Sick Pbs Electronic Pressure Switch With Display

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

D atA S h ee t

PBS Electronic Pressure Switch


with Display

PBS - electronic pressure switch,


transmitter and display in one device.

The pressure switch PBS is designed Customer-specific parametrization at


Benefits
for pressure monitoring and measure- factory is available upon request.
ment in liquid and gaseous media. The intuitive setup using the three large • Compact and robust design
The PBS is suited for general industrial buttons and the integrated display • Rotatable housing for flexible
applications such as machine and plant are according to the recommendation installation
engineering, in machine tool systems, 24574-1 of the German engineering • Safe and simple operation and
in hydraulic and pneumatic systems, for federation VDMA. set-up with three large buttons
pressure monitoring and control and for The display and the electrical connec- and clearly legible display
pumps and compressors. It is pressure tor can be rotated against the process • Wide application range
switch, transmitter and display in one connector and against each other to • Insensitive against corrosive me-
and the same device. In its standard allow well visible display orientation and dia through hermetically sealed
configuration it has two switching clean cable routing. stainless steel membrane
outputs (PNP or NPN). In addition, there • Cost reduction through IO-Link
are configurations available with one Starting from a smallest measurement
or two switching points and an analog range of 0…1 bar, there is a large
output signal (4…20 mA or 0…10 V) as number of measurement ranges availa-
well as with IO-Link. ble up to 600 bar. In addition, the PBS
offers absolute and compound ranges.
The PBS features the following functio- The zero point can be adjusted within
nalities: a span of +3% of the measurement
• Switching point and reset point range.
(Hysteresis) The PBS has a circularly welded stain-
• Window function less steel membrane. Hence, there are
• Normally open or normally closed no internal sealing elements and it is
• Switching delay well suited for a large variety even of
• Min/max memory corrosive media. The PBS is wear-free
• Password protection to prevent from and does not require maintenance. As
unintended misadjustment there is a large multitude of customa-
• Change over between pressure units ry process connectors available as
in display standard, no additional adapters are
needed. For electrical connection the
PBS has an M12x1 connector.
PBS

Technical Data

Configurations Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
bar 0…1 2 5 0…40 80 400
bar 0…1.6 3.2 10 0…60 120 550
bar 0…2.5 5 10 0…100 200 800
bar 0…4 8 17 0…160 320 1000
bar 0…6 12 34 0…250 500 1200
bar 0…10 20 34 0…400 800 1700
bar 0…16 32 100 0…600 1200 2400
bar 0…25 50 100

Unit Pressure Overpressure Burst Pressure Overpressure Burst
ranges safety pressure ranges safety pressure
bar abs 0…1 2 5 0…6 12 34
bar abs 0…1.6 3.2 10 0…10 20 34
bar abs 0…2.5 5 10 0…16 32 100
bar abs 0…4 8 17 0…25 50 100

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
bar -1…0 2 5 -1…+9 20 34
bar -1…+1.5 3.2 10 -1…+15 32 100
bar -1…+3 8 17 -1…+24 50 100
bar -1…+5 8 17

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
MPa 0…0.1 0.2 0.5 0…4 8 40
MPa 0…0.16 0.32 1 0…6 12 55
MPa 0…0.25 0.5 1 0…10 20 80
MPa 0…0.4 0.8 1.7 0…16 32 100
MPa 0…0.6 1.2 3.4 0…25 50 120
MPa 0…1 2 3.4 0…40 80 170
MPa 0…1.6 3.2 10 0…60 120 240
MPa 0…2.5 5 10

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
MPa abs 0…0.1 0.2 0.5 0…0.6 1.2 3.4
MPa abs 0…0.16 0.32 1 0…1 2 3.4
MPa abs 0…0.25 0.5 1 0…1.6 3.2 10
MPa abs 0…0.4 0.8 1.7 0…2.5 3.2 10

Errors excepted, subject to modifications

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
MPa -0.1…0 2 5 -0.1…+0.9 2 3.4
MPa -0.1…+0.15 3.2 10 -0.1…+1.5 3.2 10
MPa -0.1…+0.3 8 17 -0.1…+2.4 3.2 10
MPa -0.1…+0.5 8 17

