VRF Outdoor Unit Installation
VRF Outdoor Unit Installation
VRF Outdoor Unit Installation
Installation
97
A solid, correct base can: Avoid the outdoor unit from sinking and avoid the abnormal noise generated due
to base.
Base types: Steel structure base or concrete base (See the figure below for the general making method)
3/8inch(10mm)
Expansion bolt
Rubber shocking
proof mat
Solid ground
or roofing
Concrete basement
7-7/8inch(200mm)
The master units basement must be made on the solid concrete ground . Refer to the structure diagram to make concrete
basement in detail, or make after field measurements.
In order to ensure every point can contact equality, the basement should be on completely level.
If the basement is placed on the roofing, the detritus layer isnt needed, but the concrete surface must be flat. The standard
concrete mixture ratio is cement 1/ sand 2/ carpolite 4, and adds 3/8inch(10mm) strengthen reinforcing steel bar, the
surface of the cement and sand plasm must be flat, border of the basement must be chamfer angle.
Before construct the unit base, please ensure the base is directly supporting the rear and front folding edges of the bottom
panel vertically, for the reason of these edges are the actual supported sites to the unit.
In order to drain off the seeper around the equipment, a discharge ditch must be setup around the basement.
Please check the affordability of the roofing to ensure the load capacity.
When piping from the bottom of the unit, the base height should be no less than 7-7/8inch(200mm).
98
Installation
B
A
8-16HP
44-1/8(1120)
49-1/4(1250)
29(736)
30-1/8(765)
12HP
10HP
Outdoor unit
(38HP)
MS
MS
MS
Indoor unit A
Indoor unit B
Indoor unit C
4. Installation space
Ensure enough space for maintenance. The modules in the same system must be on the same height.
When installing the unit, leave enough space for maintenance.
Unit: in.(mm)
(Air outlet)
(Air inlet)
4(100)
(Air inlet)
39-3/8(1000)
Installation and maintenance surface
Installation
>39-3/8(1000)
>4(100)
>39-3/8(1000)
>39-3/8(1000)
99
Two rows
When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot
air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor
unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely H-h).
Please make the air director on site.
Unit: in.(mm)
100
Installation
If miscellaneous articles are piled around the outdoor unit, such articles must be 31-1/2inch(800mm) below
the top of the outdoor unit. The articles must be 31-1/2inch(800mm) below the top of the outdoor unit.
Otherwise, a mechanic exhaust device must be added.
Unit: in.(mm)
Set the snow-proof facility
In snowy areas, facilities should be installed to prevent snow. (See the figure below) (Defective facilities may
cause malfunction.) Please lift the bracket higher and install snow shield at the air inlet
and air outlet.
Snow shield for air inlet
Installation
101
47-5/8(1210)
C
A
Radius
3-9/16(90)
28-9/16(725)
4(100)
3/8(10)
3/8(10)
30-1/8(765)
Remove the
two iron filter firstly
15-1/2(393)
12-1/8(3.2)
Example B
Unit: in.(mm)
Support
50-3/4(1290)
47-5/8(1210)
47-5/8(1210)
A
Radius
3-9/16(90)
4(100)
102
Installation
28-9/16(725)
12-1/8(3.2)
Remove the two
iron filters firstly
765
3/8(10)
393
Unit: in.(mm)
Example A
Example B
A11-3/4(300)
A11-3/4(300)
B9-7/8(250)
B9-7/8(250)
C118-1/8(3000)
C118-1/8(3000)
28-9/16(725)D29-15/16(760)
15
15
12500(7350)
13500(7940)
12000(7060)
13000(7650)
11500(6760)
12500(7350)
11000(6470)
12000(7060)
10500(6180)
11500(6760)
10000(5880)
11000(6470)
9500(5590)
0(0)
10500(6180)
5(0.02) 10(0.04) 15(0.06) 20(0.08) 25(0.1)
0(0)
14/16HP
Air volume m 3/h(CFM)
15500(9120)
15000(8830)
14500(8530)
14000(8240)
13500(7940)
13000(7650)
12500(7350)
0(0)
Installation
Note:
Before install the ventilation assembly, please remove the steel
meshes firstly, otherwise, they would decrease the air supply
volume.
