Automatic Level Control Systems - Spirax Sarco
Automatic Level Control Systems - Spirax Sarco
Automatic Level Control Systems - Spirax Sarco
COVID-19
About us
Global Locations
Careers
Learn about steam
Resources and Design Tools
Contact Head Office
Contents
Introduction
Shell Boilers
Water Tube Boilers
Miscellaneous Boiler Types Economisers and Superheaters
Boiler Ratings
Boiler Efficiency and Combustion
Boiler Fittings and Mountings
Steam Headers and Off Takes
Water Treatment Storage and Blowdown for Steam Boilers
Water for the Boiler
The Feedtank and Feedwater Conditioning
Controlling TDS in the Boiler Water
Heat Recovery from Boiler Blowdown TDS Control Only
Bottom Blowdown
Water Levels in Steam Boilers
Methods of Detecting Water Level in Steam Boilers
Automatic Level Control Systems
Water Level Alarms
Installation of Level Controls
Testing Requirements in the Boiler House
Pressurised Deaerators
Steam Accumulators
On/off control
All the methods of level detection described so far can be used to produce an on/off signal for level control. The most common method of
level control is simply to start the feedpump at a low level and allow it to run until a higher water level is reached within the boiler.
With a float level control, a magnetic switch with a built-in hysteresis or dead-band will be used.
With conductivity probes, two probes are necessary, (pump on and pump off) which will give fixed switching levels.
A capacitance probe can be used to give adjustable on/off switching levels.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 1/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
In the UK, on/off type control is almost universal on boilers below about 5 000 kg/h steam generation rate because it is the least expensive
option. (In Australia and New Zealand, standards state that for boilers exceeding 3 MW (typically 5 000 kg/h), modulating control must
be fitted).
It can be argued, however, that this type of on/off control is not ideal for boiler control, because the relatively high flowrate of ‘cold’
feedwater when the pump is on reduces the boiler pressure.
This causes the burner firing rate to continuously vary as the pump switches on and off.
Taking a typical example, it can be shown by calculation that even with feedwater at 80°C, the burner firing rate may have to be 40%
higher with the feedpump on, than with the feedpump off.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 2/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
If steam loads are high, the variable steam flowrate will tend to increase water carryover with the steam, and will tend to make water levels
increasingly unstable with the associated danger of low water level lockout, particularly on multi-boiler installations.
However, the fact remains that on/off control is very widely used on boilers of small to medium output, as defined above, and that many
problems associated with steam boilers operating with large swings in load are due in part to on/off level control systems.
Advantages:
Simple.
Inexpensive.
Good for boilers on stand-by.
Disadvantages:
Modulating control
In this type of system the feedpump runs continuously, and an automatic valve (between the feedpump and the boiler) controls the
feedwater flowrate to match the steam demand.
When operating correctly, modulating control can dramatically smooth the steam flowrate chart and ensure greater water level stability
inside the boiler.
For modulating level control, the following methods can be used to sense the water level:
Recirculation
To protect the feedpump from overheating when pumping against a closed modulating valve, a recirculation or spill-back line is provided
to ensure a minimum flowrate through the pump.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 3/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
This recirculation may be controlled by a valve or with an orifice plate. The amount of water to be recirculated is not great, and guidance is
usually available from the pump manufacturer. As an indication, the orifice size will usually be between 5 mm and 7 mm for a
typical boiler.
Modulating level control by varying the speed of the boiler feedwater pump
In this type of system, a modulating signal representing boiler water level (for example, from a capacitance probe) is directed to an
electrical frequency controller. This controller in turn varies the frequency of the ac voltage to the boiler feedwater pump motor, and hence
varies its speed.
In this way the speed of the pump is modulated to provide a feedwater flowrate which matches the boiler’s demand for feedwater.
There are two ways that variable speed drive technology is generally applied:
With recirculation - When demand is satisfied and the motor speed is reduced to its minimum, and some recirculation of feedwater to the
feedtank is still required to avoid the pump overheating (see Figure 3.17.5).
Without recirculation - In this case the motor controller stops the feedpump at very low boiler loads, so recirculation is not required.
Two important factors related to stopping and starting of the pump are:
The pump must not be started and stopped within a given period of time more than is recommended by the manufacturer.
When starting, the frequency controller should be ramped up from low speed, to minimise wear on the pump.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 4/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
The principle advantage of variable speed drives is that as the speed of the pump varies, so does its power consumption, and, of course,
reduced power consumption means reduced running costs.
However, the cost savings from using variable speed drives must be related to the higher cost of the control equipment. This is usually
only viable for large boilers with wide variations in load or which operate in a lead/lag manner.
The standard single element boiler water level control system, with proportional control, gives excellent control on the majority of
boiler installations.
However, with single element proportional control, the water level must fall for the feedwater control valve to open. This means that the
water level must be higher at low steaming rates and lower at high steaming rates: a falling level control characteristic.
However, where there are very sudden load changes, on some types of water-tube boiler, single element control has its limitations.
Consider the situation when a boiler is operating within its rated capacity:
The boiler ‘water’ will actually contain a mixture of water and steam bubbles, which will be less dense than water alone.
If the demand for steam increases, the pressure in the boiler initially falls, and the control system will increase the burner firing rate.
The rate of evaporation will increase to meet the increased demand.
The increased rate of evaporation means that the boiler water will contain more steam bubbles and become even less dense.
The pressure inside the boiler is further reduced, and a proportion of the boiler water will flash to steam. The flashing of the boiler
water, plus the increased heat input as the burners turn up to maximum, means that the boiler ‘water’ will contain even more steam
bubbles, and its density will be further reduced.
