QST30 - Iso8528 G2
QST30 - Iso8528 G2
QST30 - Iso8528 G2
Description Features
This Cummins® Power Generation commercial generator Cummins® Heavy-Duty Engine - Rugged 4-cycle
set is a fully integrated power generation system, industrial diesel delivers reliable power, low emissions
providing optimum performance, reliability, and versatility and fast response to load changes.
for stationary standby, prime power, and continuous duty
applications. Permanent Magnet Generator (PMG) - Offers
enhanced motor starting and fault clearing short circuit
capability.
This generator set is available with CE Alternator - Several alternator sizes offer selectable
certification. motor starting capability with low reactance 2/3 pitch
windings; low waveform distortion with non-linear loads,
All enclosed products are designed to meet fault clearing short-circuits capability, and class H
2000/14/EC or exceed EU noise legislation 2000/14/EC insulation.
step 2006.
Control System - Standard PowerCommand® electronic
This generator set has been designed to control provides total system integration including remote
ISO8528 comply with ISO8528 regulation. start/stop, precise frequency and voltage regulation,
alarm and status message display, AmpSentry protection,
This generator set is designed in facilities
output metering, auto-shutdown.
certified to ISO9001 and manufactured in
facilities certified to ISO9001 or ISO9002. Cooling System - Standard integral set-mounted
radiator system, designed and tested for rated ambient
temperatures, simplifies facility design requirements for
rejected heat.
Engine Specifications
Design 4 cycle, in line, turbo Charged and after-cooled
Bore 140.0mm (5.51in.)
Stroke 165.1mm (6.5in.)
Displacement 30.5 liters (1860in.3)
Cylinder Block Cast iron, 50°V 12 cylinder
Battery Capacity 1280 amps at ambient temperature 32°F (0°C)
Battery Charging Alternator 35 amps
Starting Voltage 24-volt, negative ground
Fuel System Direct injection
Fuel Filter Spin on fuel filters with water separator
Air Cleaner Type Dry replaceable element with restriction indicator
Lube Oil Filter Type(s) Four spin-on, full flow; two bypass oil filters
Standard Cooling System 122°F (50°C) ambient radiator
Alternator Specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation System Class H
Standard Temperature Rise 125°C Standby
Exciter Type PMG (Permanent Magnet Generator)
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <3%
Available Voltages
50Hz Line – Neutral / Line – Line 60Hz Line – Neutral / Line – Line
• 110/190 • 220/380 • 110/190 • 139/240 • 255/440
• 115/200 • 230/400 • 115/200 • 220/380 • 277/480
• 120/208 • 240/416 • 120/208 • 230/380 • 347/600
• 127/220 • 255/440 • 127/220 • 240/416
*Note: Some options may not be available on all models – consult factory for availability.