1. Increase shutters would decreases the air supply volume, as
well as cooling (heating) capacity and energy efficiency would be
decreased, the larger angle of the shutter, the more effect to the
unit. So we dont recommend applying shutter, if necessary to
apply shutter, please ensuring the angle should not over than 15.
2. The bending place at ventilated duct should be not more than
1(show in above figure), otherwise, operation malfunction would be
caused.
3. Install the flexible connector between the unit and the air
deflector pipe to avoid vibration noise.
103
L1
L2
L3
MS2
L5
L6
MS3
N4
(28)
N3
(140)
L7
D
L8 L9
E
L10
L11
F
MS6
j
r
N13
(56)
N12
(140)
Equivalent length
N5
(140)
MS5
h
g
m
l
Outdoor unit up
N10
(56)
Permitted value
Piping
3280ft(1000m)
L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11+L
(refer to note 1)
12+L13)2+a+b+c+d+e+f+g+h+i+j+k+l+m+n
574ft(175m)
656ft(200m)
L1+L7+L9+L11+j+k+n
(refer to note 2)
(refer to note 3)
difference
n
N9
(56)
N8
(28)
Level
N7
(71)
131/295ft(40/90m)
L13
N6
(71)
MS4
L12
N11
(140)
Piping length
Piping length
Indoor unit
N2
(71)
MS1
L4
MS7
Level difference
N1
(71)
131ft(40m)
230ft(70m)
(refer to note 4)
361ft(110m)
(refer to note 5)
98ft(30m)
L7+L9+L11+j+k+n
j+k+n
/
/
/
Note:
The indoor units should be installed as possible as equal in the both sides of the U-shape branch joint.
1. When counting the total piping length, the actual length of the distribution pipes which between the first branch joint and MS
should be double:
104
Installation
1/2(12.7)
5/8(15.9)
3/4(19.1)
7/8(22.2)
1(25.4)
1/2(12.7)
5/8(15.9)
3/4(19.1)
7/8(22.2)
1(25.4)
1-1/8(28.6)
1-1/8(28.6)
1-1/4(31.8)
1-1/2(38.1)
1-5/8(41.3)
1-3/4(44.5)
1-1/4(31.8)
1-1/2(38.1)
1-5/8(41.3)
1-3/4(44.5)
2-1/8(54.0)
4. When the outdoor unit is higher than indoor units and the level difference is over 65.6ft(20m), it is recommended to set an oil
return bend every 32.8ft(10m) in the gas pipe of the main pipe, the specification of the oil return bend refers to below figure.
11-3/4(300)
11-3/4(300)
Unit: in.(mm)
5. When the outdoor unit is lower than indoor units and the level difference is more than 131ft(40m), the liquid pipe of the main
pipe need to increase one size.
W2
(12)
W1
(16)
b
a
g1
g2
g3
M
L
G1
L1
L2
L3
L4
MS2
L5
L6
MS3
L7
E
MS7
L10
L11
N13
(56)
N12
(140)
N11
(140)
L12
N5
(140)
N6
(71)
MS4
MS5
h
g
L13
MS6
j
q
N3
(140)
