typical protection application for a three winding transformer in single breaker
arrangements is shown on the figure. The system earthing principle and connection
group will vary which gives different detailed arrangements for each application.
ABB 7
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
TRIP BUSBAR&CB2/3/4
CB1
50BF TRIP CB1/3/4/X
51/67
3I>
3I> S 50BF
94/86
4 3I>
TRIP CB1
I->O 4
51N/67N
94/86 IN>
TRIP CB2 4 CB2
I->O
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I> TRIP BUSBAR 50BF
&CB1/2/3 3I>
51N/67N
IN>
4 3I>
4 4
51/67 4
3I>
4 94/86
94/86 4 TRIP
I->O CB4
TRIP CB3 50BF
I->O
3I>
25
59 SC/VC
3U> CB3
2 59N
TRIP BUSBAR
2 UN>
&CB1/2/4
27 t2 2
2
3U<
2
2
en05000275.vsd
IEC05000275 V1 EN
Figure 4. A typical protection application for a three winding transformer in multi breaker
arrangements is shown on the figure. The system earthing principle and connection
group will vary which gives different detailed arrangements for each application.
Breaker failure function is here provided for each breaker.
8 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
2. Available functions
ABB 9
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Differential protection
T2WPDIF 87T Transformer differential 1 1
protection, two winding
T3WPDIF 87T Transformer differential 1 1
protection, three
winding
HZPDIF 87 1Ph high impedance 1 3- 3- 3- 3-
differential protection A02 A02 A02 A02
REFPDIF 87N Restricted earth fault 1 2 2 2-B/ 2-B/
protection, low 1- 1-
impedance A01 A01
Impedance protection
ZMQPDIS, 21 Distance protection 4- 4- 4- 4-
ZMQAPDIS zone, quadrilateral B12 B12 B12 B12
characteristic
ZDRDIR 21D Directional impedance 2- 2- 2- 2-
quadrilateral B12 B12 B12 B12
FDPSPDIS 21 Phase selection, 2- 2- 2- 2-
quadrilateral B12 B12 B12 B12
characteristic with fixed
angle
ZMHPDIS 21 Full-scheme distance 4- 4- 4- 4-
protection, mho B13 B13 B13 B13
characteristic
ZMMPDIS, 21 Full-scheme distance 4- 4- 4- 4-
ZMMAPDIS protection, quadrilaterial B13 B13 B13 B13
for earth faults
ZDMRDIR 21D Directional impedance 2- 2- 2- 2-
element for mho B13 B13 B13 B13
characteristic
ZDARDIR Additional distance 1- 1- 1- 1-
protection directional B13 B13 B13 B13
function for earth fault
10 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
ZSMGAPC Mho impedance 1- 1- 1- 1-
supervision logic B13 B13 B13 B13
FMPSPDIS 21 Faulty phase 2- 2- 2- 2-
identification with load B13 B13 B13 B13
enchroachment
ZMRPSB 78 Power swing detection 1- 1- 1- 1-
B12/- B12/- B12/- B12/-
B13 B13 B13 B13
ABB 11
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Current protection
PHPIOC 50 Instantaneous phase 3 2 2 3 3 2-
overcurrent protection C19
OC4PTOC 51_67 Four step phase 3 2 2 3 3 2-
overcurrent protection C19
EFPIOC 50N Instantaneous residual 3 2 2 3 3 2-
overcurrent protection C19
EF4PTOC 51N_6 Four step residual 3 2 2 3 3 2-
7N overcurrent protection C19
NS4PTOC 46I2 Four step directional 2- 2- 2- 3- 3- 2-
negative phase C42 C42 C42 C43 C43 C19
sequence overcurrent
protection
SDEPSDE 67N Sensitive directional 1 1- 1- 1- 1- 1-
residual overcurrent C16 C16 C16 C16 C16
and power protection
TRPTTR 49 Thermal overload 1 1B, 1B, 2B, 2B,
protection, two time 1- 1- 1- 1-
constant C05 C05 C05 C05
CCRBRF 50BF Breaker failure 3 2 4 3 6
protection
CCRPLD 52PD Pole discordance 1 2 1 2
protection
GUPPDUP 37 Directional 1- 1- 1- 1-
underpower protection C17 C17 C17 C17
GOPPDOP 32 Directional overpower 1- 1- 1- 1-
protection C17 C17 C17 C17
BRCPTOC 46 Broken conductor 1 1 1 1 1 1
check
Voltage protection
12 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
UV2PTUV 27 Two step undervoltage 1- 1B, 1B, 1B, 1B, 2-
protection D01 1- 1- 2- 2- D02
D01 D01 D02 D02
OV2PTOV 59 Two step overvoltage 1- 1B, 1B, 1B, 1B, 2-
protection D01 1- 1- 2- 2- D02
D01 D01 D02 D02
ROV2PTOV 59N Two step residual 1- 1B, 1B, 1B, 1B, 2-
overvoltage protection D01 1- 1- 2- 2- D02
D01 D01 D02 D02
OEXPVPH 24 Overexcitation 1- 1- 2- 2-
protection D03 D03 D04 D04
VDCPTOV 60 Voltage differential 2 2 2 2 2 2
protection
LOVPTUV 27 Loss of voltage check 1 1 1 1 1 1
Frequency protection
SAPTUF 81 Underfrequency 6-E01 6-E01 6-E01 6-E01 6-E01
protection
SAPTOP 81 Overfrequency 6-E01 6-E01 6-E01 6-E01 6-E01
protection
SAPFRC 81 Rate-of-change 6-E01 6-E01 6-E01 6-E01 6-E01
frequency protection
Multipurpose protection
CVGAPC General current and 6-F02 6-F02 6-F02 6-F02
voltage protection
ABB 13
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Control
SESRSYN 25 Synchrocheck, 1 1 1-B, 1-B, 1-B,
energizing check and 2- 3- 4-
synchronizing H01 H02 H03
APC30 3 Apparatus control for up 1- 1- 1- 1- 1-
to 6 bays, max 30 H09 H09 H09 H09 H09
apparatuses (6CBs) incl.
