Product data sheet

Characteristics

ATV71HD30N4

variable speed drive ATV71 - 30kW 40HP 480V

Range of product

Altivar 71

Product or component
type

Variable speed drive

Product specific application

Complex, high-power machines

Component name

ATV71

Motor power kW

30 kW at 380...480 V 3 phases

Motor power hp

40 hp at 380...480 V 3 phases

Motor cable length

<= 100 m shielded cable


<= 200 m unshielded cable

Power supply voltage

380...480 V (- 15...10 %)

Network number of
phases

3 phases

Line current

56 A for 480 V 3 phases 30 kW / 40 hp


66 A for 380 V 3 phases 30 kW / 40 hp

EMC filter

Integrated

Assembly style

With heat sink

Apparent power

43.4 kVA at 380 V 3 phases 30 kW / 40 hp

Prospective line Isc

<= 22 kA, 3 phases

Nominal output current

52 A at 4 kHz 460 V 3 phases 30 kW / 40 hp


66 A at 4 kHz 380 V 3 phases 30 kW / 40 hp

Maximum transient current

109 A for 2 s 3 phases 30 kW / 40 hp


99 A for 60 s 3 phases 30 kW / 40 hp

Speed drive output frequency

0.1...599 Hz

Nominal switching frequency

4 kHz

Switching frequency

1...16 kHz adjustable


4...16 kHz with derating factor

Asynchronous motor
control profile

ENA (Energy adaptation) system for unbalanced


loads
Flux vector control (FVC) with sensor (current vector)
Sensorless flux vector control (SFVC) (voltage or
current vector)
Voltage/Frequency ratio (2 or 5 points)

Type of polarization

No impedance for Modbus

Complementary
Product destination

Asynchronous motors
Synchronous motors

Power supply voltage limits

323...528 V

Power supply frequency

50...60 Hz (- 5...5 %)

Power supply frequency limits

47.5...63 Hz

Speed range

1...100 for asynchronous motor in open-loop mode, without speed feedback


1...1000 for asynchronous motor in closed-loop mode with encoder feedback
1...50 for synchronous motor in open-loop mode, without speed feedback

Speed accuracy

+/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode
with encoder feedback
+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback

Torque accuracy

+/- 15 % in open-loop mode, without speed feedback


+/- 5 % in closed-loop mode with encoder feedback

Transient overtorque

170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes


220 % of nominal motor torque +/- 10 % for 2 s

Mar 9, 2013

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Braking torque

< 150 % with braking or hoist resistor


30 % without braking resistor

Synchronous motor control profile

Vector control without speed feedback

Regulation loop

Adjustable PI regulator

Motor slip compensation

Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio (2 or 5 points)
Suppressable

Diagnostic

1 LED red presence of drive voltage

Output voltage

<= power supply voltage

Insulation

Electrical between power and control

Type of cable for mounting in an enclosure

With a NEMA Type1 kit: 3-strand UL 508 cable at 40 C, copper 75 C PVC


With an IP21 or an IP31 kit: 3-strand IEC cable at 40 C, copper 70 C PVC
Without mounting kit: 1-strand IEC cable at 45 C, copper 70 C PVC
Without mounting kit: 1-strand IEC cable at 45 C, copper 90 C XLPE/EPR

Electrical connection

AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5
mm / AWG 14
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB terminal 50 mm /
AWG 1/0

Tightening torque

AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 0.6 N.m
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB 12 N.m / 102.2 lb.in

Supply

Internal supply for reference potentiometer (1 to 10 kOhm), 10.5 V DC +/- 5 % ,


<= 10 mA for overload and short-circuit protection
Internal supply, 24 V DC , voltage limits 21...27 V, <= 200 mA for overload and
short-circuit protection

Analogue input number

Analogue input type

AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max , resolution 11 bits + sign
AI2 software-configurable current 0...20 mA , impedance 242 Ohm, resolution 11
bits
AI2 software-configurable voltage 0...10 V DC, input voltage 24 V max,
impedance 30000 Ohm, resolution 11 bits

Input sampling time

AI1-/Al1+ 2 ms, +/- 0.5 ms for analog input(s)


Al2 2 ms, +/- 0.5 ms for analog input(s)
LI1...LI5 2 ms, +/- 0.5 ms for discrete input(s)
LI6 (if configured as logic input) 2 ms, +/- 0.5 ms for discrete input(s)

Response time

<= 100 ms in STO (Safe Torque Off)


AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)
R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)
R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)

Absolute accuracy precision

AI1-/Al1+ +/- 0.6 % for a temperature variation 60 C


AI2 +/- 0.6 % for a temperature variation 60 C
AO1 +/- 1 % for a temperature variation 60 C

Linearity error

AI1-/Al1+, AI2 +/- 0.15 % of maximum value


AO1 +/- 0.2 %

Analogue output number

Analogue output type

AO1 software-configurable logic output 10 V <= 20 mA


AO1 software-configurable current 0...20 mA, impedance 500 Ohm, resolution 10
bits
AO1 software-configurable voltage 0...10 V DC, impedance 470 Ohm, resolution
10 bits