2 SICK 8013162 | 2009-11


PBS

Technical Data

Configurations Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
psi 0…15 30 75 0…500 1000 2500
psi 0…25 60 150 0…1000 1740 7975
psi 0…30 60 150 0…1500 2900 11600
psi 0…50 100 250 0…2000 4000 14500
psi 0…100 200 500 0…3000 6000 17400
psi 0…160 290 500 0...5000 10000 24650
psi 0…200 400 600 0...8000 17400 34800
psi 0…300 600 1500

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
psi abs 0…15 30 75 0…100 200 500
psi abs 0…25 60 150 0…160 290 500
psi abs 0…30 60 150 0…200 400 600
psi abs 0…50 100 250 0…300 600 1500

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
psi -30 InHg...0 30 75 -30 InHg...+100 200 500
psi -30 InHg...+15 30 75 -30 InHg...+160 290 500
psi -30 InHg...+25 60 150 -30 InHg...+200 400 1500
psi -30 InHg...+30 60 150 -30 InHg...+300 600 1500
psi -30 InHg...+50 100 250

Unit Pressure Overpressure Burst Pressure Overpressure Burst
ranges safety pressure ranges safety pressure
kg/cm2 0…1 2 5 0…40 80 400
kg/cm2 0…1.6 3.2 10 0…60 120 550
kg/cm2 0…2.5 5 10 0…100 200 800
kg/cm2 0…4 8 17 0…160 320 1000
kg/cm2 0…6 12 34 0…250 500 1200
kg/cm2 0…10 20 34 0…400 800 1700
kg/cm2 0…16 32 100 0…600 1200 2400
kg/cm2 0…25 50 100

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
kg/cm2 abs 0…1 2 5 0…6 12 34
kg/cm2 abs 0…1.6 3.2 10 0…10 20 34
kg/cm2 abs 0…2.5 5 10 0…16 32 100
kg/cm2 abs 0…4 8 17 0…25 50 100
Errors excepted, subject to modifications

Unit Pressure Overpressure Burst Pressure Overpressure Burst


ranges safety pressure ranges safety pressure
kg/cm2 -1…0 2 5 -1…+9 20 34
kg/cm2 -1…+1.5 3.2 10 -1…+15 32 100
kg/cm2 -1…+3 8 17 -1…+24 50 100
kg/cm2 -1…+5 12 17

2009-11 | 8013162 SICK 2


3
PBS

Technical Data

Fatigue life 10 Mio. max. load cycles
Materials
■ Wetted parts
Pressure connection 316 L
Pressure sensor 316 L (up to 0 ... 10 bar rel 13-8 PH)
■ Housing
Lower body 316 L
Plastic head PC + ABS
Buttons TPE-E
Display window PC
■ Internal transmission fluid Silicone oil (only with pressure ranges < 0 ... 10 bar and ≤ 0 ... 25 bar abs)
Supply voltage L+ 15 ... 35 V DC
Signal output and maximum ohmic load RA 4 ... 20 mA, 3-wire RA ≤ 0.5 kOhm
0 … 10 V, 3-wire RA > 10 kOhm
adjustment zero point offset, max +3 % of span
Setting time (analog signal) 3 ms
Current consumption max. 100 mA
Total current consumption max. 350 mA / 600 mA (incl. switching current)
Switching points Individually adjustable via external control buttons
■ Type Transistor switching output PNP or NPN Number: 1 or 2
With IO-Link: C/Q1: PNP
■ Function normally open / normally closed; windows- and hysteresis function freely adjustable
■ Contact rating Supply voltage L+ - 1 V [V DC]
■ Switching current 250 mA
With IO-Link: C/Q1: 100 mA, Q2: 250 mA
■ Response time ≤ 10 ms
■ Switching delay 0 ... 50 s (adjustable)
■ Rotatability of housing Display against housing with electrical connection: 330°. Housing against process connection: 320°
■ Accuracy ≤ 0.5 % of span (setting accuracy)
Isolation voltage 500 V DC
Display
■ Design 14-Segment-LED, blue, 4-digits, height 9 mm
■ Range Electronically turnable by 180°
■ Accuracy ≤ 1.0 % of span ± 1 digit
■ Update 1000, 500, 200, 100 ms (adjustable)
Accuracy ≤ ± 1.0 % of span*)
*)
Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of
measurement per IEC 61298-2)
Non-linearity ≤ ± 0.5 % of span (BFSL) according to IEC 61298-2
Long-term drift ≤ 0.2 % of span according to IEC 61298-2
Permissible temperature of
■ Medium -20 ... +85°C
■ Ambience -20 ... +80°C
Errors excepted, subject to modifications

