FXMQ-MF OA Technical Data
FXMQ-MF OA Technical Data
FXMQ-MF OA Technical Data
FXMQ-MF
Outdoor Air Processing Unit
AMERICAS
EDUS39-900-F10
FXMQ-MF
Outdoor Air Processing Unit
1. Features ......................................................................................................2
2. Specifications ..............................................................................................4
3. Dimensions .................................................................................................5
3.1 Indoor Units .................................................................................................. 5
4. Piping Diagrams..........................................................................................7
5. Wiring Diagrams..........................................................................................8
6. Capacity Tables ..........................................................................................9
7. Operation Limit..........................................................................................12
8. Electric Characteristics..............................................................................14
9. Fan Performances.....................................................................................15
10.Sound Levels ............................................................................................17
11.Installation .................................................................................................19
12.Accessories...............................................................................................33
FXMQ-MF
Features
EDUS39-900-F10
1. Features
60 Hz only
For outdoor units of 8 HP and above
Model Names
FXMQ48MFVJU, FXMQ72MFVJU,
FXMQ96MFVJU
Air conditioning and outdoor air processing can be accomplished using a single system.
VRV Series
Outdoor Units
Air
Conditioning
Indoor Unit
Outdoor
Air Supply
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
When outdoor-air processing units are connected, the total connection capacity must be within 50% to 100% of that of the outdoor units.
When outdoor-air processing units and standard indoor units are connected, the total connection capacity of the outdoor-air processing units must not exceed 30% of that of the
outdoor units.
Outdoor-air processing units can be used without indoor units.
Connectable outdoor units: R-410A P series.
FXMQ-MF
EDUS39-900-F10
Features
Airflow rate
635
988
1,236
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
ut
r
pe
em )
r T WB
i
A
or F
do (
at
ur
Supported Cooling
Operation Range
Fan
Operation
30%
Heating
Supported
Range
Operation
23
59
66.2
90
10
0%
H R
Re umi elat
lat dity ive
ive
Hu
m
8
idi 9.6
ty
Usage Limitations
idity
Hum
tive
Rela
(92.3)
e
lativ
Re ity
20% umid
H
109.4
Notes
1. The data shown in the graph illustrates the supported operation ranges under
the following conditions.
Indoor and Outdoor Unit
Effective piping length: 25ft.
Height differential: 0ft.
2. The discharge temperature can be set using the remote controller. However,
the actual temperature may not match the temperature setting under some
circumstances due to the outdoor-air processing load or mechanical protection
controls.
3. The system will not operate in fan mode when the outdoor air temperature is
41F or below.
FXMQ-MF
BRC1E71
Wired remote controller
(option)
The "self-diagnosis function" indicates the occurrence and nature of abnormalities in the system
by displaying codes on the remote controller.
A central control system
compatible with the VRV
system can be installed.
* It is not possible to change the
discharge air temperature settings
from the central control system.
* Do not associate this equipment
into zones with standard indoor units,
as central control will not be possible.
DCS302CA71
Central remote controller
(option)
Specifications
EDUS39-900-F10
2. Specifications
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
1 Cooling Capacity
Model
Btu/h
48,000
72,000
96,000
2 Heating Capacity
Btu/h
30,000
47,000
59,000
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
Fan
in.
181/2291/4435/16
181/2543/8435/16
181/2543/8435/16
RowsStagesFin
Pitch
in.
32613
32613
32613
Face Area
ft
3.01
7.00
7.00
Model
D13/4G2DA1
D13/4G2DA1
D13/4G2DA1
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
Number of Units
Air Flow Rate (H/L)
External Static
Pressure 4
3801
3801
3801
cfm
635
988
1,236
in. WG
0.88
0.96
1.03
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
Direct Drive
Direct Drive
Glass Fiber
Glass Fiber
Glass Fiber
3/8
(Flare Connection)
3/8
(Flare Connection)
Liquid Pipes
in.
3/8
(Flare Connection)
Gas Pipes
in.