interlocking
QCBAY Apparatus control 1 1 1 1 1 1
Local Handling of LRswitch 1 1 1 1 1 1
Remote positions
LocRem LHMI control of PSTO 1 1 1 1 1 1
Control
TR1ATCC 90 Automatic voltage 1- 1- 1- 1- 2B,
control for tap changer, H11 H11 H11, H11, 2-
single control 2- 2- H16
H16 H16
TR8ATCC 90 Automatic voltage 1- 1- 1- 1- 2B,
control for tap changer, H15 H15 H15, H15, 2-
parallel control 2- 2- H18
H18 H18
TCMYLTC 84 Tap changer control and 4 4 4 4 4
supervision, 6 binary
inputs
TCLYLTC 84 Tap changer control and 4 4 4 4 4
supervision, 32 binary
inputs
SLGGIO Logic rotating switch for 15 15 15 15 15 15
function selection and
LHMI presentation
VSGGIO Selector mini switch 20 20 20 20 20 20
14 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
DPGGIO IEC61850 generic 16 16 16 16 16 16
communication I/O
functions
SPC8GGIO Single pole generic 5 5 5 5 5 5
control 8 signals
Automation AutomationBits, 3 3 3 3 3 3
Bits command function for
DNP3.0
Single command, 16 4 4 4 4 4 4
signals
VCTRSend Horizonal 7 7 7 7 7 7
communication via
GOOSE for VCTR
VCTR Horizontal 1 1 1 1 1 1
Receive communication via
GOOSE for VCTR
Secondary system supervision
CCSRDIF 87 Current circuit 2 3 3 5 4
supervision
SDDRFUF Fuse failure supervision 1 3 3 3 3
Logic
SMPPTRC 94 Tripping logic 3 2 3 5 6 2
TMAGGIO Trip matrix logic 12 12 12 12 12 12
Configuration logic 40-28 40-28 40-28 40-28 40-28 40-28
blocks 0 0 0 0 0 0
Fixed signal function 1 1 1 1 1 1
blocks
B16I Boolean 16 to Integer 16 16 16 16 16 16
conversion
B16IFCVI Boolean 16 to Integer 16 16 16 16 16 16
conversion with Logic
Node representation
ABB 15
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
IB16 Integer to Boolean 16 16 16 16 16 16 16
conversion
IB16FVCB Integer to Boolean 16 16 16 16 16 16 16
conversion with Logic
Node representation
Monitoring
CVMMXN Measurements 6 6 6 6 6 6
CNTGGIO Event counter 5 5 5 5 5 5
Event Event function 20 20 20 20 20 20
DRPRDRE Disturbance report 1 1 1 1 1 1
SPGGIO IEC61850 generic 64 64 64 64 64 64
communication I/O
functions
SP16GGIO IEC61850 generic 16 16 16 16 16 16
communication I/O
functions 16 inputs
MVGGIO IEC61850 generic 24 24 24 24 24 24
communication I/O
functions
BSStart Logical signal status 3 3 3 3 3 3
Report report
RANGE_XP Measured value 66 66 66 66 66 66
expander block
Metering
PCGGIO Pulse-counter logic 16 16 16 16 16 16
ETPMMTR Function for energy 6 6 6 6 6 6
calculation and demand
handling
16 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Designed to communicate
RET670 (A10)
RET670 (A30)
RET670 (B30)
RET670 (A40)
RET670 (B40)
RET670 (A25)
Station communication
SPA communication 1 1 1 1 1 1
protocol
LON communication 1 1 1 1 1 1
protocol
IEC60870-5-103 20/1 20/1 20/1 20/1 20/1 20/1
communication protocol
Operation selection 1 1 1 1 1 1
between SPA and
IEC60870-5-103 for SLM
DNP3.0 for TCP/IP and 1 1 1 1 1 1
EIA-485 communication
protocol
DNP3.0 fault records for 1 1 1 1 1 1
TCP/IP and EIA-485
communication protocol
Redundant station bus 1 1 1 1 1 1
communication
IEC61850-8-1, PRP
Parameter setting 1 1 1 1 1 1
function for IEC61850
IntlReceive Horizontal 59 59 59 59 59 59
communication via
GOOSE for interlocking
Goose binary receive 10 10 10 10 10 10
Multiple command and 60/1 60/1 60/1 60/1 60/1 60/1
transmit 0 0 0 0 0 0
Ethernet configuration 1 1 1 1 1 1
of links
DUODRV Duo driver configuration 1-P01 1-P01 1-P01 1-P01 1-P01 1-P01
Remote communication
ABB 17
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Binary signal transfer 6/36 6/36 6/36 6/36 6/36 6/36
receive/transmit
Transmission of analog 1 1 1 1 1 1
data from LDCM
Receive binary status 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
from remote LDCM
Scheme communication
ECPSCH 85 Scheme communication 1 1 1 1
logic for residual
overcurrent protection
ECRWPSCH 85 Current reversal and 1 1 1 1
weak-end infeed logic
for residual overcurrent
protection
18 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 19
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Three-winding applications
three-winding
power
transformer with
all three
windings
xx05000052.vsd connected
IEC05000052 V1 EN
20 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 21
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
22 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
The distance protection zones can operate, The heavy load transfer that is common in
independent of each other, in directional many transmission networks may in some
(forward or reverse) or non-directional mode. cases interfere with the distance protection
This makes them suitable, together with zone reach and cause unwanted operation.
different communication schemes, for the Therefore the function has a built in
protection of power lines and cables in algorithm for load encroachment, which gives
complex network configurations, such as the possibility to enlarge the resistive setting
parallel lines, multi-terminal lines. of the measuring zones without interfering
with the load.
Directional impedance element for
Mho characteristic ZDMRDIR The output signals from the phase selection
function produce important information
The phase-to-earth impedance elements can about faulty phase(s), which can be used for
be optionally supervised by a phase fault analysis as well.
unselective directional function (phase
unselective, because it is based on Power swing detection ZMRPSB
symmetrical components).
Power swings may occur after disconnection
Mho impedance supervision logic of heavy loads or trip of big generation plants.