■ Storage -20 ... +80°C


Rated temperature range 0 ... +80°C
Temperature error within rated temperature range ≤ 1.0 % of span typ., ≤ 2.5 % max.
Temperature coefficients within rated temperature range
■ Mean TC of zero ≤ 0.2% of span / 10 K
■ Mean TC of span ≤ 0.2 % of span / 10 K
Relative humidity 90%
CE-conformity
■ Pressure equipment directive This instrument is a pressure accessory as defined by the directive 97/23/EC
■ EMC directive 2004/108/EEC, EN 61326-2-3
Enclosure rating IP 67

4 SICK 8013162 | 2009-11


PBS

Technical Data

Shock resistance 50 g according to IEC 60068-2-27 (mechanical shock)


Vibration resistance 10 g according to IEC 60068-2-6 (vibration under resonance)
Wiring protection
■ Protection class III
■ Overvoltage protection 40 V DC
■ Short-circuit protection QA, Q1, Q2 towards M
■ Reverse polarity protection L+ towards M
Weight Approx. 200 g

Dimensions in mm
Electrical Connection
Circular connector *)
M 12x1

Pressure Connection
G 1/2
EN 837
Type code: GE

*) Mating connectors are not included in delivery.

Pressure Connections
G 1/4 Female G 1/4 1/ 4“ NPT
EN 837 DIN 3852-E per „Nominal size for US standard
Type code: G2 Type code: G1 tapered, pipe thread NPT“
Type code: N1

R 1/4 ISO7 G 1/4 Female


Type code: R1 Compatible with Ermeto
Errors excepted, subject to modifications

Type code: GH

Further pressure connections on request


For installation and safety instructions see the operating instructions for this product.

Pressure Port (0.3 or 0.6 mm) available for G 1/4 according to DIN 3852-E. (0.3 mm for p ≥ 10 bar)

2009-11 | 8013162 SICK 4


5
PBS

Wiring connections
Circular connector M12x1, 4-pin Circular connector M12x1, 5-pin

2 switching outputs or 2 switching outputs + 1 analog output


1 switching output + 1 analog output

L+ = 1 M=3 Q1 = 4 Q2 = 2 L+ = 1 M=3 Q1 = 4 Q2 = 2 QA = 5
C/Q1 = 4 QA = 2 C/Q1 = 4
Ingress Protection per IEC 60 529 IP 67 IP 67
The ingress protection classes specified only apply while the pressure transmitter is connected with female
connectors that provide the corresponding ingress protection.

Legend:
L+ Positive supply connection
M Negative supply connection
Q1 Switching output 1
C/Q1 With IO-Link: Communication/ switching output 1
Q2 Switching output 1
QA Analog output

Accessories
PVC circular plug-in connector, M12, 4-pin

Part-No. Model name Cable length


6009382 DOL-1204-G02M 2m
6009866 DOL-1204-G05M 5m
6010543 DOL-1204-G10M 10 m
6010753 DOL-1204-G15M 15 m
6034401 DOL-1204-G20M 20 m

Part-No. Model name Cable length


6009383 DOL-1204-W02M 2m
6009867 DOL-1204-W05M 5m
6010541 DOL-1204-W10M 10 m
6036474 DOL-1204-W15M 15 m
6033559 DOL-1204-W20M 20 m
Errors excepted, subject to modifications