5/8
(Flare Connection)
3/4
(Brazing Connection)
7/8
(Brazing Connection)
190
271
271
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Drain Pipe
Machine Weight (Mass)
Safety Devices
Refrigerant Control
Standard Accessories
Connectable Outdoor Units 5,6
Drawing No.
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Lbs
R-410A P series
R-410A P series
R-410A P series
C : 3D065463
C : 3D065463
C : 3D065463
Notes:
1 Nominal cooling capacities are based on the following conditions:
Outdoor temperature: 91FDB, 82FWB (68%RH)
Discharge set temp: 64FDB
Equivalent ref. piping: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Outdoor temperature: 32FDB, 27FWB (50%RH)
Discharge set temp: 77FDB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its duct collection efficiency (gravity method) 50% or more.
5 Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the outdoor unit.
6 This equipment cannot be incorporated into the remote group control of the VRV III system.
FXMQ-MF
EDUS39-900-F10
Dimensions
3. Dimensions
3.1
Indoor Units
Unit (in.)
FXMQ-MF
3D065452A
FXMQ48MFVJU
Dimensions
EDUS39-900-F10
Unit (in.)
3D065453A
FXMQ72MFVJU
FXMQ96MFVJU
FXMQ-MF
EDUS39-900-F10
Piping Diagrams
4. Piping Diagrams
4D018650C
FXMQ-MF
Wiring Diagrams
5. Wiring Diagrams
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
EDUS39-900-F10
FXMQ-MF
3D065426C
EDUS39-900-F10
Capacity Tables
6. Capacity Tables
FXMQ48MFVJU
Cooling
Outdoor air temp
FWB
62
66
70
74
FDB
78
82
86
90
Btu/h
Btu/h
Btu/h
Btu/h
capacity
Btu/h
Btu/h
67
13000
15900
71
13000
15900
75
13000
15900
18300
23300
15900
18300
22900
83
18300
22900
37700
87
17900
22600
37300
48300
91
17900
22200
37000
48000
56200
21900
36600
47600
55800
79
Btu/h
Btu/h
18300
95
59600
Heating
Outdoor air temp
FWB
19
23
27
31
FDB
35
39
43
51
55
capacity
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
22
32600
32600
32
30000
37
26600
26600
26600
42
21500
21500
21500
52
16800
16800
16800
57
12100
12100
12100
Notes:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64F for cooling operation,
77F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in
means rated capacity.
FXMQ-MF
Capacity Tables
EDUS39-900-F10
FXMQ72MFVJU
Cooling
Outdoor air temp
FWB
62
66
70
74
FDB
78
82
86
90
Btu/h
Btu/h
Btu/h
Btu/h
capacity
Btu/h
Btu/h
Btu/h
Btu/h
67
19600
24000
71
19600
24000
27600
75
19600
24000
27600
34700
79
24000
27300
34400
83
27300
34000
56500
87
27000
33700
55900
72600
91
27000
33100
55600
72000
84200
95
32700
54900
71300
83800
89300
Heating
Outdoor air temp
FWB
19
23
27
31
FDB
35
39
43
51
55
capacity
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
22
50700
50700
32
47000
37
41200
41200
41200
42
33800
33800
33800
52
26300
26300
26300
57
18900
18900
18900
Notes:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64F for cooling operation,
77F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in
means rated capacity.
10
FXMQ-MF
EDUS39-900-F10
Capacity Tables
FXMQ96MFVJU
Cooling
Outdoor air temp
FWB
62
66
70
74
FDB
78
82
86
90
Btu/h
Btu/h
Btu/h
Btu/h
capacity
Btu/h
Btu/h
67
26000
31800
71
26000
31800
75
26000
31800
36700
46200
31800
36300
45900
83
36300
45600
75400
87
36000
44900
74700
96600
91
36000
44200
74000
96000
112400
43800
73300
95300
111700
79
Btu/h
Btu/h
36700
95
119300
Heating
Outdoor air temp
FWB
19
23
27
31
FDB
22
Btu/h
Btu/h
63700
63700
Btu/h
32
59000
37
51800
42
52
57
35
39
43
51
55
Btu/h
Btu/h
Btu/h
Btu/h
42300
42300
capacity
Btu/h
Btu/h
51800
51800
42300
33200
33200
33200
23700
23700
23700
Notes:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64F for cooling operation,
77F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in
means rated capacity.