N4
(28)
L8 L9
Installation
N2
(71)
MS1
N1
(71)
N7
(71)
m
l
N8
(28)
n
N9
(56)
N10
(56)
105
Pipe name
Main pipe
L1
L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13
a, g, j, k
Indoor unit auxiliary pipe from indoor unit to the nearest branch joint or
b, c, d, e, f, h, i, l, m, n, p, q, r
direct connected MS
Branch pipe assembly between main pipe and MS
A, B, C, D, E
, , ,
L, M
MS equipment
MS1,...MS7
Unit: in.(mm)
Indoor unit main pipe in.(mm)
Available branching
Low pressure
High pressure
gas pipe
gas pipe
A<5.6(19.1)
1/2(12.7)
3/8(9.53)
1/4(6.35)
BJFT-224-CM(I)
(19.1)5.6A<16.6(56.6)
3/4(19.1)
5/8(15.9)
3/8(9.53)
BJFT-224-CM(I)
(56.6)16.6A<23(78.5)
7/8(22.2)
3/4(19.1)
3/8(9.53)
BJFT-330-CM(I)
(78.5)23A<33(112.6)
7/8(22.2)
3/4(19.1)
1/2(12.7)
BJFT-330-CM(I)
(112.6)33A<46(157)
1-1/8(28.6)
7/8(22.2)
1/2(12.7)
BJFT-710-CM(I)
(157)46A<66(225.2)
1-1/8(28.6)
7/8(22.2)
5/8(15.9)
BJFT-710-CM(I)
(225.2)66A<92(313.9)
1-3/8(34.9)
1-1/8(28.6)
3/4(19.1)
BJFT-1344-CM(I)
(313.9)92A<135(460.6)
1-5/8(41.3)
1-3/8(34.9)
3/4(19.1)
BJFT-E1344-CM(I)
(460.6)135A
1-3/4(44.5)
1-1/2(38.1)
7/8(22.2)
BJFT-E1344-CM(I)
kW(kBtu/h)
Liquid pipe
pipe assembly
Unit: in.(mm)
Main pipe in.(mm)
Low
High
pressure
pressure
gas pipe
gas pipe
8HP
7/8(22.2)
10HP
High
pressure
pressure
gas pipe
gas pipe
BJFT-330-CM(I)
7/8(22.2)
1/2(12.7)
BJFT-330-CM(I)
3/4(19.1)
1/2(12.7)
1-1/8(28.6)
7/8(22.2)
18-22HP
1-1/4(31.8)
24HP
st
Liquid
The 1 branching
pipe
pipe
3/4(19.1)
3/8(9.53)
7/8(22.2)
3/4(19.1)
12HP
1(25.4)
14-16HP
st
Liquid
The 1
pipe
branching pipe
3/4(19.1)
1/2(12.7)
BJFT-330-CM(I)
7/8(22.2)
3/4(19.1)
1/2(12.7)
BJFT-330-CM(I)
BJFT-710-CM(I)
1(25.4)
3/4(19.1)
5/8(15.9)
BJFT-710-CM(I)
5/8(15.9)
BJFT-710-CM(I)
1-1/8(28.6)
7/8(22.2)
5/8(15.9)
BJFT-710-CM(I)
1-1/8(28.6)
5/8(15.9)
BJFT-710-CM(I)
1-1/4(31.8)
1-1/8(28.6)
3/4(19.1)
BJFT-710-CM(I)
1-3/8(34.9)
1-1/8(28.6)
5/8(15.9)
BJFT-1344-CM(I)
1-3/8(34.9)
1-1/8(28.6)
3/4(19.1)
BJFT-1344-CM(I)
26-32HP
1-3/8(34.9)
1-1/8(28.6)
3/4(19.1)
BJFT-1344-CM(I)
1-3/8(34.9)
1-1/8(28.6)
7/8(22.2)
BJFT-1344-CM(I)
34-48HP
1-5/8(41.3)
1-3/8(34.9)
3/4(19.1)
BJFT-E1344-CM(I)
1-5/8(41.3)
1-3/8(34.9)
7/8(22.2)
BJFT-E1344-CM(I)
50-64HP
1-3/4(44.5)
1-1/2(38.1)
7/8(22.2)
BJFT-E1344-CM(I)
1-3/4(44.5)
1-1/2(38.1)
1(25.4)
BJFT-E1344-CM(I)
Note: the main pipe L1 can be selected form table1 or table2, the larger size should be finally selected.