ZSMGAPC Power swing detection function (ZMRPSB) is
The Mho impedance supervision logic used to detect power swings and initiate
(ZSMGAPC) includes features for fault block of selected distance protection zones.
inception detection and high SIR detection. It Occurrence of earth-fault currents during a
also includes the functionality for loss of power swing inhibits the ZMRPSB function to
potential logic as well as for the pilot channel allow fault clearance.
blocking scheme.
ZSMGAPC can mainly be decomposed in two
different parts:
1. A fault inception detection logic
5. Current protection
2. High SIR detection logic
Instantaneous phase overcurrent
Faulty phase identification with protection PHPIOC
load encroachment FMPSPDIS The instantaneous three phase overcurrent
function has a low transient overreach and
The operation of transmission networks
short tripping time to allow use as a high set
today is in many cases close to the stability
short-circuit protection function.
limit. Due to environmental considerations
the rate of expansion and reinforcement of Four step phase overcurrent
the power system is reduced, for example protection OC4PTOC
difficulties to get permission to build new
power lines. The ability to accurate and The four step phase overcurrent protection
reliable classifying the different types of fault function OC4PTOC has an inverse or definite
so that single phase tripping and time delay independent for step 1 and 4
autoreclosing can be used plays an important separately. Step 2 and 3 are always definite
roll in this matter. time delayed.
The phase selection function is design to All IEC and ANSI inverse time characteristics
accurately select the proper fault loop(s) in are available together with an optional user
the distance function dependent on the fault defined time characteristic.
type. The directional function is voltage polarized
with memory. The function can be set to be
ABB 23
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
directional or non-directional independently definite time delay independent for each step
for each of the steps. separately.
A 2nd harmonic blocking can be set All IEC and ANSI time delayed characteristics
individually for each step. are available together with an optional user
defined characteristic.
Instantaneous residual overcurrent
protection EFPIOC The directional function is voltage polarized
or dual polarized.
The Instantaneous residual overcurrent
protection EFPIOC has a low transient NS4PTOC can be set directional or non-
overreach and short tripping times to allow directional independently for each of the steps.
use for instantaneous earth-fault protection,
Sensitive directional residual
with the reach limited to less than typical
overcurrent and power protection
eighty percent of the transformer impedance
SDEPSDE
at minimum source impedance. EFPIOC can
be configured to measure the residual current In isolated networks or in networks with
from the three-phase current inputs or the high impedance earthing, the earth fault
current from a separate current input. current is significantly smaller than the short
EFPIOC can be blocked by activating the circuit currents. In addition to this, the
input BLOCK. magnitude of the fault current is almost
independent on the fault location in the
Four step residual overcurrent network. The protection can be selected to
protection EF4PTOC use either the residual current or residual
The four step residual overcurrent protection power component 3U0·3I0·cos j, for
EF4PTOC has an inverse or definite time operating quantity with maintained short
delay independent for each step separately. circuit capacity. There is also available one
nondirectional 3I0 step and one 3U0
All IEC and ANSI time-delayed characteristics
overvoltage tripping step.
are available together with an optional user
defined characteristic. Thermal overload protection, two
The directional function includes 3 options time constant TRPTTR
• voltage polarized If a power transformer or generator reaches
• current polarized very high temperatures the equipment might
• dual polarized be damaged. The insulation within the
transformer/generator will have forced
EF4PTOC can be set directional or non- ageing. As a consequence of this the risk of
directional independently for each of the steps. internal phase-to-phase or phase-to-earth
faults will increase. High temperature will
Second harmonic blocking can be set degrade the quality of the transformer/
individually for each step. generator insulation.
EF4PTOC can be configured to measure the The thermal overload protection estimates
residual current from the three-phase current the internal heat content of the transformer/
inputs or the current from a separate current generator (temperature) continuously. This
input. estimation is made by using a thermal model
of the transformer/generator with two time
Four step negative sequence
constants, which is based on current
overcurrent protection NS4PTOC
measurement.
Four step negative sequence overcurrent
protection (NS4PTOC) has an inverse or Two warning levels are available. This
enables actions in the power system to be
24 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
done before dangerous temperatures are the three phases with additional criteria from
reached. If the temperature continues to unsymmetrical phase currents when required.
increase to the trip value, the protection
initiates a trip of the protected transformer/ Directional over/underpower
generator. protection GOPPDOP/GUPPDUP
The directional over-/under-power protection
Breaker failure protection CCRBRF GOPPDOP/GUPPDUP can be used wherever
Breaker failure protection (CCRBRF) ensures a high/low active, reactive or apparent power
fast back-up tripping of surrounding breakers protection or alarming is required. The
in case the own breaker fails to open. functions can alternatively be used to check
CCRBRF can be current based, contact based, the direction of active or reactive power flow
or an adaptive combination of these two in the power system. There are a number of
conditions. applications where such functionality is
needed. Some of them are:
Current check with extremely short reset time
is used as check criterion to achieve high • detection of reversed active power flow
security against unnecessary operation. • detection of high reactive power flow
Contact check criteria can be used where the
Each function has two steps with definite
fault current through the breaker is small.
time delay. Reset times for both steps can be
CCRBRF can be single- or three-phase set as well.
initiated to allow use with single phase
tripping applications. For the three-phase Broken conductor check BRCPTOC
version of CCRBRF the current criteria can be The main purpose of the function Broken
set to operate only if two out of four for conductor check (BRCPTOC) is the detection
example, two phases or one phase plus the of broken conductors on protected power
residual current start. This gives a higher lines and cables (series faults). Detection can
security to the back-up trip command. be used to give alarm only or trip the line
CCRBRF function can be programmed to give breaker.
a single- or three-phase re-trip of the own
breaker to avoid unnecessary tripping of
surrounding breakers at an incorrect
initiation due to mistakes during testing. 6. Voltage protection
Pole discordance protection
CCRPLD Two step undervoltage protection
UV2PTUV
An open phase can cause negative and zero
sequence currents which cause thermal stress Undervoltages can occur in the power system
on rotating machines and can cause during faults or abnormal conditions. Two
unwanted operation of zero sequence or step undervoltage protection (UV2PTUV)
negative sequence current functions. function can be used to open circuit breakers
to prepare for system restoration at power
Normally the own breaker is tripped to outages or as long-time delayed back-up to
correct such a situation. If the situation primary protection.
persists the surrounding breakers should be
tripped to clear the unsymmetrical load UV2PTUV has two voltage steps, each with
situation. inverse or definite time delay.