FXMQ-MF
11
Operation Limit
EDUS39-900-F10
7. Operation Limit
FXMQ48MFVJU
ir t
em
p.
(
FW
B)
89.6
2)
3)
Ou
tdo
or
a
Operation
limit
(cooling)
NOTE
1) These figures assume the
following operating conditions.
(Indoor and outdoor units)
Equivalent pipe length: 25ft.
Level difference: 0ft.
Fan only
operation
Operation limit
(heating)
23
32
42.8
59
66.2
Outdoor air temp. (F DB)
84.2
(92.3)
106.7 109.4
C : 3D046312
FXMQ72MFVJU
ir t
em
p.
(
FW
B)
89.6
Ou
td
oo
ra
Operation
limit
(cooling)
NOTE
1) These figures assume the
following operating conditions.
(Indoor and outdoor units)
Equivalent pipe length: 25ft.
Level difference: 0ft.
2)
3)
Fan only
operation
23
12
32
59 66.2
Outdoor air temp. (F DB)
86
(92.3)
106.7 109.4
C : 3D047750
FXMQ-MF
EDUS39-900-F10
Operation Limit
FXMQ96MFVJU
tem
p.
(
FW
B)
89.6
Ou
td
oo
r
air
Operation
limit
(cooling)
NOTE
1) These figures assume the
following operating conditions.
(Indoor and outdoor units)
Equivalent pipe length: 25ft.
Level difference: 0ft.
2)
3)
Fan only
operation
Operation limit
(heating)
23
32
59
66.2
FXMQ-MF
84.2
(92.3)
106.7 109.4
C: 3D046313
13
Electric Characteristics
EDUS39-900-F10
8. Electric Characteristics
MOP
15
MOP :
MCA / MOP
MOP
14
FXMQ-MF
EDUS39-900-F10
Fan Performances
9. Fan Performances
FXMQ48MFVJU
3D065649B
FXMQ72MFVJU
3D065650B
FXMQ-MF
15
Fan Performances
EDUS39-900-F10
FXMQ96MFVJU
3D065651B
16
FXMQ-MF
EDUS39-900-F10
Overall
Location of microphone
Notes:
1. The operating conditions are assumed to be standard
(JIS conditions). Power source 208-230V, 60hz.
2. The operating values were obtained in an anechoic
chamber (conversion values).
1. Sound levels will vary depending on a range of
factors such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipment is installed.
dBA
Model
10.2
208-230V, 60Hz
FXMQ48MFVJU
43
FXMQ72MFVJU
48
FXMQ96MFVJU
48
FXMQ48MFVJU
FXMQ72MFVJU
4D068575
FXMQ-MF
17
EDUS39-900-F10
FXMQ96MFVJU
4D068577
18
FXMQ-MF
EDUS39-900-F10
Installation
11. Installation
Center of Gravity
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
Unit (in.)
Model
Product
Mass
FXMQ48MFVJU
190Lbs
FXMQ72MFVJU
FXMQ96MFVJU
AA
AB
AC
AD
AE
30-11/16 27-3/8
23-5/8
9-13/16
13
271Lbs
54-5/16
51
22-7/16
9-13/16
23-5/8
271Lbs
54-9/16
51
22-7/16
9-13/16
23-5/8
4D065444
Service Space
Selecting Installation Site
When it may exceed 86F and RH80% in the ceiling or fresh air is inducted into the ceiling, an additional insulation
(Thickness 3/8in. or more of glasswool or polyethylene form) is required.
1. Select an installation site where the following conditions are fulfilled and that meets with your customers approval.
Where is resistible against weight of the unit.
In the upper space (including the back of the ceiling) of the unit where there is no possible dripping of water from the
refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks the air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough to take the units weight, the unit could fall out of place and
cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of combustible gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.
(See the installation mamual included with the outdoor unit for REFRIGERANT PIPING.)
