Motorized Circuit Breaker (Up To 63 A) : Overcurrent and Earth Leakage Protection and Self-Reclosing

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Self-reclosing overload and earth leakage protection

Overcurrent and earth leakage protection and self-reclosing

MT
Motorized circuit breaker (up to 63 A)

Description Features

The motorized circuit breakers of the MT Se- Circuit-breaker

ries can be associated remotely. They protect Gauges In (A) 6-10-16-20-25-32-40-50-63


against short-circuits and overloads, but are Nominal cut-out power (IEC 947-2)
6 kA, in accordance with EN 60898
10 kA, in accordance with EN 60947-2
also used as a circuit breaker.
Typical curve C or D, depending on the type

Includes auxiliary contacts to indicate the sta- Nominal working voltage 240 / 415 Vac

tus of the circuit breaker. Work frequency range 50 ... 60 Hz


Operating temperature -25 ... +55 ºC
The switch can be connected again after a Storage temperature -55 ... +55 ºC
manual or circuit breaker disconnection with Motor
an electric order following the "DISCONNEC- Nominal voltage 230 Vac, ± 10 %
TION (0) - CONNECTION (1)" sequence.
Opening impulse > 50 ms
Closing impulse > 50 ms
Construction features
Fixing DIN rail
Application Dimensions
2 poles: 5.5 modules
4 poles: 7.5 modules
Mechanical working life > 20,000 operations
The MT Series is composed of motorized cir-
2 poles: 645 g
cuit breakers that can be activated remotely Weight
4 poles: 890 g
and can be used in any application that uses Degree of protection IP 40 (DIN 40050)
a connection/disconnection remote control.
Standards
They are also used as the circuit breakers
IEC 947-2, IEC 60898
associated to the self-reclosing relays.

They are a vital accessory in the self-reclos-


ing overload and earth leakage protection
process.

P2-33
Self-reclosing overload and earth leakage protection

Overcurrent and earth leakage protection and self-reclosing Dimensions

MT 2 poles

Motorized circuit breaker (up to 63 A)

4 poles

References

2 poles 4 poles

C Curve D Curve C Curve D Curve

In (A) Type Code Type Code Type Code Type Code

6 MT-C-E62-6A P20110 MT-D-E62-6A P20130 MT-C-E64-6A P20120 MT-D-E64-6A P20140

10 MT-C-E62-10A P20111 MT-D-E62-10A P20131 MT-C-E64-10A P20121 MT-D-E64-10A P20141

16 MT-C-E62-16A P20112 MT-D-E62-16A P20132 MT-C-E64-16A P20122 MT-D-E64-16A P20142

20 MT-C-E62-20A P20113 MT-D-E62-20A P20133 MT-C-E64-20A P20123 MT-D-E64-20A P20143


Conexionado Motor MT
25 MT-C-E62-25A P20114N MT-D-E62-25A P20134 MT-C-E64-25A P20124 MT-D-E64-25A P20144
L
32 MT-C-E62-32A P20115 MT-D-E62-32A P20135 MT-C-E64-32A P20125 MT-D-E64-32A P20145

40 MT-C-E62-40A P20116 MT-D-E62-40A P20136 MT-C-E64-40A P20126 MT-D-E64-40A P20146


Orden desconexión externa
50 MT-C-E62-50A P20117 2 4 MT-D-E62-50A
12 14 22 24 N L P20137 MT-C-E64-50A P20127 MT-D-E64-50A P20147
0
63 MT-C-E62-63A P20118 MT-D-E62-63A
M P20138 MT-C-E64-63A P20128 MT-D-E64-63A P20148
H H
I
Accessory - Trip coil 1 3 11 21 F6 P29101
Orden conexión externa

N L
CARGA
Connections

N L

External disconnection signal


2 4 12 14 22 24 N L
0
H H
M
I
1 3 11 21 External connection signal

N L
LOAD

P2-34