04 - Eltek 48v 3000

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Complementing the total

green telecom site!


The Flatpack2 48/3000 HE WIND brings
another renewable energy source into the
Flatpack2 family of DC power system for
telecom applications.

Configurable loading of the wind turbine allows


for maximum utilization of most 2-10kW wind
turbines in all conditions. This galvanic isolated
wind charger’s high efficiency, up to 95%,
reassures as much as possible of the
renewable energy is transferred to the
telecom load and batteries.

Eltek provides Return-on-Investment (ROI) and


total cost of ownership simulations using
professional tools and wind measurements at
site.

FLATPACK2 48/3000 HE WIND


WIND CHARGER
Doc 241119.550.DS3 – v5

APPLICATIONS KEY FEATURES


TELECOM – MOBILE / WIRELESS • HIGH EFFICIENCY
• MOBILE / WIRELESS • MAXIMUM UTILIZATION FOR MOST
• RADIO BASE STATIONS/ CELL WINDCHARGER IN 1U WIND SHELF (P/N 285762) WIND TURBINES
SITES • TELECOM SPECIFICATION
• BACKHAUL
• FULLY INTEGRATED IN ELTEK
• MICROWAVE
CONTROL SYSTEM
• BROADBAND
• LOGS WITH WIND ENERGY PRODUCED
TELECOM – FIXED • GLOBAL COMPLIANCE
• TELEPHONY SERVERS / • PATENTED HE TECHNOLOGY
SWITCHES
• FIBER OPTICS
• MICROWAVE
• CABLE
• BROADBAND
• BROADCAST

FLATPACK2 SYSTEM IN TYPE3 OUTDOOR CABINET SMARTPACK2 AND FLATPACK2 HYBRID POWER CORE

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com
FLATPACK2 48/3000 HE WIND
WIND CHARGER

Model 48/3000 HE WIND


Part number 241119.550

INPUT DATA
Voltage (nominal) 125 - 212 VAC (3ph line to line) / 176 - 300 VDC
Voltage (range) 60 - 212 VAC (3ph line to line) / 85 - 300 VDC
Frequency 451) - 661) Hz / 0Hz
Current (maximum) @ nominal input, full load 16 ARMS line
Protection Fuse

OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.5 - 57.6 VDC
Power (maximum) 3000 W
Power @ 60 VAC / 85 VDC 1380 W
Current (maximum) @ nominal input, full load 62.5 A
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Ripple < 200 mV peak to peak, 30 MHz bandwidth
Protection Fuse
Short circuit proof
High temperature protection

OTHER SPECIFICATIONS
Efficiency Up to 95.5%
Isolation 3.0 kVAC - input to output
1.5 kVAC - input to earth
500 VDC - output to earth

Alarms: Red LED 'on' Low input voltage shutdown, High and low temperature shutdown, Converter Failure,
Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure

Warnings: Yellow LED 'on' Converter in power tracking mode, Control system current limit activated, Input voltage out
of range, flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise < 46dBA at nominal input and full load
Operating temperature -40 to +75°C (-40 to +185°F), humidity 5 - 95% RH non-condensing
Output power de-rates linear from 3000W @ 45°C (113°F) to 2100W @ 75°C(167°F)
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 230 x 41.5 x 327mm (9.06 x 1.69 x 13”) / < 5 kg (11 lbs)

DESIGN STANDARDS
Electrical safety EN 60950-1
EMC ETSI EN 300 386 V.1.6.1
EN 61000-6-1 / -2 / -3 / -4
Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ROHS compliant
1) The converter does support a wider frequency range, but may have de-rated maximum power for lower frequencies. Each wind mill model must be approved by Eltek before deployment.

Doc 241119.550.DS3 – rev5 Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com