Part-No. Model name Cable length Coating colour


6033686 DOL-1204-G01MS02 1m grey
6033687 DOL-1204-G04MS02 4m grey
6033688 DOL-1204-G05MS02 5m grey
6033690 DOL-1204-G07MS02 7m grey

6 SICK 8013162 | 2009-11


PBS

PVC circular plug-in connector, M12, 5-pin

Part No. Model name Cable length


6008899 DOL-1205-G02M 2m
6009868 DOL-1205-G02M 5m
6010544 DOL-1205-G02M 10 m
6029215 DOL-1205-G02M 15 m

Part No. Model name Cable length


6008900 DOL-1205-W02M 2m
6009868 DOL-1205-W05M 5m
6010542 DOL-1205-W10M 10 m

PUR circular plug-in connector, M12, 4-pin

Part No. Model name Cable length


6025900 DOL-1204-G02MC 2m
6025901 DOL-1204-G05MC 5m
6025902 DOL-1204-G10MC 10 m
6034749 DOL-1204-G15MC 15 m
6034750 DOL-1204-G20MC 20 m
6034751 DOL-1204-G25MC 25 m

Part No. Model name Cable length


6025903 DOL-1204-W02MC 2m
6025904 DOL-1204-W05MC 5m
6025905 DOL-1204-W10MC 10 m
6034752 DOL-1204-W15MC 15 m
6034753 DOL-1204-W20MC 20 m
6034754 DOL-1204-W25MC 25 m
Errors excepted, subject to modifications

Part No. Model name Cable length


6026250 DOL-1204-G05MD 5 m, welding spark-proof

2009-11 | 8013162 SICK 6


7
PBS

PUR circular plug-in connector, M12, 4-pin

Part No. Model name Cable length


6020399 DOL-1204-W05MD 5 m, welding spark-proof

PUR circular plug-in connector, M12, 5-pin

Part No. Model name Cable length


6025906 DOL-1205-G02MC 2m
6025907 DOL-1205-G05MC 5m
6025908 DOL-1205-G10MC 10 m

Part No. Model name Cable length


6025909 DOL-1205-G02MC 2m
6025910 DOL-1205-G05MC 5m
6025911 DOL-1205-G10MC 10 m

Part No. Model name Cable length


6036384 DOL-1205-G05MAC 5 m, shielded
6036385 DOL-1205-G10MAC 10 m, shielded
6036386 DOL-1205-G20MAC 20 m, shielded

Device fixture
Part-no. Model name Description
5322501 BEF-FL-ALUPBS-HLDR Device fixture for PBS Errors excepted, subject to modifications

8 SICK 8013162 | 2009-11


PBS

Type Code
Pressure type
R Gauge
A Absolute
C Compound
Pressure Unit
B bar
M MPa
P psi
K kg/cm2
Standard measurement ranges see the following page
Process Connector
GE G 1/2 B according to EN 837
G1 G 1/4 A according to DIN 3852-E
G2 G 1/4 female according to EN 837
GH G 1/4 female, compatible with Ermeto
N1 1/4" NPT
R1 R 1/4 ISO 7 (DIN2999)
Pressure Port
S Standard pressure port
N 0.3 mm pressure port 1) 2)
M 0.6 mm pressure port 1)
Sealing
N NBR sealing 1)
F FPM/FKM sealing 1)
C Copper sealing 3)
S Stainless steel sealing 3)
0 without sealing 4)
Output Signal
A two switching outputs (PNP)
B one switching output (PNP) + 4...20 mA
C one switching output (PNP) + 0...10 V
D two switching outputs (PNP) + 4...20 mA
E two switching outputs (PNP) + 0...10 V
F two switching outputs (NPN)
G one switching output (NPN) + 4...20 mA
H one switching output (NPN) + 0...10 V
I two switching outputs (NPN) + 4...20 mA
K two switching outputs (NPN) + 0...10 V
Errors excepted, subject to modifications

