gc250 Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

 NEW AUTO-START and AMF (Automatic Mains Failure) controller for single gensets

 3 Phase mains (utility) sensing


 3 Phase generator sensing
 3 x CTs Inputs
 True RMS measurements: kW, kVA, kVAr, pf, kWh (phase & total)
 4 Configurable Digital Inputs
 3 Analogue Inputs + 1 Extra Analogue Input (instead of a digital Input) + 1 for D+
 4 Configurable Digital Output + 2 Digital Output 10A
 Interface for MPU and J1939 engines as standard
 USB serial port for configuration and FW update
 Large LCD display 128x64 with LED backlight and ICONES
 Compact dimensions: 144(W)x108(H)x40(D)mm (34mm)

 Attractive price  IP65 as protection degree with gasket always included as standard
 Periodical test
 Outstanding
 Real Time clock
performances including
AND/OR logics  Data recording: 64 Events log (64 slow trend and 42 fast trend)
 Remote start and stop
 Alternative configurations
especially used for rental  Built in alarm sounder
sets
 Free configuration software BOARD PRG
 User friendly, intuitive and
easy to use

 Italian design
Additional measures available based on the Isolated
and Auto-supplied CAN J1939 .
GC250 is the newest controller made by SICES for single
stand-by gensets.
The same controller can be also used for AUTO START
applications. A set of high efficiency LEDs are used for signalling the
Despite the compact dimensions, GC250 includes the main current status of the Generator Set and for the
engine and alternator protections like the engine speed, oil visualization of alarm occurred. By means of ICONES it
pressure, coolant temperature, frequency, voltage, current, is possible to realize the type of the alarm/shutdown
power and fuel level.
The same controller can be used for electronic engines with Engine protections
CAN interface J1939 protocol and MPU engines (non-  Fuel reserve
electronic) as well.  Min./Max. fuel level
Configuring the Inputs, Outputs and protections, GC250 can be
easily adapted to suit a wide range of applications.
 Min./Max. battery voltage
GC250 offers a wide, graphic and powerful resolution display  Min./Max. oil pressure
128x64 pixel providing ICONS for alarms/warning advices and  Min./Max. water temperature
for signalling the status of the engine, controller and data logs  Max. Power (32P)
as well.  Closing of mains contactor or genset contactor failed
All parameters can be easily configured through USB using the
 Engine over crank
free software tool (BoardPrg), which can be downloaded
thorough Sices website. It is also possible to set them directly  Over speed from generator frequency
through GC250 keyboard.  Belt breakage
 Operating conditions not reached
 Emergency Stop
Mains Voltage:
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 Generator protections
True RMS measure  Underfrequency (81U)
Max 300Vac CAT III (L-N)  Overfrequency (81O)
Max 520Vac CAT III (L-L)  Undervoltage (27)
Generator Voltages:  Overvoltage (59)
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
 Time dependent overcurrent (51)
True RMS measure
Max 300Vac CAT III (L-N)  Instantaneous overcurrent (50, 50V)
Max 520Vac CAT III (L-L)  Phase sequence (47)
Generator Currents:  Current and Voltage unbalance (46/47)
L1, L2, L3
True RMS measure. Mains protections
Rated current: 5A  Min./Max. mains voltage (27/59)
Generator and Mains Frequency meter:  Min./Max. mains frequency (81U/81O)
Resolution = 0.1 Hz.
Accuracy = ±50ppm, ±35ppm/°C (typical)  Mains failure
Battery Voltmeter:
Resolution = 0.1V
Oil Pressure Gauge:  N. 4 Configurable digital Inputs
VDO 0-10 Bar, VDO 0-5 Bar, Veglia 0-8 Bar
(Settable curve based on sensors available)  N. 3 Analogue Inputs + N.1 Additional digital Input, which
Water or Oil Thermometer: can be used as analogue + N.1 Analogue Input for D+ (if not
VDO, Veglia, BERU used in this way, they can be used as not isolated digital
(Settable curve based on sensors available) Inputs)
Fuel Level:  N. 4 Configurable digital voltage source Outputs
VDO, Veglia  N. 2 High power digital voltage source Outputs (10A) for fuel
(Settable curve based on sensors available) solenoid and engine start.
Engine revolution counter:  Built tin alarm sounder
By frequency detection.  Engine diagnostic code
D+ for the measure of the voltage alternator battery
 Real Time Clock with internal rechargeable Lithium battery
charger
 Periodical test
Power and power factor measures are available as total  AND/OR Configurable logics
measures and for each single phase too.
Maximum power and current reached values, are Operating temperature: -30°C to 70°C
registered with date and time. Storage temperature: -30°C to 80°C
Dimensions: 141(L)x113(H)x39(P)mm - Weight: 200g
Cut-Out dimensions: 18x92mm
Protection degree: IP65 (with complimentary gasket).
The display of GC250 offers a full set of info,
providing clear symbols and code concerning the
alarm occurred.
In case of multiple alarms, the display offers a clear
notification of all the failures with the related
symbol and code.
When an ECU engine is connected, the description
of the alarm is available as well.