ABB 25
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
26 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
to the generating plant, generator governor The built-in overcurrent protection feature
problems can also cause over frequency. has two settable current levels. Both of them
can be used either with definite time or
SAPTOF is used mainly for generation
inverse time characteristic. The overcurrent
shedding and remedial action schemes. It is
protection steps can be made directional with
also used as a frequency stage initiating load
selectable voltage polarizing quantity.
restoring.
Additionally they can be voltage and/or
SAPTOF is provided with an undervoltage current controlled/restrained. 2nd harmonic
blocking. restraining facility is available as well. At too
The operation is based on positive sequence low polarizing voltage the overcurrent feature
voltage measurement and requires two phase- can be either blocked, made non directional
phase or three phase-neutral voltages to be or ordered to use voltage memory in
connected. For information about how to accordance with a parameter setting.
connect analog inputs, refer to Application Additionally two overvoltage and two
manual/IED application/Analog inputs/ undervoltage steps, either with definite time
Setting guidelines or inverse time characteristic, are available
within each function.
Rate-of-change frequency
protection SAPFRC The general function suits applications with
underimpedance and voltage controlled
Rate-of-change frequency protection function
overcurrent solutions. The general function
(SAPFRC) gives an early indication of a main
can also be utilized for generator transformer
disturbance in the system. SAPFRC can be
protection applications where positive,
used for generation shedding, load shedding
negative or zero sequence components of
and remedial action schemes. SAPFRC can
current and voltage quantities are typically
discriminate between positive or negative
required.
change of frequency.
SAPFRC is provided with an undervoltage
blocking. The operation is based on positive
sequence voltage measurement and requires
two phase-phase or three phase-neutral
9. Secondary system
voltages to be connected. For information supervision
about how to connect analog inputs, refer to
Application manual/IED application/
Current circuit supervision
Analog inputs/Setting guidelines.
CCSRDIF
Open or short circuited current transformer
cores can cause unwanted operation of many
ABB 27
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
the neutral point current on a separate input practice is more associated with voltage
taken from another set of cores on the transformer switching during station
current transformer. operations.
A detection of a difference indicates a fault in
the circuit and is used as alarm or to block
protection functions expected to give
unwanted tripping. 10. Control
Fuse failure supervision SDDRFUF
Synchrocheck, energizing check,
The aim of the fuse failure supervision and synchronizing SESRSYN
function (SDDRFUF) is to block voltage
measuring functions at failures in the The Synchronizing function allows closing of
secondary circuits between the voltage asynchronous networks at the correct
transformer and the IED in order to avoid moment including the breaker closing time,
unwanted operations that otherwise might which improves the network stability.
occur. Synchrocheck, energizing check, and
The fuse failure supervision function basically synchronizing (SESRSYN) function checks
has three different algorithms, negative that the voltages on both sides of the circuit
sequence and zero sequence based breaker are in synchronism, or with at least
algorithms and an additional delta voltage one side dead to ensure that closing can be
and delta current algorithm. done safely.
The negative sequence detection algorithm is SESRSYN function includes a built-in voltage
recommended for IEDs used in isolated or selection scheme for double bus and 1½
high-impedance earthed networks. It is based breaker or ring busbar arrangements.
on the negative-sequence measuring Manual closing as well as automatic reclosing
quantities, a high value of voltage 3U2 can be checked by the function and can have
without the presence of the negative- different settings.
sequence current 3I2.
For systems which are running asynchronous
The zero sequence detection algorithm is a synchronizing function is provided. The
recommended for IEDs used in directly or main purpose of the synchronizing function
low impedance earthed networks. It is based is to provide controlled closing of circuit
on the zero sequence measuring quantities, a breakers when two asynchronous systems are
high value of voltage 3U0 without the going to be connected. It is used for slip
presence of the residual current 3I0. frequencies that are larger than those for
synchrocheck and lower than a set maximum
For better adaptation to system requirements, level for the synchronizing function.
an operation mode setting has been
introduced which makes it possible to select Apparatus control APC
the operating conditions for negative The apparatus control functions are used for
sequence and zero sequence based function. control and supervision of circuit breakers,
The selection of different operation modes disconnectors and earthing switches within a
makes it possible to choose different bay. Permission to operate is given after
interaction possibilities between the negative evaluation of conditions from other functions
sequence and zero sequence based algorithm. such as interlocking, synchrocheck, operator
A criterion based on delta current and delta place selection and external or internal
voltage measurements can be added to the blockings.
fuse failure supervision function in order to Apparatus control features:
detect a three phase fuse failure, which in
28 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 29
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
VSGGIO can be controlled from the menu or protection including a channel transmission
from a symbol on the single line diagram time, can be achieved. This short operate
(SLD) on the local HMI. time enables rapid autoreclosing function
after the fault clearance.
Single point generic control 8
signals SPC8GGIO The communication logic module for
directional residual current protection
The Single point generic control 8 signals enables blocking as well as permissive under/
(SPC8GGIO) function block is a collection of overreaching schemes. The logic can also be
8 single point commands, designed to bring supported by additional logic for weak-end
in commands from REMOTE (SCADA) to infeed and current reversal, included in
those parts of the logic configuration that do Current reversal and weak-end infeed logic
not need extensive command receiving for residual overcurrent protection
functionality (for example, SCSWI). In this (ECRWPSCH) function.
way, simple commands can be sent directly
to the IED outputs, without confirmation. Current reversal and weak-end
Confirmation (status) of the result of the infeed logic for residual
commands is supposed to be achieved by overcurrent protection ECRWPSCH
other means, such as binary inputs and
The Current reversal and weak-end infeed
SPGGIO function blocks. The commands can
logic for residual overcurrent protection
be pulsed or steady.