Locations where a maintenance hole can be installed. (Refer to Fig. 2)
CAUTION
Install the indoor and outdoor units, power supply wires and transmission wires at least 3.3ft. away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3ft. may not be sufficient enough to eliminate the noise.)
FXMQ-MF
19
Installation
EDUS39-900-F10
21 or more
2. Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight of the unit or
not. If there is a risk, reinforce the ceiling before installing the unit.
26 or more
(Service space)
Outdoor-air
processing unit
(Upper face)
44 or more
(Service space)
(length: in.)
Fig. 1
20
FXMQ-MF
EDUS39-900-F10
Installation
Bolt Pitch
Preparations Before Installation
1. Relative positions of the unit and suspension bolt. (Refer to Fig. 2)
45-3/16
Suspension bolt (4)
43-5/16
Air outlet
Air inlet
Inspection hatch
23-5/8
Approx. 5-7/8
26 or more
(Service space)
Outdoor-air
processing unit
44 or more
(Service space)
Unit
FXMQ48MFVJU
29-9/32
27
FXMQ7296MFVJU
50-3/8
51
Fig. 2
2. Install a canvas duct to the air outlet and air inlet so that
vibration from the unit isnt transmitted to the duct or ceiling.
You should also apply acoustic (insulation material) to the
inside of the duct, and vibration insulation rubber to the
suspension bolts.
3. Open the installation hole. (Pre-set ceilings)
Once the installation hole is opened in the ceiling where the
unit is to be installed, pass refrigerant and drain pipe and the
power supply, transmission, and remote controller wire to the
units pipe and wire connection ports.
After opening the ceiling hole, it might be necessary to
reinforce the ceiling frame to prevent shaking or to maintain
the levelness of the ceiling.
Consult an architect or carpenter for details.
4. Install suspension bolts.
(Use bolts of 3/8in. diameter.)
Install the unit where supporting structures are strong
enough to bear the units weight. Use embedded inserts or
anchor bolts with new buildings and hole-in-anchors with old
buildings. Adjust the distance to the ceiling beforehand.
FXMQ-MF
(length: in.)
Installation example
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Outdoor-air processing unit
Note) All the above parts are field supplied.
Fig. 3
21
Installation
EDUS39-900-F10
Installation
Unit Installation
Installing optional accessories before installing the unit is easier. See the installation manuals included with the
optional accessories.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts designated
by our company.
1. Temporarily install the unit.
Mount the hanger brackets to suspension bolts. Secure the hanger brackets on the top and the bottom with nuts
<1>~<3> (M10, field supplied) and washers (M10, accessory 10)).
Nut <1>
(Field supply)
Washer
(accessory 10))
Hanger bracket
(attached with main body)
Main body
Nut <2>
(Field supply)
Nut <3>
(Field supply)
Fig. 4
Drain socket
Vinyl tube
Hanger bracket
setting bolt
1 or less
Air inlet side
Air inlet side
1 or less
Drain
socket
Drain
socket
Fig. 5
Sealing pad 6)
Slit of
sealing
pad
Hanger
bracket
Fig. 6
CAUTION
Setting the unit at an angle opposite to the drain socket or air inlet side might cause leaks.
22
FXMQ-MF
EDUS39-900-F10
Installation
CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil inside the flare portions before connecting. (Refer to Fig. 7)
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover it
with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such as
ir, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
TThe outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or
disconnecting pipes to/from the unit. (Refer to Fig. 8)
Refer to Table 2 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare section inside with ester oil or ether oil, rotate three or four times first,
then screw in. (Refer to Fig. 7)
Refer to Table 2 for tightening torque.
Table 2
FXMQ72MFVJU
FXMQ96MFVJU
3/8
3/8
24.1 29.4
0.504 0.520
5/8
45.6 55.6
0.760 0.776
5/8
90 2
R0.016-0.031
FXMQ48MFVJU
Pipe
size
45 2
Unit to be connected
Liquid pipe
diameter
Table 1
Note:
Use the flare nuts attached with the unit.
CAUTION
Over-tightening may damage the flare and cause a refrigerant leakage.
