Electrical Unpriced BOQ-23 07 2019
Electrical Unpriced BOQ-23 07 2019
Electrical Unpriced BOQ-23 07 2019
TOTAL RS.
Supply & ITC of 3 Phase, 4 wire, 415 V, 0.8 P.F, 50 Hz. type
panels as specified in section of MV Switchgear
The fabrication shall be made with 14SWG cold rolled sheet with
M/c pressing. The surface shall be rigorously treated for derusting
in 7tank process with dephosphating and painting with at least 2
coats of approved paint. The panel shall be totally enclosed metal
clad type with double gasketting with rubber/resin lining. The
panel shall be of Siemen's Grey painted inside and shall be having
control directory pasted inside the panel. Panel shall have cable
entry provision from the top and bottom with suitable alley as the
case may be. The panel shall be tested for the same KA rating of
the relevant highest rating ACB / MCCB. All components shall have
relevant IS/IEC approvals without fail. Panels shall be suitable for
415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall
also be provided in case of large panels. Approval shall be taken
for each panel in the form of shop drawings before fabrication.
Galvanised hardwares with zinc passivation shall be used in
fabrication of panels.
i) Main Al. bus bars with bar type feeder connections & all internal
wiring and connections
vi) All ammeters with C.T's, voltmeter and energy meters with
necessary fuses.
Each Supply and Installation of 10kVA Pure Sine wave Inverter with
1.1.13 12V/60AH X 8 Nos of Tubular batteries approx.15mins with all 1
necessary battery racks and links.
630A TP Al. busbar suitable for receiving incoming cables/Bus duct 12 Step APFC
Relay having feature of changing the sequence of o peration with Auto/Manual
selector switch. Auto/Manual Indicating lamps. Set of Phase indicating lamps with
2A control MCBs. One No. Control Transformer 415/230V AC rating as required
with 2A control MCBs for Meterin g and Control Circuit. 3 Sets of 50 kVAR each set
having 63A, TP MCCB (21 kA) capacitor duty contactor, ON/OFF indicating lamps
with 2A control MCBs and ON/OFF push buttons. 4 Sets of 25 kVAR each set
having 40A, TP MCCB (21 kA) capacitor duty contactor, ON/OFF indicating lamps
with 2A control MCBs and ON/OFF push buttons. 1 Sets of 20 kVAR each set
having 25A, TP MCCB (21 kA) capacitor duty contactor, ON/OFF indicating lamps
with 2A control MCBs and ON/OFF push buttons. 2 Sets of 10 kVAR each set
having 25A, TP MCCB (21 kA) capacitor duty contactor, ON/OFF indicating lamps
with 2A control MCBs and ON/OFF push buttons. 2 Sets of 5 kVAR each set
having 16A, TP MCB (21 kA) capacitor duty contactor, ON/OFF indicating lamps
with 2A control MCBs and ON/OFF push buttons.
1.1.15 Each
Preparation & submission of 4 sets (Client / Concultant / Contractor / Site
each) of hard copies & soft copies in the form of e-mail / CD, of all the
required Electrical Services As Built drawings, Approved Panel GA
Drawings, Panel Test Certificates & approval from the client / consultant & LS
Submission of testing reports, earthing test reports, opearating manuals,
warranty / guarantee cards etc. complete as required. (All drawing's
printouts shall be of A3/A2/A1 size as required.)
X-577/ ELECTRICAL
RPMC FACTORY AT DAHEJ FOR BLVL
REV : 0
QTY. RATE
ITEM PAY
DESCRIPTION Material Installatio AMOUNT
NO. UNIT
Supply n
1.1.16 Each
Preparation of detailed drawing of the substation and complete
electrification scheme fully complied with relevant standards of Indian
Electricity Act. This includes : 1) Preparation of proposed drawings as per
electrical standards 2) Test Commissioning of the System 3) Final
Commissioning. This work is inclusive of : a) Liasioning with Electrical
Inspector/Central electricity Authority (CEA) for obtaining their
permission /approval for energisation of electrical installation for final LS
commissioning b) Filing all relevant applicatiions as per Procedure of
Electrical Inspector/CEA c) Furnishing technical information as required by
CEA/Electrical Inspector d) Payment of all applicable fees as required for
obtaining approval. All incidental costs(if any) must be borne by the
contractor and he shall not seek clients assistance for obtaining relevant
documents
X-577/ ELECTRICAL
RPMC FACTORY AT DAHEJ FOR BLVL
REV : 0
QTY. RATE
ITEM PAY
DESCRIPTION Material Installatio AMOUNT
NO. UNIT
Supply n
1.1.18.11 Each 1
Expansion joints
1.1.18.12 Each 1
Adaptor Box at Transformer end - with 2 mm sheet
1.1.18.13 Each 1
Adaptor Box at Panel end -40x40x6 Channel box with 2 mm sheet .