L IO-Link, two switching outputs PNP


N IO-Link, one switching output PNP (Q1) + 4...20 mA
P IO-Link, one switching output PNP (Q1) + 0...10 V
Q IO-Link, two switching outputs PNP + 4...20 mA
R IO-Link, two switching outputs PNP + 0...10 V

PBS - S S A 0 Continuation see the following page


1) 3)
Only with process connection G 1/4 A acc. to DIN 3852E Only with process connection G 1/2 B acc. to EN837
2) 4)
≥ 10 bar Delivery of process connection G 1/4 acc. to DIN 3852E including sealing

2009-11 | 8013162 SICK 8


9
PBS

Type Code
Electrical Connector
M M12 x 1, 4-pin, IP 67 1)
5 M12 x 1, 5-pin, IP 67 2)
Design Specifics
Z without design specifics
G free from oil and grease

PBS - S S A 0
1)
For variant with one switching and one analog output or 2 switching outputs
2)
For variants with 2 switching outputs and one analog output

Measurement ranges bar /Gauge Pressure bar / Absolute Pressure bar / Compound Pressure
1X0 0...1 bar 1X0 0...1 bar abs 1X0 -1...0 bar
1X6 0...1.6 bar 1X6 0...1.6 bar abs 2X5 -1...+1.5 bar
2X5 0...2.5 bar 2X5 0...2.5 bar abs 4X0 -1...+3 bar
4X0 0...4 bar 4X0 0...4 bar abs 6X0 -1...+5 bar
6X0 0...6 bar 6X0 0...6 bar abs 010 -1...+9 bar
010 0...10 bar 010 0...10 bar abs 016 -1...+15 bar
016 0...16 bar 016 0...16 bar abs 025 -1...+24 bar
025 0...25 bar 025 0...25 bar abs
040 0...40 bar
060 0...60 bar
100 0...100 bar
160 0...160 bar
250 0...250 bar
400 0...400 bar
600 0...600 bar

Measurement ranges MPa / Gauge Pressure MPa / Absolute Pressure MPa /Compound Pressure
X10 0...0.1 MPa X10 0...0.1 MPa abs X10 -0.1...+0 MPa
X16 0...0.16 MPa X16 0...0.16 MPa abs X25 -0.1...+0.15 MPa
X25 0...0.25 MPa X25 0...0.25 MPa abs X40 -0.1...+0.3 MPa
X40 0...0.4 MPa X40 0...0.4 MPa abs X60 -0.1...+0.5 MPa
X60 0...0.6 MPa X60 0...0.6 MPa abs 1X0 -0.1...+0.9 MPa
1X0 0...1 MPa 1X0 0...1 MPa abs 1X6 -0.1...+1.5 MPa
Errors excepted, subject to modifications

1X6 0...1.6 MPa 1X6 0...1.6 MPa abs 2X5 -0.1...+2.4 MPa
2X5 0...2.5 MPa 2X5 0...2.5 MPa abs
4X0 0...4 MPa
6X0 0...6 MPa
010 0...10 MPa
016 0...16 MPa
025 0...25 MPa
040 0...40 MPa
060 0...60 MPa

10 SICK 8013162 | 2009-11


PBS

Type Code

Measurement ranges psi / Gauge Pressure psi / Absolute Pressure psi / Compound Pressure
015 0...15 psi 015 0...15 psi abs 015 -30 InHg...0 psi
025 0...25 psi 025 0...25 psi abs 030 -30 InHg...+15 psi
030 0...30 psi 030 0...30 psi abs 040 -30 InHg...+25 psi
050 0...50 psi 050 0...50 psi abs 045 -30 InHg...+30 psi
100 0...100 psi 100 0...100 psi abs 065 -30 InHg...+50 psi
160 0...160 psi 160 0...160 psi abs 115 -30 InHg...+100 psi
200 0...200 psi 200 0...200 psi abs 175 -30 InHg...+160 psi
300 0...300 psi 300 0...300 psi abs 215 -30 InHg...+200 psi
500 0...500 psi 315 -30 InHg...+300 psi
1K0 0...1000 psi
1K5 0...1500 psi
2K0 0...2000 psi
3K0 0...3000 psi
5K0 0...5000 psi
8K0 0...8000 psi