Torque wrench
Spanner
Fig. 7
Piping union
Flare nut
Fig. 8
FXMQ-MF
23
Installation
EDUS39-900-F10
Further tightening
angle
3/8
60 to 90 degrees
Approx. 7-7/8in.
5/8
30 to 60 degrees
Approx. 11-13/16in.
After checking the pipe-connection for gas leakage, be sure to insulate the liquid and gas pipe, referring to Fig.9, 10
and the following points.
FXMQ48MFVJU
1. Insulate the liquid and gas pipes using the insulation for fitting (accessory 3), 4))
(Tighten both edges with clamping material.)
2. Make sure the insulation for fitting (accessory 4)) on the gas pipe has its seams facing up.
3. For the gas pipe, wrap the sealing pad (accessory 5)) around the insulation for fitting (accessory 4)) (flare nut part)
Insulation
for fitting
Insulation
(accessory 4))
(Attached with main body)
Flare nut
Eliminate a gap
Sealing pad
(accessory 5))
Main body
Insulation (Field supply)
Gas pipe
Liquid
pipe
Fig. 9
FXMQ72 96MFVJU
1. Insulate the liquid pipe using the insulation for fitting (accessory 3)).
(Tighten both edges with clamping material.)
2. Use the attached pipe (accessory 1)) for connecting the gas pipes and make sure to insulate the gas pipes (using
field supplied insulation) all the way to the base where they connect to the unit.
3. The turning torque of the hexagon head bolts (accessory 8)) to connect the attached pipe (accessory 1)) to the unit is
15.9 - 21.3ft/lbf.
Insulation
(Field supply)
Eliminate
a gap
Main body
Insulation
(Attached with
main body)
Eliminate
a gap
Gas
pipe
Liquid
pipe
Main body
Insulation
(Attached with
main body)
Clamps
(accessory 11))
Attached pipe
(accessory 1))
Spring washer (accessory 7))
Hexagon head bolt (accessory 8))
Insulation for fitting
(accessory 3))
Insulation
(Field
supply)
Flare nut
Fig. 10
24
FXMQ-MF
EDUS39-900-F10
Installation
CAUTION
Be sure to insulate any field pipe all the way to the pipe connection inside the unit. Any exposed pipe may cause
cndensate or burns if touched.
CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal (BCuP-2/
B-Cu93P-710/795) which does not require flux.
(Flux has extremely harmful infulence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will
cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and
could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or while inserting
nitrogen into the refrigerant piping. Once this is done, connect the unit with a flared or a flanged connection.
Nitrogen should be set to 2.90PSI with a pressure-reducing valve if brazing while inserting nitrogen into the piping.
Refrigerant
piping
Pressure-reducing valve
Part to be
brazed
Taping
hands
valve
Nitrogen
Nitrogen
Fig. 11
FXMQ-MF
25
Installation
EDUS39-900-F10
If converging multiple drain pipes, install according to the procedure shown below. (Select an appropriate central
drain pipe thickness for the units they will be connected to.)
4in.
or more
CAUTION
Do not connect the drain pipe directly to sewage pipes that smell of ammonia. The ammonia in the sewage might
enter the unit through the drain pipes and corrode the heat exchanger.
GENERAL INSTRUCTIONS
26
wAll field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also WIRING DIAGRAM label attached to the electrical components box lid.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the terminal board
wiring to the outdoor unit is properly matched. If wiring and piping between the outdoor unit and the indoor unit are
mismatched, the system may cause a malfunction.
A ground fault circuit interrupter capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply wire connected to the
outdoor unit, the capacity of the ground fault circuit interrupter and switch, and wire instructions.
Be sure to ground the unit.
Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground during
lightning.
FXMQ-MF
EDUS39-900-F10
Installation
ELECTRICAL CHARACTERISTICS
Units
Model
Power supply
Hz
Volts
Voltage range
MOP
FLA
2.1
15
380
1.7
3.6
15
380
2.9
4.1
15
380
3.3
FXMQ48MFVJU
FXMQ72MFVJU
60
208-230
Max. 253
Min. 187
FXMQ96MFVJU
MCA:
W:
MOP:
FLA:
Fan motor
MCA
Model
Breaker
Size
Wire
Size
AWG
18-2
FXMQ48MFVJU
FXMQ72MFVJU
15A
FXMQ96MFVJU
Notes:
1. Select the particular size of electrical wire for power supply wire in accordance with the standards of the given nation
and region.