106
Installation
Illustration
2 units
g2
g1
Main pipe
L
3 units
g3
g2
g1
4 units
g4
g3
Main pipe
M
G1
g2
L
g1
M
G1
Main pipe
G2
Table 3: Outdoor unit connection pipe selection (g1, g2, g3, g4, G1, G2)
Pipe
Unit: in.(mm)
Liquid pipe
8/10/12HP
7/8(22.2)
3/4(19.1)
1/2(12.7)
14/16HP
1-1/8(28.6)
7/8(22.2)
5/8(15.9)
G1
1-3/8(34.9)
1-1/8(28.6)
3/4(19.1)
G2
1-5/8(41.3)
1-3/8(34.9)
7/8(22.2)
g1,g2,,g3,g4
2 units
L: BJCT-02-CM(I)
3 units
L+M: BJCT-03-CM(I)
4 units
L+M+N: BJCT-04-CM(I)
5/8(15.9)
3/8(9.53)
BJF-224-CM(I)
Table 6: Indoor unit auxiliary pipe from indoor unit to the nearest branch joint or direct connected MS
selection (b, c, d, e, f, h, i, l, m, n, p, q, r) Unit: in.(mm)
The pipe length from indoor unit to the nearest
kW(kBtu/h))
MS32.8ft(10m)
MS32.8ft(10m)
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
A<5.6(19.1)
1/2(12.7)
1/4(6.35)
5/8(15.9)
3/8(9.53)
(19.1)5.6A<16(54.6)
5/8(15.9)
3/8(9.53)
3/4(19.1)
1/2(12.7)
Installation
107
6.3 Example
The example is as blow:
(Provided that the capacity of outdoor unit is (16+12+10) HP, the equivalent length of all pipes in this system is
larger than 90m, the pipe length from the 1st branch joint to the farthest indoor unit is less than 40m, and the
pipe from indoor unit to the nearest branch joint or direct connected MS is less than 10m.
W3
(10)
W2
(12)
W1
(16)
b
a
g1
g2
g3
M
L
G1
L1
L2
L3
N2
(71)
MS1
L4
MS2
L5
L6
MS3
L7
L8 L9
E
MS7
L10
L11
N13
(56)
N12
(140)
N11
(140)
L12
N5
(140)
N6
(71)
MS4
MS5
h
g
L13
MS6
j
q
N3
(140)
N4
(28)
N1
(71)
N7
(71)
m
l
N8
(28)
n
N9
(56)
N10
(56)
1. Select indoor unit auxiliary pipes from indoor unit to the nearest branch joint or direct connected MS: b, c, d,
e, f, h, i, l, m, n, p, q, r.
Refer to table 6, the pipes of b, c, e, f, h, i, m, n, p, q and r are 5/8(15.9)/ 3/8(9.53), and the pipes of d and l
are 1/2(12.7)/1/4(6.35).
2. Select indoor unit auxiliary pipes between MS and downstream branch joint: a, g, j, k.
Refer to table 5, the pipes of a, g, j and k are 5/8(15.9)/ 3/8(9.53), the brand pipe assembly , , and
are BJF-224-CM(I).
3. Select indoor unit main pipes: L1~L13
The downstream indoor units of L3 are N1 and N2, which capacity is 7.12=14.2kW(48.5kBtu/h). Refer to
table 1, the indoor unit main pipe L3 is 3/4(19.1) /5/8(15.9)/ 3/8(9.53), select MSFT-02C-CM for MS1.
The downstream indoor unit of L5 is N3, which capacity is 14 kW(47.8kBtu/h). Refer to table 1, the indoor
unit main pipe L5 is3/4(19.1) /5/8(15.9)/ 3/8(9.53), select MSFT-02C-CM for MS2.
The downstream indoor unit of L6 is N4, which capacity is 2.8 kW(9.6kBtu/h). Refer to table 1, the indoor
unit main pipe L6 is 1/2(12.7)/ 3/8(9.53)/ 1/4(6.35), select MSFT-02C-CM for MS3.
The downstream indoor units of L4 are N3 and N4, which capacity is 14+2.8=16.8 kW(57.3kBtu/h). Refer to
table 1, the indoor unit main pipe L4 is 7/8(22.2)/ 3/4(19.1)/ 3/8(9.53), the branch pipe assembly C is
BJFT-330-CM(I).
The downstream indoor units of L2 are N1, N2, N3 and N4, which capacity is 7.12+14+2.8=31 kW
(105.8kBtu/h). Refer to table 1, the indoor unit main pipe L2 is 7/8(22.2)/ 3/4(19.1)/ 1/2(12.7), the
branch pipe assembly B is BJFT-330-CM(I).
The downstream indoor unit of L12 is N5, which capacity is 14 kW(47.8kBtu/h). Refer to table 1, the indoor
unit main pipe L12 is 3/4(19.1)/ 5/8(15.9) /3/8(9.53), select MSFT-02C-CM for MS4.