Discrete output number

Discrete output type

R1A, R1B, R1C configurable relay logic NO/NC, electrical durability 100000 cycles
R2A, R2B configurable relay logic NO, electrical durability 100000 cycles

Minimum switching current

Configurable relay logic 3 mA at 24 V DC

Maximum switching current

R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4,


R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4,
R1, R2 on resistive load, 5 A at 250 V AC, cos phi = 1,
R1, R2 on resistive load, 5 A at 30 V DC, cos phi = 1,

Discrete input number

Discrete input type

LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm


LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
LI6: switch-configurable PTC probe 0...6 , impedance: 1500 Ohm
PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to[pace]ISO
13849-1 level d

Discrete input logic

LI1...LI5 negative logic (sink), > 16 V (state 0), < 10 V (state 0)


LI1...LI5 positive logic (source), < 5 V (state 0), > 11 V (state 0)
LI6 (if configured as logic input) negative logic (sink), > 16 V (state 0), < 10 V
(state 0)
LI6 (if configured as logic input) positive logic (source), < 5 V (state 0), > 11 V
(state 0)

Acceleration and deceleration ramps

Automatic adaptation of ramp if braking capacity exceeded, by using resistor


Linear adjustable separately from 0.01 to 9000 s
S, U or customized

Braking to standstill

By DC injection

Protection type

Drive against exceeding limit speed


Drive against input phase loss
Drive break on the control circuit
Drive input phase breaks
Drive line supply overvoltage
Drive line supply undervoltage
Drive overcurrent between output phases and earth
Drive overheating protection
Drive overvoltages on the DC bus
Drive short-circuit between motor phases
Drive thermal protection
Motor motor phase break
Motor power removal
Motor thermal protection

Insulation resistance

> 1 MOhm at 500 V DC for 1 minute to earth

Frequency resolution

Analog input 0.024/50 Hz


Display unit 0.1 Hz

Communication port protocol

CANopen
Modbus

Type of connector

1 RJ45 for Modbus on front face


1 RJ45 for Modbus on terminal
Male SUB-D 9 on RJ45 for CANopen

Physical interface

2-wire RS 485 for Modbus

Transmission frame

RTU for Modbus

Transmission rate

20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face

Data format

8 bits, 1 stop, even parity for Modbus on front face


8 bits, odd even or no configurable parity for Modbus on terminal

Number of addresses

1...127 for CANopen


1...247 for Modbus

Method of access

Slave for CANopen

Marking

CE

Operating position

Vertical +/- 10 degree

Depth

266 mm

Height

550 mm

Width

240 mm

Product weight

37 kg

Option card

CC-Link communication card


Controller inside programmable card
DeviceNet communication card
Ethernet/IP communication card
Fipio communication card
I/O extension card
Interbus-S communication card
Interface card for encoder
Modbus Plus communication card
Modbus TCP communication card
Modbus/Uni-Telway communication card
Overhead crane card
Profibus DP communication card
Profibus DP V1 communication card

Environment
Noise level

64 dB conforming to 86/188/EEC

Dielectric strength

3535 V DC between earth and power terminals


5092 V DC between control and power terminals

Electromagnetic compatibility

1.2/50 s - 8/20 s surge immunity test conforming to IEC 61000-4-5 level 3


Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3 level 3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Standards

EN 55011 class A group 2


EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C3
EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 60721-3-3 class 3C1
IEC 60721-3-3 class 3S2
UL Type 1

Product certifications

CSA
C-Tick
GOST
NOM 117
UL

Pollution degree

2 conforming to EN/IEC 61800-5-1


3 conforming to UL 840

IP degree of protection

IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP20 on upper part without blanking plate on cover conforming to EN/IEC
61800-5-1
IP21 conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP54 on lower part conforming to EN/IEC 61800-5-1

Vibration resistance

1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6


1.5 mm peak to peak (f = 3...13 Hz) conforming to EN/IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to EN/IEC 60068-2-27

Relative humidity

5...95 % without condensation conforming to IEC 60068-2-3


5...95 % without dripping water conforming to IEC 60068-2-3

Ambient air temperature for operation

-10...50 C without derating

Ambient air temperature for storage

-25...70 C

Operating altitude

<= 1000 m without derating


1000...3000 m with current derating 1 % per 100 m

RoHS EUR status

Compliant

RoHS EUR conformity date

0946

ATV71HD30N4

Product data sheet


Dimensions Drawings

UL Type 1/IP 20 Drives


Dimensions without Option Card

Dimensions in mm
a

240

550

266

206

531.5

11

9.44

21.65

10.47

8.11

20.93

0.45

0.23

Dimensions in in.

Dimensions with 1 Option Card (1)

Dimensions in mm
a

c1

240

289

206

531.5

11

c1

9.44

11.38

8.11

20.93

0.45

0.23

Dimensions in in.

(1) Option cards: I/O extension cards, communication cards or "Controller Inside programmable card.