1.1.18.14 Each Aluminium Interconnecting Busbar at Transformer end - 500mm ( with Hardware - 1
Nots and Bolts )
1.1.18.15 Each Aluminium Interconnecting Busbar at Panel end -500 mm ( with Hardware - Nots 1
and Bolts
1.1.18.16 m 50
Al Earthing strip - 50x6 ( with Hardware - Nots and Bolts )
1.1.18.17 Each 8
Threaded Rod (1.5m Length , Dia 16 mm ) with anchor Fastener
1.1.18.18 Each LS
MS Structure supports for Indoor or outdoor application .
1.1.18.19 Each 1
Shaft Cantiliver angle support with C Channel for Vertical spring or Rigid hangers
1.1.18.20 Each 2
Canopy -1.6 mm Thickness
Supply & ITC of all MCB Distribution Boards (10KA), made out of
14sWG MS sheet steel enclosure with hinged MS /over flanged cover
incliding cutouts for operating the MCB's.Comprising of fully
insulated phase busbars,neutral & earth bus with bakelite phase
barriors. Supplied with wire sets,cable ties,identification lables pvc
insulator shoes for incoming wire etc.Distribution panels shall be
Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-
5.Degree of protection for following type of distribution panel
enclosure shall be as per IS:13947-1993.(i). IP 42 for indoor panels.
(ii). IP 55 for outdoor panels.All MCB’s used for protection of
resistive and lightly inductive load shall be type “B” characteristic
and inductive (motor) load shall be of type “C” characteristic and
discharge lamps and UPS etc. shall be of type D characteristic.
2.1.1 INVERTER DB 1
Incomer :
63A DP RCBO,30mA
a) RYB phase indicating lamps - 1 set
b) Multifunction Meter with necessary CT, PTs
Outgoing :-
16 - 50A DP MCBs - 6.NoS.
2.1.5 Each ELDB 1 ( Emergency Lighting DB 1) Office & Passage Area - 8 Way S 1
INCOMER:-
40A DP RCBO ( 30mA ) :-1No.
OUTGOING:-
10A SP MCB :-4Nos.
20A SP MCB :-2Nos.
3.0 CABLING
Power Cabling
Supply & Laying of heavy duty 1100V grade XLPE inner & outer PVC
Steel armoured cables with AL / Cu conductors and as specified
.Supplying & laying of following 1100 volt grade XLPE insulated PVC
sheathed aluminium conductor armoured cables as per specification in
in section 1.0 to 6.0 of MV Cabling and shown on dwgs including cable
trays, clamped cost to include other acessories required for
installation includes anchor fastners wall with suitable clamps, saddles
fixing bolts including connecting testing and commissioning.
3.1.1
m 118
0 4Cx2.5mm² Copper Armoured XLPE PVC Cable
3.1.1
m 243
1 3Cx6mm² Copper Armoured XLPE PVC Cable
3.1.1
m 2214
2 3Cx4mm² Copper Armoured XLPE PVC Cable
3.1.1
m 4872
3 3Cx2.5sq.mm Copper Armoured XLPE PVC Cable
3.1.1 3Cx2.5sq.mm Copper Armoured XLPE PVC Cable laid underground for
m 600
4 Street lights
X-577/ ELECTRICAL
RPMC FACTORY AT DAHEJ FOR BLVL
REV : 0
QTY. RATE
ITEM PAY Materia
DESCRIPTION AMOUNT
NO. UNIT l Installation
Supply
Cable Termination
3.2.1
Nos 2
0 4Cx2.5mm² Copper Armoured XLPE PVC Cable
3.2.1
Nos 24
1 3Cx6mm² Copper Armoured XLPE PVC Cable
3.2.1
Nos 172
2 3Cx4mm² Copper Armoured XLPE PVC Cable
3.2.1
Nos 154
3 3Cx2.5sq.mm Copper Armoured XLPE PVC Cable
PVC DUCTS
Supply and ITC of Rigid PVC duct all it's necessary junction
3.3 Nos
box,couplers,bend etc.
Supply and erecting of perforated type HOT dip Galvanised Iron Cable
3.4 tray of 14G, 2mm thickness of specific dimensions. The cable tray can
be ceiling hung / fixed to wall with proper supports like threaded rods,
nots, nuts together with tees, bends etc. The trays shall be earthed
b) 1100V grade PVC copper wires as specified. The PVC wires should
comply IS :694-1990. The GI conduits should comply with IS 3418-1989
for rigid conduits. The interiors of the GI coduits should be free from
obstruction and should be ISI marked. No GI conduit less than 20mm in
diameter shall be used.
c) Conduiting and wiring excluding switches, sockets ( Including back
box) & including supply & fixing of pipe conduits with junction box,
couplers, bends, elbows, PVC plates, wires etc. complete with box
earthing, interconnections etc.
f) NOTE:-
Primary Light Point : From DB to Switchboard and from Switchboard to
each light point will be considered as Primary Light Point.
