Electrical Load List Rev00
Electrical Load List Rev00
Electrical Load List Rev00
PDMC
WAPCOS LTD,
UJJAIN
CONTRACTOR:
TITLE :
NAME SIGN DATE
Quantity
Voltage Total Final required
Unit
Feeder Power Unit Rating in Running Usage load in KVA after
Sl.no Equipment Location Rating Efficiency
Total Type factor KVA Load in Factor consideration of
Running Standby (KW) 415VAC/
Connected KVA usage factor
230VAC
(g)=(d)/(e x f) (h)=(a) x
(a) (b) (c )=(a) + (b) (d) (e) (f) (i) (j)
x 100 (g)
1 PRIMARY UNIT
1 Mechanical Fine Screen Fine Screen channel 2 0 2 1.1 415 DOL 0.8 81.8 1.68 3.36 100% 3.36
2 Belt Conveyor Fine Screen channel 1 0 1 1.1 415 DOL 0.8 81.8 1.68 1.68 100% 1.68
3 Detritor Mechanism Detritor 2 0 2 1.5 415 DOL 0.83 82.8 2.18 4.37 100% 4.37
4 Classifier Detritor 2 0 2 1.5 415 DOL 0.83 82.8 2.18 4.37 100% 4.37
5 Organic return Pump Detritor 2 0 2 0.37 415 DOL 0.83 70.1 0.64 1.27 100% 1.27
C-TECH
6 Decanter SBR 6 0 6 0.55 415 VFD 75.1 0.73 1.00 6.02 100% 6.02
7 C Tech Basins Air Blower Air Blower Building 3 0 3 160 415 VFD 0.86 94.8 196.25 588.75 100% 588.75
8 C Tech Basins Air Blower Air Blower Building 6 3 9 160 415 Soft starter 0.86 94.8 196.25 1177.51 100% 1177.51
9 RAS Pumps SBR 6 1 7 7.5 415 Star-Delta 0.81 88.7 10.44 62.63 100% 62.63
10 SAS Pumps SBR 6 1 7 9.3 415 Star-Delta 0.84 89.3 12.40 74.39 100% 74.39
11 Dewatering Pumps STP 2 0 2 2.2 415 DOL 0.78 84.3 3.35 6.69 100% 6.69
CENTRIFUGE AREA
12 Centrifuge Centrifuge Building 1 1 2 22 415 VFD 0.78 84.3 33.46 33.46 100% 33.46
13 Centrifuge feed Pump Centrifuge Building 1 1 2 3.7 415 DOL 0.78 84.3 5.63 5.63 100% 5.63
14 Poly Dosing Pump Centrifuge Building 1 1 2 0.75 415 DOL 0.73 79.6 1.291 1.29 100% 1.29
PROJECT : UJJAIN MUNCIPAL CORPORATION,UJJAIN, DIST,
PDMC : WAPCOS LTD,UJJAIN DOCUMENT NO. DATE REV
CONTRCTOR : TATA PROJECT LIMITED ,SECUNDERBAD,TELANGANA TPL-340062-UJN-STP-EL-EL-4001 05.07.18 0
DESIGNED BY : ECO PROTECTION ENGINEERS PVT LTD.,CHENNAI,600101. DESIGNED CHECKED APPROVED SHEET
TITLE : ELECTRICAL LOAD LIST FOR 92.5MLD SEWAGE TREATMENT PLANT AT UJJAIN. PM BGV A4
Quantity
Voltage Total Final required
Unit
Feeder Power Unit Rating in Running Usage load in KVA after
Sl.no Equipment Location Rating Efficiency
Total Type factor KVA Load in Factor consideration of
Running Standby (KW) 415VAC/
Connected KVA usage factor
230VAC
15 Poly dosing Agitator Centrifuge Building 1 1 2 1.5 415 DOL 0.8 82.8 2.264 2.26 100% 2.26
Sludge Sump Pump
16 Sludge Sump Air Blower 1 1 2 3.7 415 DOL 0.84 86.3 5.104 5.10 100% 5.10
House
17 Sludge Thickener Thickener 1 0 1 3.7 415 DOL 0.78 84.3 5.627 5.63 100% 5.63