Dimensions with 2 Option Cards (1)

Dimensions in mm
a

c2

240

312

206

531.5

11

c2

9.44

12.28

8.11

20.93

0.45

0.23

Dimensions in in.

(1) Option cards: I/O extension cards, communication cards or "Controller Inside programmable card.

Product data sheet


Mounting and Clearance

ATV71HD30N4

Mounting Recommendations
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate
accessories.
Install the unit vertically:
Avoid placing it close to heating elements
Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.

Clearance

Mounting Types
Type A Mounting

Type B Mounting

Type C Mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20.
The protective blanking cover may vary according to the drive model (refer to the user guide).
The protective blanking cover must be removed from ATV 71PN4Z drives when they are mounted in a dust and damp proof enclosure.

Specific Recommendations for Mounting the Drive in an Enclosure


Ventilation
To ensure proper air circulation in the drive:
7

Fit ventilation grilles.


Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must
provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).

Use special filters with IP 54 protection.


Remove the blanking cover from the top of the drive.

Dust and Damp Proof Metal Enclosure (IP 54)


The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions: dust, corrosive gases, high humidity with
risk of condensation and dripping water, splashing liquid, etc.
This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50C.

Product data sheet

Connections and Schema

ATV71HD30N4

Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping
Category 0 According to IEC/EN 60204-1
Three-Phase Power Supply with Upstream Breaking via Contactor

A1
KM1
L1
Q1
Q2
Q3
S1,
S2
T1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)

ATV71 drive
Contactor
DC choke
Circuit-breaker
GV2 L rated at twice the nominal primary current of T1
GB2CB05
XB4B or XB5A pushbuttons
100 VA transformer 220 V secondary
Line choke (three-phase); mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020 mA) or voltage (010 V) analog input.
Reference potentiometer.

All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping
Category 0 According to IEC/EN 60204-1

Three-Phase Power Supply with Downstream Breaking via Switch Disconnector

A1
L1
Q1
Q2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)

ATV71 drive
DC choke
Circuit-breaker
Switch disconnector (Vario)
Line choke (three-phase), mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020mA) or voltage (010V) analog input.
Reference potentiometer.

All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping
Category 0 According to IEC/EN 60204-1

10

Three-Phase Power Supply, Low Inertia Machine, Vertical Movement

A1
A2
F1
L1
Q1
S1
S2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)

ATV71 drive
Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the Power Removal
function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24V via the safety
contacts on the XPSAC module. These contacts are independent for each drive.
Fuse
DC choke
Circuit-breaker
Emergency stop button with 2 contacts
XB4 B or XB5 A pushbutton
Power supply: 24Vdc or Vac, 48Vac, 115Vac, 230Vac.
S2: resets XPS AC module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
Requests freewheel stopping of the movement and activates the Power Removal safety function.
Line choke (three-phase), mandatory for and ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
The logic output can be used to signal that the machine is in a safe stop state.
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NFC93-550, external diameter
2.54mm /0.09in., maximum length 15m / 49.21ft. The cable shielding must be earthed.
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020mA) or voltage (010V) analog input.
Reference potentiometer.

All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping
Category 1 According to IEC/EN 60204-1

11

Three-Phase Power Supply, High Inertia Machine

A1
A2
(5)
F1
L1
Q1
S1
S2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)

ATV71 drive
Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal
safety function for several drives on the same machine. In this case the time delay must be adjusted on the drive controlling the motor
that requires the longest stopping time. In addition, each drive must connect its PWR terminal to its + 24V via the safety contacts on
the XPS ATE module. These contacts are independent for each drive.
Fuse
DC choke
Circuit-breaker
Emergency stop button with 2 N/C contacts
Run button
Power supply: 24Vdc or Vac, 115Vac, 230Vac.
Requests controlled stopping of the movement and activates the Power Removal safety function.
Line choke (three-phase), mandatory for ATV71HC11YHC63Y drives (except when a special transformer is used (12-pulse)).
S2: resets XPSATE module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a
maximum time delay of 300 seconds.
The logic output can be used to signal that the machine is in a safe state.
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40YHC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the source position (for other connection types, refer to the user guide).
Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NFC93-550, external diameter
2.54mm/0.09in., maximum length 15m/49.21ft. The cable shielding must be earthed.
Logic inputs LI1 and LI2 must be assigned to the direction of rotation: LI1 in the forward direction and LI2 in the reverse direction.
There is no PO terminal on ATV71HC11YHC63Y drives.
Optional DC choke for ATV71HM3, ATV71HD11M3XHD45M3X, ATV71075N4D75N4 and ATV71PN4Z drives. Connected in
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
Software-configurable current (020 mA) or voltage (010 V) analog input.
Reference potentiometer.

All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

12

Product data sheet


Performance Curves

ATV71HD30N4

Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For
intermediate temperatures (e.g. 55C), interpolate between 2 curves.

X
(1)

Switching frequency
Mounting type

Above 50C, the drive should be fitted with a control card fan kit.

13