ECRWPSCH is a supplement to Scheme
Single command, 16 signals communication logic for residual overcurrent
protection ECPSCH.
The IEDs can receive commands either from
a substation automation system or from the To achieve fast fault clearing for all earth
local HMI. The command function block has faults on the line, the directional earth-fault
outputs that can be used, for example, to protection function can be supported with
control high voltage apparatuses or for other logic that uses communication channels.
user defined functionality. The 670 series IEDs have for this reason
available additions to scheme communication
logic.
If parallel lines are connected to common
11. Scheme busbars at both terminals, overreaching
communication permissive communication schemes can trip
unselectively due to fault current reversal.
This unwanted tripping affects the healthy
Scheme communication logic for line when a fault is cleared on the other line.
residual overcurrent protection This lack of security can result in a total loss
ECPSCH of interconnection between the two buses. To
To achieve fast fault clearance of earth faults avoid this type of disturbance, a fault current
on the part of the line not covered by the reversal logic (transient blocking logic) can
instantaneous step of the residual overcurrent be used.
protection, the directional residual Permissive communication schemes for
overcurrent protection can be supported with residual overcurrent protection can basically
a logic that uses communication channels. operate only when the protection in the
In the directional scheme, information of the remote IED can detect the fault. The
fault current direction must be transmitted to detection requires a sufficient minimum
the other line end. With directional residual fault current, out from this IED. The
comparison, a short operate time of the fault current can be too low due to an
30 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
opened breaker or high-positive and/or zero- information on the local HMI and on the
sequence source impedance behind this IED. Substation automation system about:
To overcome these conditions, weak-end
• measured voltages, currents, frequency,
infeed (WEI) echo logic is used.
active, reactive and apparent power and
power factor
• primary and secondary phasors
• positive, negative and zero sequence
12. Logic currents and voltages
• mA, input currents
• pulse counters
Tripping logic SMPPTRC
A function block for protection tripping is Supervision of mA input signals
provided for each circuit breaker involved in
the tripping of the fault. It provides pulse The main purpose of the function is to
prolongation to ensure a trip pulse of measure and process signals from different
sufficient length, as well as all functionality measuring transducers. Many devices used in
necessary for correct co-operation with process control represent various parameters
autoreclosing functions. such as frequency, temperature and DC
battery voltage as low current values, usually
The trip function block includes functionality in the range 4-20 mA or 0-20 mA.
for evolving faults and breaker lock-out.
Alarm limits can be set and used as triggers,
Trip matrix logic TMAGGIO e.g. to generate trip or alarm signals.
Trip matrix logic TMAGGIO function is used The function requires that the IED is
to route trip signals and other logical output equipped with the mA input module.
signals to different output contacts on the IED.
Event counter CNTGGIO
TMAGGIO output signals and the physical
outputs allows the user to adapt the signals Event counter (CNTGGIO) has six counters
to the physical tripping outputs according to which are used for storing the number of
the specific application needs. times each counter input has been activated.
ABB 31
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
32 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
information is used for different purposes in substation. It can also be used inside the
the short perspective (for example corrective same IED, to attach a RANGE aspect to an
actions) and long perspective (for example analog value and to permit measurement
functional analysis). supervision on that value.
The Disturbance recorder acquires sampled Measured value expander block
data from selected analog- and binary signals RANGE_XP
connected to the Disturbance report function
(maximum 40 analog and 96 binary signals). The current and voltage measurements
The binary signals available are the same as functions (CVMMXN, CMMXU, VMMXU and
for the event recorder function. VNMMXU), current and voltage sequence
measurement functions (CMSQI and VMSQI)
The function is characterized by great and IEC 61850 generic communication I/O
flexibility and is not dependent on the functions (MVGGIO) are provided with
operation of protection functions. It can measurement supervision functionality. All
record disturbances not detected by measured values can be supervised with four
protection functions. Up to ten seconds of settable limits: low-low limit, low limit, high
data before the trigger instant can be saved in limit and high-high limit. The measure value
the disturbance file. expander block (RANGE_XP) has been
The disturbance recorder information for up introduced to enable translating the integer
to 100 disturbances are saved in the IED and output signal from the measuring functions to
the local HMI is used to view the list of 5 binary signals: below low-low limit, below
recordings. low limit, normal, above high-high limit or
above high limit. The output signals can be
Event function used as conditions in the configurable logic
When using a Substation Automation system or for alarming purpose.
with LON or SPA communication, time-
tagged events can be sent at change or
cyclically from the IED to the station level.
These events are created from any available 14. Metering
signal in the IED that is connected to the
Event function (EVENT). The event function
Pulse counter logic PCGGIO
block is used for LON and SPA
communication. Pulse counter (PCGGIO) function counts
externally generated binary pulses, for
Analog and double indication values are also
instance pulses coming from an external
transferred through EVENT function.
energy meter, for calculation of energy
IEC61850 generic communication consumption values. The pulses are captured
I/O function SPGGIO by the binary input module and then read by
the function. A scaled service value is
IEC61850 generic communication I/O available over the station bus. The special
functions (SPGGIO) is used to send one Binary input module with enhanced pulse
single logical signal to other systems or counting capabilities must be ordered to
equipment in the substation. achieve this functionality.
IEC61850 generic communication Function for energy calculation and
I/O functions MVGGIO demand handling ETPMMTR
IEC61850 generic communication I/O Outputs from the Measurements (CVMMXN)
functions (MVGGIO) function is used to send function can be used to calculate energy
the instantaneous value of an analog output consumption. Active as well as reactive
to other systems or equipment in the
ABB 33
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
IEC05000056-LITEN V1 EN
34 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 35
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
36 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
dedicated IEC 60870-5-103 port depending on contact for connection to an antenna. It also
ordered SLM module) and one port is includes an optical PPS ST-connector output.
dedicated for LON communication.
IRIG-B Time synchronizing module
Line data communication module LDCM The IRIG-B time synchronizing module is
Each module has one optical port, one for used for accurate time synchronizing of the
each remote end to which the IED IED from a station clock.
communicates.
