1-Channel Digital Limit Switch Schuhmann Messtechnik

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

1-channel DGW 1.

00 G
digital limit switch DGW 1.00 T

FEATURES
Input:
Current 0(4)...20 mA or
Voltage 0(2)...10 V
Output:
2 relays with change over contacts
Parameterization, handling and
actual value indication by display
Door installation and GDC version
with integrated transmitter feeding
Galvanic 3-way isolation
of 4 kV

FUNCTION
The digital DGW 1.00 is used for the limit value con- The DGW 1.00 GDC has additionally an integrated
trol of standard inputs. 2-wire, the DGW 1.00 T additionally a 2- and a 1
2
The parameterization is carried out by front side 3-wire transmitter feeding. 3
4
push-buttons and indicated by display. At the current input 4...20 mA or the optional
The 4-digit actual value indication is free scalable. voltage input of 2...10 V the Live-Zero monitoring is
Based on the input, the ON and OFF switchpoints active. At the same time, each relay out of the valid
(limits) of the two independent relays can be freely range of 3,9...20,8 mA (1,9...10,4 V) is falling off.
42 90
defined. This automatically results in a hysteresis. The
ON-delay and the delay release times of the relays are
132,5

138,5
separately adjustable.
The status indication of the relays is displayed as
bargraphs.
6

48 96

54,2
Auxiliary power: 230 V AC/ 24 V DC/ wide range
12

1- 2+

Power supply
Input
+ Input 1 5 9 Output 1
106

- Input 1 4 ADC uP 7

12 Output 2
Push-button 78
10
Display 50.00
10 11 12
3

9
1 2 3 4

22,5

11
2

8
1

connections for top hat rail

03-01
1-channel DGW 1.00 G
digital limit switch DGW 1.00 T

OVERVIEW-MENU
adjustable
description main menu*1 description
range
available
display

operating mode
actual indicated
value, scaled

change
value
- 999 ... + 9999 display*2

(comma free scale start ≙


settable) zero point

- 999 ... + 9999 display*2


(comma free scale end ≙
settable) full scale

change
value
value from scale

operating mode (PA. F)


switch on point switch on point
start to scale end
relay 1 relay 2
possible

)
parameterizing mode (PA.
value from scale
switch off point switch off point
start to scale end
relay 1 relay 2
possible

0,1 ... 999,9 sec. on-delay on-delay


(comma defined) relay 1 relay 2

0,1 ... 999,9 sec. delayed release delayed release


(comma defined) relay 1 relay 2

EA 2e (0...20 mA)
select zero point
lI FE 2e (4...20 mA)*3
operating mode

back to actual
indicated value displayed for
2 seconds

Legend: selection next *1 There is a constant change between the actual indicated value and the dispay of the menu item.
*2 The display is free scalable, e.g. instead of the 4…20 mA 0…100 m³ is being displayed.
*3 Live-Zero is monitoring the range: relay out of range of 3,9...20,8 mA fallen off.

03-02
1-channel DGW 1.00 G
digital limit switch DGW 1.00 T

changeover parameterizing mode/ operating mode:


actual push operating push parameterizing autom. actual
display 2-3 sec. mode 2-3 sec. mode return display

CHANGE VALUE (select to change the menu item):

change value:
preset change value changed confirm position 1 change changed confirm value changed save and
value position 1 to „6“ value changed position 2 to „3“ value to „36“ back

define decimal place:


previous confirm position 1 change select confirm „0“ confirm value changed save and
value position 1 unchanged position 2 comma comma selected value to „0,2“ back

delete decimal place:


previous change comma confirm comma confirm change position 2 confirm value changed save and
value position 1 confirmed value set value with value to „50“ back

delete positions:
previous go to position 2 change change position 2 confirm space saved, save and
value position 2 changeable position 2 with to „ _ “ value value: „9“ back

Details of operation: Legend:


The displayed position gets changed with the Optional door installation: Digit on display blinks.
push-button . Values such as to , minus , Push red push-button longer than 2 seconds: Display of comma.
comma and space are possible. code requested. Enter default code to change space
Use the push-button to confirm the actual position and parameters, otherwise display only. selection
go to the next or return to the main menu after changing the confirm
last digit. Break-off possible by pushing longer.

