Asco Series 314 Exida Sil Certificate 2016

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Certificate / Certificat

Zertifikat /
ASC 1301001 C001
exida hereby confirms that the:

Series 8314 Solenoid Valves


The manufacturer
may use the mark:

ASCO
Florham Park, NJ - USA
Has been assessed per the relevant requirements of:

IEC 61508 : 2010 Parts 1-7


and meets requirements providing a level of integrity to:

Systematic Capability: SC 3 (SIL 3 Capable)


Random Capability: Type A Element
Revision 1.4 April 3, 2016
Surveillance Audit Due
April 1 , 2019

SIL 2 @ HFT=0; SIL 3 @ HFT = 1; Route 2H


PFDAVG and Architecture Constraints
must be verified for each application
Safety Function:
The Valve will move to the designed safe position when deenergized / energized within the specified safety time.
Application Restrictions:
The unit must be properly designed into a Safety Instrumented
Function per the Safety Manual requirements.

Place embossed
seal here for
originals, lining it
up at the bottom

ANSI Accredited Program

Evaluating Assessor

Certifying Assessor

PRODUCT CERTIFICATION
#1004

Page 1 of 2

Certificate / Certificat / Zertifikat /


ASC 1301001 C001
Systematic Capability: SC 3 (SIL 3 Capable)
Random Capability: Type A Element
SIL 2 @ HFT=0; SIL 3 @ HFT = 1; Route 2H
PFDAVG and Architecture Constraints
must be verified for each application

Series 8314 Solenoid


Valves

Systematic Capability :
The product has met manufacturer design process requirements of Safety
Integrity Level (SIL) 3. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not
be used at a SIL level higher than stated.
Random Capability:
The SIL limit imposed by the Architectural Constraints must be met for
each element. This device meets exida criteria for Route 2H.

IEC 61508 Failure Rates in FIT*


For valves used in a final element assembly, SIL must be verified
for the specific application using the following failure rate data.
Failure rates for the Series 8314 Solenoid Valves in FIT*
sd
0 FIT
0 FIT

Failure Category
8314
8314 with PVST

su
97 FIT
97 FIT

dd
0 FIT
99 FIT

du
100 FIT
1 FIT

Applications
Series 8314 Solenoid

De-energize on trip, normally closed

* FIT = 1 failure / 109 hours


SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFDavg considering redundant architectures,
proof test interval, proof test effectiveness, any automatic diagnostics, average
repair time and the specific failure rates of all products included in the SIF. Each
element must be checked to assure compliance with minimum hardware fault
tolerance (HFT) requirements.
64 N Main St
Sellersville, PA 18960

The following documents are a mandatory part of certification:


Assessment Report: ASC 13/01-001 R002 V2 R1

T-061, V1R8

Safety Manual: V9629R4


Page 2 of 2