Electrical (BNC) and optical connection (ST)
Alternative cards for Medium range (1310 nm for 0XX and 12X IRIG-B support.
single mode) and Short range (850 nm multi
mode) are available. Transformer input module TRM
The transformer input module is used to
Galvanic RS485 serial communication galvanically separate and transform the
module
secondary currents and voltages generated by
The Galvanic RS485 communication module the measuring transformers. The module has
(RS485) is used for DNP3.0 communication. twelve inputs in different combinations of
The module has one RS485 communication currents and voltage inputs.
port. The RS485 is a balanced serial
Alternative connectors of Ring lug or
communication that can be used either in 2-
Compression type can be ordered.
wire or 4-wire connections. A 2-wire
connection uses the same signal for RX and
High impedance resistor unit
TX and is a multidrop communication with
no dedicated Master or slave. This variant The high impedance resistor unit, with
requires however a control of the output. The resistors for pick-up value setting and a
4-wire connection has separated signals for voltage dependent resistor, is available in a
RX and TX multidrop communication with a single phase unit and a three phase unit.
dedicated Master and the rest are slaves. No Both are mounted on a 1/1 19 inch apparatus
special control signal is needed in this case. plate with compression type terminals.
B C
D
xx05000003.vsd
IEC05000003 V1 EN
ABB 37
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3
(mm)
38 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 39
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
40 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 41
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
configuration
(50/60 Hz)
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
1A
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5A
5I, 1A 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
+4I, 5A
+3U
7I+5U, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
1A
7I+5U, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I+6U, 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
1A
6I+6U, 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
*) Metering
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-
processing function blocks.
42 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 43
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
44 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Figure 15. Binary output module (BOM). Output contacts named XA corresponds to rear
position X31, X41, and so on, and output contacts named XB to rear position
X32, X42, and so on.
ABB 45
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Figure 17. Binary in/out module (IOM). Input contacts named XA corresponds to rear position
X31, X41, and so on, and output contacts named XB to rear position X32, X42,
and so on.
46 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
BUS A
BBP-TRIP BUS B
QB1-OPEN
QB1-CL
BLOCK LW 3I>
BBP STEP QB2-OPEN
QB2-CL -QB1
ST BFP 3PH -QB2
BUCH TRIP
SUDDEN P
-QA1
OT TRIP CLOSE QA1 C
CLOSE Reinf C
WT TRIP
TRIP QA1 T
OT WARN TRIP Reinf C
MAIN 2 TRIP T
QA1-OPEN C
WT WARN
QA1-CL
OIL LOW
QA1-SPR UNCH
GAS ALARM
-BI1 P1
TRM1:1-3
TO MAIN 2 RELAY
TO BUS PROT
SIGNALLING
FAULT
QO -T1
TRM1:7
-N.BI1 QW
= TAP POS
MIM1:1 -N.BI1
TC IN MAN
TRM1:8
TC IN AUTO
-BI1
HV BUSBAR TRIP TO BUS PROT
MV BUSBAR TRIP
MAN SC OK TO MAIN 2 RELAY
TRM1:4-6
P1
QA1-OPEN
QA1-CL
TRIP QA1 T
C
TRIP Reinf
T
C
TRM1:10
MCB OK
-BU1
IRF
- +
en05000262.vsd
IEC05000262 V1 EN
Figure 18. Typical connection diagram for two winding transformer in a single breaker
arrangement. Note! Including IO for control option.
ABB 47
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
BUS A
BBP-TRIP -QB1
QB1-OPEN
QB1-CL
BLOCK LW 3I> QB6-OPEN
BBP STEP
QB6-CL -QB62
ST BFP 3PH -BI1 P1
BUCH TRIP TRM1:4-6
SUDDEN P
-QA1
CLOSE QA1 C TO MAIN 2
OT TRIP CLOSE Reinf C
QB61-CL
FAULT
QB9-OPEN
QB9-CL -QB9
TRM2:4
QO -T1
QW
= TAP POS
MIM1:1
TC IN MAN
TC IN AUTO TRM2:5
TRIP QA1 T
TRIP Reinf C
BBP-TRIP T
C
TRM2:10
MCB OK
-BU1
IRF
- +
en05000263.vsd
IEC05000263 V1 EN
Figure 19. Typical connection diagram for two winding transformer in a multi breaker
arrangement. Note! Including IO for control option.
48 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
BUS A
BUS B
BBP-TRIP
QB1-OPEN
ST BFP QB1-CL
3PH QB2-OPEN
QB2-CL
-QB1
BLOCK TW 3I> -QB2
BBP STEP
BUCH TRIP
SUDDEN P
-QA1
CLOSE QA1 C
OT TRIP CLOSE Reinf C
-BI1 P1
TRM1:1-3
QA1-OPEN
TO MAIN 2 RELAY
QA1-CL
SPR UNCH
TO BUS PROT
SIGNALLING
CLOSE QA1
CLOSE Reinf
FAULT
TRIP QA1
TRIP Reinf
QO
TRM1:7
QW
TC IN MAN
TC IN AUTO TRM1:8
TRIP QA1 T
TRIP Reinf C
T
C
TRM1:11
-BU1
MCB OK
-BU1
TRM1:12 Res. for Bus 2
VT
IRF
- + en05000265.vsd
IEC05000265 V1 EN
Figure 20. Typical connection diagram for three winding transformer in a single breaker
arrangement. Note! Including IO for control option.
