Emsd - Gov.hk-Application Guide To Variable Speed Drives VSD PDF
Emsd - Gov.hk-Application Guide To Variable Speed Drives VSD PDF
Emsd - Gov.hk-Application Guide To Variable Speed Drives VSD PDF
emsd.gov.hk/en/energy_efficiency/energy_management/publications/application_guide_to_variable_speed_driv
es_vsd
Print
In Hong Kong, most of the 3-phase ac motors in buildings are fitted to fans and pumps.
The flow from most fans and pumps is either constant or controlled by restricting the
flow by mechanical means, e.g. dampers are used on fans and valves are used on
pumps. This mechanical constriction will control the flow and may reduce the load on
the fan or pump motor, but the constriction itself adds an energy loss that is obviously
inefficient. Hence if the flow can be controlled by reducing the speed of the fan or pump
motor, more efficient means of achieving flow control could be offered.
As the speed of the fan or pump is reduced, the flow will reduce proportionally, while the
power required by the fan or the pump will reduce with the cube of the speed. This level
of potential energy saving makes the use of Variable Speed Drive (VSD) a cost-effective
investments in energy efficiency which can be considered for motors.
A VSD can be regarded as a frequency converter rectifying ac voltages from the mains
supply into dc, and then modifies this into a ac voltage with variable amplitude and
frequency. The motor is thus supplied with variable voltage and frequency, which
enables infinitely variable speed regulation of three-phase, asynchronous standard
induction motors.
1/7
Application of VSD in Primary Air-Handling Units (PAU)
Conventional fresh air supply introduced into a high-rise commercial building is normally
fed via a Primary Air-handling Unit (PAU) at constant air volume. The conventional PAU is
part of a central air conditioning system usually used to supply fresh conditioned air via
riser ductwork to the floors it served at constant rate, regardless of the actual needs of
the zones served. The PAU brings outside air, at a designed temperature of 33.5?X C, into
filters prior to pre-cooling it to 20?X C and delivers it via fans and ductwork to serve
individual floors. This system is designed for "worst case" condition and end up wasting
energy relative to the needs of the building for most of the operational life. No
modulation method had normally been allowed in the design other than the original
balancing of the system. The system is normally operated continuously from 8:00 am to
6:00 pm for general offices building.
Demand control on PAUs using carbon dioxide offers a unique opportunity for building
services engineers and building owners to resolve the problem of how to reduce energy
costs while optimising indoor air quality.
2/7
Rather these reactions are more related to the build-up of other contaminants and
irritants in the space when ventilation levels are low. CO 2 is therefore often considered a
good surrogate indicator of indoor air quality.
According to ASHRAE Standard 62-1989 " Ventilation for Acceptable Indoor Air Quality",
ventilation maintaining an indoor CO 2 content of 1000 ppm is considered ideal. CO 2
lower than 800 ppm is considered as over-ventilated. Some of the government office
buildings investigated under the Pilot EMO Implementation Programme have average
measured CO 2 concentration below 700 ppm. Therefore CO 2 based demand control
ventilation has good potential to reduce energy consumption while optimising indoor air
quality.
The CO 2 based demand control can also be achieved by the direct application of CO 2
sensors for real time speed control of PAU. Recent innovations in gas sensor designs
have considerably improved the long-term performance and cost of CO 2 sensors,
making it one of the fast growing segments of the HVAC control industry. The CO 2
sensors should be located at some strategic location where "worst case" occurred. The
figure below shows a possible arrangement of a variable flow PAU using VSD and CO 2
sensors.
3/7
to its VAV box and opens or closes the VAV box to maintain the defined temperature
setpoint. As the zone becomes satisfied, the VAV box modulates to a close position. The
pressure in the ductwork would then begin to rise as the openings in the VAV box close.
Traditionally, inlet guide vanes or discharged dampers are installed in the AHUs to
prevent this over pressurisation and save energy. These devices work by creating
resistance and a pressure drop to the air entering the ductwork or reducing the
efficiency of the fan. The more the VAV boxes in the system close, the more the dampers
close to maintain static duct pressure. The dampers or inlet guide vanes for the fan are
commonly controlled by a controller maintaining a fixed pressure in the supply ductwork
downstream of the AHU.
While dampers and inlet guide vanes work to maintain a constant pressure in the
ductwork of a VAV system, the utilisation of VSD could save much more energy and
reduce the complexity of the installation. Instead of creating an artificial pressure drop or
causing a decrease in fan efficiency, the VSD decrease the speed of the fan to provide
the flow and pressure required by the system. The figure below shows a modified VAV
system with VSD in lieu of the conventional star-delta motor starter and motorised
dampers for static pressure control in the ductwork.
For new high-rise building projects involving CO 2 -based demand control ventilation via
central PAUs, it would be more appropriate to include individual duct-mounted CO 2
sensors at the return air ducts to control the amount of fresh air drawn from the main
riser duct at the AHU rooms on each floor. The total demand of fresh air required to be
handled by PAUs should then be control either via static pressure sensors in the main air
duct or summation of individual fresh air requirement at each floor together with
appropriate DDC controllers and VSDs. A typical configuration diagram of the system is
shown in the figure below
4/7
Application of VSD in Secondary Chilled Water Circuit
Primary pumps in a primary/secondary pumping can be used to maintain a constant
flow through chillers that encounter operation or control difficulties when exposed to
variable flow.
In chilled water systems, the primary loop consists of primary pumps sized to handle the
chillers designed flow rate at a discharge pressure just high enough to circulate the water
through the chiller and the rest of the primary piping loop. The secondary chilled water
loop is a variable flow system consists of secondary pumps sized to circulate chilled
water to handle full capacity of the cooling loads connected on the circuit. During light
load condition, most of the two-port control valves on the loads are not fully open
resulting in pressure rise in the secondary chilled water loop. In a conventional system, a
5/7
by-pass valve connected across the cooling loads will be used to by-pass the secondary
water flow and regulate the flow to loads and balance the water pressure in the system.
A differential pressure sensor normally controls the by-pass valve.
The figure shows a new arrangement of the secondary chilled water circuit with VSD in
lieu of by-pass valve for regulation chilled water flow according to the actual loading
requirement. Energy saving is achieved in pump motors in most of the time when the
cooling loads are not at full capacity and maximum chilled water flow is not required.
For more information about the application of VSDs in building air conditioning systems,
please contact the Energy Efficiency Office at tel no. 2808 3465
6/7
7/7