18 Thickener feed Sump Pump Thickener 1 1 2 4 415 DOL 0.84 86.7 5.492 5.49 100% 5.49
19 Thickener dilution water Pump Thickener 2 1 3 7.5 415 Star-Delta 0.8 82.8 11.322 22.64 100% 22.64
20 Centrate Pump Thickener 1 1 2 22 415 Star-Delta 0.83 91.6 28.937 28.94 100% 28.94
21 Lighting Power Centrifuge Building 1 0 1 2.2 415 MCCB 0.78 84.3 3.346 3.35 100% 3.35
CHLORINATION BUILDING
22 Chlorine Booster Pump CCT 1 1 2 5.5 415 DOL 0.78 84.3 8.365 8.36 100% 8.36
23 Leak Absorption Blower CCT 1 1 2 3.7 415 DOL 0.78 84.3 5.627 5.63 100% 5.63
24 Caustic Recirculation Pump CCT 1 1 2 1.5 415 DOL 0.78 84.3 2.281 2.28 100% 2.28
OTHER LOAD
25 Indoor Lighting STP 1 0 1 10 415 MCCB 0.8 80 15.625 15.63 100% 15.63
26 Outdoor Lighting STP 1 0 1 10 415 MCCB 0.8 80 15.625 15.63 100% 15.63
27 Exhaust Fan for AirBlower Building Air Blower Building 7 0 7 0.45 415 MCCB 0.8 80 0.703 4.92 100% 4.92
28 Exhaust Fan for Chlorine Building Chlorine Building 2 0 2 0.45 415 MCCB 0.8 80 0.703 1.41 100% 1.41
29 Exhaust Fan for Admin Building Admin Building 17 0 17 0.45 415 MCCB 0.8 80 0.703 11.95 100% 11.95
30 Exhaust Fan Centrifuge Building Centrifuge Building 3 0 3 0.45 415 MCCB 0.8 80 0.703 2.11 100% 2.11
31 EOT for Air Blower Air Blower Building 2 0 2 5.5 415 MCCB 0.8 80 8.594 17.19 50% 8.59
32 EOT Crane for Centrifuge House Centrifuge Building 1 0 1 2.2 415 MCCB 0.78 84.3 3.346 3.35 50% 1.67
33 EOT Crane for Chlorine House CCT 1 0 1 1.5 415 MCCB 0.78 84.3 2.281 2.28 50% 1.14
34 PLC Power STP 1 0 1 2.2 230 MCCB 0.8 80 3.438 3.44 50% 1.72
PROJECT : UJJAIN MUNCIPAL CORPORATION,UJJAIN, DIST,
PDMC : WAPCOS LTD,UJJAIN DOCUMENT NO. DATE REV
CONTRCTOR : TATA PROJECT LIMITED ,SECUNDERBAD,TELANGANA TPL-340062-UJN-STP-EL-EL-4001 05.07.18 0
DESIGNED BY : ECO PROTECTION ENGINEERS PVT LTD.,CHENNAI,600101. DESIGNED CHECKED APPROVED SHEET
TITLE : ELECTRICAL LOAD LIST FOR 92.5MLD SEWAGE TREATMENT PLANT AT UJJAIN. PM BGV A4
Quantity
Voltage Total Final required
Unit
Feeder Power Unit Rating in Running Usage load in KVA after
Sl.no Equipment Location Rating Efficiency
Total Type factor KVA Load in Factor consideration of
Running Standby (KW) 415VAC/
Connected KVA usage factor
230VAC
GATES & VALVES
35 Motorized Inlet Gate Valve SBR 4 0 4 1.1 415 RDOL 0.8 81.4 1.689 6.76 100% 6.76
36 Motorized Discharge Valve(BFV) SBR 6 0 6 1.1 415 RDOL 0.8 81.4 1.689 10.14 100% 10.14
37 Motorized Isolation Valve(BFV) SBR 6 0 6 0.75 415 RDOL 0.73 79.6 1.291 7.74 100% 7.74
38 Motorized Air Vent Valve(SV) SBR 6 0 6 0.75 415 RDOL 0.73 79.6 1.291 7.74 100% 7.74
Transformer Capacity