CAT32 1.25MVA Technical Data Sheet 12 Leads Out 240V
CAT32 1.25MVA Technical Data Sheet 12 Leads Out 240V
CAT32 1.25MVA Technical Data Sheet 12 Leads Out 240V
Electric Power
Specifications
Generator Set Specifications
Minimum Rating 830 ekW (910 kVA)
Maximum Rating 1000 ekW (1250 kVA)
Voltage 220 to 4160
Frequency 50 or 60 Hz
Speed 1500 or 1800 RPM
Engine Specifications
Engine Model C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 145 mm 5.71 in
Displacement 32.1 L 1958.86 in³
Stroke 162 mm 6.38 in
Compression Ratio 15.0:1
Aspiration TA
Governor Type Adem™A4
Fuel System MEUI
SS-9404821-18332039-001 SS Page 1 of 7
Generator
• Matched to the performance and output characteristics of Cat engines
• Industry leading mechanical and electrical design
• Industry leading motor starting capabilities
• High Efficiency
Seismic Certification
• Seismic Certification available.
• Anchoring details are site specific, and are dependent on many factors such as generator set size, weight,
and concrete strength.
• IBC Certification requires that the anchoring system used is reviewed and approved by a Professional
Engineer
• Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC
2007, CBC 2010
• Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
SS-9404821-18332039-001 SS Page 2 of 7
Standard Equipment
Air Inlet
• Air Cleaner
Cooling
• Package mounted radiator
Exhaust
• Exhaust flange outlet
Fuel
• Primary fuel filter with integral water separator
• Secondary fuel filter
• Fuel priming pump
Generator
• Matched to the performance and output characteristics of Cat engines
• Load adjustment module provides engine relief upon load impact and improves load acceptance and
recovery time
• IP23 Protection
Power Termination
• Bus Bar
Control Panel
• EMCP 4 Genset Controller
General
• Paint - Caterpillar Yellow except rails and radiators gloss black
Optional Equipment
Exhaust
• Exhaust mufflers
Generator
• Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
• Anti-condensation heater
• Oversize and premium generators
SS-9404821-18332039-001 SS Page 3 of 7
Power Termination
• Circuit breakers, UL listed
• Circuit breakers, IEC compliant
Control Panels
• EMCP (4.2) (4.3) (4.4)
• Generator temperature monitoring & protection
• Load share module
• Digital I/O module
• Remote monitoring software
Mounting
• Rubber anti-vibration mounts
• Spring-type vibration isolator
• IBC isolators
Starting/Charging
• Battery chargers
• Oversize batteries
• Jacket water heater
• Heavy-duty starting system
• Charging alternator
• Air starting motor with control and silencer
General
• The following options are based on regional and product configuration:
• Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
• UL 2200 package
• EU Certificate of Conformance (CE)
• CSA Certification
• EEC Declaration of Conformity
• Enclosures: sound attenuated, weather protective
• Automatic transfer switches (ATS)
• Integral & sub-base fuel tanks
• Integral & sub-base UL listed dual wall fuel tanks
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their
respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well
as corporate and product identity used herein, are trademarks of Caterpillar and may not be used
without permission.
SS-9404821-18332039-001 SS Page 4 of 7
C32 ACERT
1000 ekW/ 1250 kVA/ 60 Hz/ 1800 rpm/ 240 V/ 0.8 Power Factor
Rating Type: MISSION CRITICAL STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
C32 ACERT
1000 ekW/ 1250 kVA
60 Hz/ 1800 rpm/ 240 V
Metric English
Package Performance
Genset Power Rating with Fan @ 0.8 Power Factor 1000 ekW
Genset Power Rating 1250 kVA
Aftercooler (Separate Circuit) N/A N/A
Fuel Consumption
100% Load with Fan 262.7 L/hr 69.4 gal/hr
75% Load with Fan 195.9 L/hr 51.7 gal/hr
50% Load with Fan 135.9 L/hr 35.9 gal/hr
25% Load with Fan 80.8 L/hr 21.3 gal/hr
Cooling System¹
Engine Coolant Capacity N/A N/A
Inlet Air
Combustion Air Inlet Flow Rate 82.6 m³/min 2915.6 cfm
Max. Allowable Combustion Air Inlet Temp 48 ° C 118 ° F
Exhaust System
Exhaust Stack Gas Temperature 473.4 ° C 884.2 ° F
Exhaust Gas Flow Rate 214.7 m³/min 7582.8 cfm
Exhaust System Backpressure (Maximum Allowable) 10.0 kPa 40.0 in. water
SS-9404821-18332039-001 SS Page 5 of 7
TSS-EM0450-00-GS-EPG-9404821.pdf © 2015 Caterpillar All Rights Reserved Page 1 of 3
ELECTRIC POWER - Technical Spec Sheet
STANDARD
C32 ACERT
1000 ekW/ 1250 kVA/ 60 Hz/ 1800 rpm/ 240 V/ 0.8 Power Factor
Rating Type: MISSION CRITICAL STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
Heat Rejection
Heat Rejection to Jacket Water 359 kW 20395 Btu/min
Heat Rejection to Exhaust (Total) 965 kW 54857 Btu/min
Heat Rejection to Aftercooler 249 kW 14173 Btu/min
Heat Rejection to Atmosphere from Engine 127 kW 7243 Btu/min
Heat Rejection to Atmosphere from Generator 46 kW 2616 Btu/min
Alternator²
Motor Starting Capability @ 30% Voltage Dip 4350 skVA
Current 3007 amps
Frame Size 1447
Excitation IE
Temperature Rise 105 ° C
Emissions (Nominal)³
NOx 3009.7 mg/Nm³ 6.1 g/hp-hr
CO 89.8 mg/Nm³ 0.2 g/hp-hr
HC 5.1 mg/Nm³ 0.0 g/hp-hr
PM 8.3 mg/Nm³ 0.0 g/hp-hr
1. For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing
restriction from factory.
2. UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting
characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
3. Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D &
E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of
77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data
shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based
on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
SS-9404821-18332039-001 SS Page 6 of 7
TSS-EM0450-00-GS-EPG-9404821.pdf © 2015 Caterpillar All Rights Reserved Page 2 of 3
ELECTRIC POWER - Technical Spec Sheet
STANDARD
C32 ACERT
1000 ekW/ 1250 kVA/ 60 Hz/ 1800 rpm/ 240 V/ 0.8 Power Factor
Rating Type: MISSION CRITICAL STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for
availability.
MISSION CRITICAL STANDBY:Output available with varying load for the duration of the interruption of the normal
source power. Average power output is 85% of the standby power rating. Typical peak demand up to 100% of standby
rated ekW for 5% of the operating time. Typical operation is 200 hours per year, with maximum expected usage of 500
hours per year.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when
used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific
customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and
Biodiesel capability, please consult your Cat dealer.
www.Cat-ElectricPower.com
SS-9404821-18332039-001 SS Page 7 of 7
TSS-EM0450-00-GS-EPG-9404821.pdf © 2015 Caterpillar All Rights Reserved Page 3 of 3