108
Installation
The downstream indoor units of L13 are N6 and N7, which capacity is 7.12=14.2 kW(48.5kBtu/h). Refer to
table 1, the indoor unit main pipe L13 is 3/4(19.1)/ 5/8(15.9) /3/8(9.53), select MSFT-02C-CM for MS5.
The downstream indoor units of L10 are N5, N6 and N7, which capacity is 14+7.12=28.2 kW(96.2kBtu/h).
Refer to table 1, the indoor unit main pipe L10 is 7/8(22.2)/ 3/4(19.1)/ 1/2(12.7), the branch pipe
assembly F is BJFT-330-CM(I).
The downstream indoor units of L11 are N8, N9 and N10, which capacity is 2.8+5.62=14 kW(47.8kBtu/h).
Refer to table 1, the indoor unit main pipe L11 is 3/4(19.1)/ 5/8(15.9) /3/8(9.53), select MSFT-02C-CM
for MS6.
The downstream indoor units of L9 are N5~N10, which capacity is 14+5.62+7.12+2.8=42.2 kW
(144kBtu/h). Refer to table 1, the indoor unit main pipe L9 is 1-1/8(28.6)/ 7/8(22.2)/ 1/2(12.7), the
branch pipe assembly E is BJFT-710-CM(I).
The downstream indoor units of L8 are N11~N13, which capacity is 142+5.6=33.6 kW(114.6kBtu/h). Refer
to table 1, the indoor unit main pipe L8 is1-1/8(28.6)/ 7/8(22.2)/ 1/2(12.7), select MSFT-04C-CM for
MS7.
The downstream indoor units of L7 are N5~N13, which capacity is 143+7.12+5.63+2.8=75.8 kW
(258.6kBtu/h). Refer to table 1, the indoor unit main pipe L7 is 1-3/8(34.9)/ 1-1/8(28.6)/ 3/4(19.1), the
branch pipe assembly D is BJFT-1344-CM(I).
The downstream indoor units of L1 are N1~N13, which capacity is 144+7.14+5.63+2.82=106.8 kW
(364.4kBtu/h). Refer to table 1, the indoor unit main pipe L1 is 1-5/8(41.3)/ 1-3/8(34.9)/ 3/4(19.1), the
branch pipe assembly A is BJFT-E1344-CM(I).
4. Select main pipe: L1
For the capacity of outdoor unit is 38HP, the equivalent length of all pipes in this system is larger than
295ft(90m), refer to table 2, the main pipe L1 is 1-5/8(41.3)/ 1-3/8(34.9)/ 7/8(22.2), the branch pipe
assembly A is BJFT-E1344-CM(I).
As the main pipe L1 is selected as 1-5/8(41.3)/ 1-3/8(34.9)/ 3/4(19.1) from step 3, and 1-5/8(41.3)/
1-3/8(34.9)/ 7/8(22.2) from step 4, we finally select the larger pipe 1-5/8(41.3)/ 1-3/8(34.9)/ 7/8(22.2)
as main pipe L1.
5. Outdoor unit connection pipe (g1, g2, g3, G1,L+M) selection (refer to table3, table 4)
The pipe g1 is connected to 10HP outdoor unit. Refer to table3, the diameter of g1 is 7/8(22.2) /3/4(19.1)
/1/2(12.7)
The pipe g2 is connected to 12HP outdoor unit. Refer to table3, the diameter of g2 is 7/8(22.2) /3/4(19.1)
/1/2(12.7)
The pipe g3 is connected to 16HP outdoor unit. Refer to table3, the diameter of g3 is 1-1/8(28.6)/
7/8(22.2) /5/8(15.9)
The upstream outdoor unit quantity of G1 is two. Refer to table3, the diameter of G1 is 1-3/8(34.9)/
1-1/8(28.6)/ 3/4(19.1)
The quantity of combined outdoor units is three. Refer to table4, the outdoor branch assembly is L+M:
BJCT-03-CM(I)
Note: For the detail dimension and installation information pipe, please read the branch pipe installation manual carefully.