Measurement ranges kg/cm2 / Gauge Pressure kg/cm2 / Absolute Pressure kg/cm2 / Compound Pressure
1X0 0...1 kg/cm2 1X0 0...1 kg/cm2 abs 1X0 -1...0 kg/cm2
1X6 0...1.6 kg/cm2 1X6 0...1.6 kg/cm2 abs 2X5 -1...+1.5 kg/cm2
2X5 0...2.5 kg/cm 2
2X5 0...2.5 kg/cm abs
2
4X0 -1...+3 kg/cm2
4X0 0...4 kg/cm2 4X0 0...4 kg/cm2 abs 6X0 -1...+5 kg/cm2
6X0 0...6 kg/cm2 6X0 0...6 kg/cm2 abs 010 -1...+9 kg/cm2
010 0...10 kg/cm 2
010 0...10 kg/cm abs2
016 -1...+15 kg/cm2
016 0...16 kg/cm2 016 0...16 kg/cm2 abs 025 -1...+24 kg/cm2
025 0...25 kg/cm2 025 0...25 kg/cm2 abs
040 0...40 kg/cm 2

060 0...60 kg/cm2


100 0...100 kg/cm2
160 0...160 kg/cm2
250 0...250 kg/cm2
400 0...400 kg/cm2
600 0...600 kg/cm2
Errors excepted, subject to modifications

2009-11 | 8013162 SICK 10


1
Australia Österreich
8013162-TL83/2009-11-01 ∙ DIV09/FD ∙ Printed in Germany (2009-11) ∙ Subject to change without notice ∙ The specified product features and technical data do not represent any guarantee ∙ 01 US modiefied 4c int32

Phone +61 3 9497 4100 Phone +43 (0)22 36 62 28 8-0


1800 33 48 02 – tollfree E-Mail [email protected]
E-Mail [email protected] Polska
Belgium/Luxembourg Phone +48 22 837 40 50
Phone +32 (0)2 466 55 66 E-Mail [email protected]
E-Mail [email protected] Republic of Korea
Brasil Phone +82-2 786 6321/4
Phone +55 11 3215-4900 E-Mail [email protected]
E-Mail [email protected] Republika Slowenija
Ceská Republika Phone +386 (0)1-47 69 990
Phone +420 2 57 91 18 50 E-Mail [email protected]
E-Mail [email protected] România
China Phone +40 356 171 120
Phone +852-2763 6966 E-Mail [email protected]
E-Mail [email protected] Russia
Danmark Phone +7 495 775 05 34
Phone +45 45 82 64 00 E-Mail [email protected]
E-Mail [email protected] Schweiz
Deutschland Phone +41 41 619 29 39
Phone +49 211 5301-301 E-Mail [email protected]
E-Mail [email protected] Singapore
España Phone +65 6744 3732
Phone +34 93 480 31 00 E-Mail [email protected]
E-Mail [email protected] Suomi
France Phone +358-9-25 15 800
Phone +33 1 64 62 35 00 E-Mail [email protected]
E-Mail [email protected] Sverige
Great Britain Phone +46 10 110 10 00
Phone +44 (0)1727 831121 E-Mail [email protected]
E-Mail [email protected] Taiwan
India Phone +886 2 2375-6288
Phone +91–22–4033 8333 E-Mail [email protected]
E-Mail [email protected] Türkiye
Israel Phone +90 216 587 74 00
Phone +972-4-999-0590 E-Mail [email protected]
E-Mail [email protected] USA/Canada/México
Italia Phone +1(952) 941-6780
Phone +39 02 27 43 41 1 800-325-7425 – tollfree
E-Mail [email protected] E-Mail [email protected]
Japan
Phone +81 (0)3 3358 1341
E-Mail [email protected]
Nederlands
Phone +31 (0)30 229 25 44
E-Mail [email protected]
Norge  More representatives and agencies
Phone +47 67 81 50 00 in all major industrial nations at
E-Mail [email protected] www.sick.com

SICK AG | Waldkirch | Germany | www.sick.com