0
Secondary Light Point : Looping from Primary Light Point will be
considered as Secondary Light Point and will be controlled from the
same switch provided for Primary Light Point.
Primary Points from switch board to first light point:- The final subcircuit
4.1.1 Pt. wiring commencing from the switch boards to light point complete 18
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Primary Points from switch board to first light point:- The final subcircuit
4.1.6 Pt. wiring commencing from the switch boards to light point complete 29
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
STORE ROOM
Primary Points from switch board to first light point:- The final subcircuit
4.1.12 Pt. wiring commencing from the switch boards to light point complete 9
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Primary Points from switch board to first light point:- The final subcircuit
4.1.17 Pt. wiring commencing from the switch boards to light point complete 18
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
COMMMON AREA
Wiring of ceiling fan points with 1.5mm sq 1100 V grade wires in 25mm
concealed MMS PVC Conduits including providing fan hook box Ceiling
fan point complete with fan hook , SP Switch and regulator (at diffrent
4.1.24 Pt. 45
location) and earthing of fixtures and outlet box with 1.5mm sq PVC
Wires. (With 2Rx1.5Sq.mm and 1Rx1.5Sq.mm and 20mm rigid
conduits) circuit wiring should be of 2Rx2.5Sq.mm + 1Rx1.5Sq.mm
STORE MAINTENANCE
Primary Points from switch board to first light point:- The final subcircuit
4.1.28 Pt. wiring commencing from the switch boards to light point complete 2
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
UTILITY AREA
Primary Points from switch board to first light point:- The final subcircuit
4.1.33 Pt. wiring commencing from the switch boards to light point complete 2
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Primary Points from switch board to first light point:- The final subcircuit
4.1.38 Pt. wiring commencing from the switch boards to light point complete 7
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
UTILITY AREA
Primary Points from switch board to first light point:- The final subcircuit
4.1.43 Pt. wiring commencing from the switch boards to light point complete 4
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Pt.
Primary Points from switch board to first light point:- The final subcircuit
4.1.48 wiring commencing from the switch boards to light point complete 3
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
LT ROOM
Primary Points from switch board to first light point:- The final subcircuit
4.1.53 Pt. wiring commencing from the switch boards to light point complete 2
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Pt. Primary Points from switch board to first light point:- The final subcircuit
4.1.58 wiring commencing from the switch boards to light point complete 7
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
4.1.60 Pt. 16A Switch Socket 250V (With 2Rx2.5Sq.mm and 1Rx1.5Sq.mm ) 6
Pt. Primary Points from switch board to first light point:- The final subcircuit
4.1.62 wiring commencing from the switch boards to light point complete 6
(with 3Rx1.5Sq.mm and 20/25mm conduits and 6A 1 way SP Switch.)
Wiring of ceiling fan points with 1.5mm sq 1100 V grade wires in 25mm
concealed MMS PVC Conduits including providing fan hook box Ceiling
4.1.66 Pt. fan point complete with fan hook , SP Switch and regulator and 19
earthing of fixtures and outlet box with 1.5mm sq PVC Wires. (With
2Rx1.5Sq.mm and 1Rx1.5Sq.mm and 20mm rigid conduits)
Wiring and Installation for exhaust fan point with 1.5mm sq. 1100V
grade wires in concealed 25mm MMS PVC conduits including providing
and fixing of 6A flush mounted switch at the normal switch level in
4.1.67 Pt. 2mm thick GI Box on convenient location as per drg and 6A 3 Pin flush 12
mounted socket out near exhaust fan and earthing of exhaust fan
through the third pin of the socket outlet with 1.5mm.Sq PVC wires.
(With 2Rx1.5Sq.mm and 1Rx1.5Sq.mm and 20mm rigid conduits)
ITC of Calidum LED SMD High Bay Light 200W, 230V, with all
5.1.2 Nos. TBC
accessories as required
Earthing Stations
Earthing shall be done at indicated location by the
Consultants. The minimum distance between the two earth
station shall be 3 meters and that from the building shall be
5.1
2500 mm. The earthing conductor shall be of the same
material as the electrode, viz. GI or copper and in the form of
wire or strip as specified.
b) Watering pipe.
No Bimetallic Connector 22
7.3 EARTHING
No Earth Pit 22
No FurseCEM 66