Installation
109
Correct way
Correct way
Wrong way
Wrong way
A direction view
Wrong
Correct
10
10
Horizontal surface
For avoiding oil accumulate at the outdoor unit, please install the branching pipes properly.
110
Installation
tg
5
1
2
3
4
5
6
Refrigerant pipe
Part to be brazed
Taping
Hands valve
Pressure-reducing valve
Nitrogen
Do not use anti-oxidants when brazing the pipe joints. Residue can clog pipes and break equipment.
Do not use flux when brazing copper-to-copper refrigerant piping. Use phosphor copper brazing filler alloy
(BCuP) which does not require flux.
Flux has an extremely harmfully influence on refrigerant pipe systems. For instance, if chlorine based flux is
used, it will cause pipe corrosion in particular, if the flux contains fluorine, it will deteriorate the refrigerant oil.
Installation
111
MS
Nitrogen
Indoor unit
Liquid pipe
Nitrogen
Nitrogen
Note:
Pressurized nitrogen (3.9MPa; 40kgf/cm2) is used for airtightness test.
It is not allowed to use oxygen, combustible gas or toxic gas to conduct the airtightness test.
When welding, please use wet cloth insulating the low pressure valve for protection.
To avoid the equipment be damaged, the pressure maintained time should not last too long.
10. Vacuum
Use the vacuum pump which vacuum level lower than -0.1MPa(-14.5PSI) and the air discharge capacity
above 40L/min(1.41ft3/min).
The outdoor unit is not necessary to vacuum, dont open the outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump could result as -0.1MPa(-14.5PSI) or below after 2 hours or above operation. If
the pump operated 3 hours or above could not achieve to -0.1MPa(-14.5PSI) or below, please check
whether water mix or gas leak inside of the pipe.
Pressure gauge with the switch is installed between vacuum pump and system pipes.
112
Installation
Respectively connect the vacuum pump in the gas balance valve and oil balance valve
Open the gas balance valve and oil balance valve of the outdoor unit
After the system is powered on, press the key of SW4 until displaying -000.And then
press the key of forced cooling, then UA is displayed.
Into vacuum mode
Connect with vacuum pump
When get the vacuum level -0.1MPa, the pump should keep running for 20-60 minutes
or above)
Caution:
Dont mix up the different refrigerants or abuse the tools and measurements which directly contact with refrigerants.
Dont adopt refrigerant gas for air vacuuming.
If vacuum level could not get to -0.1MPa, please check whether resulted by leakage and confirm the leakage site. If no leakage,
please operate the vacuum pump again 1 or 2 hrs.
Installation
113
1/4(6.35)
0.051(0.023)
3/8(9.53)
0.132(0.060)
1/2(12.7)
0.264(0.120)
5/8(15.9)
0.396(0.180)
3/4(19.1)
0.594(0.270)
7/8(22.2)
0.836(0.380)
1(25.4)
1.21(0.550)
1-1/8(28.6)
1.56(0.710)
Fill the additional quantity of calculated refrigerant from the low-pressure pipe and liquid pipe.
The system is back to electricity after power outages,and then quit from the vacuum state.
Outdoor units
Network
centralized
accounting
monitoring
Indoor units
Outdoor units
Indoor units
centralized
communication communication
contros
114
Hz
Power supply
Compressor
Voltage
Min.
Max.
MCA
TOCA
MFA
MSC
RLA
(V)
(V)
(V)
(A)
(A)
(A)
(A)
(A)
OFM
kW
FLA
(A)
38VF008T119010
50
380~415
342
440
18.4
20.8
25
17.4
0.42
3.6
38VF010T119010
50
380~415
342
440
20.6
22.1
25
17.4
0.42
3.6
38VF012T119010
50
380~415
342
440
21.8
22.8
25
17.4
0.42
3.6
38VF014T119010
50
380~415
342
440
27.9
31.8
35
0.71
5.9
38VF016T119010
50
380~415
342
440
33.4
32.8
35
0.71
5.9
17.4+
10.5
17.4+
10.5
Installation
The current value of combination unit is the total value of each basic model (refer to Units Combination Table in
Part1)
For example: 46HP=16HP+16HP+14HP
Power current: MCA=33.4+33.4+27.9=94.7A
TOCA=32.8+32.8+31.8=97.4A
MFA=35+35+35=105A
Compressor: RLA=(17.4+10.5)+ (17.4+10.5)+ (17.4+10.5)=83.7A
OFM: FLA=5.9+5.9+5.9=17.7A
Notes:
1. RLA is based on the following conditions, Indoor temp. 27C(80.6oF) DB/19C(66.2oF) WB, Outdoor temp. 35C(95oF) DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range.
