As Built
As Built
As Built
2.00.00 CONSTRUCTION
(#FIXED TYPE)
2.02.00 Installation
2.02.04 Additional base channel for embedment in : Fabricated base frame of 75mm height with black paint
foundation shade
2.02.05 Front access : Hinged door
2.02.06 Rear access : Bolted cover for L4.5/T3.5 panels Item10 & 70,
Hinged door for S1.5 for item 20-60 & 80-90.
2.03.00 Degree of protection for enclosure : IP42 for above 1600A Rating’s,
IP52 for upto 1600A Rating.
2.04.00 Painting
2.06.00 Sheet steel thickness of various parts : As per SIEPAN-8PU standard (Refer Annexure-II)
2.07.02 Limit switch for Trolley position : Provided for test & service position
3.00.00 BUSBARS/CONNECTIONS
3.01.08 Insulation (except at joints & tap-offs) : Heat shrunk PVC sleeves
3.01.10 Location/arrangement of main busbars : In busbar chamber at top/horizontal formation except for
Neutral
3.02.02 Rated current / Size : 50% of Main Busbar rating / Refer Annexure -A
3.02.04 Rated short time withstand current and its : 30KA for 1sec.
duration
4.02.02 Source for above : Tapped from Bus side through Control transformers with
Change over Ckt.
4.03.02 Source for above : Tapped from Bus side through Control transformers with
Change over Ckt
4.04.02 Source for above : Tapped from Phase and Neutral of the incoming side of the
Incomer
4.05.02 Source for above : Tapped from Phase and Neutral of the incoming side
4.05.04 Rating : 100W for each front for 8PU-S1.5 panels & 200W for
8PU-L4.5/T3.5 panels
4.05.07 Location of Control/Protection Equipment : Cable Alley of each MCC panel & LT compartment for CB
4.06.02 Source for above : Tapped from Phase and Neutral of the incoming side
4.06.07 Location of Control/Protection Equipment : Cable Alley of each MCC panel & LT compartment for CB
panels
4.07.02 Source for above : Tapped from Phase and Neutral of the incoming side
4.07.07 Location of Control/Protection Equipment : Cable Alley of each MCC panel & LT compartment for CB
panels
4.09.01 Details and applicable circuits : B1,B2 for 240V AC supply for Panel/Motor Space Heater;
B3-B4 for 110V AC Motor & Power Feeder Control supply ;
B5,B6 for 110V DC External supply for ACB Motor/ACB
Closing/ACB tripping/Indication supply.
5.00.00 WIRING
5.01.00 Power Circuits (PVC insulated copper stranded flexible of grey colour)
5.02.00 Auxiliary Circuits (PVC insulated copper stranded flexible of grey colour)
5.03.04 Circuit identification : White Printed Tubular ferrules at terminations as per “Local
End Dependant Marking”
5.04.02 Between shipping sections : By Siemens at site (Works to provide necessary length of
wires complete with lugs & ferrules at both ends,
terminated at one end and the length coiled at that end)
6.01.01 Entry from : Provision for Busduct Entry at PMCC Incomer from TOP.
6.03.01 Type : Drawout Lyra contact for Drawout (S1.5) panels ,Fixed
Stud type for Non Drawout Panels & Busbar for ACB
panels.
6.04.01 Type of terminals for CB feeders : Drawout type for CB and fixed terminals for external
6.04.05 Type of fixed terminals for CT : Polyamide type (Elmex KLTDM4 or equivalent for
shorting).
6.05.01 Arrangement for connection to external earthing : One hole with bolt & nut on earth busbar at each end
grid
6.05.02 Earthing of meters and relays mounted on door : All metal parts connected to door through mounting screw
6.05.03 Earthing of All doors : With 2.5mm sq. PVC (Yellow Green Colour) insulated
copper wire to the frame
7.00.00 EQUIPMENT
7.02.00 Fuse-switches/MCCBs
8.00.03 All Gland Plate shall be 3mm Thick & for single core cable AL.Gland plate shall be provided.
8.00.04 Not more than 2 wires shall be terminated at one control terminal.
8.00.05 Danger Board name plate shall be provided on front & rear of the panel in English & Hindi
8.00.07 All power outgoing feeder upto 100A PVC insulated wire connection and above 100A incoming connection Copper
busbar & outgoing connection Aluminum busbar shall be provided.
8.00.08 Board Name Plates shall be provided at Top of the Center panel.
8.00.11 Neoprene gaskets for all the doors & removable covers shall be provided.
8.00.12 Feeder Name Plate shall be provided on front & rear of the ACB Panel.
8.00.16 Danger board Name Plate shall be provided for VBBC,HBBC on front & Rear.
ANNEXURE – I
MAKES OF EQUIPMENT
Equipment Make
Air Circuit Breaker Siemens
MCCB / MPCB Siemens
Power / Auxiliary Contactors Siemens
Overload Relays Siemens
CT Siemens
Control Transformer Precise
Transducers Rishabh
Multifunction Meters Siemens (Profibus PAC4200) PCC I/C & O/G
Secure (RS-485 ELITE-441) Other MCC I/C
Analogue Meters AE
Digital Schneider Electric/Secure
Push Buttons / Indicating Lamps Siemens
Control Switches Kaycee
Breaker Control Switches Kaycee
Power receptacles Anchor
MCB Siemens
Control Fuse/Link/Base Siemens
Control Terminals Elmex/Phenoix/Wago
Lugs Billet / 3D
Wire RR Kable
Test terminal block DAV
ANNEXURE – A
SR. No. ITEM No. SWITCHBOARD QTY. MAIN B/B SIZE MAIN (R-Y-B) SIZE NEUTRAL
RATING
1 10 PMCC 1X 4000A 2X2X200X10 AL 3X120X10 AL
2 20 AQC BOILER MCC 1X 250A 1X80X10 AL 1X40X10 AL
3 30 PREHEATER BOILER 1X 400A 1X80X10 AL 1X40X10 AL
MCC-1
4 40 PREHEATER BOILER 1X 400A 1X80X10 AL 1X40X10 AL
MCC-2
5 50 AUXILIARY MCC 1X 400A 1X80X10 AL 1X40X10 AL
6 60 STG MCC 1X 400A 1X80X10 AL 1X40X10 AL
7 70 EMERGENCY MCC-1 1X 630A 1X80X10 AL 1X40X10 AL
8 80 EMERGENCY MCC-2 1X 400A 1X80X10 AL 1X40X10 AL
9 90 EMERGENCY MCC-3 1X 250A 1X80X10 AL 1X40X10 AL