03-03
DGW 1.00 G Input:
I: load-independent DC current: 0(4)...20 mA input resistance approx. 50 Ω
DGW 1.00 T connection: terminal 4 - , 5 +
optional/ alternatively:
U: load-independent DC voltage: 0(2)...10 V input resistance approx. 100 kΩ
Additional at DGW 1.00 GDC and DGW 1.00 TW:
DGW 1.00 G
transmitter feeding: approx. 20 V at 20 mA
~ - Auxiliary power
~+
Output:
FUNKTION
2 relay outputs: changer FUNKTION limit range DC current
+3 ? 2-wire transmitter
1 2 3
-5 I (only DGW 1.00 GDC) max. switching current 8A 8,0

- max. switching voltage: 250 V AC 5,0


+ Input mechanical life cycle: 30 x 106 cycles

current [A]
contact life cycle: 105 cycles
1,0
4 5 6 connection: see connection
diagram 0,5
Actual value display 1
0,2
Relay status display 1 - resistive load 2
1 2 3 4 0,1
2 - inductive load 0 40 80 120 160
voltage [V]
200 240 280

Push-buttons
Adjustment:
The functions are adjusted by 2 front side push-buttons and display (see page 03-2 and 03-3).
7 8 9
Output 1 Display:
4-digit LC-display with 2 bargraphs to indicate the relay status of output 1 and 2.

10 11 12
Output 2

DGW 1.00 T Relay 1 Relay 2


20
19 Output 2
Environmental conditions: Mounting details:
18
17 Storage temperature: -40...+70 °C Housing for top hat rail
16 Operating temperature: 0...55 °C Type of protection: IP 40 housing
15 Output 1 Isolation voltage: 4 kV eff. 1 sec. IP 10 clamps
14 input-output-auxiliary voltage Mounting rail fixed according to
13 EN 50022-35 x 6,2 mm
Auxiliary power:
12 + Feeding output Width: 22,5 mm
Housing for top hat rail: Weight: 250 g
11
230 V AC: 230 V AC Material: Polyamide PA
10
<3W Flammability class: V0 (UL94)
9
24 V UC: 20...45 V AC Approval: CE
8
10...70 V DC Connection: screw clamps
7
<3W ≤ 2 x 2,5 mm²
6
5
Door installation: Door installation:
Wide range: 20...253 V AC/ DC Type of protection: IP 54 Front
4 + Input
3 –
<3W Front frame: 96 x 48 mm
2 ~+ Auxiliary power Characteristics of transmission: Installation depth: 138,5 mm
1 ~– Linearity error: < 0,03 % Weight: 290 g
of final value Material: PC/ ABS
2-wire transmitter
-4 Temperature error: < 30 ppm/ K Flammability class: V0 (UL94)
? Approval: CE
I + 12 Feeding output Directive: Connection: pluggable
3-wire transmitter EMC Directive: 2014/30/EU* screw clamps
? -3 Low Voltage Directive: 2014/35/EU 0,14...1,5 mm²
I/U + 12 Feeding output *minimum deviations possible during
HF-radiation influence For safety reasons we recommend to
4 Input I mount the housing for top hat rail with a
distance of approx. 5 mm to each other.
Schuhmann GmbH & Co. KG
Römerstraße 2
D-74363 Güglingen Ordering information: Type: DGW 1.00 G 230 V AC housing
Tel. + 49 71 35 50 56
27.02.2018

Voltage input optional! DGW 1.00 GDC 24 V UC housing


Fax + 49 71 35 53 55 Please specify special signals in clear text: DGW 1.00 TW wide range door inst.
www.schuhmann-messtechnik.de 0(2)...10 V

03-04