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%
6. Selection wire size based on the larger value of MCA or TOCA
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
MCA: Min. Circuit Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW)
Installation
115
Leakage
protector
Manual
switch
Outdoor unit
GND
Outdoor unit
GND
GND
Outdoor unit
Branch box
GND
Outdoor unit
Power facilities 1
Outdoor unit
GND
Leakage
protector
Manual
switch
GND
Outdoor unit
GND
Outdoor unit
GND
Branch box
Outdoor unit
GND
Power facilities 2
(with leakage protector)
Outdoor unit
GND
Leakage protector
Manual switch
Branch box
Indoor unit
10
11
12
13
14
15
16
Note:
Set refrigerant piping system, signal wires between indoor units and signal wires between outdoor units into one system.
Power must unified supply to all indoor units in the one system.
Please do not put the signal wires and power wires in the same wire tube; keep distance between the two tubes. (Keep
distance above 11-13/16inch(300mm), when current capacity of power supply less than 10A, and Keep distance above
19-11/16inch(500mm), when current capacity of power supply less than 50A).
Make sure to address the outdoor unit which is in combination type.
116
Installation
(P Q E)
(H1 H2 E) (H1 H2 E) (H1 H2 E)
(open)
matching
resistor
(P Q E)
MS
MS
(open)
(open)
matching
resistor
MS
(open)
group control
(open)
matching
resistor
matching
resistor
matching
resistor
MS
Installation
117
Outdoor Unit
(Slave)
Outdoor Unit
(Slave)
Outdoor Unit
(Slave)
CRF-10-CM
CCM03
To RS485/RS232 (F1,F2,E)
Converter
(X,Y,E)
(H1,H2,E)
(H1,H2,E)
(H1,H2,E)
(K1,K2,E)
(K1,K2,E)
(K1,K2,E)
CCM02
(P,Q,E)
To RS485/RS232 (F1,F2,E)
Converter
query
Set
Previous
M
Module
Ok
Next
Page up
Page down
(P,Q,E)
(K1,K2,E)
(P,Q,E)
Address Lock
CRC-10-CM
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
(P,Q,E)
Indoor Unit
Indoor Unit
(P,Q,E)
(P,Q,E)
(P,Q,E)
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
(P,Q,E)
Indoor Unit
Indoor Unit
(P,Q,E)
Indoor Unit
118
Indoor Unit
Indoor Unit
(P,Q,E)
Indoor Unit
(P,Q,E)
Indoor Unit
Indoor Unit
Indoor Unit
(P,Q,E)
Indoor Unit
Indoor Unit
Installation
Silent mode
S3
S12
ENC3
S12
ENC3
S12
ENC3
S12
119
Model(indoor unit)
Room Name
Eg: Indoor unit (A) of the
first system on second floor
is recorded as:-2F-1A
120
Installation
Outdoor unit
Indoor unit
Calculate the critical thickness through following steps, and take necessary actions.
1. Calculate the refrigerant charge A
2. Total refrigerant charge = delivered refrigerant charge (nameplate) + supplemental refrigerant charge
Leakage detector alarming device
3. Calculate the indoor volume (B) (as the minimum volume)
related to mechanical ventilator
4. Calculate the refrigerant thickness.
A/B critical thickness 0.3kg/m3(0.02Ibs./ft3)
Indoor unit
Countermeasure to over-high refrigerant thickness
OA
1. Install mechanical ventilator to reduce the refrigerant thickness
under critical level. (Ventilate regularly)
2. Install leakage detector alarming device related to mechanical
ventilator if you cannot regularly ventilate.
air-vent
Installation
121