Characteristics
ATV71HD30N4
Range of product
Altivar 71
Product or component
type
Component name
ATV71
Motor power kW
30 kW at 380...480 V 3 phases
Motor power hp
40 hp at 380...480 V 3 phases
380...480 V (- 15...10 %)
Network number of
phases
3 phases
Line current
EMC filter
Integrated
Assembly style
Apparent power
0.1...599 Hz
4 kHz
Switching frequency
Asynchronous motor
control profile
Type of polarization
Complementary
Product destination
Asynchronous motors
Synchronous motors
323...528 V
50...60 Hz (- 5...5 %)
47.5...63 Hz
Speed range
Speed accuracy
+/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode
with encoder feedback
+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback
Torque accuracy
Transient overtorque
Mar 9, 2013
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Braking torque
Regulation loop
Adjustable PI regulator
Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio (2 or 5 points)
Suppressable
Diagnostic
Output voltage
Insulation
Electrical connection
AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5
mm / AWG 14
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 50 mm /
AWG 1/0
Tightening torque
AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 0.6 N.m
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 12 N.m / 102.2 lb.in
Supply
AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max , resolution 11 bits + sign
AI2 software-configurable current 0...20 mA , impedance 242 Ohm, resolution 11
bits
AI2 software-configurable voltage 0...10 V DC, input voltage 24 V max,
impedance 30000 Ohm, resolution 11 bits
Response time
Linearity error
R1A, R1B, R1C configurable relay logic NO/NC, electrical durability 100000 cycles
R2A, R2B configurable relay logic NO, electrical durability 100000 cycles
Braking to standstill
By DC injection
Protection type
Insulation resistance
Frequency resolution
CANopen
Modbus
Type of connector
Physical interface
Transmission frame
Transmission rate
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face
Data format
Number of addresses
Method of access
Marking
CE
Operating position
Depth
266 mm
Height
550 mm
Width
240 mm
Product weight
37 kg
Option card
Environment
Noise level
64 dB conforming to 86/188/EEC
Dielectric strength
Electromagnetic compatibility
Standards
Product certifications
CSA
C-Tick
GOST
NOM 117
UL
Pollution degree
IP degree of protection
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP20 on upper part without blanking plate on cover conforming to EN/IEC
61800-5-1
IP21 conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP54 on lower part conforming to EN/IEC 61800-5-1
Vibration resistance
Shock resistance
Relative humidity
-25...70 C
Operating altitude
Compliant
0946
ATV71HD30N4
Dimensions in mm
a
240
550
266
206
531.5
11
9.44
21.65
10.47
8.11
20.93
0.45
0.23
Dimensions in in.
Dimensions in mm
a
c1
240
289
206
531.5
11
c1
9.44
11.38
8.11
20.93
0.45
0.23
Dimensions in in.
(1) Option cards: I/O extension cards, communication cards or "Controller Inside programmable card.
Dimensions in mm
a
c2
240
312
206
531.5
11
c2
9.44
12.28
8.11
20.93
0.45
0.23
Dimensions in in.
(1) Option cards: I/O extension cards, communication cards or "Controller Inside programmable card.
ATV71HD30N4
Mounting Recommendations
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate
accessories.
Install the unit vertically:
Avoid placing it close to heating elements
Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
Clearance
Mounting Types
Type A Mounting
Type B Mounting
Type C Mounting
By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20.
The protective blanking cover may vary according to the drive model (refer to the user guide).
The protective blanking cover must be removed from ATV 71PN4Z drives when they are mounted in a dust and damp proof enclosure.
ATV71HD30N4
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping
Category 0 According to IEC/EN 60204-1
Three-Phase Power Supply with Upstream Breaking via Contactor
A1
KM1
L1
Q1
Q2
Q3
S1,
S2
T1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
ATV71 drive
Contactor
DC choke
Circuit-breaker
GV2 L rated at twice the nominal primary current of T1
GB2CB05
XB4B or XB5A pushbuttons
100 VA transformer 220 V secondary
Line choke (three-phase); mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020 mA) or voltage (010 V) analog input.
Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping
Category 0 According to IEC/EN 60204-1
A1
L1
Q1
Q2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
ATV71 drive
DC choke
Circuit-breaker
Switch disconnector (Vario)
Line choke (three-phase), mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020mA) or voltage (010V) analog input.
Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping
Category 0 According to IEC/EN 60204-1
10
A1
A2
F1
L1
Q1
S1
S2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
ATV71 drive
Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the Power Removal
function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24V via the safety
contacts on the XPSAC module. These contacts are independent for each drive.
Fuse
DC choke
Circuit-breaker
Emergency stop button with 2 contacts
XB4 B or XB5 A pushbutton
Power supply: 24Vdc or Vac, 48Vac, 115Vac, 230Vac.
S2: resets XPS AC module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
Requests freewheel stopping of the movement and activates the Power Removal safety function.
Line choke (three-phase), mandatory for and ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
The logic output can be used to signal that the machine is in a safe stop state.
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NFC93-550, external diameter
2.54mm /0.09in., maximum length 15m / 49.21ft. The cable shielding must be earthed.
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020mA) or voltage (010V) analog input.
Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping
Category 1 According to IEC/EN 60204-1
11
A1
A2
(5)
F1
L1
Q1
S1
S2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
ATV71 drive
Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal
safety function for several drives on the same machine. In this case the time delay must be adjusted on the drive controlling the motor
that requires the longest stopping time. In addition, each drive must connect its PWR terminal to its + 24V via the safety contacts on
the XPS ATE module. These contacts are independent for each drive.
Fuse
DC choke
Circuit-breaker
Emergency stop button with 2 N/C contacts
Run button
Power supply: 24Vdc or Vac, 115Vac, 230Vac.
Requests controlled stopping of the movement and activates the Power Removal safety function.
Line choke (three-phase), mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
S2: resets XPSATE module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a
maximum time delay of 300 seconds.
The logic output can be used to signal that the machine is in a safe state.
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NFC93-550, external diameter
2.54mm/0.09in., maximum length 15m/49.21ft. The cable shielding must be earthed.
Logic inputs LI1 and LI2 must be assigned to the direction of rotation: LI1 in the forward direction and LI2 in the reverse direction.
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020 mA) or voltage (010 V) analog input.
Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
12
ATV71HD30N4
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For
intermediate temperatures (e.g. 55C), interpolate between 2 curves.
X
(1)
Switching frequency
Mounting type
Above 50C, the drive should be fitted with a control card fan kit.
13