ABB 49
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
BUS A
TO SECOND BAY
BBP-TRIP -QB1
QB1-OPEN
QB1-CL
BLOCK TW 3I>
QB62-OPEN
BBP STEP
QB62-CL -QB62
ST BFP 3PH
BUCH TRIP
-BI1 P1
TRM1:4-36
SUDDEN P -QA1
CLOSE QA1 C TO MAIN 2
C
OT TRIP CLOSE Reinf
TRIP QA1 T
WT TRIP C
TRIP Reinf
=1-Q0-OPEN MAIN 2 TRIP T
OT WARN C
=2-Q0-OPEN =1-Q0-CL
WT WARN =2-Q0-CL
=1-Q0-SPR UNCH
OIL LOW =2-Q0-SPR UNCH
-BI1 P1
GAS ALARM TRM1:1-3 -QA1
CLOSE QA1 C
C
TO MAIN 2
CLOSE Reinf
TRIP QA1 T
C
TRIP Reinf MAIN 2 TRIP
TO BB PROT T
QB6-OPEN C
QB6-CL
SIGNALLING
QB61-CL
Q9-OPEN
Q9-CL
-Q9
-T1
TRM1:7
= TAP POS
TC IN MAN
TC IN AUTO TRM1:8
QO
TC IN LOC. MCB OR
MCB-OK FUSE QW
TC RAISE
TC LOWER -BU1
TRM2:7-9
-BI1
HV BUSBAR TRIP TO BUS PROT -BI1
MV BUSBAR TRIP TRM2:4-6
CLOSE QA1 TO MAIN 2 RELAY
-QA1 P1
MAN SC OK
CLOSE Reinf C
C
TRIP QA1
TRIP Reinf TRM2:1-3 T
C
P1
QA1-OPEN
QA1-OPEN T
QA1-CL C
QA1-CL
SPR UNCH
SPR UNCH -QA1
CLOSE QA1 C
C
CLOSE Reinf
TRIP QA1 T
C
TRIP Reinf
T
C
TRM1:11
-BU1
MCB OK
-BU1
TRM1:12 Res. for Bus 2
VT
IRF
en05000259.vsd
- +
IEC05000259 V1 EN
Figure 21. Typical connection diagram for three winding transformer in a multi breaker
arrangement. Note! Including IO for control option.
50 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
General
Definitions
Reference The specified value of an influencing factor to which are referred the
value characteristics of the equipment
Nominal The range of values of an influencing quantity (factor) within which, under
range specified conditions, the equipment meets the specified requirements
Operative The range of values of a given energizing quantity for which the equipment,
range under specified conditions, is able to perform its intended functions
according to the specified requirements
Analog inputs
Table 4. TRM - Energizing quantities, rated values and limits for protection transformer
modules
ABB 51
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 5. TRM - Energizing quantities, rated values and limits for measuring transformer
modules
52 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Auxiliary DC voltage
ABB 53
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 10. BIM - Binary input module with enhanced pulse counting capabilities
54 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 12. IOM - Binary input/output module contact data (reference standard: IEC
61810-2)
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 55
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary
outputs
56 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 14. SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Table 15. BOM - Binary output module contact data (reference standard: IEC 61810-2)
ABB 57
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Influencing factors
58 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 59
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
60 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Test According to
Immunity EN 50263
Emissivity EN 50263
Low voltage directive EN 50178
ABB 61
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Differential protection
Table 24. Transformer differential protection T2WPDIF, T3WPDIF
62 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 63
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Impedance protection
Table 27. Distance measuring zone, Quad ZMQPDIS
64 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 28. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
ABB 65
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
66 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 30. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
ABB 67
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
68 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Current protection
Table 33. Instantaneous phase overcurrent protection PHPIOC
ABB 69
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
70 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 71
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
72 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 73
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 38. Sensitive directional residual overcurrent and power protection SDEPSDE
74 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 38. Sensitive directional residual overcurrent and power protection SDEPSDE,
continued
Function Range or value Accuracy
Operate time, non- 60 ms typically at 0 to 2 x Iset -
directional residual over
current
Reset time, non- 60 ms typically at 2 to 0 x Iset -
directional residual over
current
Operate time, start 150 ms typically at 0 to 2 x Iset -
function
Reset time, start function 50 ms typically at 2 to 0 x Iset -
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content ± 2.0% of heat content trip
trip value
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content ± 2.0% of heat content trip
trip
ABB 75
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
76 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 77
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Voltage protection
Table 45. Two step undervoltage protection UV2PTUV
78 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
(0.18 × k )
IEEE : t =
( M - 1) 2
EQUATION1319 V1 EN (Equation 2)
where M = (E/f)/(Ur/fr)
Minimum time delay for (0.000–60.000) s ± 0.5% ± 10 ms
inverse function
Maximum time delay for (0.00–9000.00) s ± 0.5% ± 10 ms
inverse function
Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms
ABB 79
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
80 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Frequency protection
Table 51. Underfrequency protection SAPTUF
ABB 81
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Multipurpose protection
Table 54. General current and voltage protection CVGAPC
See table 93 and table 94 Parameter ranges for customer See table 93 and table 94
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
82 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
High and low voltage limit, (1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
voltage dependent operation ± 1.0% of U for U>Ur
ABB 83
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
84 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 85
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Control
Table 57. Synchronizing, synchrocheck and energizing check SESRSYN
86 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 87
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Table 58. Voltage control TR1ATCC, TR8ATCC, TCMYLTC and TLCYLTC, continued
Function Range or value Accuracy
Alarm level of active power in (-9999.99–9999.99) MW ± 1.0% of Sr
forward and reverse direction
Alarm level of reactive power in (-9999.99–9999.99) MVAr ± 1.0% of Sr
forward and reverse direction
Time delay for alarms from power (1–6000) s ± 0.5% ± 10 ms
supervision
Tap position for lowest and highest (1–63) -
voltage
mA for lowest and highest voltage (0.000–25.000) mA -
tap position
Type of code conversion BIN, BCD, GRAY, SINGLE, mA -
Time after position change before (1–60) s ± 0.5% ± 10 ms
the value is accepted
Tap changer constant time-out (1–120) s ± 0.5% ± 10 ms
Raise/lower command output pulse (0.5–10.0) s ± 0.5% ± 10 ms
duration
88 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Scheme communication
Table 59. Scheme communication logic for residual overcurrent protection ECPSCH
Table 60. Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH
ABB 89
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Logic
Table 61. Tripping logic SMPPTRC