2. Allowable length of transmission wire between indoor/outdoor units and between the indoor unit and the remote
controller is as follows.
(1) Outdoor unit Indoor unit:
Max. 3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit Remote controller:
Max. 1640ft.
(3) Max. branches No. of branches :16
3. Up to 16 branches are possible for unit-to unit cabling. No branch is allowed after first branch. (Refer to Fig. 15)
Branch
Subbranching
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
Fig. 15
FXMQ-MF
27
Installation
EDUS39-900-F10
HOW TO CONNECT WIRINGS (Remove the electric parts box lid and wire as shown in the
figure below.)
Power supply
terminal block (X1M)
Transmission
terminal block (X2M)
Lock nut
(Field
supply)
Conduit
(Field
supply)
Remote controller
wire
Transmission
wire
Power supply
wire
Electrical components
box lid
Ground wire
Clamp
(accessory 11))
Wiring
(Remote controller
and transmission)
Wire locking
bracket
Fig. 16
X1M
X2M
Wiring
through
hole <2>
Insulation tube
(accessory 2))
Wiring
through
hole <1>
Clamp
(accessory 11))
Clasp
Fig. 17
CAUTION
Wire the electrical components box so that the wiring is at least 3/8in. above the bottom of the electrical components
box.
Be sure to attach the sealing material or putty (field supplied) to the wiring through holes to prevent the infiltration of
water as well as any insects and other small creatures from outside. Otherwise a short-circuit may occur inside the
electrical components box.
28
FXMQ-MF
EDUS39-900-F10
Installation
When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, make sure the lid on the electrical components box fits
snugly by arranging the wires neatly and attaching the electrical components box lid firmly. When attaching the
electrical components box lid, make sure no wires get caught in the edges. Pass wire through the wiring through
holes to prevent damage to them.
Make sure the remote controller wire, the transmission wire and power supply wire, ground wire do not pass through
the same locations outside of the unit, separating them by at least 2in., otherwise electrical noise (external static)
could cause mistaken operation or breakage.
PRECAUTIONS
1. Use round crimp-style terminals for connecting wires to the power supply terminal block.
If unavailable, observe the following points when wiring.w
Do not connect wires of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying
excessive force to the terminal.
Attach insulation sleeve
Size
M3.5
M4
M5
Tightening torque
0.58 0.72 ftlbf
0.87 1.06 ftlbf
2.23 3.01 ftlbf
3. Do not connect wires of different gauge to the same ground terminal. Looseness in the connection may deteriorate
protection.
4. Outside of the unit, keep transmission wire and remote controller wire at least 2in. away from power supply wire and
ground wire. The unit may malfunction if subjected to electrical noise (external static).
5. For remote controller wiring, refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the
remote controller.
6. Never connect power supply wire to the transmission terminal block (X2M). A mistake of the sort could damage the
entire system.
7. Use only specified wire and tightly connect wires to terminals. Be careful wires do not place external stress on
terminals. Keep wiring in neat order and so as not to obstruct other equipment such as the electrical components box
lid. Make sure the lid closes tight. Incomplete connections could result in overheating, and in worse case, electric
shock or fire.