As the pressure falls, the specific volume of the steam increases, and the resulting higher velocity at which the steam is drawn off the
boiler can create a ‘swell’ of the steam bubble/water mixture, resulting in an apparent rise in water level.
The level controls will detect this apparent rise in water level, and start to close the feedwater control valve, when in fact more water
is required. The situation now, is that there is a high steam demand, and no water is being added to the boiler to maintain the level.
A point is reached where the ‘swell’ in the water will collapse, possibly to a level below the low level alarms, and the boiler can
suddenly ‘lockout’, bringing the plant off-line.
Two element control reverses the falling level control characteristic to ensure that the water level is made to rise at high steaming rates.
This strives to ensure that the quantity of water in the boiler stays constant at all loads, and that during periods of increased, sudden steam
demand, the feedwater control valve opens.
The system works by using the signal from a steam flowmeter installed in the steam discharge pipework to increase the level controller set
point at high steam loads.
First element - Level signal from the water within the boiler.
Second element - Flow signal from the steam flowmeter in the boiler steam off-take.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 5/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Any boiler installation which experiences frequent, sudden changes in load may work better with a two element feedwater control system.
Where process load changes are severe (breweries are a common application) two element control should be considered and would appear
to be necessary where there are sudden load changes of more than 25%, on a boiler.
Three element control as shown in Figure 3.17.8, involves the two signal elements as previously mentioned, plus a third element, which is
the actual measured flowrate of feedwater into the boiler. Three element control is more often seen in boiler houses where a number of
boilers are supplied with feedwater from a common, pressurised ring main.
Under these circumstances the pressure in the feedwater ring main can vary depending on how much water is being drawn off by each of
the boilers.
Because the pressure in the ring main varies, the amount of water which the feedwater control valve will pass will also vary for any
particular valve opening. The input from the third element modifies the signal to the feedwater control valve, to take this variation in
pressure into consideration.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 6/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Advantages:
Steady steam pressure and flowrate within the boiler’s thermal capacity.
More efficient burner operation.
Less thermal stress on the boiler shell.
Less boiler water carryover.
Can use a central feedpump station.
Less wear and tear on the feedpump and burner.
Disadvantages
More expensive.
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 7/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Feedpump must run continually.
Less suitable for ‘stand-by’ operation.
Possibly greater electricity consumption.
Investors
Privacy Policy
Legal Notice
Abkhazia
Aland Island
Albania
Andorra
Armenia
Austria
Azerbaijan
Belarus
Bosnia & Herzegovina
Bulgaria
Croatia
Cyprus
Estonia
Faroe Islands
Georgia
Gibraltar
Greece
Greenland
Guernsey
Iceland
Ireland
Isle of Man
Jersey
Latvia
Liechtenstein
Lithuania
Luxembourg
Macedonia
Malta
Moldova
Monaco
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 9/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Montenegro
Nagorno-Karabakh
Netherlands Antilles
San Marino
Serbia
Slovakia
Slovenia
Svalbard
American Samoa
Anguilla
Antigua & Barbuda
Aruba
Bahamas
Barbados
Bermuda
British Virgin Islands
Cayman Islands
Dominica
Montserrat
Saint Barthelemy
Saint Kitts & Nevis
Saint Lucia
Saint Martin
Saint Pierre and Miquelon
Saint Vincent & the Grenadines
Turks and Caicos Islands
US Virgin Islands
Belize
Bolivia
Costa Rica
Cuba
Dominican Republic
Ecuador
El Salvador
Falkland Islands
Grenada
Guyana
Haiti
Honduras
Jamaica
Nicaragua
Panama
Paraguay
Puerto Rico
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 10/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Suriname
Trinidad &Tobago
Uruguay
Venezuela
Afghanistan
Bangladesh
Bhutan
Brunei
Christmas Island
Cocos (Keeling) Islands
Cook Islands
East Timor
Fiji
French Polynesia
Guam
Hong Kong
Kiribati
Kyrgyzstan
Laos
Macao
Maldives
Marshall Islands
Micronesia
Mongolia
Nauru
Nepal
New Caledonia
Niue
Norfolk Island
Northern Mariana Islands
Pakistan
Palau
Papua New Guinea
Pitcairn Islands
Samoa
Solomon Islands
Sri Lanka
Tajikistan
Tokelau
Tonga
Turkmenistan
Tuvalu
Uzbekistan
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 11/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Vanuatu
Wallis & Futuna
Algeria
Angola
Ascension Island
Bahrain
Benin
Botswana
Burkina Faso
Burundi
Cameroon
Cape Verde
Central African Republic
Chad
Comoros
Côte d'Ivoire
Djibouti
DR Congo
Equatorial Guinea
Eritrea
Ethiopia
Gabon
Gambia
Ghana
Guinea
Guinea-Bissau
Iraq
Israel
Kuwait
Lebanon
Lesotho
Liberia
Libya
Madagascar
Malawi
Mali
Mauritania
Mauritius
Mayotte
Mozambique
Namibia
Niger
Nigeria
Oman
Qatar
Rwanda
Sahrawi Arab Democratic Republic
Saint Helena
São Tomé & Príncipe
Saudi Arabia
Senegal
Seychelles
Sierra Leone
Somalia
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 12/13
24/04/2020 Automatic Level Control Systems | Spirax Sarco
Swaziland
Tanzania
Togo
Tristan da Cunha
Tunisia
Uganda
United Arab Emirates
Yemen
Zambia
Zimbabwe
Close
Spirax Sarco
This region has not yet joined our new website. You will now continue to the existing site for Spirax Sarco
Continue
https://www.spiraxsarco.com/learn-about-steam/the-boiler-house/automatic-level-control-systems 13/13