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicRSMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicPulseTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicTimerSet 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicLoopDelay 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms
Trip Matrix Logic 6 6 - - -
Boolean 16 to 4 4 8 - -
Integer
Boolean 16 to 4 4 8 - -
integer with
Logic Node
Integer to 4 4 8 - -
Boolean 16
Integer to 4 4 8 - -
Boolean 16 with
Logic Node
90 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Monitoring
Table 63. Measurements CVMMXN
ABB 91
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Function Value
Buffer capacity Maximum number of events in 1000
the list
Resolution 1 ms
Accuracy Depending on time
synchronizing
92 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Function Value
Buffer capacity Maximum number of indications presented 96
for single disturbance
Maximum number of recorded disturbances 100
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on
time
synchronizing
Function Value
Buffer capacity Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and 340 seconds (100 recordings)
maximum number of channels, typical value) at 50 Hz
280 seconds (80 recordings) at
60 Hz
ABB 93
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Metering
Table 72. Pulse counter PCGGIO
94 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Station communication
Table 74. IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
ABB 95
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Function Value
Protocol IEC 61850-8-1
Communication speed 100 Base-FX
96 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Remote communication
Table 82. Line data communication module
ABB 97
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Hardware
IED
Table 84. Water and dust protection level according to IEC 60529
Connection system
98 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out
Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled ± 1.0 ms typically
measurement values
Function Value
Max antenna cable attenuation 26 db @ 1.6 GHz
Antenna cable impedance 50 ohm
Lightning protection Must be provided externally
Antenna cable connector SMA in receiver end
TNC in antenna end
ABB 99
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
100 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Inverse characteristic
Table 93. ANSI Inverse time characteristics
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ABB 101
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
102 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
ABB 103
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
U> = Uset
U = Umeasured
104 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
ABB 105
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
U> = Uset
U = Umeasured
106 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
22. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RET670*1.2-A30-A01A02B12C05D01D03E01F02H09-B1-X0-C-B-KA-B3X0-A-ABC-X-XD. Using the code of each
position #1-12 specified as RET670*1-2 2-3 3 3 3 3 3 3 3-4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11
11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 -
RET670* - - - - - . -
9 - 10 - 11 - 12
- . -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 1.2
Selection for position #1.
ABB 107
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
108 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 109
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A Note: Only for A10/A25/A30
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fibre connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules
Compression terminals K
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.
110 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
ABB 111
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
Slot position (rear view) Note: Max 3 positions in 1/2
rack, 5 in 3/4 rack with 2 TRM
and 11 in 1/1 rack with 2 TRM
1/2 Case with 1 TRM █ █ █ Note: Only for A10/A25/A30
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X
Binary output module 24 output A A A A A A A A A A Note: Maximum 4 (BOM+SOM
relays (BOM) +MIM) boards.
BIM 16 inputs, RL24-30 VDC, 30 mA B B B B B B B B B B Note: Only 1 BIM in A10
BIM 16 inputs, RL48-60 VDC, 30 mA C C C C C C C C C C
BIM 16 inputs, RL110-125 VDC, 30 D D D D D D D D D D
mA
BIM 16 inputs, RL220-250 VDC, 30 E E E E E E E E E E
mA
BIM 16 inputs, RL24-30 VDC, 50 mA B B B B B B B B B B
1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C C C C C C C C C
1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 D D D D D D D D D D
mA 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
mA
BIM 16 inputs, RL24-30 VDC for F F F F F F F F F
pulse counting
BIM 16 inputs, RL48-60 VDC for G G G G G G G G G
pulse counting
BIM 16 inputs, RL110-125 VDC for H H H H H H H H H
pulse counting
BIM 16 inputs, RL220-250 VDC for K K K K K K K K K
pulse counting
IOM 8 inputs, 10+2 output, L L L L L L L L L
RL24-30 VDC
IOM 8 inputs, 10+2 output, M M M M M M M M M
RL48-60 VDC
IOM 8 inputs, 10+2 output, N N N N N N N N N
RL110-125 VDC
IOM 8 inputs, 10+2 output, P P P P P P P P P
RL220-250 VDC
IOM 8 inputs, 10+2 output, L1 L1 L1 L1 L1 L1 L1 L1 L1
RL24-30 VDC, 50 mA
IOM 8 inputs, 10+2 output, M M M M M M M M M
RL48-60 VDC, 50 mA 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, N N N N N N N N N
RL110-125 VDC, 50 mA 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, P1 P1 P1 P1 P1 P1 P1 P1 P1
RL220-250 VDC, 50 mA
IOM with MOV 8 inputs, 10-2 U U U U U U U U U
output, 24-30 VDC
IOM with MOV 8 inputs, 10-2 V V V V V V V V V
output, 48-60 VDC
IOM with MOV 8 inputs, 10-2 W W W W W W W W W
output, 110-125 VDC
112 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Remote end communication, DNP serial comm. #11 Notes and Rules
and time synchronization modules
X312
X313
X302
X303
X322
X323
Slot position (rear view)
Serial communication unit for station communication #12 Notes and Rules
X301
X311
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain
functions can only be ordered in combination with other functions and that some functions require specific
hardware selections.
Please refer to the available functions table for included application functions.
Accessories
ABB 113
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
Two winding transformer with internal RHGS 6 Case or RHGS 12 Case with mounted
neutral on current circuits. Two pcs can be RTXP 24 and the on/off switch for dc-supply
used in applications for three winding are ordered separately. Please refer to Section
transformers in single or multi-breaker "Related documents" for reference to
arrangement (ordering number RK926 215- corresponding documents.
BD)
Two winding transformer with external
neutral on current circuits. Two pcs can be
114 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-MB
dependent resistor for 20-100V operating voltage
High impedance resistor unit 1-ph with resistor and voltage 1 2 3
dependent resistor for 100-400V operating voltage Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-DC
dependent resistor for 100-400V operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
ABB 115
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
User documentation
Rule: Specify the number of printed manuals requested IEC Quantity: 1MRK 504 114-UEN
Operator’s manual
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
116 ABB
Transformer protection RET670 1MRK 504 118-BEN B
Pre-configured
Product version: 1.2 Issued: September 2011
Related documents
ABB 117
118
Contact us
www.abb.com/substationautomation