FXMQ-MF
29
Installation
EDUS39-900-F10
WIRING EXAMPLE
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 SYSTEMS)
Power supply
Outdoor unit
Transmission wire
Main
switch
Switch
Fuse
Indoor unit
Remote controller
Fig. 18
IN/D OUT/D
F1 F2 F1 F2
Power supply
208-230V
Power supply
208-230V
60Hz
60Hz
L1 L2
L1 L2
L1 L2
Outdoor
unit Power supply Power supply Power supply
208-230V
208-230V
208-230V
Control box
IN/D OUT/D
F1 F2 F1 F2
L1 L2
L1L2
P1 P2 F1 F2 T1 T2
Unit A
L1L2
P1 P2 F1 F2 T 1 T2
P1 P2 F1 F2 T1 T2
L1L2
P1 P2
P1 P2
Most
downstream
unit
Fig. 19
L1 L2
60Hz
L1 L2
Most
downstream
unit
L1 L2
P1 P2
60Hz
P1 P2 F1 F2 T1 T2
Unit C
Unit B
P1 P2
L1L2
60Hz
L1 L2
P1 P 2 F1 F2 T1 T2
Unit A
L1 L2
Unit B
P1 P 2 F1 F2 T1 T2
L1 L2
P1 P2 F1 F2 T1 T2
L1 L2
P1 P 2 F1 F2 T1 T2
Unit C
P1 P2
P1 P2
Fig. 20
P1 P2
Control by 2
remote controllers
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the same system. However, branch switches and branch
ground fault circuit interrupters must be selected carefully.
30
FXMQ-MF
EDUS39-900-F10
Installation
Air outlet
Power wire
Remote controller
Drain pipe
Air filter
(Optional accessory)
Ground wire
Heat exchanger
Fan
Air filter
(Optional accessory)
Operation Range
Use the system in the following temperature and humidity ranges for safe and effective operation.
COOLING
[F]
OUTDOOR TEMPERATURE
TEMPERATURE
DB
66 to 109 (Note)
WB
89 or below
HUMIDITY
30% to 90%
(Long time operation in a humidity over 90% may cause condensation on the unit and
dripping.)
FXMQ-MF
31
Installation
EDUS39-900-F10
[F]
HEATING
OUTDOOR TEMPERATURE
DB
23 to 59 (Note)
2) When using the central remote controller, mixture of indoor units & Outdoor-air Processing
units in the same zone is not available, because the setting temperature are different.
ZONE1
ZONE2
ZONE3
ZONE1
ZONE2
3) Don't set the R/C of Outdoor-air processing unit as the master remote controller.
32
FXMQ-MF
EDUS39-900-F10
Accessories
12. Accessories
Standard Accessories
Name
Attached pipe
Insulation tube
Sealing pad
Sealing pad
Quantity
2 pcs.
1 each
1)
2)
5)
6)
Inside diameter 1
4) for gas pipe
Shape
Slit
Inside diameter
1-1/4
(Only FXMQ48MFVJU)
(Only FXMQ72
96MFVJU)
(Only FXMQ48MFVJU)
Others
7) Spring washer (M10)
(2 pcs. only for
FXMQ7296MFVJU)
8) Hexagon head bolt
(M10 1-9/16)
(2 pcs. only for
FXMQ7296MFVJU)
9) Screws for flange
connection (M5)
(16 pcs. for
FXMQ48MFVJU,
28 pcs. for
FXMQ7296MFVJU)
10)Washers (8 pcs.)
11)Clamps (10 pcs.)
12)Installation manual
13)Operation manual
3P086156-12Y
No.
Type
Item
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
65%
KAFJ372L140
90%
KAFJ373L140
KAFJ373L280
Filter chamber 1
KDJ3705L140
KDJ3705L280
KAFJ371L140
KAFJ371L280
2
3
KAFJ372L280
3D065445
Notes:
1.Filter chamber has a suction-type flange. (Main unit does not have.)
Dimensions and weight of the equipment may vary depending on the options used.
Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
Some options may not be used in combination.
Operating sound may increase somewhat depending on the options used.
Type
Item
FXMQ-MFVJU
Wireless
BRC4C82
Wired
BRC1D71
Remote controller
Remote sensor
KRCS01-1B
DCS302C71
BRC1E71
KJB311AA
DCS301C71
KJB212AA
Schedule timer
DST301B61
DTA104A61
DTA109A51
KRP1B71
10
KRP4A71
C:3D043022F
Note:
1. Electrical box (No.4-1/5-1) is required for controller (No.4/5).
FXMQ-MF
33
Accessories
34
EDUS39-900-F10
FXMQ-MF
AMERICAS
[email protected]
www.daikinac.com
February
2010
August 2010
EDUS39-900-F10_a
Printed in U.S.A. 08/10 AKFS.K